You are on page 1of 4

RAYSTAT-EX-02

SURFACE SENSING MECHANICAL THERMOSTAT

This EEx d approved surface sensing thermostat provides


temperature control for all nVent RAYCHEM BTV, QTVR, KTV,
VPL and XTV heating cables in hazardous areas. The switching
temperature range is –4°C to +163°C and is adjustable externally
to the Ex enclosure by a dial mounted under a bolted-on cover
and seal.
R
CO AY
NT ST
RO A
L T T-E
The switching current capacity is 22 A. It has a single pole
HE X

change-over switch with volt-free contacts.


RM -02
OS
TE TA
MPE
RAT
T
UR
SC
HA
LT
ER
FU
R

Cable entry is through a single 3/4" NPT thread entry.


nVent RAYCHEM cable glands are available to suit non-armoured
and armoured cable.
The 3 m long stainless steel fluid filled bulb and capillary give
freedom to locate the enclosure remote from the bulb. The bulb
exposure range is –50°C to +215°C.
The cast aluminium construction with stainless steel fittings
gives a lightweight unit which can be pipe mounted using nVent
RAYCHEM support brackets or surface mounted.

THERMOSTAT
Area of use Hazardous area: Zone 1, Zone 2 (Gas), Zone 21, Zone 22 (Dust)
Ordinary

APPROVALS
LCIE 08 ATEX 6095 X
Ex II 2 G D
IECEx LCI 08.0036X
Ex d IIC T6
Ex tD A21 IP66 T80°C
 TC RU С-ВЕ.ИМ43.В.01764 ООО "ТехИмпорт"
1Ex d IIC T6 Gb X
Ex tb IIIC T80°C Db X
Ta -40°C…+60°C IP65
Made in USA

ENCLOSURE

Body and lid Lacquer coated cast aluminium with stainless steel fittings and nitrile rubber internal lid seal
Protection IP 65 if installed with nVent RAYCHEM cable glands GL-33 or GL-34
Lid fixing Screw thread lid locked in place by a 2 mm hexagonal key grub screw
Entry 1 x 3/4" NPT
Ambient operating temperature –40°C to +60°C

Raychem-DS-DOC2210-RAYSTATEX02-EN-1812 nVent.com | 1
RAYSTAT-EX-02
TEMPERATURE SENSING
Type Fluid filled bulb and capillary
Dimensions Capillary 3 m long, bulb 197 mm x 8 mm
Material Stainless steel (Type 55316)
Exposure temperature –50°C to +215°C
Minimum bend radius Do not bend bulb, 15 mm for capillary

DIMENSIONS (IN MM)

∅8

101.5
114.5 30.5
101.5 8.5

51
25.4
101.5
114.5
197

Hex.
3/4" NPT entry
167

∅ 1.5

SWITCHING
Type Single pole change over volt free contacts (SPDT)
Rating 22 A at 480 Vac, switching (100.000 cycles)

SETTING
Range –4°C to +163°C
Repeatability ±1.7 K
Differential 5K
Accuracy (switch on) ±4.5°C at 21°C ambient and 50°C sensor temperature
Method External knob and dial

CONNECTION TERMINALS
Supply 3 terminals for 1 to 4 mm2 conductors
Internal earth Single bolt for 1 to 4 mm2 conductors
External earth Single bolt and clamp for 1 to 4 mm2 conductors

CONNECTION DETAILS AND THERMOSTAT CONTROL SYSTEM

RAYSTAT-EX-02

Junction
box
L
Supply N
C NO NC
L L N N

Note: If live link is present,


it must be removed by
installer Heating cable conductor
Heating cable conductor
Heating cable braid

Raychem-DS-DOC2210-RAYSTATEX02-EN-1812 nVent.com | 2
RAYSTAT-EX-02
Maximum recommended heating cable lengths (230 V supply)
The maximum recommended heating cable length is restricted by the electrical protection sizing or the switching capacity of the
RAYSTAT-EX-02.
For circuits and electrical protection rated up to and including 20 A
Use the maximum recommended heating cable lengths, mentioned in the cable datasheet.
For circuits and electrical protection rated above 20 A but less than or equal to 22 A
Use the shorter length of the values given in the cable datasheet and those given for your switching temperature in the
table below.
For circuits and electrical protection rated above 22 A, RAYSTAT-EX-02 must NOT be connected for direct switching.

