Professional Documents
Culture Documents
Del Col
Del Col
a r t i c l e i n f o a b s t r a c t
Article history: Several correlations are available in the open literature for computing the heat transfer coefficient during
Received 28 April 2009 flow boiling inside plain channels. With respect to halogenated refrigerants, these correlations are usually
Received in revised form 31 October 2009 compared to data taken in a limited range of evaporation temperature and reduced pressure. More
Accepted 31 October 2009
recently, the adoption of new refrigerants, such as high pressure HFCs and carbon dioxide, requires to lar-
gely extend the pressure range of application of such correlations. Besides, the design of evaporators for
some heat pumping applications, where temperatures are set at higher values as compared to usual evap-
Keywords:
orating temperatures in air-conditioning equipment, requires proper validation of the computing meth-
Flow boiling
Refrigerants
ods.
High pressure The present paper aims at comparing four well-known predicting models to a new database collected
Smooth tube during flow boiling of HCFC (R22) and HFC refrigerants (R134a, R125 and R410A) in a horizontal 8 mm
internal diameter tube. This database is characterized by saturation temperature ranging between
25 °C and 45 °C, reduced pressure spanning between 0.19 and 0.53. Mass velocity ranges between 200
and 600 kg m2 s1 and heat flux between 9 and 53 kW m2.
Evaporating heat transfer coefficients of halogenated refrigerants at such high temperatures have not
been reported in the open literature so far. The discussion of the results will enlighten some similarities
with experimental trends presented in the literature for evaporating carbon dioxide.
Two models tested here show good prediction capabilities of the present experimental data, but not for
all the data sets in the same way. For the purpose of practical use, a simple modification of the correlation
by Gungor and Winterton [1] is proposed, showing that this is able to catch the experimental trends of
the present database with good agreement.
Ó 2009 Elsevier Inc. All rights reserved.
0894-1777/$ - see front matter Ó 2009 Elsevier Inc. All rights reserved.
doi:10.1016/j.expthermflusci.2009.10.035
D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245 235
Nomenclature
conventional data. High pressure and low surface tension have ma- The heat transfer coefficients are measured during flow boiling
jor effects on nucleate boiling heat transfer characteristics. of halogenated refrigerants inside a 8 mm plain copper tube. The
Recent flow boiling papers [2–6] reporting data on halogenated test section is a counter flow tube-in-tube evaporator, where the
refrigerants display limited values of reduced pressure, up to 0.2. refrigerant flows in the inner tube while the heating water flows
Seo and Kim [2] measured heat transfer coefficients during the in the annulus.
evaporation of R22 from 15 to 5 °C saturation temperature, while This new data is compared against some models available in the
Saiz Jabardo and Bandarra Filho [3] performed an experimental literature with the aim of discussing the capability and the accu-
study of convective boiling with R22, R134a and R404A at 8 °C racy of those models in the prediction of the heat transfer coeffi-
and 15 °C. Kim et al. [4] measured the R410A flow boiling heat cient. They are the correlations by Gungor and Winterton [1], Liu
transfer coefficients in smooth and microfin tubes at 15, 5 and Winterton [11], Kandlikar [12] and Wojtan et al. [13,14].
and 5 °C saturation temperature. Park and Hrnjak [5] reported
and compared heat transfer coefficients of R410A and CO2 in a
6.1 mm inner diameter smooth tube during evaporation at low 2. Experimental apparatus and procedure
temperature (15 °C and 30 °C).
Silva Lima et al. [6] reported heat transfer coefficients taken 2.1. Flow boiling apparatus
during flow boiling of R134a in a 13.8 mm internal diameter tube
at saturation temperature ranging between 5 and 20 °C, mass A schematic of the experimental setup is provided in Fig. 1. The
velocity of 300 and 500 kg m2 s1, heat flux of 7.5 and experimental facility consists of two loops: the refrigerant loop and
17.5 kW m2. The influence of saturation temperature is discussed the water loop. In the first loop the refrigerant is pumped as sub-
at different values of heat flux and mass flux. cooled liquid and then it is heated – and in some cases partially
A wider range of reduced pressure can be found in [7,8]. Greco evaporated – in the preheater to achieve the desired conditions
and Vanoli [7] reported heat transfer coefficients in a 6 mm tube at the inlet of the test section. The refrigerant enters the tube side
with R22, R134a, R404A, R410A and R507A in a wide range of of the test section as subcooled liquid or saturated vapor and then
evaporating pressure, between 3 bar and 12 bar. Maximum evapo- it is vaporised against the hot water flowing in the annulus. After,
rating temperatures were reached for R404A and R134a, corre- the two-phase mixture leaves the test section and goes to a braised
sponding to 23.5 and 28.6 °C, respectively. In [8] the same plate condenser, where it is fully condensed and subcooled. A blad-
authors discussed the effect of the evaporating pressure on the der accumulator connected to a nitrogen bottle is installed in the
heat transfer coefficients for R410A and R404A, with reduced pres- refrigerant loop. The refrigerant flow can be independently con-
sure up to 0.24 and 0.32 respectively. trolled by a magnetic coupled gear pump.
