Professional Documents
Culture Documents
FIRE SUPPRESSION means slowing down the rate of burning, whereas, CONTROL means keeping the fire from
spreading or holding the fire to one area. EXTINGUISHMENT is putting the fire completely out.
FOUR METHODS OF FIRE EXTINGUISHMENT AND HOW IT WORKS
Extinguishing a fire is somewhat comparable to the elimination of life. For example; the cooling of the fire may be
compared to asphyxiation (elimination of the oxygen supply), and the separation may be compared with malnutrition
or starvation. The tetrahedron concept adds a fourth element - chemical reaction.
Under the triangle-of-fire-concept, there are three (3 ways of suppressing, controlling, and extinguishing a fire,
namely:
1. Cooling - The cooling process uses an extinguishing agent whose primary characteristic is heat absorption.
Water is the best general cooling agent for firefighting purposes. Used on Class A fires, the water absorbs the heat
generated at the surface of the burning material, thus, reducing the temperature of the material below its flash point.
Water can be also used on Class B fires, which include flammable petroleum products. As with a Class A fire, the
water absorbs much of heat, reducing the vaporization rate of the liquid fuel. This is the most noticeable in a fire
involving lubricating oil, whose flashpoint is between 300 to 450 degrees F. It is of less value in a fire involving
gasoline, with its flashpoint at -45 degrees F. water could never cool gasoline below its flashpoint. The extinguishing
ability of the water is broken into fine particles to accelerate heat absorption.
2. Smothering – excludes the oxygen from the fuel so that the gases or vapours of the fuel cannot ignite and
continue the combustion. CO2 and AFFF are used in this purpose.
3. Separation – the removal of the fuel, as in the example of turning off a valve in a gas line prevents the fuel and
oxygen from coming together. If fuel is not available, the heat, regardless of the temperature, cannot affect the fuel,
therefore, therefore, there is no fire.
These three
methods of extinguishment explain how fires are extinguished with the used of water, CO2, and foam. They do not
entirely account for the account for the results obtained by vaporizing liquids or dry chemicals.
The next paragraph will explain the fourth element, the chemistry of fire in terms the theory of reactivity.
4. Chemical Chain Reaction – the fourth method of extinguishment is known as inhibition or the interruption of
chemical reaction.
The sequence of events in suppressing or extinguishing a fire with dry chemicals or vaporizing liquids includes some
aspects of the first three methods.
Using the potassium bicarbonate (dry chemical) as an example, you can follow the process of the fourth method of
extinguishment. Remember this is a rapid reaction and does not necessarily happen one step at a time.
First, the heat of the fire vaporizes the potassium bicarbonate thereby producing water, carbon dioxide, and
potassium dioxide. In the process of vaporization and the change of these compounds, a substantial. Amount of heat
is absorbed by the water and some smothering occurs due to the release of CO2.
Second, the chemical reaction resulting when the potassium dioxide unites with the water formed by the fire creates
an amount of potassium hydroxide.
Third, some potassium hydroxide reacts with certain products released from the fuel, thus forming water and
potassium monoxide. Other potassium hydroxide molecules react with the free hydrogen of the combustion to form a
potassium atom and molecules o water. Finally, this combination of reactions halts the process of fuel uniting with
oxygen of the air, thereby breaking the chemical chain reaction and stopping the fire.
Finally, this combination of reactions halts the process of fuel uniting with oxygen of the air, thereby breaking the
chemical chain reaction and stopping the fire.
EXTINGUISHING AGENTS
The effectiveness of an extinguisher on a particular fire depends on the amount and type of agent in the extinguisher.
Different extinguishing agents can be used to put out a certain class of fire by one or more methods.
1. Removing oxygen;
2. Removing the fuel;
3. Removing heat; and
4. Interrupting the chemical chain reaction.
Some extinguishing agents may be able to extinguish more than one class of fire. They are marked with multiple
letters or multiple numerical-letter ratings.
The following are the most common extinguishing agents, the class of fire they are used, and the extinguishing
methods used:
1. WATER used only on Class A fires. Water is the most effective in cooling the burning material below its ignition
temperature. It is the most commonly used agent in firefighting.
In its natural state, it is highly stable and may be used to extinguish most types of fire if properly applied. Due to its
conductive properties, water should not be used on electrical fires.
Additives:
There are many additives for water used in fire-fighting. Each of these has a specific purpose and effect on the water.
