A. Transformer Room
B. HT Room
HV Room for two (2) transformers
4.5x5.0m 4.5x5.0m 4.5x5.0m
(WxL)
HV Room for six (6) transformers
4.5x10.0m 4.5x10.0m 4.5x10.0m
(WxL)
Space required for each additional
80cm 80cm 80cm
panel
Room Height 3.5m 3.5m 3.5m
Page 1 of 4
Description 1000kVA 1250kVA 1600kVA
C. Main LT Breaker
Nos. 7 7 11
Max. Length of LT Cable from
20m 20m 20m
Transformer to LT Panel
E. Fault Level
Page 2 of 4
A. General
5. The space in the front shall be wide enough for loading and off-
loading of transformers from truck with crane.
6. The floor level of the transformer room shall not be higher from
the outside level by more than 300mm but to a minimum of
150mm. (towards transformer access door).
Page 3 of 4
The information presented above deals mainly with the building spaces
and arrangement for the installation of the related equipment.
Lighting
Ventilation
Fire protection