No data at higher reduced pressure is available for halogenated The thermodynamic conditions at the inlet of the test section
refrigerants, but higher reduced pressure values can be found in are determined from pressure and temperature if the liquid is sub-
flow boiling studies with carbon dioxide. Yun et al. [9] and Oh cooled. In the case of saturated vapor, the inlet vapor quality to the
et al. [10] have reported CO2 evaporating heat transfer coefficients test section is determined from the heat extracted in the preheater,
and compared them to the values measured with halogenated which can be controlled varying water temperature and flow rate.
refrigerants. Those comparisons are usually made with R134a or In the same way, the heat transfer rate in the test section can be
R22 at the same saturation temperature as CO2, which means far varied by adjusting water temperature and flow rate. Thus vapor
different pressure and much different thermophysical properties quality, mass velocity, and heat flux can be independently
between the carbon dioxide and the halogenated refrigerant. controlled.
Therefore, in the graphs of heat transfer coefficient, carbon dioxide The preheater and the test section are coaxial tube-in-tube heat
and R134a usually display opposite trends, with CO2 heat transfer exchangers, in which the refrigerant flowing inside the tube is
coefficient decreasing while R134a coefficient increasing with heated and vaporised by hot water flowing in the annulus side.
vapour quality [9]. In the hot water circuit, an electrical heater supplies the water with
The aim of the present paper is to report new data measured the power transferred to the refrigerant.
during flow boiling of halogenated refrigerants at high saturation The temperature of the hot water entering the preheater and
temperature, which allow to cover a range of reduced pressure the test section is controlled by a secondary water circuit. The
from 0.2 to 0.5, which is usually not covered by experimental dat- water from the test section and from the electric boiler are mixed
abases and thus can be used for assessment of predicting models. together in a storage tank, where the water temperature is
236 D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245
maintained constant. Thermostatic control of the water is accom- where Q_ is the heat flow rate exchanged in the tube, A is the heat
plished by adjusting the electrical power supplied to the heater. transfer surface area, Ts is the mean saturation temperature, Tw,in
The experimental setup used for the present experiments is the and Tw,out are the wall temperatures at inlet and outlet. The heat
same as used for condensation tests [15]. flow rate is obtained from the energy balance on the water side:
Q_ ¼ m
_ wat cwat ðT wat;in T wat;out Þ ð3Þ
2.2. Test section and data reduction
Enthalpy change and vapour quality change in the test section
The test section is divided into two different sectors: a pre-con- are obtained from the heat flow rate and the refrigerant mass flow
ditioning section around 300 mm long, where the refrigerant flow, rate, which is measured by a Coriolis effect mass flow meter, in-
under vaporisation, achieves a fully developed flow regime, and serted downstream of the pump. Measured heat transfer coeffi-
the measuring section, around 1.0 m long, in which the heat trans- cients can be looked at as quasi-local values, since the vapour
fer coefficient is measured. This structure is obtained using a single quality change is in the range 15–25% for most of the data.
1.6 m long inner tube and two separate heating water jackets, con- For each test run, the refrigerant mass flux is controlled by set-
nected in series on the water side. ting the gear pump. Saturation temperature can be controlled by
The inner tube, which is the test tube, is instrumented with varying the pressure in the apparatus using the bladder accumula-
eight copper-constantan (type T) thermocouples embedded in its tor. During test runs, saturation temperature variation within ±1 K
wall to measure the surface temperature. The thermocouples are around the target value was allowed. Since no electrical heating is
inserted and soldered into four equidistant axial grooves. Four used in the present apparatus, the heat flux can be varied by set-
thermocouples are located 100 mm past the inlet of the measuring ting the water temperature at the inlet of the test section.
section. The other four thermocouples are located 100 mm before As previously stated, the experimental heat transfer coefficients
the outlet. are reduced from the measured values of saturation temperature
The water temperature change in the test tube is measured by a and wall temperature. The saturation temperature is obtained
four junction copper-constantan thermopile inserted into appro- from the pressure, which in turn is determined as a linear interpo-
priate mixing chambers. A metal helix is wound around the test lation between the values measured at inlet and outlet of the test
tube inside the annulus, in order to avoid stratification in the water section: because of the low pressure drop in the tube, this assump-
flow and to get high heat transfer coefficient on the water side to- tion leads to negligible error in the data reduction.
