PERFORMANCE SPECIFICATION

TJN
PERFORMANCE SPECIFICATION

CONTENTS

1 General

2 Characteristic Energising Quantity

3 Auxiliary Energising Quantity

4 Characteristics

5 Accuracy Reference Conditions

6 Accuracy

7 Accuracy – General

8 Accuracy Influencing Quantities

9 Thermal Withstand

10 Burden

11 Output Contacts

12 Environmental Withstand

List of Figures
1 IDMTL Curves (Time Multiplier = 1.0)

2 Starter Operating Time

3 Instantaneous Highset Operating Time

[09-01 – Rev 1] Page 1 of 8


PERFORMANCE SPECIFICATION

1. GENERAL

Performance Data to IEC 255-3

2. CHARACTERISTIC ENERGISING QUANTITY

AC Current In 1Amp / 5 Amps


Frequency 50 Hz

3. AUXILIARY ENERGISING QUANTITY

Nominal Operating Range


VAUX 24, 30, 48, 110 Volts DC 18V to 135V DC
VAUX 48, 110, 220 Volts DC 43V to 280V DC
110 Volts AC
VAUX 110, 220 Volts DC 88V to 300V DC
110, 230 Volts AC

4. CHARACTERISTICS

4.1 Operating Characteristics


Phase and Earth Fault time delayed Elements Inverse Characteristics, Definite Time
Delay Characteristics
Phase and Earth Fault Highset Elements Instantaneous

4.2 Over Current Settings


Phase Fault 0.05xIn to 2.5xIn in steps of 0.05 In
Earth Fault 0.05xIn to 2.5xIn in steps of 0.05 In
Highset Phase Fault 0.5xIn to 25xIn in steps of 0.5 In
Highset Earth Fault 0.5xIn to 25xIn in steps of 0.5 In

[09-01 – Rev 1] Page 2 of 8


PERFORMANCE SPECIFICATION

4.3 Operating Times


Phase Fault IDMTL Operating Time can be calculated as follows :
Characteristics K
t = -------------- x tP
(I/IS) α - 1
where I = Fault current
Is = Setting current
tP = Time Multiplier for Phase
SI 3 K=0.14 α = 0.02
SI 1 K=0.0613 α = 0.02
VI K=13.5 α = 1.0
EI K=80.0 α = 2.0
LTI K=120.0 α = 1.0
Earth Fault IDMTL Characteristics Operating Time can be calculated as follows :
K
t = -------------- x tE
(I/IS) α - 1
where I = Fault current
Is = Setting current
tE = Time Multiplier for Earth
SI 3 K=0.14, α = 0.02
SI 1 K=0.0613 , α = 0.02
VI K=13.5, α = 1.0
EI K=80.0, α = 2.0
LTI K=120.0, α = 1.0
P/F Time Multiplier 0.025 to 1.0 in steps of 0.025
E/F Time Multiplier 0.025 to 1.0 in steps of 0.025
P/F DTL 0 Secs to 20 Secs in steps of 0.01 Secs
E/F DTL 0 Secs to 20 Secs in steps of 0.01 Secs
Highsets Shaped Instantaneous
Reset Time 0 to 60 Secs in steps of 1 sec

(Either any one of Inverse Characteristics or DTL can be selected)

Figure 1 shows the operating time for the five IDMTL curves with time multiplier = 1.
Figure 2 shows the operating time for the overcurrent starter.
Figure 3 shows the operating time for instantaneous Highset.

5. ACCURACY REFERENCE CONDITIONS

General IEC 255-3


Settings All settings
Current input for DTL 1.1 x IS
Auxiliary Supply Nominal
Frequency 50 Hz
Ambient Temperature 20° C

6. ACCURACY

Phase / Earth Operating Current 104% of setting ; ±4% or ± 10 mA


(Starter)
Reset ≥ 94% of setting
Repeatability ± 1%

Highset Operating Current 100% of setting ; ±4% or ± 10mA


Reset 94% of setting
Repeatability ± 1%

[09-01 – Rev 1] Page 3 of 8


PERFORMANCE SPECIFICATION

IDMTL Operate Times ± 5% or ± 30 mSecs


DTL Operate Times ± 1% or ± 30 mSecs
Starter Operate Times ± 5 mSecs
Highset Operate Times ± 5 mSecs
Repeatability ± 1% or ± 5 mSecs

7. ACCURACY - GENERAL

Transient Overreach of Highsets for X/R ≥ -5%


upto 100
Disengaging Time < 75 mSecs
Overshoot Time < 40 mSecs
Reset Time ± 4%

8. ACCURACY INFLUENCING QUANTITIES

Temperature
Ambient Temperature -10° C to + 55° C
Variation over Range ≤ 5%

Frequency
Variation 47 Hz to 52 Hz
Setting Variation ≤ 4%
Operating Time Variation ≤ 4%

