You are on page 1of 20

S210-100 IOM/MAY2003

File: SERVICE MANUAL - Section 70


Replaces: S210-100 IOM/AUG 2000
Dist: 3, 3a, 3b, 3c

Installation - Operation - Maintenance

!"#$%& '(

Hygienic Air Handling Units

THIS MANUAL CONTAINS RIGGING, ASSEMBLY, START-UP, AND


MAINTENANCE INSTRUCTIONS. READ THOROUGHLY BEFORE
BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN DAMAGE OR IMPROPER
OPERATION OF THE UNIT.
S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 2 INSTALLATION, OPERATION, AND MAINTENANCE

Contents
Pre-Installation Requirements ...................................................................................................................... 3
Training & Safety Considerations ............................................................................................................ 3
Identification and Inspection of Shipment ............................................................................................... 3
Transit Damage Claims ........................................................................................................................... 3
Preliminary Siting/Layout Considerations ............................................................................................... 4
Preliminary Field Piping Design Considerations .................................................................................... 4
Installation Procedures ................................................................................................................................. 5
Installation Tools ...................................................................................................................................... 5
Foundation Information ............................................................................................................................ 5
Erecting the ACUair® SYSTEM ............................................................................................................... 6
Duct Work ................................................................................................................................................. 6
Electrical Wiring ....................................................................................................................................... 8
Drain Pan Piping ...................................................................................................................................... 8
Piping Requirements ............................................................................................................................... 8
Inlet Hood and Filter Assembly ................................................................................................................ 9
Start-up & Operation .................................................................................................................................... 10
Initial Start-up (for new ACUair® SYSTEM Units) ................................................................................. 10
Inspection ....................................................................................................................................... 10
Blower, Motor, Drives ...................................................................................................................... 10
Filters .............................................................................................................................................. 10
24-Hour Run In ............................................................................................................................... 10
Daily Operation ...................................................................................................................................... 10
Start-up After Prolonged Shutdown ....................................................................................................... 11
Recommended Maintenance Intervals ................................................................................................. 11
Spare Parts Recommendations ............................................................................................................ 11
ACUair® Maintenance ................................................................................................................................. 11
Maintenance Intervals ........................................................................................................................... 11
Recommended Spare Parts .................................................................................................................. 12
Filters ...................................................................................................................................................... 12
Lubrication ............................................................................................................................................. 13
Standard Motors ............................................................................................................................. 13
Special Motors ................................................................................................................................ 13
Fan Bearings ................................................................................................................................... 13
Blower Bearing Lubrication Guidelines ................................................................................................ 13
Drive Train .............................................................................................................................................. 13
Sheave Inspection .......................................................................................................................... 13
Sheave Alignment .......................................................................................................................... 13
Belt Replacement and Tensioning ......................................................................................................... 14
Blower Belt Tension Guidelines ...................................................................................................... 14
New Belt Run-in ..................................................................................................................................... 15
Coil Maintenance ................................................................................................................................... 15
Control Dampers Installation, Operation, and Maintenance Instructions ............................................ 15
Coil Assembly ........................................................................................................................................ 16
Finish and Sealing ................................................................................................................................. 16
Unit Cleaning and Sanitation ................................................................................................................ 16
Initial Start-up ......................................................................................................................................... 16
Monthly Service ..................................................................................................................................... 16
Troubleshooting ........................................................................................................................................... 18
ACUair® WARRANTY AGREEMENT .......................................................................................................... 19

SAFETY PRECAUTION DEFINITIONS


Indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
Indicates a potentially hazardous situation or practice which, if not avoided, will result in death or
serious injury.

Indicates a potentially hazardous situation or practice which, if not avoided, will result in damage to
equipment and/or minor injury.

NOTE: Indicates an operating procedure, practice, etc., or portion thereof which is essential to highlight.
ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
INSTALLATION Page 3

lock out and tag machinery before working on the unit.


Preinstallation Requirements Proper safety precautions such as the use of insulating
TRAINING & SAFETY CONSIDERATIONS soles/gloves and a trained “lookout buddy” are indispens-
able. Ice formation in cold weather can present fall/slip haz-
The ACUair® precision-engineered hygienic air handling ards. Icing safety procedures should be mandatory when
systems provided by YORK Refrigeration Systems utilizes the daily ambient temperature falls below 40°F.
the finest in HVACR materials and corrosion protection to
deliver dependable, consistent, and accurate control of tem- ACUair® systems typically serve in a continuous-duty ca-
perature and humidity in process room air steams. This pacity and must be properly sited, installed, and connected
manual provides the information needed for safe installa- in the field (by others) to appropriately sized and installed
tion, operation, and maintenance. Close attention to the wiring for electrical power/controls, air ducting, refrigerant
instructions and guidelines provided will ensure the long- lines, and fuel piping. The engineering plans, piping lay-
est possible system life and dependable, consistent outs, etc. for all peripheral “field” work should be detailed in
performance. accordance with local/governing codes and the best indus-
try standards and practices.
Before installing, operating, or
maintaining the system, it is recom- If you have any comments or questions regarding this
mended that only experienced manual or the ACUair® system, you are urged to call your
HVACR contractors, operators, and maintenance labor installing contractor and/or sales representative.
be used (in conjunction with formal training on the
ACUair® system’s design and features). Reading and un- IDENTIFICATION AND INSPECTION OF
derstanding of this manual should serve as the mini- SHIPMENT
mum application-specific training requirement.
Upon arrival of the ACUair® shipment, the system should
ACUair® system installation, operation, and maintenance not be signed for until it is carefully checked against the bill
involves heavy rotating machinery operating at high speed of lading to ensure that all shipping crates and cartons have
and high voltage. Normal operations and maintenance pro- been received. Any items that appear to be missing should
cedures may require working at elevations, enclosed space be noted on the shipping papers. Damage claim protocol
entry, or use of hand and power tools. Taking these consid- generally requires that receiving personnel immediately
erations into account along with the hygienic nature of notify an appropriate transportation company representa-
ACUair® applications, it is clear that safety should always tive for inspection and reporting form execution. Frick / ®