Ways or Methods Water Extinguishes Fires
Cooling - The outstanding heat absorbing qualities of water make it an excellent cooling agent. In the cooling
process, water is applied in large enough amounts to reduce the temperature of the surface of the burning material to
below its flashpoint. The amount of water required depends on the burning material (temperature) and the manner in
which water is applied (straight or fog stream).
Smothering - When water is used to smother a fire, stream must be generated in sufficient amounts to exclude or
displaced air. If the steam generated is confined in the combustion zone, the smothering action will be enhanced. In
ordinary combustibles, the cooling effect of the water not the smother-normally causes extinguishment. The
smothering effect does not does not completely extinguish the fire; rather, it has a tendency to suppress flaming.
Usage:
Water is generally used on Class A fires. Fires involving high flashpoint liquids (such as heavy fuel oil, and asphalt)
may be extinguished when water is effectively applied in spray form. Water may also be used to extinguish Class C
and Class D fires in some cases. In these cases, use extreme caution to avoid injury to personnel and/or damage to
equipment.
2. CARBON DIOXIDE (CO2) - A number of its properties make C02 a desirable extinguishing agent. It is non-
combustible and non-reactive with most substances. CO2 provides its pressure for discharge from storage cylinders
or extinguishers. Being a gas, CO2 can penetrate and spread to all parts of fire.
Effects:
Extinguishment with CO2 is primarily by Smothering. It covers or blankets the burning materials and reduces the
oxygen content to below levels needed for combustion. Even though it is very cold, it has a little cooling effect on a
fire when compared with equal amounts of water. This is the reason when fires that have been apparently
extinguished with CO2 re-ignite from hot surfaces or embers as the CO2 dissipates.
Usage:
Due to its non-conductivity, CO2 is very effective for use on Class C fires. It is also used on Class B fires, but another
agent is needed in blanketing or smothering on large are fires to prevent re-ignition.
CO2 can cause unconsciousness and death in connections needed for extinguishment. A 9% concentration is about
all most people can take without becoming unconscious within just a few minutes.
3. DRY CHEMICAL - The dry chemical extinguishing agents in use today are mixtures of powders and various
additives that improve the storage, flow, and water repellency of the powders. Sodium bicarbonate, Potassium
bicarbonate, and mono ammonium phosphate are some of the powders commonly used today. Dry chemical is stable
at low temperatures, but it has an upper storage temperature of 140°F. At temperatures above 1400F some caking or
sticking of the powder occurs. These agents are said to be non-toxic, but in discharging large amounts they may
cause some breathing and visibility problems.
Effects:
Flames banish almost at once when dry chemical is applied directly to the fire area. But the exact chemistry and
mechanism of the extinguishing agent are not fully known. It has been suggested that the dry chemical agents inhibit
the chain reaction in the combustion zone has a greater effect in the extinguishment than the smothering or cooling
actions and radiation shielding have.
Usage:
There are Two Basic Types of Dry Chemical:
a). Ordinary and Regular Dry Chemical - generally refer to those powders that are intended for use on Class B or
Class C fires.
b). Multi-purpose Dry Chemical - refers to a powders listed for use on Class A, B, C fires.
Be careful not to confuse ordinary, regular, or multipurpose dry chemical with "dry powder".
4. DRY POWDER - Dry powder is a generally term for agents used to extinguish combustible metal fires.
No one dry powder has been found to be effective on all types of combustible metals.
Effects:
Dry powder generally extinguishes fires by excluding air from the combustible metal. To some extent, heat is
absorbed by the powder to lower the e temperature of the metal to below ignition point (as with G.I. powder).
Usage:
Dry powder is used primarily on Class D fires and should not be used on other types of fire, due to limited value on
these fires.
5. AFFF - AQUEOUS FILM FORMING FOAM - has replaced protein foam for all around firefights purposes.
Protein base foam is now used primarily for runway foaming operations and for some training purposes.
Effects:
The quick "knock-down" and "heat reduction" properties of AFFF have proven it to be a highly effective agent. These
properties, combined with its ability to seal the surface of burning hydrocarbon fires to prevent "flashback”, make it an
outstanding and effective extinguishing agent with which to work. When AFFF is applied to the surface of a
flammable liquid fire, the surface active material (surfactant) provides a vapor sealing effect. This is not only
extinguishes the fire built also prevents the release of fuel vapors which could result in flashbacks. This vapor seal is
also very hard to break-up by walking, or moving some hose lines through it.
