Professional Documents
Culture Documents
Five Switching Devices You Are Likely To Spot in Most of The Low Voltage Switchgear
Five Switching Devices You Are Likely To Spot in Most of The Low Voltage Switchgear
Five switching
devices you are likely to spot in a low voltage switchgear
Depending on the type, switching devices can be used for single or multiple
switching tasks. Switching tasks can also be conducted by a combination of several
switchgear units.
IEC 60947-1 contains the general stipulations for all types of low voltage
switching devices. Further general stipulations for electromechanical control circuit
devices and switching elements can be found in IEC 60947-5-1. The standards set
down ratings for all devices, and defined test values are assigned to these.
Devices for up to 690 V, for example, have a test level of 1890 V for the rated
insulation voltage. The rated impulse withstand voltage U imp (stated on the switch or
noted in the manufacturer’s documentation) for service in power distribution is as a
rule 6 kV (IEC 60947-1, Table H1).
Figure 1 – Examples of
applications for low voltage switching devices
Where:
1. Circuit-breaker,
2. Fuse,
3. Disconnector,
4. Load-break switch,
5. Fused switch-disconnector,
6. Motor starter (motor protection switch),
7. Contactor,
8. Overload relay,
9. Switch-disconnector with fuses,
10. Residual current-operated circuit-breaker (RCCB),
11. Miniature circuit-breaker,
12. Residual current-operated circuit-breaker with overcurrent hipping (RCBO),
13. Residual current-operated miniature circuit-breaker (RCD)
When constructing low voltage installations it must be ensured that no higher
voltages than the rated insulation voltages of the devices can occur .
Table of contents:
1. Circuit breakers
2. Contactors
3. Motor starters
4. Disconnectors, load-break switches and switch disconnectors
5. Fuses
1. Circuit breakers
Circuit-breakers are defined in IEC 60947-2. Circuit-breakers most be capable of
making, conducting and switching off currents under operational conditions.
Furthermore, they must trip in accordance with defined current/time characteristics
under overload and short-circuit conditions.
The basic classification criteria for low voltage circuit-breakers are the design
(compact or open) and the quenching principle (non-current limiting or current
limiting).
They are available for rated currents of up to 6300 A. The rated short-time current l c,
is up to 100 kA.
Figure 2 – ABB’s
compact circuit breakers type EMAX 2 AND TMAX XT with ekip trip units
Current limiting circuit-breakers limit the short-circuit current before the peak of the
first half-wave is reached. Limitation of the peak value significantly reduces the
dynamic and thermal stresses on the connected system.
Figure 3 – Limitation of
the prospective short-circuit current
Current limiting circuit-breakers are particularly suitable for short-circuit protection
of switchgear with a relatively low switching capacity (back-up protection).
Selection of circuit-breakers is first based on the rated voltage Ue, the rated current
and the rated short-circuit breaking capacity. A distinction is made between two
values for rated short-circuit breaking capacity:
The rated short-time current lcw the utilization category, the ambient temperature and
the installation conditions are then to be taken into account. The rated short-time
current lcw is a peak value which is stipulated in accordance with Table 1, but which
does not fundamentally provide any new information.
The utilization category classifies the breaker’s design-related characteristics with
regard to selectivity. The distinction is made between:
L – Overload, with settings for trip threshold (current) and inverse time delay.
S – Selective short-circuit protection, with settings for trip threshold and delay
time with constant energy or definite time characteristic.
I – Instantaneous short-circuit protection, with setting for trip threshold.
G – Earth fault protection, with settings for trip and inverse time delay with
constant energy or definite time characteristic.
Circuit-breakers can also be equipped with residual current releases, making it
possible to implement operator protection. Against direct and indirect contact and
protection against fire.
Figure 5 –
Time/current characteristics of protection releases
2. Contactors
Electromagnetic contactors are defined in IEC 60947-4-1. They are mechanical
switching devices with only one position of rest, which are not operated manually
and are capable of connecting, conducting and disconnecting currents in the circuit
under service conditions, including operational overload.
Apart from the electromagnetic actuation most often used, there are
also contactors with pneumatic or electropneumatic actuation . For contactors
and control devices on a semiconductor basis, IEC 60947-4-2 covers motor current
circuits, and IEC 60947-4-3 covers non-motor loads with a.c. voltage.
Figure 6 – Example of 3
pole, 100 amp, non-reversing across the line contactor with 24V DC coil and 1 NO
and 1 NC auxiliary contacts
Contactors are selected by utilization categories, as shown in Table 2. In addition,
the ratings (voltage, current, ambient temperature and control voltage) are to be
considered. Background conditions such as switching frequency, number of poles,
type of coordination, short-circuit level, start-up conditions and contact life are also
to be taken into account.
There are various aids and programs available from manufacturers and in the
Internet for selection of contactors. The contactor must be capable of correct
operation within a range of 85% to 110% of the rated control voltage, with control
current flowing. Important accessories for contactors include for example clip-on
auxiliary contact blocks and overload relays for fitting to the contactor output
terminals.
The auxiliary contacts of contactors are „positively driven” in accordance with IEC
60947-5-1. NC auxiliary contacts in the contactors are „ mirror contacts“, i.e. they
cannot be closed at the same time as the NO main contacts. The positive driving
and mirror property are essential in the implementation of safety circuits.
T
able 2 – Utilization categories for contactors to IEC 60947-4-1
Go back to Table of Contents ↑
3. Motor starters
Motor starters based on electromechanical switching devices are also defined in
IEC 60947-4-1. Accordingly, motor starters (Figure 7) are used to start motors,
accelerate them to normal speed, ensure motor operation, disconnect the motor
from the power supply and, by means of suitable protection systems, protect the
motor and the corresponding circuit in the case of overload.
The starter may function as a direct-on-line starter ( DOL), reversing starter (REV),
star-delta starter (YD), heavy starter (HD) or soft starter.
As motor starters are as a rule used on the power distribution level, the components
most be designed for a rated impulse withstand voltage U imp of 6 kV.
Figure 7 –
Basic structure of a motor starter
The protection requirements play a decisive role in the design of a motor starter
(Figure 8).
Figu
re 8 – Alternatives for motor control
Overload relays detect overloading of the motor or the failure of a phase, and then
act on the contactor to switch the motor off. There are both thermal and electronic
overload relays, with various tripping classes (e.g. Class 10 or Class 30) for normal
starting or heavy starting of the motor.
For direct online starting the overload relay is set to the rated service current of
the motor (le), and for star-delta starting to 0.58 × le.
In its simplest version, a motor starter can consist of a single device, namely
a circuit-breaker with thermal / electromechanical releases . A manual motor
starter switch is a circuit-breaker with a special tripping characteristic, as shown in
Figure 8.
Figure 9 –
Functions of a manual motor starter
Go back to Table of Contents ↑
Disconnector
The isolating function of the disconnector in the open position is
characterized by the following features:
Switch-disconnector
A switch-disconnector is a load-break switch that meets the requirements specified
for an isolating distance in the open position.