be the top priority. ACUair® should also be notified of any claims made.
Frick recommends that every ACUair® system user ana-
®
The following system components should be inspected:
lyze and develop an installation-specific safety regime that
takes into account such variables as specific site/system • Blower Sheaves, Belts, Bearings/Supports, Shafts, And
features, personnel qualifications, hazard identification, etc. Fan-Wheel
The following elements of operational safety are recom- • Coil(s), Gas Train, Control Panels, Sensors, And Air Lou-
mended for inclusion in every client’s ACUair® system safety vers/Actuators
plan/requirements: • Filters And Other Parts Shipped Loose Inside The System
NOTE: Configure all power switches and controls to pro- Parts shipped loose include filters and any other miscella-
vide an open, safe circuit before and during maintenance neous items that need to be installed in the field (by others).
procedures, until the system is cleared by management These items will likely be shipped in sealed box(es) that is/
for normal on-line operations. For extended shutdowns, are secured inside the ACUair® system. Open each of the
it is recommended that a qualified technician remove operating “manway” access doors to locate all of the “loose
fuses from “fused-disconnect panels” or otherwise open item” packages.
the circuit in an accepted, secure manner. All ACUair® systems are identified by a nameplate perma-
Fans – All fan covers, guards, and shaft retainers (if any) nently attached to the system. Figure 1 - ID Plate Informa-
must be in place before applying power to an ACUair® sys- tion shows a copy of the ID plate as supplied with the system.
tem. Always disengage and lock out power before allowing
interior inspections. To prevent foreign objects from being TRANSIT DAMAGE CLAIMS
sucked into rotating fan blades, never allow operation with
manway/door off/open. The unit should be carefully inspected for shipping dam-
age. The ACUair® system owner’s authorized agent who
Enclosed space inspections – Inspections of coils, filters, signs for the shipment is responsible for making damage
etc., requires machinery lockout and the use of a “lookout claims (per ICC requirement). Request immediate inspec-
buddy” at a minimum – consult your internal safety policy tion and form execution by the agent of the carrier.
and OSHA requirements for additional recommended safety
procedures. Contact the Frick /ACUair® parts and warranty department
®

to report damage claims. Prompt/timely reporting and ad-


Vibration and noise – Discontinue or stop machinery that equate documentation will likely help significantly in the
emits unusual vibration and noise. The source must be in- reporting process.
vestigated (and apparent discrepancies corrected) before
testing or placing the system back in operation. NOTE: When inquiring about the system or ordering re-
pair parts, provide the MODEL and SERIAL NUMBERS
Wet Surface Precautions – Poorly maintained/wetted ma- from the data plates. See Figure 1 - ID Plate Information.
chinery requires care to avoid electrical shocks from inad-
equate/loose field wiring/connections. All personnel must
S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 4 INSTALLATION

Sufficient space must always be available to allow adequate


airflow to the ACUair® system fresh air inlet and exhaust
louvers. In general, ACUair® systems should always be
placed on concrete pads, piers or structural steel so that
exhaust air discharge of the fan orifice is at or above the
elevation of nearby walls or structures/equipment.

For other minimum spacing requirements see Figure 2 for


examples showing ACUair® system(s) installed next to
single/multiple walls.

PRELIMINARY FIELD PIPING


DESIGN CONSIDERATIONS
All ACUair ® systems require
strongly supported and properly
anchored field piping. NO field pip-
ing is to be supported by the ACUair® system itself. Wind
Figure 1 - ID Plate Information loading, temperature variation, etc., must be considered
to allow for movement between the system, adjoining
building, ducting, and field piping. A qualified cooling sys-
PRELIMINARY SITING/ tem design engineer should provide final field-piping
LAYOUT CONSIDERATIONS plans and specifications.
All ACUair® systems must be located to minimize the effect Before finalizing piping installation plans, it is recommended
of exhaust air recirculation. Recirculated exhaust air can that related plans for system/plant expansion be discussed
significantly derate an ACUair® System’s capacity. It is the with your field piping/system designer and Frick /ACUair®
®

owner’s responsibility to properly locate each system and/ sales representative. Incorporating appropriate pipe open-
or consult with a qualified engineer before laying out struc- ings/sizes now (for existing and future needs) allows for
tural/foundation supports and installing the ACUair® system. easier installation in the future.

NOTES:
1. THE MINIMUM DISTANCE FROM THE
EXHAUST FAN HOUSING TO ANY OBJECT
IS ONE FAN WHEEL DIAMETER. IF THE
OBJECT IS ANY CLOSER THE FAN BLAST
COULD DAMAGE THE OBJECT.
2. THE MINIMUM DISTANCE FROM AN
ACCESS DOOR, IN THE OPEN POSITION,
TO AN OBJECT IS THE DOOR WIDTH, I.E.
24", PLUS 8").
3. THE MINIMUM DISTANCE FROM ANY
ELECTRICAL ENCLOSURE TO AN OB-
JECT IS 48". ACUair FEELS IT WOULD BE
ADVISABLE TO CHECK WITH STATE AND
LOCAL ELECTRICAL CODES.
4. A MINIMUM OF 36" IS NECESSARY TO
ALLOW FOR PROPER TRAPPING OF
DRAIN PIPES ON EITHER SIDE OF THE
UNIT.
5. IT IS ACUair's ADVICE TO CONSULT
THE PIPING CONTRACTOR AS TO HOW
MUCH SPACE IS REQUIRED FOR THE
COIL PIPING. A MINIMUM WALK SPACE
OF 30" SHOULD BE LEFT BETWEEN THE
FINAL FIELD PIPING TO ANY OBJECT.
6. AS WITH ANY LARGE EQUIPMENT
PLACEMENT CONSIDERATION OF MAIN-
TENANCE, SERVICE AND PART/COMPO-
NENT REPLACEMENT SHOULD BE AL-
LOWED WHEN DESIGNING SPACE FOR
THE UNIT.

Figure 2 - ACUair System-to-Wall Spacing Requirements


ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
INSTALLATION Page 5

Installation Procedures INSTALLATION TOOLS


To complete the installation of an ACUair® air handling sys-
NOTE: The following instructions are not intended to re-
tem, the following tools are required:
place the service of a mechanic, skilled and experienced
in the installation or repair of ventilation and air condi- • Drift pins
tioning equipment. It is only to acquaint a skilled service • 8-foot straight edge
person with ACUair® HVAC equipment. • Level
Installation of an Frick /ACUair® system involves construct-
®
• Assorted open-end wrenches
ing heavy foundations and/or structural steel supports as • Socket set
well as erecting and anchoring the system. Frick /ACUair®
® • Belt tension gage
strongly recommends that a qualified, bonded, and insured • Caulk Gun
mechanical general contractor be used to perform this heavy • Tape measure
structural work.
FOUNDATION INFORMATION
To facilitate crane use, it is advisable to clear and secure
the designated access area a day in advance to ensure ACUair systems are shipped in two or more sections. These
®

smooth/safe operations the day of the lift. sections must be anchored to suitable “footings” - concrete pads,
concrete piers, or structural steel, capable of supporting the total
Some units have an unbalanced system operating weight plus a significant safety margin
load – extreme care should be as determined by a qualified structural engineer. Support “footing”
taken during initial handling to pro- and anchoring requirements will vary with live loads (expected
vide for a balanced load. Once the ACUair® system sec- snow/ice buildup) seismic, and wind loading.
tions are set and secured in position, the ACUair® SYSTEM
must be secured with permanent anchors to an appropri- See Figures 3 and 4 for ACUair® unit support methods.
ate foundation. If the support “footings” are in the form of two steel beams,
During construction, survey the project site periodically to each should be sized in accordance with standard engi-
ensure that no unattended ACUair® SYSTEM components neering practices. Structural design should account for 55%
or contractor materials/tools remain unsecured. Electrical of the operating weight of the system as a uniform load on
must be made safe against unauthorized site visitors, van- the beam, allowing for a maximum deflection of 1/360 of the
dalism, or weather. length, not to exceed 1/2 inch.