Usage:
As with any other extinguishing agent, its effectiveness depends on the proper application. The AFFF is designed to
be applied at a 6% mixture (94 parts water to 6 parts AFFF concentrate). This mixture should be applied in a rainfall
manner, or lobbing effect to allow rapid spreading over the surface. It is used primarily to extinguish on Class B fires.
It may be used on Class A fires but may be less effective than plain water. Foam spray (fog) is more conductive than
plain water fog, because the material contained in the foam allows the water to conduct electricity. \
6. HALONS (HALOGENATED AGENTS) -These agents have been used for over 50 years. Continuous research
has brought these agents to the present high degree of effectiveness in interrupting the chain reaction they possess
along with a decrease in life safety hazard.
The older (better known) agents such as carbon tetra-chloride (Halon 104) and chlorobromomethane (Halon 1011)
are less effective and more toxic than the newer agents now in use.
Halon 1211 (bromochlorodifluoromethane) is a gas at normal temperature, but with its relatively high boiling point
(+25 F), requires pressurization to expel it at a satisfactory rate for extinguishment. Halon 1211 is discharge both
partly as a liquid spray and partly as a gas.
Halon 1301 (bromotrifluoromethane) is treated as a C liquefied gas and, like carbon dioxide, requires no pressurizing
agent for expulsion at normal temperature. Nitrogen may be added to storage containers when temperature is below
0 F, to ensure adequate discharge pressure.
Halon 1301 is the least toxic of the Halons. This low toxicity allow for safe discharge from total flood systems in
occupied spaces such as computer rooms.
Halon is a generic term for halogenated hydrocarbons and is a chemical compound that contains carbon plus one
more elements from the halogens series (fluorine chlorine, bromine, or iodine).
Although a very large number of halogenated compounds exist, only a few are used to a significant extent as fire
extinguishing agents. Halogenated vapor is a non-conductor of electricity and is effective in fighting surface fires in
such commodities as flammable liquids, most solid combustible materials, and electrical.
Effects:
Halogenated agents work chemically to extinguish fire. They stop combustion process by breaking the fire chain
reaction and prevent further fire propagation. This chemical fire-stopping action happens with only a low
concentration of halogenated agent used. Application of the agent may be applied locally by g a compressed bottle of
non-combustible gas similar to a carbon dioxide fire extinguisher. This type of application is effective in controlling or
extinguishing surface fire involving flammable liquid, solids, or gases, such a dip tanks, quench tanks, spray booths,
oil-filled transformers, or vapor vents.
Usage:
Halogenated agents are very effective on Class B and Class C fires and have some effects or success on Class A
fires.
WEEK 8
FIRE EXTINGUISHER
· It is a mechanical device usually made of metal, containing chemicals, fluids, or gases for stopping fires, the
means for application of its contents for the purpose of putting out fire (particularly small fire) before it propagates,
and is capable of being readily moved from place to place.
· It is a portable device used to put out fires of limited size.
Classes of Fire Extinguishers:
1. Portable Fire Extinguisher - Portable fire extinguishers offer the greatest potential for immediately controlling
workplace fires. Their portability and relatively easy operation often make them ready for use within seconds.
Classification and Ratings:
Different type of fire extinguishers is designed to extinguish fires involving different types of fuels. Extinguishers are
classified as Class A, B, C, and D or combination depending on the fire against their agents is effective.
The class of extinguisher should be on the extinguisher shell. The "picture symbol” labelling system now in use is
designed to make the operation of fire extinguishers more effective and safe to use through the use of less confusing
pictorial labels. The system also emphasizes when not to use an extinguisher on certain types of fires.
Class A type of extinguisher is used on fires involving ordinary combustible materials such as wood, clothes,
and paper.
Class B extinguisher is used on fires involving liquids, grease, and gases.
Class C extinguishers are used on fires involving energized electrical equipment.
Class D extinguisher is used on fires involving combustible metals such as titanium, magnesium, zirconium,
sodium, and potassium.
Information Indicated on the Extinguisher
1. Date of original filling;
2. Chemical contents;
3. Type of extinguisher;
4. Operating instruction and safety procedure in usage
5. Name and address of the manufacturer;
6. Name and address of the dealer.
Fire Extinguisher Ratings
Class A and Class B extinguishers carry a numerical rating to indicate how large a fire an experienced person
can put out with the use of an extinguisher.