Harmonic Current
Operating Time Variation for harmonics ≤ 5%
during fault upto 350 Hz

Auxiliary DC Supply - IEC 255 - 11


Allowable superimposed AC component ≤ 12% of DC component
Allowable Breaks/dips in supply (collapse to ≤ 20 mSecs
zero from nominal voltage)

9. THERMAL WITHSTAND

Continuous and Limited Period Overload


3.0 x In Continuous
3.5 x I n for 10 minutes
4.0 x I n for 5 minutes
5.0 x I n for 3 minutes
6.0 x I n for 2 minutes

Short Term Overload


5A Rating 230A for 3 Sec
1A Rating 57.7A for 3 Sec

10. BURDEN

Current Transformers
AC Burden Impedance
5A Rating ≤ 0.2 VA ≤ 0.01 Ohms
1A Rating ≤ 0.05 VA ≤ 0.05 Ohms
Note: Burdens and Impedance’s are measured at nominal current rating.

[09-01 – Rev 1] Page 4 of 8


PERFORMANCE SPECIFICATION

Auxiliary Supply
DC Burden AC Burden
Quiescent (Typical) 5 Watts 12 VA
Max. 10 Watts 24 VA
Note: Maximum burdens are measured with all six optional relays fitted.

11. OUTPUT CONTACTS

Carry continuously : 5 Amp AC or DC

Make and Carry


(limit L/R ≤ 40 mSecs and V ≤ 300 volts)
for 0.2 Sec 20 A AC or DC

Break
(limit ≤ 5A or ≤ 300 volts)
AC Resistive 1250 VA
AC Inductive 250 VA @ PF ≤0.4
DC Resistive 75 W
DC Inductive 50 W @ L/R ≤40 mSecs

Minimum Number of operations 1000 at Maximum Load

12. ENVIRONMENTAL WITHSTAND

Temperature - IEC 68-2-1/2


Operating Range -10° C to +55° C
Storage Range -25° C to +70° C

Humidity - IEC 68-2-3


Operational Test 56 days at 40° C and 93% RH

Transient Overvoltage - IEC 255-5


Between all terminals and Earth or between 5kV 1.2/50 µs, 0.5Joules
any two terminals without damage or
flashover

Insulation - IEC 255-5


Between any terminal and Earth 2.0kV rms for 1 min
Between Independent circuits 2.0kV rms for 1 min
Across normally open contacts 1.0kV rms for 1 min

High Frequency Disturbance - IEC 255-22-1 Class III


Variation
2.5kV common (longitudinal) mode ≤ 3%
1.0kV series (Transverse) mode ≤ 3%

Electrostatic Discharge - IEC 255-22-2 Class III


Variation
6 kV Contact Discharge ≤ 5%
8 kV Air Discharge ≤ 5%

Radio Frequency Interference - IEC 255-22-3 Class III


Variation
20 MHz to 1000 MHz. 10V/m ≤ 3%

[09-01 – Rev 1] Page 5 of 8


PERFORMANCE SPECIFICATION

Fast Transient - IEC 255-22-4 Class IV


Variation
4kV 5/50 nS, 2.5 kHz repetitive ≤ 3%

Vibration (Sinusoidal) - IEC 255-21-1 Class I


Variation
Vibration Response 0.5 gn ≤ 5%
Vibration endurance 1.0 gn ≤ 5%

Shock and Bump - IEC 255-21-2 Class I


Variation
Shock Response 5 gn 11 ms ≤ 5%
Shock withstand 15 gn 11 ms ≤ 5%
Bump Test 10 gn 16 ms ≤ 5%

Mechanical Classification
6
Durability in excess of 10 operations

[09-01 – Rev 1] Page 6 of 8


PERFORMANCE SPECIFICATION

10000

1000

100
( Sec )
Time

10
Long Time Inverse

Standard Inverse 3 Secs.

Standard Inverse 1.3 Secs.


1
Very Inverse

Extremly Inverse
0.1

0.01
1 10 100
Current ( multiples of setting )

Figure 1 - IDMTL Curves ( Time Multiplier = 1.0 )

[09-01 – Rev 1] Page 7 of 8


PERFORMANCE SPECIFICATION

60

50

40
Operating time (mSecs)

30

20

10

0
0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0
Multiples of Current Setting

Figure 2 - Starter Operating Time

60.0

50.0

40.0
Operating time (mSecs)

30.0

20.0

10.0

0.0
0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0
Multiples of Current Setting

Figure 3 Instantaneous Highset Operating Time

[09-01 – Rev 1] Page 8 of 8