Structural beams need to be shimmed level before final


anchoring. NOTE: Shims between the beams and the sys-
tem should not be used, as this will not provide adequate
support.

Figure 3 - Support Method


S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 6 INSTALLATION

NOTES:
1. SEE UNIT INSTALLATION DIMENSION DRAWING FOR UNIT WIDTH,
LENGTH AND WEIGHT.
2. ALTERNATE METHODS OF SUPPORT TO INCLUDE
SUPPORT AT ALL SECTION SPLITS.
* SUPPORT DESIGNED AND SUPPLIED BY OTHERS.
DRAWING FOR REFERENCE ONLY.
** LEGS TO SUPPORT THE FRAME ABOVE
THE FINISHED ROOF. NUMBER OF
LEGS AND DESIGN BY OTHERS.

Figure 4 - Support Method Alternative

ERECTING THE ACUair SYSTEM ® the section split should be caulked and then the U-channel
placed on top of the caulk and section split. The U-channel is
As mentioned above, the first ACUair® section is hoisted
then self drilled to the upright flanges of the section split. Caulk
into place. Following this procedure, the remaining sec-
the ends of the upright section and the U-channel.
tions are hoisted into position, located, and bolted together.
Note: lifting-cable length is critical as shown in the rig- Unit Section Splits
ging of two sections in Figure 5 Assembly and Place-
Some units are shipped in two or more sections, and have
ment Instructions.
a section split which must be properly prepared and sealed
ERECTION NOTES: to maintain the integrity of the unit casing. Prior to installa-
tion, one of the section splits must have the factory supplied
• For Extended Lifts, Use All Lifting Points and Safety Slings. gasketing installed on the face of the section split.
For Final Placement, Use All Lifting points.
The unit sections must be pulled tightly together before
• Use Spreaders and Blocking To Protect the Flanges of
final installation. Using the lifting lugs, with a chain or cable
the Casing and Prevent Caving In Sides.
puller, is an excellent way to slide the sections together.
•· All safety precautions should be vigilantly enforced while
crane is on site. Only properly trained members of the NOTE: Do not use the bolting flanges on the interior of
crane’s crew should handle hook cables, slings, spread- the unit to draw the unit sections together. Once the unit
ers, etc. sections have been pulled together, bolt the internal sec-
tion split flanges together using the factory supplied bolts,
Care should be taken to avoid handling or shock due to
washers, and nuts.
dropping of the ACUair® unit. NEVER push or pull the unit.
For lifting, slings must be provided with the spreader bars Access for Service
to prevent damaging the housing of the unit. All rigging
materials are to be provided by others. The unit must be ACUair® units have access doors on the units. The mini-
lifted by all four lifting lugs on each section. mum of one door width, 18-24 inches, must be available on
the service door side of the unit for maintenance and ser-
If the unit is to be handled other than vicing. Ideally, a space the width of the unit should be avail-
with the lifting lugs, it must be done able, on one side of the unit, for possible heating and cool-
only using the perimeter base of the ing coil removal.
unit. Extreme caution must be used so as not to damage
the underside of the air-handling unit. In addition, most ACUair® units have an electrical control
panel located on the same side as the doors. By code, this
Some units have an unbalanced door must open at least 90°.
load. Extreme care should be taken
on initial handling of the unit to make DUCT WORK
sure the load is properly balanced.
All duct work for the ACUair® units must be made and in-
Once the sections have been bolted together, both the interior stalled in accordance with all State and local codes and
and exterior seams of the section splits should be completely acceptable industry standards. In all applications of the
caulked water and airtight. The unit is supplied with a U-chan- ACUair® units, the duct work must be a type that is clean-
nel, which goes across the top of the section split. The top of able. The duct work should be taped and sealed so that it is
ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
INSTALLATION Page 7

Figure 5 - Assembly and Placement Instructions

Figure 6 - Connecting Unit Sections


S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 8 INSTALLATION

completely water and air tight. The duct work must be insu- When units are shipped in two or more sections, some of
lated on the exterior of the unit. If the duct work is located on the factory wiring is disconnected for shipping purposes. All
the roof, the insulation must be totally weatherproofed. The wiring is of a cable design and all leads are marked with the
top of the duct work should also be pitched, for water runoff, terminal connection. Once the unit sections have been
if the unit is located on the roof. pulled together, the lead should be fed into the control panel
and reconnected to the pertinent terminal. The entrance
If the duct work is located inside of the controlled area, it into the control panel should then be sealed watertight us-
must be of a double wall construction. The exterior of the ing appropriate conduit seals and packing material.
insulation must be covered with a washable, non-
deteriorating type material. All conduit connections should be brought in to the side or
bottom of the control cabinet, NEVER THE TOP, due to po-
All duct work must be of a cleanable type design. Duct work tential leaking.
must be complete with access and inspection ports in stra-
tegic locations. All interior components within the duct, such DRAIN PAN PIPING
as dampers and turning
If the unit is equipped with a cooling coil, the cooling coil
ELECTRICAL WIRING drain pan should be completely trapped with a minimum of
a four inch water seal. The drain pans in the other sections
All field wiring on the ACUair® unit must be in accordance are primarily used for cleaning and sanitizing purposes.
with National Electric Code and State and local codes. The Therefore, under normal circumstances, they can be sim-
control panel is located on the exterior of the ACUair® unit. ply capped and opened only during the cleaning cycle. If all
Before wiring the unit, make certain of the drains are to be piped, each must have its own sepa-
that the electrical characteristics rate trap.
stamped on the unit motor, control
PIPING REQUIREMENTS
transformer and that shown on the wiring diagram agree
with the available power source. 1. General – Every effort must be made in field piping to
keep the stresses to a minimum on the coil connections.
A terminal strip is provided for simplified control wire hookup.
Refer to the unit wiring diagram for proper control wiring. It a. Allow for thermal expansion and contraction of all field
is essential that all controls are wired in accordance with piping.
the wiring diagram and it is mandatory that all safety con- b. Do not rely on the coil connections to support the weight
trols are wired and operational. The manufacturer’s war- of the field piping.
ranty is revoked when modifications are made in the wiring c. Design piping to minimize transmittal of vibration
control system without factory approval. through the piping to the unit coils.