gether with appropriate values for the water temperature The pressure measurement at the inlet of the test tube is com-
decrease. pared to the refrigerant temperature directly measured in the adi-
Two digital strain gauge pressure transducers (absolute and dif- abatic sector before the test section. When saturated refrigerant
ferential transducers) are connected to manometric taps to mea- flows in the tube, the difference between saturation temperature
sure the vapour pressure upstream and downstream of the test determined from pressure and directly measured refrigerant tem-
tube. Refrigerant temperatures at inlet and outlet of the test sec- perature is within the experimental uncertainty of the two sen-
tion are measured by means of adiabatic sections, with thermocou- sors. For pure fluids, the two values differ by less than 0.15 K at
ples inserted into both the refrigerant flow and the tube wall. high mass velocity. Higher deviations are found at low vapour
The heat flow rate transferred in the test tube is derived from an quality, and are probably due to non-equilibrium in the flow
enthalpy balance on the heating water side. The average heat and to local sub-cooling at the inlet of the test section. Since an
transfer coefficient a is obtained from the following equation: important contribution to the experimental uncertainty is associ-
ated to the determination of the saturation temperature, the sat-
Q_ uration-to-refrigerant temperature difference has been compared
a¼ ð1Þ
ADtml to the wall superheat for each test run: the data points character-
ðT w;in T w;out Þ ized by ratios of temperature difference (saturation minus refrig-
Dtml ¼ T T s
ð2Þ erant) to wall superheat higher than 5% have not been considered
w;in
ln T w;out T s in the present work.
D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245 237
Table 3
Experimental conditions of the present database (the width of range for evaporating temperature and heat flux in each data set is also reported).
Np pRED Tev G q x
(/) (/) (°C) (kg m2 s1) (kW m2) (/)
R134a 36 0.19–0.29 31 (0.5, +1.0) 400 28.5 (3%, +4%) 0.07–0.87
43 (0.1, +1.0) 400 14.0 (7%, +4%)
43 (1.0, +1.0) 400 26.5 (3%, +3%)
43 (0.5, +0.5) 600 30.0 (2%, +2%)
45 (0.5, +0.5) 200 14.0 (6%, +6%)
R22 15 0.26–0.29 35 (1.0, +1.5) 400 26.5 (3%, +4%) 0.21–0.72
35 (2.5, +2.0) 400 52.5 (1%, +1%)
R125 37 0.37–0.41 26 (1.5, +1.0) 200 9.0 (7%, +7%) 0.16–0.91
26 (1.0, +1.0) 200 14.5 (3%, +2%)
26 (2.0, +0.5) 400 12.0 (7%, +6%)
26 (1.0, +1.5) 400 21.0 (8%, +8%)
R410A 20 0.49–0.53 40 (1.0, +1.0) 200 15.0 (1%, +1%) 0.12–0.95
41 (0.5, +1.0) 200 23.0 (8%, +5%)
41 (1.0, +2.0) 400 24.0 (6%, +6%)
Fig. 2. R134a heat transfer coefficients vs. vapour quality at 31 and 43 °C saturation Fig. 5. R125 heat transfer coefficients vs. vapour quality at 26 °C saturation
temperature Ts. Average values of mass velocity G and heat flux q are reported for temperature (Ts). Average values of mass velocity G and heat flux q are reported for
each set. each set.
Fig. 3. R134a heat transfer coefficients vs. vapour quality. Average values of Fig. 6. R410A heat transfer coefficients vs. vapour quality. Average values of
saturation temperature Ts, mass velocity G and heat flux q are reported for each set. saturation temperature Ts, mass velocity G and heat flux q are reported for each set.
and lasts until the liquid remains at the bottom of the tube. For the tension. The important role of these parameters will be discussed
two test runs depicted in Fig. 2 the dryout inception is predicted at in the following.
0.75–0.77 vapor quality by the Wojtan et al. [13] map, in agree- In Fig. 5, at 200 kg m2 s1 mass velocity the inception of dryout
ment with the present experimental trends. occurs at vapour quality between 0.8 and 0.9, depending on the
Fig. 3 reports the heat transfer coefficients measured during heat flux. At 400 kg m2 s1 mass velocity, dryout inception is
flow boiling of R134a at 43–45 °C saturation temperature, corre- found before 0.8 vapor quality. Being the surface tension much
sponding to around 0.3 reduced pressure. Mass velocity G is equal lower in comparison with R134a and R22, the liquid film may be
to 200 and 400 kg m2 s1, while heat flux q goes from 14 to entrained more easily into the vapour core and the dryout incep-
26.5 kW m2. tion can be encountered at lower quality.
