249.0mm
44.5mm
(1U)
482.5mm
(19”)
Tools
PZ2
PH1
Flat 6mm
Flat 3.5mm
Torque Recommendations
Type Torque
& Size (Nm)
T1 Screws M6 2.5
T2 Screws M3 0.3
Parts Overview
(1-2) (1-2)
1 PH1(2x)
2
ccw 1.5cm
0.5cm
Top Lock
A(M3) Cover
A(M3)
A1
A1
Compack controller (A3)
not inserted
CAUTION: Cabinet
Slide/rail mounted equipment is not to be used
as a shelf or a work space.
To comply with UL requirements and support
the sliding drawer shelf, always fasten the
Minipack 1U system to the cabinet, right A1
below a rigid, supporting surface (plate or
cabinet mounted equipment).
A1
1
B(~M6)
PZ2 (2x)
(T1) B(~M6)
cw
2 Cabinet
PZ2 (2x) Sliding Drawer Shelf in
Maintenance Position
3
ccw
(1/2 turn)
External AC Fuses
Recommended Rating
16A-C Type Hy/Mag (Europe)
20A-C Type Hy/Mag (USA)
AC Mains
Max 10mm2(6AWG)
(OFF)
4 Correct
Polarity
3 1 Max 2.5mm2(12AWG)
CAUTION:
When using “Dual Mains Input” For installations
(two feeds 1phase 100-250VAC), Batteries in USA and Canada only!
turn AC mains OFF, remove the
internal 3 wires Mains Loom ML Fasten All
– An AC Overvoltage Protec-
between TBY and TBX and connect Cables tion Device (OVP) must be
8 2
the second Mains feed to TBX. Internal 3 wires
installed in the system’s AC
Mains Loom, ML input. The device must comply
(blue, black, yellow FB1&FB2 with overvoltage category II
& green)
OFF(0) according to IEC60950-1,
Class II by IEC61643-1 or
Mains Protection Cover Class C by DIN VDE0675
L AC Mains Input 1
N Flat 3.5mm (T3)
Max 4mm2(10AWG)
WARNING: A3
Electric Do NOT unscrew the
Shock load fuses while power A3
is ON and the load
cables connected!
To disconnect the load Handle A3
while power is ON, raised in
always unplug the load open
position
terminals (E). The load Handle in
fuse can then be locked Flat Locked
position Compack Controller
unscrewed.
6=Dig 3–
5=Dig 3+ Pin 1
Inputs
4=Dig 2–
3=Dig 2+
2=Dig 1– Pin 1
1=Dig 1+
Ethernet
6 9=AL3-nc
8=AL3-no
7=AL3-c
Outputs
6=AL2-nc
I/O Alarms 5=AL2-no
Max 1.5mm2 (14AWG) 4=AL2-c Contacts
3=AL1-nc shown with
2=AL1-no de-energized
1=AL1-c coil (Alarm)
2 PH1(2x)
(T2)
A1
cw
A(M3)
1 A(M3) C(~M6)
3
Top Lock PZ2 (2x)
Cover (T1) C(~M6) Cabinet
cw
PZ2 (2x)
4
5
cw
(1/2 turn)
A1
Start Up 1-4
A1
A4
WARNING: A1
A2
1
Mount blind covers in
Electric unused rectifier slots! Blind
Shock Cover A2
A1 A2
CAUTION:
2 A2 Cabinet
Double Pole / Neutral Fusing. AC Mains FB1&FB2
There is a Mains fuse in each line.
ON ON(1)
PH1
3 4
cw
Technical Specifications
AC Input 100-250V, 14.8A max
Frequency 45-66Hz
DC Output 43.5-57.6V, 33.3A max
Suitable for connection to IT systems