Figure 7 - Duct Attachment


ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
INSTALLATION Page 9

2. Steam Piping – When a steam coil is supplied, the steam Halocarbon refrigeration coils have
piping must be installed in accordance with state and local not been evacuated or totally dried
codes and accepted industry practices. Please refer to the at the factory. It is the customer’s/
supplied piping diagram for specific information. contractor’s responsibility to provide adequate evacua-
tion of the evaporator coil and ensure that the coil is dry
Prior to shipment, steam coils are pressure tested for a and water free before start-up of the system.
maximum operating pressure of 150 PSI. It is recommended
that the steam pressure be reduced to 15-50 PSI or lower 5. Water or Glycol Coils – It is essential that the piping for
for maximum steam coil life and optimum control operation. the system be done so that all lines can be drained and so
that there are no traps or pockets on the system where
3. Refrigerant Piping – When cooling coil is supplied, all water or glycol can collect and possibly freeze. All piping
refrigeration piping must be installed in accordance with all should be pitched away from the unit coil plus the piping
state and local codes and standard industry practices. should be made so that the coil can be filled with antifreeze
Please refer to the manufacturers refrigerant piping dia- solution during freezing weather.
gram for specific information.
INLET HOOD AND FILTER ASSEMBLY
There must be sufficient flexibility in the piping so that any
vibration from the unit is not transmitted to the building and The outside air inlet hoods for some of the units are shipped
so that the piping joints at the unit are not stressed. All separately for field mounting.
refrigeration lines must be checked and secured to prevent
wear or vibration at all operating conditions. ACUair® units can have two different varieties of inlet hoods.
Refer to the unit specific drawing to determine which type is
4. Evaporator Coils – The evaporator coils are tested for supplied.
150 PSI operating pressure. It is the contractor’s and/or
customer’s responsibility to provide controls and reliefs on The hood is assembled as shown in Figure 8.
the system to prevent refrigeration pressures from becom-
ing higher than the tested operating pressure.

aaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa a a
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
a a aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaa
a aaaaaaaaaaaaaaaaaaaaaaaa

Figure 8 - Optional Hood Assembly


S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 10 OPERATION

Start-up & Operation 2. Belt Tension

a. Adjust belt tension if slipping is evident.


Before attempting to start up and operate any electrical
cooling equipment such as an ACUair® system unit, it is b. Check belt tension after 50 hours of operation and
essential that all personnel associated with it have a basic again after 100 hours of operation.
knowledge of how and why the unit operates in normal
ACUair® SYSTEM fan motors are available for variable fre-
conditions. The following description outlines a standard
quency drive. A high-quality, pulse-width-modulating drive
unit’s general features, operation, and controls.
with proper precautions against voltage spikes allows the
An ACUair® SYSTEM (Hygienic air handler) is an engineered motor to be run as low as 20HZ. This will provide part load
heat transfer device that provides some or all of the listed capacity by reducing unit airflow.
functions: cooling, dehumidification, pressurization, filtra-
Filters
tion, heating, exhaust, and condensation control. Each unit
is engineered and designed for the specific application. The filters for the ACUair® unit are shipped in their original
cartons. The unit includes the necessary filter frames and
Safeties and controls vary with each ACUair® SYSTEM in- filter clips. The filter clips are shipped tie wrapped to the
stallation and may be interfaced with ancillary equipment frames. Once the unit is completely installed and thoroughly
or system controls. All operators should be thoroughly cleaned, the prefilters and final filters should be installed in
trained in an integrated cooling system’s sequence of op- their respective holding frames. Once the final filter sec-
erations and safeties. tions have been installed, the final filter section and the
supply air duct work should be cleaned and sanitized.
INITIAL START-UP
(FOR NEW ACUair SYSTEM UNITS)
® On units equipped with final filters, a final filter pressure
gauge is shipped mounted. The high-pressure tube is con-
After installation of the ACUair® SYSTEM unit, controls, and nected to the gauge at the factory. The open port on the
necessary ancillary/auxiliary equipment, the entire cooling gauge should then be piped to the pilot tube that needs to
system should be prepared before placing the ACUair® SYS- be field installed in the ductwork downstream of the final
TEM unit on-line for the first time. Specifically, the following filters using the tubing supplied.
prestart measures must be completed satisfactorily to en-
sure readiness of the ACUair® SYSTEM. 24-Hour Run In
After 24 hours of operation under load, the following ser-
NOTE: Do not attempt any inspection or maintenance
vices should be performed:
unless the electrical supply has been completely dis-
connected and locked out. 1. Check unit for any unusual noise or vibration.
Inspection 2. Readjust fan belt tension if required.
Do not start the unit until the following inspections prove
operational readiness. Avoid accidents or equipment fail- DAILY OPERATION
ure by rectifying any unsatisfactory condition. The unit should be inspected, cleaned, and lubricated on a
• Inspect general condition of unit, e.g., structural integrity, periodic basis. The required services and recommended
anchors/supports, etc. frequency for each are summarized in the Operation and
Maintenance Schedule in this manual.
• Confirm drive assembly condition and alignment of mo-
tor, bearings/collars, and fan/shaft. A daily ACUair® SYSTEM operations log is a good method
• Confirm proper belt condition and tension. (See Mainte- to assure that no problems develop that may go unchecked.
nance Section) Entries to this “rough” log should be made once each shift.
Any notations should be entered as they occur (or internal
• Check fans and guards for obstructions. policy dictates). It is essential that the maintenance man-
• Check fan(s) for correct rotation and electrical hookup. ager examine notations (from the previous 24 hours) on a
• Understand and prepare for first 24 hour operation mea- daily basis.
sures e.g., new belt run-in procedures. (See New Belt As safety/weather dictates, a visual check of the ACUair®
Run-in section) unit should be made once each shift (daily at a minimum) to
• Understand and prepare the unit prestart-up checklist. check operating conditions. Unusual leaks, noise, vibra-
See Appendix A for the prestart up form. tion, part damage/failures, or vandalism should be logged
Blower, Motor, Drives immediately. Corrective action should be initiated immedi-
ately as operations permit - or ensuing service scheduled.
1. Mechanical Tightness
Associated equipment should also be part of the daily op-
a. Check tightness of fan bearing bolts. erational checks for the ACUair® SYSTEM unit. In particular,
b. Check tightness of blower wheels to shafts. filtration performance is important to satisfactory and prob-
lem-free ACUair® SYSTEM unit operation.
c. Check tightness of blower, motor, and sheave.
d. Check tightness of all motor mounting bolts.
ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
OPERATION, MAINTENANCE Page 11

START-UP AFTER PROLONGED SHUTDOWN 6. Check the voltage and current of all three legs of the fan mo-
tors. The current should not exceed the rated service factor. After
Since the ACUair® SYSTEM is exposed to freezing condi- prolonged shutdowns, the motor insulation should be checked
tions and other natural stresses, it is mandatory that main- with a Megger Tester prior to restarting the motors.
tenance personnel conduct a thorough start-up before run-
ning the unit after a prolonged shutdown. 7. Start the fan(s) and check for proper rotation as indi-
cated by sticker on unit.
At minimum, the following checks must be preformed:

1. Clean any debris from guards, fans, eliminators, heat


ACUair® Maintenance
transfer coils, and filters. MAINTENANCE INTERVALS
2. Turn the fan(s) by hand to ensure rotation without ob- Maintenance of the ACUair® SYSTEM is relatively easy if suf-
struction. ficient consideration is given to the minimum maintenance
requirements for keeping air handling units performing to speci-
3. Check and, if necessary, adjust the fan belt tension. (See fication. These can be easily scheduled using the following
Belt Replacement and Tensioning section) “easy reference” preventative maintenance guide provided in
the following Recommended Maintenance Intervals table.
4. Prior to start-up, lubricate the fan shaft and motor bear-
ings. The ball bearings are factory lubricated, but should be Before performing any maintenance or inspection, make
relubricated if the unit has been sitting on site for more than certain that all power has been disconnected, locked out,
a year before start-up. and tagged properly.
5. Check the locking collar on each fan shaft bearing and
tighten if necessary.