As previously shown, the heat transfer coefficient first decreases The heat transfer coefficients measured with R410A at around
and then increases with quality, with the presence of a local min- 40 °C saturation temperature are plotted in Fig. 6. R410A is a nearly
imum both at G = 200 kg m2 s1, q = 14 kW m2 and at azeotropic mixture, displaying a pressure of 24.3 bar at 40 °C. Test
G = 400 kg m2 s1, q = 26.5 kW m2. The positive effect of the heat results are reported for two data sets, at different values of mass
flux on the heat transfer coefficient can be seen here by comparing velocity and heat flux.
data sets at same mass velocity but different heat flux. For both data sets, the experimental heat transfer coefficient
At the same heat flux, at low vapour quality, the difference be- diminishes when increasing vapour quality, for the entire range
tween heat transfer coefficients at different mass velocities, of vapour quality. This trend is clearly different from the one plot-
200 kg m2 s1 and 400 kg m2 s1, is limited, since nucleate boil- ted in Fig. 3 for R134a, at roughly the same operating conditions.
ing is expected to be dominant in this region. R134a and R410A present different thermophysical properties (Ta-
R22 displays a higher pressure than R134a at the same evapo- ble 4): at 40 °C saturation temperature the reduced pressure is con-
rating temperature. Heat transfer coefficients taken during flow siderably higher for R410A, leading to a much higher vapor density
boiling of R22 at 400 kg m2 s1 mass velocity, 26.5 kW m2 aver- (103 kg m3 for R410A vs. 50 kg m3 for R134a) and much lower
age heat flux and 35 °C saturation temperature, are plotted in vapour velocity in the tube, at the same mass flux.
Fig. 4, for vapour quality between 0.2 and 0.7. The heat transfer With halogenated refrigerants, an increase of the heat transfer
coefficients display a constant trend with vapour quality. When coefficient with vapour quality is expected at usual evaporating
increasing the heat flux to 52 kW m2, higher heat transfer coeffi- temperatures. Therefore, this experimental trend of R410A is unu-
cients by around 15% are measured. On average, the heat transfer sual in the literature. Nevertheless, this decreasing profile is similar
coefficient at the high heat flux seems constant with quality and to the one measured for carbon dioxide [9,10]. The authors in both
to some extent it seems to decrease. From the map by Wojtan papers [9,10] have shown that the effect of mass velocity on the
et al. [13], the inception of dryout at 52 kW m2 heat flux should heat transfer coefficient of CO2 is not important at low vapour
be at 0.7 vapor quality, which seems to be in agreement with the quality (up to 0.4), while the heat transfer is heat flux dependent,
data. However, the data set at 52 kW m2 heat flux is characterized suggesting that the nucleate boiling mechanism is dominant in this
by high vapour quality change, up to 50%; therefore, no precise region. Also Pettersen [17] reported heat transfer coefficients mea-
information on the dryout inception can be obtained. sured with carbon dioxide, at constant heat flux and mass velocity,
A trend of the heat transfer coefficient roughly constant with showing that the higher the evaporating temperature the stronger
vapour quality is measured also with R125 at 400 kg m2 s1 mass the heat transfer decrease vs. vapour quality.
velocity, 21 kW m2 average heat flux and 26 °C saturation tem- Similarities with carbon dioxide can explain the experimental
perature, as plotted in Fig. 5. In the data set at 200 kg m2 s1 mass trend found here for R410A. Therefore, for the sake of comparison,
velocity and 9 kW m2 average heat flux, the heat transfer coeffi- thermophysical properties of carbon dioxide at 5 °C are also re-
cient slightly decreases with vapour quality, suggesting a weak role ported in Table 4.
of the convective boiling. This is due to the thermophysical proper- For carbon dioxide [9] and here for R410A, the drop in heat
ties of this fluid, which is a component of R410A. Although the transfer coefficient is due to the large dominance of nucleate boil-
average evaporating temperature is only 26 °C, it corresponds to ing at low vapour qualities and to partial dryout of the liquid film.
14.1 bar and 0.39 reduced pressure. As reported in Table 4, R125 The dominance of nucleate boiling at low qualities is caused by the
displays a significantly lower liquid-to-vapour density ratio as thermophysical properties of the fluid, such as low surface tension
compared to R134a, for example, and a significantly lower surface and low liquid-to-vapour density ratio.
As the evaporating temperature increases, at low vapour qual-
ity, the nucleate boiling becomes more active because of the lower
Table 4 surface tension as compared to other refrigerants, which means
Properties of saturated vapour.
that more active nucleation sites at a specified heat flux exist. A
R134a R22 R125 R410A* CO2 lower surface tension would also increase the probability of liquid
Temperature (°C) 40 35 25 40 5 entrainment in the vapour core.