HEATING- CABLE REFERENCE


10BTV2-CT/-CR
8BTV2-CT/-CR
3BTV2-CT/-CR

5BTV2-CT/-CR

20XTV2-CT-T2
12XTV2-CT-T3

15XTV2-CT-T3
8XTV2-CT-T3
4XTV2-CT-T3
20QTVR2-CT
10QTVR2-CT

15QTVR2-CT

20KTV2-CT
15KTV2-CT
8KTV2-CT
5KTV2-CT

15 VPL2

20VPL2
10VPL2
5VPL2
Switching
temp. (°C) L max. (m) - Maximum recommended heating cable length
5 200 165 120 105 110 85 65 230 145 105 85 65 200 145 90 65 220 145 95 70
10 200 165 120 105 110 90 65 235 150 110 85 65 205 145 90 65 220 150 95 70
15 200 165 120 105 115 90 70 245 155 110 85 65 210 150 95 65 220 150 95 70
20 200 165 120 105 115 95 75 250 160 115 90 65 215 155 95 70 220 150 100 70
25 200 165 120 105 115 95 75 250 165 120 90 70 220 160 100 70 220 155 100 75
30 200 165 120 105 115 95 80 250 170 125 95 70 225 160 100 70 220 155 100 75
35 200 165 120 105 115 95 85 250 180 130 95 75 225 165 105 75 220 155 100 75
40 200 165 120 105 115 95 90 250 180 135 100 75 225 170 105 75 220 155 105 75
45 200 165 120 105 115 95 95 250 180 140 100 75 225 175 110 80 220 155 105 75
50 200 165 120 105 115 95 105 250 180 145 105 80 225 180 115 80 220 155 105 75
55 200 165 120 105 115 95 110 250 180 145 110 80 225 180 115 85 220 155 105 80
60 200 165 120 105 115 95 110 250 180 145 110 85 225 180 120 85 220 155 110 80
65 200 165 120 105 115 95 110 250 180 145 115 85 225 180 125 90 220 155 110 80
70 -- -- -- -- 115 95 110 250 180 145 120 90 225 180 130 95 220 155 110 80
75 -- -- -- -- 115 95 110 250 180 145 120 90 225 180 130 95 220 155 115 80
80 -- -- -- -- 115 95 110 250 180 145 125 95 225 180 130 100 220 155 115 85
85 -- -- -- -- 115 95 110 250 180 145 130 100 225 180 130 105 220 155 115 85
90 -- -- -- -- 115 95 110 250 180 145 130 100 225 180 130 110 220 155 120 85
95 -- -- -- -- 115 95 110 250 180 145 130 105 225 180 130 110 220 155 120 85
100 to 110 -- -- -- -- 115 95 110 250 180 145 130 110 225 180 130 110 220 155 120 85
115 to 120 -- -- -- -- -- -- -- 250 180 145 130 110 225 180 130 110 220 155 125 90
125 to 150 -- -- -- -- -- -- -- -- -- -- -- -- 225 180 130 110 220 155 125 95

MOUNTING METHOD
nVent RAYCHEM support bracket nVent RAYCHEM SB-100, SB-101, SB-110, SB-111, SB-125 or surface mounting with 4 fixing holes
(M6) on 101.5 x 101.5 mm centres

SETTING
Power cable gland for armoured cable GL-33 493217-000
Power cable gland for non-armoured cable GL-34 931945-000
(to be ordered separately)

ORDERING DETAILS
Part description RAYSTAT-EX-02
PN (Weight) 404385-000 (1.77 kg)

Raychem-DS-DOC2210-RAYSTATEX02-EN-1812 nVent.com | 3
North America Europe, Middle East, Africa Asia Pacific Latin America
Tel +1.800.545.6258 Tel +32.16.213.511 Tel +86.21.2412.1688 Tel +1.713.868.4800
Fax +1.800.527.5703 Fax +32.16.213.604 Fax +86.21.5426.3167 Fax +1.713.868.2333
thermal.info@nvent.com thermal.info@nvent.com cn.thermal.info@nvent.com thermal.info@nvent.com

Our powerful portfolio of brands:


nVent.com CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACER

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice. 4
Raychem-DS-DOC2210-RAYSTATEX02-EN-1812

You might also like