RECOMMENDED MAINTENANCE INTERVALS


EVERY 3 EVERY 12
TYPE OF SERVICE START-UP WEEKLY MONTHLY MONTHS MONTHS
Inspect General Condition of Unit X X
Clean debris from unit X X X
Check condition of prefilters X X X
Check pressure drop of final filters X X X
Check drains X X
Inspect heat transfer section X X
Lubricate damper bearings X X
Check and adjust fan belt tension X X
Check burner operation/safties X X
Check unit for unusual noise or vibration X X
Check fan bearing locking collars X X
Check motor voltage current X X
Lubricate fan shaft bearings X X
Lubricate motor base adjusting screws X X
Lubricate the fan motors X X
Check fan for rotation without obstruction X X
Check fan for proper rotation X X
Inspect protective finish X X X
Inspect/adjust damper linkage X X

SPARE PARTS RECOMMENDATIONS It is also advisable to reorder parts prior to taking existing
spares from inventory. This policy helps prevents downtime
ACUair® recommends that customers maintain the follow- due to “forgotten” spare parts order placement.
ing spare parts “in stock” for the ACUair® SYSTEM air han-
dling unit. By maintaining this inventory of spare parts, The type and recommended stock level for each part is
change-out requirements can be immediately satisfied dur- listed in the following Recommended Spare Parts List.
ing preventative maintenance inspections.
S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 12 MAINTENANCE

RECOMMENDED SPARE PARTS* - CURRENT DESIGN


DESCRIPTION FRICK P/N IMECO P/N QTY
QUANTUM™ CONTROL:
Switch Differential Pressure 111Q0280889 0016600453 1
Output Module 240 VAC 111Q0281061 0016600454 1
Input Module 90-140 VAC 333Q0000116 0016600455 1
Relay 120 VAC DPDT 333Q0000194 0016036314 1
Base For DPDT Relay 333Q0000195 0016036315 1
DC Power Supply 640B0060H01 0016600456 1
DC Power Supply 640B0064H01 0016600457 1
Switch Differential Pressure (Unit High Pressure) 649A0998H02 0016600458 1
Fuse, 2A (M-O-A Switch Module) 333Q0001738 0016038016 4
DIRECT-FIRED BURNER:
Flame Relay (for > 2.5 MBTUH burner) — 0088729 1
Flame Relay (for < 2.5 MBTUH burner) — 0088730 1
Purge Card — 0088731 1
UV Flame Amplifier — 0088732 1
Flame Rod Amplifier — 0016040725 1
UV Scanner — 0088733 1
UNIT:
Direct-Fired Burner Air flow Switch 642A0015H01 0016032305 1
Temperature Sensor 640A0035H01 0016022326 2
Smoke Detector (standard on direct-fired units, optional on all others) — 0016037501 1
Humidity Sensor (when ordered as an option) — 0016037402 1
Ammonia Sensor (when ordered as an option) — 0016037507 1
Actuator (return/outside air) — 0016022701 1
Actuator (exhaust fan) — 0016022704 1
Prefilters 24 x 24 x 2" — 0016016600 See Below
Prefilters 24 x 12 x 2" — 0016016700 See Below
Final Filters 24 x 24 x 12" — 0016017009 See Below
Final Filters 12 x 24 x 12" — 0016017012 See Below
NOTE: Fan Belts, Fan Bearings, Fan Bushings, Damper Motors, and Fuses are application specific. Refer to the Spare Parts
List supplied by model & s/n, or contact YORK Refrigeration, Dixon, IL.

FILTERS
MODEL and QUANTITY
TYPE SIZE (in) IMECO P/N AA-10 AA-15 AA-20 AA-30 AA-40 AA-50 AA-60 AA-70
Prefilters 24 x 24 x 2 0016016600 4 6 8 12 15 20 28 28
24 x 12 x 2 0016016700 — — — — 3 — — —
Final Filters 24 x 24 x 12 0016017009 4 6 8 12 15 20 28 28
12 x 24 x 12 0016017012 — — — — 3 — — —
NOTE: These lists are based on one unit. When stocking for more than one unit, the quantity should be adjusted to meet
your individual requirements.
FILTER REPLACEMENT SCHEDULE
Filters
The prefilters, intermediate filters (if applicable), and the Dust Collector Inter-
Filters and mediate Final
final filters (if applicable) are shipped in their original car-
Date 30% Prefilters Filters Filters
tons. The filter frames are factory installed in the unit, and
January X X
the correct filter clips are attached to the filter frames. After February
the unit is completely installed, the filters should be installed March X
in their respective frames. After installation, the final filter April
section and the supply air duct work should be cleaned and May X
sanitized. June X
July X X X
On units that have the final filters mounted directly in the August X
discharge opening, some field mounting of the final filter September X
gauge is required. After the unit and the duct work is com- October
pletely installed, the factory supplied pilot tube should be November X
December
mounted in the supply ductwork and piped to the gauge.

The Filter Replacement Schedule is provided as a guide- spected at regular intervals. The filters should be replaced if
line for filter replacement. The filters should be visually in- they appear excessively dirty or if they appear to be dam-
ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
MAINTENANCE Page 13