The ratings are based on reproducible physical test conducted by Underwriter's Laboratories that are designed to
determine the extinguishing capability for each size and type of extinguisher.
· Class A Ratings
An extinguisher for Class A fires could have any one of the following ratings. The numerical rating for this
class of fire extinguisher refers to the amount of water the fire extinguisher holds and the amount of fire it will
extinguish.
· Class B Ratings
An extinguisher for Class B fires could have any one of the following ratings. The numerical rating for this type
of extinguisher states the approximate number of square feet of flammable liquid fire that a non-expert
individual can expect to extinguish.
· Class C Ratings
Extinguishers rated for Class C fires are tested only for electrical conductivity. However, no extinguisher
gets Class C ratings without a Class A and/or Class B rating. This class of fire extinguisher does not have a
numerical rating. The letter "C" indicates that the extinguishing agent is non-conductive.
· Class D Ratings
Class D extinguishers are tested on metal fires. The agent used depends on the metal for which the
extinguisher was designed. Check the extinguisher faceplate for the unit's effectiveness on specific metals. There is
no picture designator for Class D extinguishers. This type of extinguisher generally have no rating nor are they given
a multi-purpose rating for use on other types of Class D fires.
The Most Common Extinguishing Agents Used:
1. WATER - used only on Class A fires. These extinguishers contain water and compressed gas and should only
be used on Class A fires. Water is the most effective in cooling the burning material below its ignition temperature.
Under certain conditions, the steam converted from the water will exclude oxygen and smother the fire.
Anti-freeze solutions added to the water in some of these extinguishers prevent freezing but add nothing to the
effectiveness. Most of the extinguishers are 2% gallons in capacity and it will deliver a stream up to 40 feet
horizontally contains water and compressed gas.
2. DRY CHEMICALS: Dry Chemical extinguishers ners are usually rated for multi-purpose use. It contains an
extinguishing agent and uses a compressed, non-flammable gas as a propellant.
Types:
a. Regular or ordinary (sodium and potassium bicarbonate respectively) used only Class B or C Class fires.
b. Multi-purpose dry chemicals (ammonium phosphate) used on Class A, Class B, and Class C.
Dry chemicals inhibit the chain reaction and, to a certain degree, cool and smother the fire. These agents are
chemically treated with a substance to keep them water resistant and free flowing. This also helps prevent packing of
the chemical while stored inside the extinguisher. These dry chemical extinguishers may be found in sizes which
range from 2 1/2 to 30 pounds.
3. CARBON DIOXIDE - used on Class B and Class C fires. CO2 extinguishes fire by smothering, reducing the
oxygen level below that which supports combustion. These extinguishers are only effective from 3 to 8 feet. Under
certain conditions, the coldness of the gas also helps put out the fire. It is an inert gas. When CO2 is stored under
pressure in a cylinder or tank such a fire extinguisher, it changes from a vapor to a liquid.
When it passes through the discharge valve a. of a fire extinguisher, it changes from a liquid to a gas and the
expansion chills it to low temperatures so that proximate 30 % of the liquid CO2 is converted into solid dioxide "snow"
or "dry ice." The cooling will often cause ice to form around the "horn" where the gas is expelled from the
extinguisher. Since there is the possibility that the fire could re-ignite, continue to apply the agent even after the fire
appears to be out.
4. FOAM - used only on Class A and B fires. Foam removes fuel by forming a layer over a burning liquid and
preventing flammable vapors from escaping. Foam will also smother by keeping Oxygen from mixing with the vapors
and cool with a constant layer of water bearing foam.
5. HALONS - used on Class B and C fires. These liquefied gases are most effective in interrupting the chain
reaction, but they also have slight smothering and cooling effects. These are made up of carbon and one or more
halogen elements like fluorine, chlorine, iodine, and bromine. These types of extinguishers are often used to protect
valuable electrical equipment since they leave no residue to clean up. Halon extinguishers have a limited range,
usually from 4-6 feet. The initial application should be made at the base of the fire, even after the fires have been put
out.
6. METAL/SAND EXTINGUISHERS these types of extinguishers are primarily used for flammable metals (Class
D) and have the characteristics of a blanketing effect (smothering) on the fire. The most common extinguishing agent
used is sodium chloride.