Pressure (bar) 10.17 13.55 13.78 24.22 39.70 Furthermore, due to a higher vapour density and thus a lower
Latent heat (kJ kg1) 163.0 172.3 110.4 158.9 214.9 vapour velocity, the suppression of the nucleate boiling will be de-
Liquid density (kg m3) 1146.7 1150.1 1189.4 975.3 896.0 layed. In order to show the increasing relative importance of nucle-
Vapour density (kg m3) 50.09 57.99 90.56 103.27 114.62
Liquid to vapor density ratio 22.9 19.8 13.1 9.4 7.8
ate boiling with pressure, Greco and Vanoli [8] have calculated for
Liq. thermal conductivity 74.72 78.91 59.41 85.67 104.31 R410A the vapour quality at which nucleation is fully suppressed
(W m1K1 103) by using the correlation by Sato and Matsumara [18]. At constant
Vap. thermal conductivity 15.45 12.28 15.18 19.52 21.60 mass flux, in fact, the quality at which nucleation is suppressed
(W m1K1 103)
strongly increases with pressure.
Liq. viscosity (Pa s 106) 161.45 146.92 139.72 98.08 90.82
Vap. viscosity (Pa s 106) 12.37 13.01 13.77 16.01 15.36 As the evaporating temperature increases, at higher quality, the
Surface tension 6.13 6.70 3.83 3.23 3.62 heat transfer coefficient is more rapidly reduced because of the for-
(N m3 103) mation of dryout patches in the annular mist flow.
*
R410A is a nearly azeotropic mixture (the difference of dew to bubble tempera-
Finally, it may be interesting to point out that the tube inclina-
ture at 24 bar is equal to 0.12 K). In this table average values for pressure and for tion has also a different effect on the dryout when changing evap-
surface tension are reported. orating temperature. In the present tests with R410A carried out in
240 D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245
Table 5 fer et al. [19] explained the effect of tube orientation on the dryout
Comparison between experiments and models by Gungor and Winterton [1], Liu and by using the Froude number defined as follows:
Winterton [11], Kandlikar [12] Wojtan et al. [14].
pffiffiffiffiffiffi
xcr G= qv
Gungor and Winterton Liu and Winterton Fr ¼ pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
ffi ð4Þ
eR (%) eAB (%) rN (%) eR (%) eAB (%) rN (%)
gðcos uÞdðql qv Þ
R134a 21.2 21.2 10.5 14 14.2 9 where u is the tube inclination and xcr is the mean quality in the
R22 13.4 13.9 9.7 13.5 17.4 18.1 transition region from completely wetted to completed dry heating
R125 19.1 19.1 8.2 5.5 14.2 17.6
surface. They found pronounced stratification effects and thus an
R410A 18.7 18.7 8.9 22.4 24.3 20.7
All 18.89 18.97 9.56 2.40 16.28 20.56 extended transition range for Fr < 7. The lower the Froude number,
the stronger the influence of tube inclination on the boiling crisis: in
Kandlikar Wojtan et al.
their experiments, they found that the vapour quality change
R134a 4.4 14.7 18.7 12.3 16.4 14
among these two points (completed wetted and completed dry)
R22 27.9 30.8 29.7 19.1 21.7 19.6
R125 22.6 28.4 27.3 5.2 16.9 20.7
was well interpolated by the equation:
R410A 7.7 25.4 31.1 27.3 28 22.1
16
All 11.88 23.88 29.02 4.88 19.20 23.54 Dxcr ¼ ð5Þ
ð2 þ FrÞ2
When comparing R410A at 5 °C and 40 °C evaporating temper-
atures, assuming the same mean quality in the transition region, at
a horizontal tube, the annular flow must be asymmetric from a cer- 40 °C the Froude number (Eq. (4)) is reduced by more than 30%
tain quality, due to the tube orientation. The influence of the tube while the Dxcr (Eq. (5)) is increased by 70% as compared to 5 °C
orientation on the occurrence of the dryout may be significant. Ke- temperature.
Fig. 7. Comparison of experiments with models by Gungor and Winterton [1], Liu and Winterton [11], Kandlikar [12], Wojtan et al. [14].
D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245 241
4. Assessment of correlations By replacing the nucleate boiling term Sap they obtained a cor-
relation in the form:
4.1. Predicting methods !
h x i0:75 q 0:41
0:86 l
a ¼ al 1 þ 3000Bo þ 1:12 ð7Þ
As a result of the present experimental data, it has been found 1x qv
that an evaporating temperature increase leads to an enhanced
contribution of nucleate boiling while convective mechanism is where al is the single phase liquid heat transfer coefficient, Bo is the
penalized and partial dryout may occur earlier. boiling number, ql and qv are densities of liquid and vapour,
In the following the experimental data is compared against four respectively.
well-known correlations available in the open literature. They are Liu and Winterton [11] proposed a general correlation for satu-
the models by Gungor and Winterton [1], Liu and Winterton rated and subcooled flow boiling in tubes and annuli, using the ap-
proach of an asymptotic model with exponent n = 2:
[11], Kandlikar [12] and Wojtan et al. [14].