aged in any way. The prefilters should be changed if they DRIVE TRAIN
become wet. Failure to follow a filter maintenance schedule
with the factory-specified filters can lead to higher operat- Belt tension should be checked every month as described in
ing costs, reduced system performance, and contaminated Belt Tensioning and Replacement section. The sheaves
air entering the space. should be tight on the shafts and should be aligned properly
to minimize belt wear. The belts should be checked for wear
Filters should be ordered from the Baltimore Parts Cen- along the edges, as any irregularity will cause vibration.
ter. Phone:800-336-7264; Fax: 800-976-1613; E-mail:
baltimore.parts@york.com. Sheave Inspection
Check the sheaves for proper alignment, excessive corro-
LUBRICATION
sion, and wear or damage. Also, check the belt for exces-
Standard Motors sive heat. If the belt is too hot to touch, then the sheaves
may be damaged or need aligning.
Standard ACUair® fan motors are specifically designed for
this application to be maintenance free and no greasing is If the sheaves have excessive corrosion or are worn or
required. Standard motors are furnished with vent connec- damaged, they should be replaced. Check for sharp edges
tions to prevent condensation. Please make sure the vents from wear or pitting of the grooves from corrosion. Either
are not obstructed. Replacement motors are available from condition will promote belt wear and increase turnover.
ACUair ®. Part numbers can be found on the motor Groove gauges are also available to make it easy to see if
nameplate. the grooves are worn. If more than 1/32” of wear can be
seen, the sheave should be replaced.
Special Motors
Sheaves for the motor and fans are designed for this spe-
On occasion, special motors (i.e. two-speed, Chem Duty,
cialized application and are available from ACUair® (do not
etc.) may be specified. These motors must be maintained
substitute).
per the motor supplier’s recommendations and may require
external lubrication lines and special grease. NOTE: The Alignment of sheaves is extremely important for proper belt
grease for special motor bearings and the fan bearings installation. The sheaves are aligned at the factory, but should
may not be compatible. Please check the lubrication la- be rechecked when new belts are installed. Use a straight
bel on the unit. edge to check alignment. Misalignment will show up as a
gap between the outside face and the straight edge. Two
Fan Bearings
conditions for misalignment exist, angular and parallel.
BLOWER BEARING LUBRICATION GUIDELINES
To check both parallel and angular alignment, refer to Fig-
Recommended Lubrication Schedule (in Months)
ure 9 and follow these instructions:
Bearing Bore Diameter in Inches
1. While placing a straight edge across the top of both
11/8" - 15/8" - 2" - 211/16" - 37/16 -
motor and fan sheaves, check for four points of contact.
Fan RPM ½" - 1" 1½" 15/16" 2½" 33/16" 315/16"
To 500 6 6 6 6 5 4
500 - 1,000 6 6 6 5 4 3
1,000 - 1,500 5 5 5 4 3 2
1,500 - 2,000 5 4 4 3 2 1
2,000 - 2,500 4 4 3 2 1 -
2,500 - 3,000 4 3 2 1 2 -
3,000 - 3,500 3 2 2 2 - -
3,500 - 4,000 3 2 1 - - -
4,000 - 4,500 2 1 1 - - -
4,500 - 5,000 2 1 - - - -
If unusual environmental conditions exist - temperatures
below 32°F or above 200°F, moisture or contaminants -
more frequent lubrication is required.
Add grease slowly with a handgun until a slight bead of
grease forms at the seal. Be careful not to unseat the seal
by overlubricating.

A high quality lithium based grease conforming to NLGI


Grade 2 consistency, such as those listed below, should be
used:

Mobil 532 Texaco Multifak #2


Mobilux #2 Texaco Premium RB
B Shell Alvania #2 Unirex N2

Figure 9 - Sheave Alignment


S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 14 MAINTENANCE

2. If a four-point contact is achieved, skip to the belt tension can reduce belt and bearing life. It is not recom-
tensioning section. mended that belt dressing be used when belt slippage oc-
curs as this will damage the belt and cause premature fail-
3. To adjust for parallel misalignment, adjust the motor or ure.
fan shaft sheave.
1. Decrease the center distance between the sheaves (by
BELT REPLACEMENT AND TENSIONING turning the tensioning nut counter clockwise) so the sheaves
are somewhat loose.
Replacement
When it is necessary to replace the belt, follow these steps: 2. Apply tension to the belt by turning the tensioning nut
clockwise.
1. Lock out and tag the starter.
3. Operate the drive a few minutes to seat the belt in the
2. After the power has been turned off and the motor guard sheave grooves. Observe the operation of the drive during
removed, loosen the motor mount adjustment nuts. start-up. A slight bowing of the slack side of the drive indi-
cates proper tension. If the slack side remains taut during
3. Move the motor until there is enough slack in the belt so the peak load, the drive is to tight. Excessive bowing or
it can be removed without prying. slippage indicates insufficient tension. If the belt squeals as
4. Remove the old belts and inspect for unusual wear. Ex- the motor comes on, it is not tight enough. The drive should
cessive wear may indicate problems with alignment or be stopped and the belt tightened.
sheave damage. 4. NOTE: Do not overtighten the drive. If the above pro-
5. Use replacement belts from the factory to ensure a proper cedure still results in the belt squealing, but the belt is
belt equivalent. still taut on the slack side, a more precise method of
testing the belt tension must be used. In this case, use a
6. Inspect other drive components such as bearings and belt-tensioning gage available from V-belt drive manu-
sheaves for alignment, wear, lubrication, etc. facturers or from ACUair®.
7. Clean the sheaves of debris before installing the new All belt tension measuring devices should include operating
belt. instructions. These are spring-loaded devices that use a hook
to place tension on a stationary belt. Tension readings are
8. Install the new belt, align the drive, and tension the belt observed at a point where the belt deflects a predetermined
according to the procedures outlined here. distance. Tension is usually applied at the belt span’s midpoint
Tensioning as measured between the tangent of belt contact for both
sheaves. Reference Blower Belt Tensioning Guidelines table.
Proper belt tension is very important to ensure maximum belt
life. If too little tension is applied, the belt will slip. Too much

BLOWER BELT TENSION GUIDELINES


DIAMETER OF STANDARD WRAPPED S-TX RAW EDGE
SMALL SHEAVE CONSTRUCTION MOLDED COG CONSTRUCTION
BELT INITIAL RE- INITIAL RE-
SECTION FROM (in) TO (in.) TENSION (lb) TENSION (lb) TENSION (lb) TENSION (lb)
2.50 2.80 40 30 50 40
2.80 3.65 50 40 60 50
3V/3VX
3.65 5.00 60 50 70 55
5.00 — 70 55 100 75
5.50 6.30 110 85 140 110
6.30 9.00 140 110 160 120
5V/5VX
9.00 14.00 160 120 180 140
14.00 — 170 130 190 150
2.50 3.20 40 30 60 50
3.20 4.00 50 40 70 55
A/AX/4L
4.00 5.20 60 50 80 60
5.20 — 70 55 90 70
3.60 5.00 60 50 90 70
5.00 6.40 80 60 100 80
B/BX/5L
6.40 8.00 90 70 110 85
8.00 — 100 80 120 90
5.50 8.00 140 110 180 140
8.00 10.50 160 120 190 145
C/CX
10.50 14.00 180 140 200 150
14.00 — 200 150 220 170
ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
MAINTENANCE Page 15