7. HALOTRON I EXTINGUISHERS - These extinguishers are intended for use on class B and Class C fires.
Halotron I is an ozone-friendly replacement for Halon 1211 (which was banned by international agreements starting
1994). This "clean" agent discharges as a liquid, has a high visibility during discharge, does not cause thermal or
static shock, leaves no residue and is non-conducting. These properties make it ideal for computer rooms, clean
rooms, telecommunications equipment, and electronics, and it is expensive.
8. FE-36 - (HYDROFLUOROCARBON-236FA OR KNOWN AS HFC-236FA) it is a DuPont-manufactured Halon
1211 replacement. This agent is less toxic than both Halon 1211 and Halotron I. It has a zero ozone-depleting effect
or potential. FE-36 is not scheduled for phase-out whereas Halotron production to slated to cease in 2015.
9. WATER MIST EXTINGUISHERS - Ideal used for Class A fire where a potential Class C hazard exists. Unlike
an ordinary water extinguisher, the misting nozzle provides safety from electric shock and reduces scattering of
burning materials. In non-magnetic versions, water mist extinguishers are the preferred choice for MRI or NMR
facilities or for deployment on mine sweepers. MRI (Magnetic Resonance Imaging) NMR's (Nuclear Magnetic
Resonance Spectrometers)
STEPS IN USING PORTABLE FIRE EXTINGUISHERS:
1. Pull the pin at the top of extinguisher. When in place, the pin keeps the handle from being pressed, breaking
the plastic or wire inspection band.
2. Point the nozzle or outlet toward the base of the fire. If the hose is clipped to the extinguisher body, unclip it
first. 3.
3. Press the handle above the carrying handle to discharge the agent. To stop the discharge, release the handle.
4. Sweep the nozzle in side to side motion before the flames to spread the extinguishing agent. Direct the agent
at the base of the flames. After the fire is out, probe for smoldering hot spot or liquids that could reignite. Make sure
the fire is out. Back away from the fire area to protect yourself from possible danger or flashback.
Remember the acronym, "P.A.S.S.”
· P - Pull the Pin.
· A - Aim extinguisher nozzle at the base of the flames.
· S - Squeeze trigger while holding the extinguisher upright.
· S - Sweep the extinguisher nozzle from side to side, covering the area of the fire with the extinguishing agent.
INSPECTION AND MAINTENANCE OF EXTINGUISHERS:
Once a fire extinguisher is purchased and installed, it becomes the responsibility of the owner to maintain the
extinguisher so that it remains fully operable. To fulfill this responsibility, there should be a program to provide for the
periodic inspection of each extinguisher and an effective extinguisher maintenance program.
Procedures for Inspecting Various Types of Extinguishers:
1. Check accessibility and proper location;
2. Check for tag for date of last recharge or inspection;
3. Check nozzle for obstruction and operations;
4. Examine for corrosion (leaks at seams) or mechanical damage; The
5. Check lock pin and seal;
6. Determine if full (water level, pressure gauge, weight);
7. Examine condition of hose and hose coupling:
8. Check horns for cracks, dirt, or grease it accumulations;
9. Date of inspection and initials of inspector.
Damaged Extinguishers
Leaked, corroded, or otherwise damaged extinguisher shells or cylinders should be discarded or returned to the
manufacturer for repair.
CAUTION: Never Try To Repair The Shell or Cylinder Subjected To Pressure. If an extinguisher shows slight
damaged or corrosion and it is questionable whether it is safe to use, it should be given a hydrostatic test by the
manufacturer or a qualified testing agency. Leaking hose, leaking gaskets, nozzles, can be replaced by fire brigade
personnel.
Testing Extinguishers:
State when, how, and by whom extinguishers are service tested and hydrostatically tested:
Extinguishers, fire hoses and other fire safety equipment (alarms, exit signs, emergency lights) need to be checked
on a regular basis to ensure they are in working condition. A quick visual check is to be done at least monthly by the
monitoring personnel in the area. Under OSHA regulations extinguishers and hoses must be checked and
documented at least once a year by a qualified inspector.
A sign-off tag should be present for documentation purposes, to verify that the extinguishers have been inspected.
1. Service Test - a service test of an extinguisher 8 an operational test of the extinguisher to see to it that it is
operating properly. This test is normally conducted at least once a year during the scheduled maintenance cycle.