All these methods consider the Chen’s basic postulate, which a ¼ ½ðSanb Þn þ ðF al Þn 1=n ð8Þ
associates convective and nucleate boiling heat transfer mecha-
nisms in the flow boiling heat transfer coefficient prediction. where F is the convective enhancement factor, and is expressed as a
Gungor and Winterton [1] proposed a simplified general corre- function of vapour quality, Prandtl number and vapour and liquid
lation for saturated flow boiling inside tubes and annuli based on density; S is the suppression factor which depends on the liquid
the superposition model, which assumes that the heat transfer Reynolds number; al is the liquid single phase heat transfer
coefficient is the sum of a nucleate boiling and a convective boiling coefficient.
contribution. The method by Wojtan et al. [14] is a flow pattern based meth-
od; the prediction of the heat transfer coefficient is based on a dia-
a ¼ Eal þ Sanb ð6Þ
batic two-phase flow pattern map [13], which was updated from
Fig. 8. Ratio of calculated to experimental heat transfer coefficient plotted vs. vapour quality. Predictions are made with models by Gungor and Winterton [1], Liu and
Winterton [11], Kandlikar [12], Wojtan et al. [14].
242 D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245
the previous work by Kattan et al. [20]. The stratified-wavy region transfer coefficients at higher quality and above all those referred
has been subdivided into sub-zones and the annular-to-dryout and to R410A.
dryout-to-mist transition curves have been added. The heat trans- The model by Wojtan et al. [14] shows a similar behaviour as
fer coefficients are calculated from the evaluation of wet and dry the Liu and Winterton correlation; it tends to underpredict low va-
perimeters, obtained from the relative flow pattern: pour quality data points and overpredict high quality ones.
With the methods by Liu and Winterton [11] and Wojtan et al.
hdry av þ ð2p hdry Þawet [14], most of the data points referred to R134a, R22 and R125 are
a¼ ð9Þ
2p predicted with an agreement within ±30%. In the case of R410A,
The authors have proposed an asymptotic model with exponent on the other hand, the calculated values are on average higher than
n = 3 for convective and nucleate boiling terms of the heat transfer the experiments by 22% using the first method and 27% using the
coefficient for the wet perimeter. The heat transfer coefficient for second one.
the dry perimeter is calculated as for vapour flow forced When considering the Kandlikar correlation, the ratio of calcu-
convection. lated to experimental values shows that the present model is able
An additional method, the correlation proposed by Kandlikar to catch the experimental trend vs. vapour quality only for the
[12] for saturated two-phase flow boiling heat transfer inside hor- R134a data set. For the data sets referred to the other fluids, heat
izontal and vertical tubes, is used in the present comparison. It transfer coefficients are overpredicted at low vapour quality.
incorporates a fluid-dependent parameter FFL in the nucleate boil- The ratio of calculated to experimental heat transfer coefficient
ing term. The fluid-dependent parameter was given by Kandlikar is plotted vs. heat flux in Fig. 9, vs. mass flux in Fig. 10 and vs. re-
for a limited number of tested fluids, but the author stated the cor- duced pressure in Fig. 11. It may be noted that the deviations be-
relation can be extended to other fluids by evaluating the fluid- tween experiments and predictions do not depend either on heat
dependent parameter for each fluid. flux or mass flux or reduced pressure when applying the Gungor
Kandlikar [21] provided the fluid-dependent parameter for and Winterton [1] correlation. With regard to the predictions plot-
R134a and R22, which is equal to 1.63 and 2.2 respectively. Addi- ted vs. reduced pressure (Fig. 11), Wojtan et al. [14] and Liu and
tional values of the parameter FFL for a wide range of refrigerants Winterton [11] correlations display a similar trend. Instead, the
were provided by Melin [22] as reported in [21]: for R125 the value model by Kandlikar [12] presents the same deviations for the
recommended by Melin is 2.27. Finally, the value of FFL for the aze- whole range of reduced pressure.
otropic mixture R410A is taken from Wattelet et al. [23]: they
determined a value of 3.3 using their data set.
4.2. Comparisons
The comparison with the above correlations was made for all
the data points excluding those at high quality presenting a sharp
decrease of the heat transfer coefficient due to the dryout. The
determination of these points was done by looking both at the
experimental trend of the heat transfer coefficients and at the pre-
dicted flow regime by means of the map by Wojtan et al. [13]. As a
consequence, eight data points have been excluded from these
comparisons, since those methods, except the one by Wojtan
et al. [14], are not applicable to the dryout zone. In total, 34 runs
with R134a, 15 with R22, 35 with R125 and 16 with R410A are
compared against the models. It should be noted here that, apart
from the dryout characteristics, no other filter has been applied
to the data in the comparisons.
