Professional Documents
Culture Documents
Surge Protective Devices in TN Systems
Surge Protective Devices in TN Systems
If a Type 1 or 2 surge protective device (SPD) is installed downstream of a residual current device, it has to be
expected that, because of the discharged impulse current to PE, this process will be interpreted as residual current
by a residual current device (RCD), and it interrupts the circuit.
Equivalents for SPD classifications
(In the following lines we will use the designation SPD Type 1,SPD Type 2, SPD Type 3)
Definition Definition
acc. to IEC acc.
61643 to EN
61643
SPDs which withstand the partial lightning SPD class I SPD Type 1
current with a typical waveform 10/350
μs require a corresponding impulse test
current Iimp
The suitable test current Iimp is defined in the Class I test procedure of IEC 61643-1
Moreover, if an SPD Type 1 is loaded with partial lightning currents it must be assumed that the high dynamics of
the lightning current will cause mechanical damage on the residual current device (Figure 1 below).
This would override the protective measure “protection against electric shock under fault conditions”.
Figure 1 – RCD destroyed by lightning impulse
current
Of course, this must be avoided. Therefore both lightning current arresters Type 1 and SPDs Type 2 should be
used upstream of the residual current device. Hence, for SPDs Type 1 and 2, the only possible measure for
“protection against electric shock under fault conditions” is using overcurrent protective devices.
The use of SPDs must therefore always be considered in conjunction with a fuse as the overcurrent protective
device. Whether or not a supplementary separate backup fuse must be designated for the arrester branch,
depends on the size of the next upstream supply fuse and the backup fuse approved for the SPD.
The following maximum continuous voltages apply to SPDs Type 1, 2 and 3 when used in TN systems
(Figures 2 and 3 A to B):
Figure 2 –
“3-0” circuit in TN-C systems
Figure 3A
– “4-0” circuit in TN-S systems
Figure 3B
– “3+1” circuit in TN-S systems
<="" ins="" style="box-sizing: border-box; display: block;">
TN-C-S systems
Figure 4 illustrates an example of the connections for use of lightning current arresters and surge protective
devices in TN-C-S systems.
Figure 4 –
Use of SPDs in TN-C-S systems
It can be seen that SPDs Type 3 are used downstream of the residual current device (RCD). In this context, please
note the following:
As a result of the frequency of switching surges in the terminal circuits, SPDs Type 3 are primarily employed to
protect against differential mode voltages. These surges generally arise between L and N.
A surge limitation between L and N means that no impulse current is discharged to PE. Thus, this process can
also not be interpreted as residual current by the RCD. In all other cases, SPDs Type 3 are designed for a nominal
discharge capacity of 1.5 kA. These values are sufficient in the sense that upstream protective stages of SPDs
Type 1 and 2 take over the discharge of high energy impulses. When using an RCD capable of withstanding
impulse currents, these impulse currents are not able to trip the RCD or cause mechanical damage.
TN-S systems
The Figures 5 to 9 illustrate the use of SPDs as part of the lightning protection zones concept, and the
required lightning and surge protective measures for a TN-C-S system.