Professional Documents
Culture Documents
Les 03 Grounding
Les 03 Grounding
p1
Grounding vs Earthing
Grounding
Method used to connect power system neutral to earth
mat
Current limited by source and neutral impedance
Refer to IEEE Std 142 (1982, 1991, 2007) and
SANS 10200 (1985, 2015)
Earthing and bonding (safety)
Connection of equipment enclosures to earth mat, eg
SANS 10142 / 10199 / 10292
p2
Grounding Methods 1
Ungrounded System
Neutral connection on transformer is not connected to earth at all
p3
Grounding Methods 2
Solid grounding
Neutral connection on transformer is solidly connected to earth (0V)
p4
Grounding Methods 3
Resistance grounding
Neutral connection on transformer is connected to earth (0V)
through a fixed resistance to limit the earth fault current
p5
Low resistance grounding
Earth fault limited to 300 A to 1000 A max
This applies to all MV systems in South Africa
p6
High resistance grounding
Fault current limited to approximately 10 A
Used in MV generator applications (power stations)
Used in large captive MV motor applications
Used in LV systems in mines
p7
Grounding Methods 4
Reactance grounding
Neutral connection on transformer is connected to earth (0V)
through a fixed reactance to limit the earth fault current
p8
Grounding Methods 5
Petersen Coil grounding (arc suppression)
Neutral connection on transformer is connected to earth through a
variable reactance to neutralize the capacitive earth fault current.
Results in arc extinction.
p9
Grounding Methods 6
NEC grounding (with and without resistance)
In MV delta connected systems no earth connection is available. A three-phase
neutral electromagnetic compensator is connected to allow earth fault currents
to flow - allowing detection of these faults.
p11
Problems (caused by natural system impedances)
Phase Faults (limited only by positive sequence
impedance of system)
High Fault Currents.
Only limited by positive sequence impedance of power system.
Earth Faults
Solid grounding means high earth fault currents
Limited by positive, negative and zero sequence impedance of
power system.
p12
Consequences
High fault currents damage equipment extensively.
Danger of fire hazard.
This leads to long outage times.
Lost production and lost revenue.
High fault currents in earthing/bonding system gives rise to high
touch potentials - dangerous to human life.
High fault currents are more hazardous in igniting gases.
Explosion Hazard.
p13
Solutions
Phase Segregation (spacing far apart)
Eliminates phase-to-phase faults.
Resistance Grounding
Means lower earth fault currents
Value can be chosen during design stage to limit current to
desired value - say 350 A
p14
Benefits of low resistance grounding ..1
Fault damage now minimal
Reduces fire hazard (especially in mines)
p15
Benefits of low resistance grounding ..2
Low fault currents reduce possibility of igniting gases.
Minimises explosion hazard.
p16
p17
NER construction
p18
NECRT construction
p19
Earthing and touch potentials
Two examples
p20
Touch Potentials (Reb =1 Ω)
Person touches
motor
enclosure -
now live
1 730 V
p21
Touch Potentials (Reb = 10 Ω)
Lower
touch
1 730 V potential
p22
Any questions ?
p23