2. Hydrostatic Test - hydrostatic test is an internal pressure check of an extinguisher cylinder or shell to detect
possible failure under pressure. Normally, during the testing the cylinder or shell is filled with water (hydro). The test
should be conducted immediately upon discovering of any indication of mechanical injury or corrosion to those
extinguishers which exert internal pressure.
The Following Are Extinguishers Recommended For Testing Every 5 Years: I.
1. Cartridge operated water extinguishers;
2. Stored pressure water extinguishers;
3. Dry Chemical with soldered brass or stainless steel shells;
4. Carbon Dioxide - NOTE: CO2 extinguishers with a cylinder made to DOT specifications should be tested
according to DOT requirements.
WEEK 10
HAZARDOUS MATERIAL IDENTITICATION
Hazard Classification
In the year 1976, the U.S. Department of Defense (DoD) used a hazard classification and identification system all its
own for explosives and other dangerous materials.
After many years of study, the DoD implemented the present classification system based on a system recommended
for international use by the United Nations Organization (UNO).
Below are the listings of all nine UNO Classes of Dangerous Materials:
Class 1 Explosives
Class 1 is divided into four divisions which indicate the type of hazards expected.
A. Class Division1.1
Mass detonating explosives comparable to Quantity-Distance (Q-D) Class 7 and M designated items. Assigned to
this class are principally blast hazards. They may be expected to mass detonate when a small portion is initiated by
any means, such as fire, severe concussion or impact impulse of an initiating agent.
B. Class Division 1.2
Non-mass detonating, fragment producing explosives. These items for which the principal hazards may be fragments,
toxicity, or blast.
C. Class Division 1.3
It includes explosives that present a mass fire hazard. Items assigned to this class usually burn vigorously with little
or no possibility of no possibility of extinguishing fires that have gained headway in storage situations. Explosions
normally are confined to pressure propagating Shock waves or damaging blast or damaging blast pressures beyond
the specified magazine distance. A serious fire-spread hazard can exist from projected burning fragments of
propellant, incendiary materials, packing materials, etc.
D. Class Division 1.4
It includes explosives with a moderate fire hazard, but no blast hazard. Items assigned to this class primarily present
fire hazards producing no blast and virtually no fragmentation or toxic hazards beyond the normal1 fire hazard
(clearance) distance.
Class 2 - Gases: Compressed, liquefied or dissolved under pressure.
Class 3 - Flammable Liquids
Class 4 - Flammable Solids
Class 5 - Oxidizing Substances and Organic Peroxides
Class 6- Poisonous (toxic) and Infectious Substances
Class 6 is divided into 2 divisions
A. Class Division 6.1 Poisonous (toxic) gas, vapors or substances:
These materials are comparable to Q-D Class 8, which includes those CB agents and items normally assembled with
explosive components, or where explosive components present little or no blast or fragment hazards. No quantity-
distances separations have been specifically established for this class as a whole. Special safety criteria or
instructions have not been provided with the stock involved and safety separation appears necessary because of
agent persistency, volatility, toxicity, or other particular feature, requests for information should be made to higher
headquarters.
B. Class Division 6.2 Substances containing disease-producing micro-organisms.
This class division category is included for information only.
Class 7 Radioactive Substances
Class 8-Corrosives
Class 9 Miscellaneous dangerous substances (substances which present a danger not covered by the other classes).
NOTE: The word "Gasoline" may be used in place of "Flammable" for highway transportation of gasoline. The words
"Fuel oil" may be used in place of "Combustible" for highway transportation of fuel oil that is not classed as a
"flammable liquid."
IMPORTANT
1. All four sides of the vehicle must be placarded. Placement of the front placard may occur on either the cab or
the cargo body, from any other marking or sign.
2. Placard must be placed at least 3 inches away from any other marking or sign. Double placarding should be
adjacent to each other.
3. Combinations of vehicles, each of which contains hazardous materials, shall be each placarded in accordance
with the above chart.
FIGURE 3
SOURCE: http://readyandsafe.mt.gov/Home/Articles/nine-elements-of-a-hazardous-material-plan
WEEK 11
OVERHAUL
A complete and detailed check of the structures and materials involved in the fire to
make sure that every spark and ember has been extinguished and to have an
assurance against re-ignition.
SALVAGE
An action taken by the firefighters in preventing excessive damage by fire, smoke, and water with the use salvage
cover or by removing materials out from the burning building