Table 5 reports average, mean absolute and standard deviations
obtained from the comparison between experimental and calcu-
lated heat transfer coefficients for each data set.
Calculated vs. experimental heat transfer coefficients are plot-
ted in Fig. 7 for all the models. On average, the correlation by Gun-
gor and Winterton [1] underpredicts the experimental data by 20%
(average deviation is equal to 19%). The other models show better
agreement with data, although their prediction accuracy depends
on the data set. On average, the model by Liu and Winterton [11]
provides the best value of average and mean deviations, equal to
2.4% and 16.3% respectively. The second method providing the best
agreement is the one by Wojtan et al. [14], with 4.9% average devi-
ation and 19.2% mean deviation. Predictions by Kandlikar [12] are
highly scattered leading to a standard deviation equal to 29%.
In Fig. 8 the ratio of calculated to experimental heat transfer
coefficient is depicted and plotted vs. vapour quality for the four
models. The correlation by Gungor and Winterton can catch the
trend with vapour quality but it severely underestimates present
data. The correlation by Liu and Winterton [11] displays much bet- Fig. 9. Ratio of calculated to experimental heat transfer coefficient plotted vs. heat
ter average agreement with data and is able to follow the experi- flux. Predictions are made with models by Gungor and Winterton [1] and Liu and
mental trend for some fluids, but it tends to overpredict the heat Winterton [11].
D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245 243
4.3. Modified Gungor and Winterton correlation the experimental heat transfer coefficients measured for R134a
at 43 °C saturation temperature, 400 kg m2 s1 mass velocity
As shown in the previous graphs, the prediction accuracy of the
Gungor and Winterton [1] correlation is not significantly affected
by any parameter (vapour quality, heat flux, mass velocity, reduced
pressure), as it is also suggested by the low value of standard devi-
ation for each data set. The standard deviation for all the data
points is less than 10%.
For this reason, as a tool for practical applications, the heat
transfer coefficient provided by Gungor and Winterton [1] can be
multiplied by 1.2 in order to get a much closer agreement with
data:
Fig. 11. Ratio of calculated to experimental heat transfer coefficient plotted vs.
reduced pressure. Predictions are made with models by Gungor and Winterton [1]
and Wojtan et al. [14].
Fig. 10. Ratio of calculated to experimental heat transfer coefficient plotted vs.
mass flux. Predictions are made with models by Gungor and Winterton [1] and Fig. 12. Comparison of experiments with model by Gungor and Winterton [1]
Kandlikar [12]. modified as in Eq. (10).
244 D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245
[1] K.E. Gungor, R.H.S. Winterton, Simplified general correlation for saturated flow
boiling and comparisons of correlations with data, Chemical Engineering
Research and Design 65 (2) (1987) 148–156.
[2] K. Seo, Y. Kim, Evaporation heat transfer and pressure drop of R-22 in 7 and
9.52 mm smooth/micro-fin tubes, International Journal of Heat and Mass
Transfer 43 (2000) 2869–2882.
[3] J.M. Saiz Jabardo, E.P. Bandarra Filho, Convective boiling of halocarbon
refrigerants flowing in a horizontal copper tube – an experimental study,
Experimental Thermal and Fluid Science 23 (2000) 93–104.
[4] Y. Kim, K. Seo, J.T. Chung, Evaporation heat transfer characteristics of R-410A in
7 and 9.52 mm smooth/micro-fin tubes, International Journal of Refrigeration
25 (2002) 716–730.
[5] C.Y. Park, P.S. Hrnjak, CO2 and R410A flow boiling heat transfer, pressure drop,
and flow pattern at low temperatures in a horizontal smooth tube,
International Journal of Refrigeration 30 (2007) 166–178.
[6] R.J. Silva Lima, J.M. Quibén, J.R. Thome, Flow boiling in horizontal smooth
tubes: new heat transfer results for R-134a at three saturation temperatures,
Applied Thermal Engineering 29 (2009) 1289–1298.
[7] A. Greco, G.P. Vanoli, Flow-boiling of R22, R134a, R507, R404A and R410A
inside a smooth horizontal tube, International Journal of Refrigeration 28
(2005) 872–880.
[8] A. Greco, G.P. Vanoli, Flow boiling heat transfer with HFC mixtures in a smooth
horizontal tube. Part I: experimental investigations, Experimental Thermal and
Fluid Science 29 (2005) 189–198.
