0 04/01/2022 A.

Samy For Approval


Rev Date Created by Description
Project

EZZ Steel Meltshop Expansion


220/30kV AIS S/S

Owner

Consultant:

Drawing Title:

Zigzag Transformer & NER Calculation

Originator Document Number Rev


0
SIEMENS (4)G55071-A2105-VD00C7
energy Pages No.
6
EZZ Steel Meltshop Expansion
220/30kV AIS S/S

I. PURPOSE
This calculation purpose is to adequately size the 30kV ZigZag Transformer & NGR for Ezz Steel S\S Extension

II. CALCULATION INPUT DATA


Refering to the specs S-Schedual (S-3) the following Data is considered to Size the Earthing transformer and the NGR.
Description Input Data Unit
Connection Group ZN
Rated Voltage 36 kV
Syestem Voltage 30 kV
Fault current 0.200 kA
Fault duration 30 Sec

III. Earthing Transformer Rated Data


The required impedance at neutral point for the specified ground fault current according to the above input data
VL
The total Z impedance for 3 phase (ohm) =
√3 . I SC
30
=
√3 . 0.200
Z impedance for 3 phase (ohm) = 86.603 86.603 Ω

The single phase impedance of the earthing transformer with a ZN connection = 3 x 3-Phase Impedance
Z impedance for 1 phase (ohm) = 3 X 86.603 = 259.809 Ω

Zigzag transformer Rated KVA

As Zigzag transformer does not carry the fault current continuously, short time Sizing factor ( K factor ) should be considered:

K factor for time 30 SEC according to ANSI C57.109 defines damage characteristics for oil-
filled, power transformers 0.158

the calculated S rating (KVA) = K Vph Isc

30 X 0.200 X 1000
then the short time calculated S rating (KVA) = Vph Isc = = 3464.102 kVA
√3

So the selected continous S rating is KVA = 0.158 X 3464.102 = 547.329 kVA

3S
The calculated precentage impedance of zigzag transformer (%) = X 100
√3 . VL . I SC
3 X 547.329
= X 100
√3 X 30 X 0.200 X 1000

the calculated precentage impedance of zigzag transformer (%) = 15.80%

Zigzag transformer actual impedance Determination


selected S base (MVA) 0.547329 MVA
selected V base ( kV) 30 kV

2
V
Zbase (Ohm) =
S
30^2
= = 1644.35 Ω
0.547329

So, Z actual of zigzag (ohm) for 1 phase = ZP.U X Zbase


= 1644.35 X 0.158 = 259.8073 Ω

assuming X >>>> R

reactance (X) of zigzag ( ohm) for 3 Z actual


=
phase 3
259.8073
= = 86.603 Ω
3
EZZ Steel Meltshop Expansion
220/30kV AIS S/S

NGR Rating Determination


Normally, we use a combination of R-X, depending on the grounding conditions i.e,
a. A highly inductive grounding is not preferred as this would lead to decrease in life of breaker contacts.
b. A highly resistive grounding would make the system unstable, and costly as the transformer is overdesigned, to insure that
it can take excessive fault current, incase the resistor falls.
Where X/R = 3 is good value in order to avoid the above mentioned problems so,

the calculated resistor ohm R = X/3


86.603
= = 28.867667 Ω
3
the selscted resistor ohm 30 Ω.
Calculate the actual neutral system impedance and grounding current fault

the combined Z of the Connected NGR with the ZigZag Transformer = 𝑥 +𝑅

Z actual of system in ( ohm) = √( (86.603)^2 + (30)^2)

Z actual of system in ( ohm) = 91.652 Ω

VL
Maximum fault current IS.C =( )/ 𝑥 +𝑅
√3
30
IS.C =( )/√( (86.603)^2 + (30)^2)
√3

I actual ground fault in KA 0.188981341 KA


EZZ Steel Meltshop Expansion
220/30kV AIS S/S
250MW,220/30KV TR. Ext.

ANEEXES
SCHEDULE "S - 3"
PARTICULARS AND GUARANTEE

No. Description Unit 30kV


11.2 30kV winding neutral point equipment

A) Current transformer

Ratio A 1250-2500/1, 200/1

Number of cores 1, 1

Burden (at high ratio) VA 30


Accuracy 5P30, CLX

Winding/terminal material Copper

B) Earthing Transformers
a) Rated power (at all tapings) —

b) Connection Group A ZN
c) Insulation Level kV 170
d) Continuous current duration Sec. 30

e) Cooling ONAN
f) Max. Ambient temp. °C 47
g) Rated current A 200
C) Neutral Resistor
a) Resistance OHM To be calculated by the bidder

Fault current A 200


Fault duration Sec 30
Rated voltage KVrms 36

Insulation level: One minute Power


frequency voltage withstand between kVrms/kVpe
70/170
resistance H.V terminal and earthed ak
enclosure /BIL

12 Earthing System

12.1 Earthing system resistance in summer OHM S 0.5

12.2 Touch voltage V S 65

12.3 Earth fault current KA 40

12.4 Duration of earth fault Sec. 1

12.5 Material of the rod & main / sub grid Copper


COl’1dUCtOl'S 8L risers
M

resistance 200A ,
30Sec.