NEW BELT RUN-IN Ammonia refrigeration could share the air stream with food
products and personnel. As such, proper maintenance of
During initial startup of new belts, a belt run-in procedure is
coils, to prevent corrosion and leaks, is essential to prevent
recommended. During start-up, follow these instructions:
product loss and to ensure the safety of plant personnel.
During start-up, look and listen for unusual noise or vibration.
A typical refrigerated food processing facility sparkles with
1. After shutting down and locking out the starter, check stainless steel food contact surfaces and clean work spaces.
the bearings and motor. If they feel hot, the belt tension may However, evaporators that are suspended overhead, trap-
be too tight. ping airborne contaminants and corrosive elements in the
coils, are usually not so sparkly. Dirty coils are unsanitary.
2. Run the drive under full load for 24 hours of continuous They must be cleaned regularly with simple, gentle, wash
operation. Running the belts under full load allows them to and rinse procedures.
seat themselves into the grooves.
For all coils, chlorine-based cleansing solutions, acidic
3. After running the drive, check the tension of the belts. cleansing solutions and highly alkaline cleansing solutions
Re-tension to the recommended values. are hazardous to the coil's health. Use a mildly alkaline
cleanser. Consult with your chemical supplier and read the
This run-in procedure will reduce the future need for re-
Material Safety Data Sheet for your cleansing solution.
tensioning and will help extend the life of the belts.
NOTE: Air units move air (and airborne contaminants)
COIL MAINTENANCE across the coil. Protect the coil from corrosion by wash-
Examine your environment. If structure, equipment, or other ing and rinsing frequently.
elements of your facility show rust or corrosive effects, your
coils are not likely to be impervious to the same effects of CONTROL DAMPERS
the environment. Consider this when formulating your main- INSTALLATION, OPERATION, AND
tenance program. MAINTENANCE INSTRUCTIONS
Do not allow ice buildup. If a coil remains partially frosted 1. Location – Field openings for dampers must be prop-
after a defrost, it is unlikely to ever completely clean itself in erly sized. Do not force a factory damper into undersized
a subsequent defrost. If a coil is allowed to build ice into a field ductwork or attempt to fill an oversized opening. This
solid block, the ice can cause stresses to develop which will bend the frames causing air leakage. Dampers must
are capable of breaking coil tubes and piping. also be installed plumb and square. Twisted and distorted
frames develop stresses causing linkage to bind and corre-
NEVER take shortcuts to clear ice
lating improper blade operation. All control damper seams
from a coil by applying an open
must be caulked air and watertight.
flame to melt ice or frost.
2. Obstructions – Configuration of damper frames per-
The water used to wash the coils should be analyzed prior
mits the use of screws, rivets, or welding to attach damper(s)
to use to determine its suitability. It should not contain dis-
to ducts or housings. Fastener ends must not protrude in
solved chemicals or organisms. Contact a specialist to test
any way, which can interfere with blade movement. Cor-
the water, then follow his recommendations. Establish and
rectly mounted dampers allow free and smooth operation
follow a regular testing and treatment schedule.
from completely closed to fully open.
All refrigeration coils must be evacuated to remove mois-
3. Multiple Assemblies – Where dampers consist of more
ture prior to charging. Do not leave system or coils open
than one panel, sections are mounted together to form larger
and idle prior to start-up. Internal corrosive damage can
dampers. Matching frame members must be tightly welded
result.
or bolted together in the field. Multiple sections require ad-
Make sure piping is properly supported. Evaporators are ditional structural support (provided on site by others) to
not designed to support external piping. Evaporator piping insure complete rigidity. Horizontally mounted dampers may
and distributor tubing is not to be used for support or stepped sag unless supported adequately. Blade motion is transmit-
on during the construction process. ted between adjacent panels by common blade shaft cou-
plings and jackshafts. It is important that all shafts are accu-
The use of threading compounds at coil flanges with par- rately aligned, otherwise blade edges will bind and prevent
ticles of metals (i.e. copper) embedded in the compounds a good seal.
can cause corrosion due to contact of dissimilar metals.
Double check the compatibility of your construction materi- 4. Actuators – Operation of dampers may be manual us-
als with the coil material of construction. ing locking quadrant handles, chain operators or other de-
vices. For automatic operation, electric or pneumatic actua-
Further, isolate aluminum coils from steel piping via tors can be connected to dampers either internally or exter-
gasketed flanges and sleeved bolts. nally. Dampers constructed with multiple panels require in-
dividual actuators or jackshafts. Actuators or multiple ac-
Sensing devices, which detect the presence of ammonia,
tuators should be of adequate torque capacity to effectively
should be employed in your system.
open and close the damper according to its type, size, loca-
tion, and its function in the system (relative to air velocity
and static pressure requirements).
S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 16 MAINTENANCE

5. Lubrication – Before initial operation, all moving parts Finish and Sealing
of dampers should be first cleaned and then thoroughly
ACUair® units utilize silicon for air and water sealing on the
lubricated. Dampers furnished with stainless steel side seals
interior and exterior. The sealing on the units should be
should also have the seals lubricated generously. Damp-
inspected and repaired as nessacary.
ers should then be manually operated several times until
linkages and blades operate freely. The repairs need to be done using USDA approved silicon.
6. General Maintenance – Dampers require proper main- UNIT CLEANING AND SANITATION
tenance in order to function correctly. Blade shafts, linkages,
stainless steel side seals (if applicable) and other moving The unit should be thoroughly cleaned at regular intervals.
parts should be periodically cleaned and lubricated. A light Your chemical supplier should be consulted when picking
molybdenum oil in aerosol cans is preferable since the jet the proper cleaning chemicals.
nozzle permits pinpointing the stream of lubricant where re- DISCONNECT ALL ELECTRICAL
quired. It usually contains an evaporating solvent and dries POWER BEFORE CLEANING THE UNIT.
to a nonoily film, which will not attract dirt. For dampers lo-
cated in difficult or impossible to reach locations, field access Before cleaning, any capped drain pipes should be un-
panels/doors are required as installed by others. capped, and motors should be draped with plastic. During
cleaning, the following components should NOT be directly
NOTE: In food plant applications a USDA approved sili- sprayed with water: Motors, Damper Motors, Bearings, Pitot
con lubricant should be used! Tubes, Filters, and Electronic Sensors.
7. Periodic Inspections – All automatic dampers should
INITIAL START-UP
be checked and serviced on a regular schedule. The rec-
ommended interval is monthly and should never exceed 1. Blower Alignment – Shipping and installation may
three months. Malfunctioning dampers can lead to improper cause misalignment of the blower, motor and belts. Be-
control of space temperatures, excessive infiltration, and fore starting the unit, rotate the blower by hand to make
increased energy costs. certain that all components rotate freely. Start the motor,
and let it run for one hour. Shut down the motor and dis-
8. Inspection Checklist – At a minimum, include the fol- connect the electrical power. Touch all of the blower bear-
lowing items in scheduled inspections: ings. The bearings should be slightly warmer than the air
• Observe damper motors and actuators through an oper- passing through the unit, and each bearing should be
ating cycle to check for defects and binding. Check mount- approximately the same temperature as the other bear-
ing bolts for integrity. ings. If any of the bearings is noticeably hotter than other
• Adjust actuator linkages so those dampers open and close bearings, or if they are too hot to touch, the blower and
fully for given stroke. motor may be out of alignment.
• Check tightness of closed blades – readjust linkage for 2. Mechanical Tightness
any blades that may not close fully. a. Check tightness of fan bearing bolts.
• Replace any damaged blades – clean operating parts.
b. Check tightness of blower, motor, and pulleys.
• Check blade edge and side seal – replace as necessary.
c. Check tightness of all motor mounting bolts.
• Check pins, straps, bushings, etc., for wear and replace
3. Belt Tension – The blower belts are factory set to the
as required.
proper tension, but they may loosen during shipping and
• Lubricate all moving part contact points and side seals. installation. Check the belt tension after one hour, 50 hours,
• Check caulked joints between the damper frames and and 100 hours of operation. Adjust tension if necessary.
the main structure – repair if the possibility of air or water
leakage exists. MONTHLY SERVICE
COIL ASSEMBLY It is recommended that the unit undergo a thorough monthly in-
spection. The inspection should include the following areas:
An ACUair® air handling unit's operational readiness is de-
pendent on the condition of the coil. Coils that are dirty, 1. Blowers, Motors, and Drives
blocked from airflow, or physically damaged may affect over- a. Shut down the unit , and disconnect all electrical power.
all heat transfer capability of the ACUair® SYSTEM to a Touch all of the blower bearings. The bearings should
significant degree. be slightly warmer than the air passing over them, and
they should all be approximately the same tempera-
Periodically conduct a visual inspection of the coil section ture. If any of the bearings are noticeably warmer than
and refrigerant line connections. Remove any airborne de- the other bearings, or if any of the bearings are too hot
bris that may have collected on the face of the coils to touch, grease should be applied via the Zerk fitting.
themselves.
The bearings should be greased in accordance with
Further need for cleaning or repair of an ACUair® SYSTEM the included Blower Bearing Lubrication Guidelines.
coil should be left to the judgement of a certified or b. Check the tightness of the blower bearing bolts, the
factory-trained service person. Contact the local ACUair® blower, motor, and pulleys, and the motor mounting
representative if a coil or its connections appears to have bolts.
been significantly damaged.
ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
MAINTENANCE Page 17