[9] R. Yun, Y. Kim, M.S. Kim, Y. Choi, Boiling heat transfer and dryout phenomenon
Fig. 14. Experimental and calculated heat transfer coefficients vs. vapour quality of CO2 in a horizontal smooth tube, International Journal of Heat and Mass
for R410A. Transfer 46 (2003) 2353–2361.
[10] H.-K. Oh, H.-G. Ku, G.-S. Roh, C.-H. Son, S.-J. Park, Flow boiling heat transfer
characteristics of carbon dioxide in a horizontal tube, Applied Thermal
and 26.5 kW m2 heat flux: the experimental uncertainty band and
Engineering 28 (2008) 1022–1030.
the predictions by means of Liu and Winterton [11] correlation, [11] Z. Liu, R.H.S. Winterton, General correlation for saturated and subcooled flow
Wojtan et al. [14] model and the modified correlation from Eq. boiling in tubes and annuli, based on a nucleate pool boiling equation,
(10) are also reported. The graph in Fig. 14 reports experimental International Journal of Heat and Mass Transfer 34 (1991) 2759–2766.
[12] S.G. Kandlikar, A general correlation for saturated two-phase flow boiling heat
and predicted values for R410A at 41 °C saturation temperature, transfer inside horizontal and vertical tubes, Journal of Heat Transfer 112
400 kg m2 s1 mass velocity and 24 kW m2 heat flux. (1990) 219–228.
[13] L. Wojtan, T. Ursenbacher, J.R. Thome, Investigation of flow boiling in
horizontal tubes: part I – a new diabatic two-phase flow pattern map,
International Journal of Heat Mass Transfer 48 (2005) 2955–2969.
5. Conclusions [14] L. Wojtan, T. Ursenbacher, J.R. Thome, Investigation of flow boiling in
horizontal tubes: part II – development of a new heat transfer model for
New heat transfer data measured during flow boiling of R134a, stratified-wavy, dryout and mist flow regimes, International Journal of Heat
Mass Transfer 48 (2005) 2970–2985.
R22, R125 and R410A at high saturation temperature, and thus [15] A. Cavallin, G. Censi, D. Del Col, G.A. Longo, L. Rossetto, Experimental
high reduced pressure, are presented in this paper. Reduced pres- investigation on condensation heat transfer and pressure drop of new HFC
sure covers a range between 0.2 and 0.5. Experimental trends of refrigerants (R134a, R125, R32, R410A, R236ea) in a horizontal smooth tube,
International Journal of Refrigeration 24 (1) (2001) 74–88.
heat transfer coefficient vs. vapour quality vary depending on fluid
[16] ISO, Guide to the Expression of Uncertainty in Measurement, 1995.
and experimental conditions: the heat transfer coefficient in- [17] J. Pettersen, Flow vaporization of CO2 in microchannel tubes, Experimental
creases with vapour quality (for R134a), is roughly constant (for Thermal and Fluid Science 28 (2004) 111–121.
[18] T. Sato, H. Matsumura, On the conditions of incipient subcooled-boiling with
R134a, R22, R125) or even decreases with vapor quality (in the case
forced convection, Bulletin of JSME 7 (26) (1964) 392–398.
of R410A). The discussion of results have evidenced that nucleate [19] V. Kefer, W. Kohler, W. Kastner, Critical heat flux and post-CHF heat transfer in
boiling plays a key role at high evaporating pressure. Besides, the horizontal and inclined evaporator tubes, International Journal of Multiphase
decreasing heat transfer coefficients measured for R410A vs. va- Flow 15 (3) (1989) 385–392.
[20] N. Kattan, J.R. Thome, D. Favrat, Flow boiling in horizontal tubes: part 3 –
pour quality have been explained by discussing similarities with development of a new heat transfer model based on flow pattern, Journal of
carbon dioxide data available in the literature. Heat Transfer 120 (1998) 156–165.
D. Del Col / Experimental Thermal and Fluid Science 34 (2010) 234–245 245
[21] S.G. Kandlikar, Flow boiling in circular tubes, in: Handbook of Phase Change, [23] J.P. Wattelet, J.C. Chato, B.R. Christoffersen, J.A. Gaibel, M. Ponchner, P.J. Kenny,
Boiling and Condensation, London, 1999, p.367–402. R.L. Shimon, T.C. Villaneuva, N.L. Rhines, K.A. Sweeney, D.G. Allen, T.T.
[22] M. Melin, Measurements and modelling of convective vaporization for Heshberger, Heat Transfer Flow Regimes of Refrigerants in a Horizontal Tube
refrigerants in a horizontal tube, Ph.D. Thesis, Chalmers University of Evaporator, ACRC TR-55, University of Illinois at Urbana-Champaign, 1994.
Technology, Goteborg, Sweden, 1996.