c. Check the blower belt tension. The belts should be


tensioned in accordance with the included Blower Belt
Tension Guidelines. Visually inspect the belts for indi-
cations of wear. Replace the belts if there is evidence
of cracking, fraying, or uneven wear.
2. Filters
a. Visually inspect the prefilters, intermediate filters (if
applicable) and final filters (if applicable). If the prefilter
media appears damaged in any way, or if the media
becomes wet, the prefilters should be changed imme-
diately. If the intermediate filter media, or final filter
media appears damaged, the filters should be changed
immediately. The filter maintenance schedule included
with this manual should be used as a guide for normal
filter replacement.
3. Unit Exterior
a. Visually inspect the unit exterior. The seams between
panels are factory sealed with silicon, and should be
resealed if there appears to be any degradation of the
original seal. Any scratches to the exterior of the unit
should be repainted with the factory supplied touch-
up paint.
b. Check the tightness of the door seals. If there is any
indication of air infiltrating or escaping the unit via the
doors, the door handles should be adjusted to provide
a tighter seal.
S210-100 IOM ACUair® HYGIENIC AIR HANDLING UNITS
Page 18 INSTALLATION, OPERATION, AND MAINTENANCE

Troubleshooting
Symptom Probable causes and Corrections
Motor doesn’t start Check MOA module to see if in AUTO (green light if on/red light if
fuse is blown)
Check blower door switch
Check smoke/ammonia detectors (if applicable)
Check end switch on OA dampers (if applicable)
Check fuses
Check over loads
Check power to coil on starter
Check power from starter to motor
Motor starts but quits shortly after. Check fan belts
Check tubes to airflow switch to be clean
Check power through air flow switch
Check rotation of fan
Cooling doesn’t come on Check MOA module to see if in AUTO (green light if on/red light if
fuse is blown)
Check set point for cooling
Check OA lockout setpoint (lockout should be below OA Temp)
Check power to valve
Steam valve doesn’t modulate Check setpoint for heat
Check OA lockout setpoint (lockout should be above OA Temp)
Check output for steam valve
Direct-fired burner doesn’t light Check setpoint for heat
Check OA lockout setpoint (lockout should be above OA Temp)
Check MOA module to see if in AUTO ( green light if on/red light if
fuse is blown)
Check burner safety circuit. Eg. High gas pressure switch, Low
gas pressure switch, high temp limit, burner door switch
Check to make sure OUTSIDE air dampers are open and
RETURN dampers are shut
Check burner airflow switch
Check and clean UV scanner
Check and gap pilot assembly (3/16" gap) Check gas supply
Indirect-fired burner doesn’t light Check setpoint for heat
Check OA lockout setpoint (lockout should be about OA Temp)
Check MOA module to see if in AUTO (green light if on / red light
if fuse is blown)
Check blower on burner
Check lockout alarm on Honeywell control
Check burner airflow switch
Check low fire end switch on burner damper motor
Check spark rod and flame rod
Check pilot assembly
Exhaust fan doesn’t start Check MOA module to see if in AUTO ( green light if on / red light
if fuse is blown)
Check disconnect switch on fan
Check overload
Check power to and from starter
Check damper end switch ( if applicable )
ACUair® HYGIENIC AIR HANDLING UNITS S210-100 IOM
INSTALLATION, OPERATION, AND MAINTENANCE Page 19
!"#$%™ !"#$%&'(#")*!%+%,-...
/0'"(#*"(1%!!")#2%!($2#*(
/0'"(#*"(1%!!")#2%!($2#*(
"(#*"(1%!!")#2%!($2#*(!&'#%&(™!
Preengineered for Lower Cost
Distributed System with Remote Control
Single-Cable Network
Easy to Expand or Upgrade

System integration is what we do…


Q-NET™ ... supports open-protocols for SCADA systems
(i.e. Allen Bradley DF1 and Modbus ASCII)
Q-NET™ ... connects for local or remote access
Q-NET™ ... can be applied to both new and existing systems
Q-NET™ means precise control 24 hours a day, seven days a week
Q-NET™ distributed architecture means faster, easier, economical installations
Q-NET™ delivers increased operating efficiency and lowers energy costs

Now available on Frick’s ACUair® hygienic air handlers, condensers,


screw compressors, evaporators, and refrigerant vessels, too.

30'"(45++(06
0'"(45++(0670!#0
"(45++(067 ,"(%4 (89:;3<(#")
0!#0, *!%+%,-($2#*(0++(=
(#")*!%+%,-($2#*(0++(=&2)
*!%+%,-($2#*(0++(=&2)'>(?&
&2)' %65)#@A
(?&%65)#@A

YORK Refrigeration Systems


1590 Dutch Road, Dixon Illinois 61021
Phone: 815-288-3859 • Fax: 815-288-1409 • www.frickcold.com

© 2003 YORK Refrigeration Systems

You might also like