Professional Documents
Culture Documents
Lutron 367-2597 - Vive - Design - Guide
Lutron 367-2597 - Vive - Design - Guide
lighting control
Load
controllers
Integration
Vive Installation
Madison College — Madison, Wisconsin
2 | Lutron Lutron | 3
Scalable solutions — start small and grow Energy-saving control strategies
Vive wireless solutions offer a multi-strategy approach that accommodates your Combine lighting control strategies to maximize efficiency
budget and performance needs now and for the future of your building.
hat is the savings opportunity?
W
Lutron solutions can save 60% or more lighting energy.
1 2 3 4
Potential savings
20 – 60%
Occupancy/vacancy sensing turns lights ON
when occupants are in a space and OFF when they
Occupied: On Vacant: Off vacate the space. Lighting
Single Single Multiple Entire Plug load control automatically turns off loads 15 – 50%
after occupants leave a space.
space floor floors building Appliance On Appliance Off Controlled Load
Start by adding Expand to new areas Duplicate the Vive offers seamless
10 – 30%
80%
control in a single or an entire floor at success of one floor integration to other High-end trim sets the maximum light level
space and expand any time without across other floors building management based on customer requirements in each space.
as budgets reprogramming or as your business systems to control every
Max: 100% Max: 80% Lighting
and occupant replacing existing expands or tenants light in your building.
schedules allow. equipment. change. Control can
be independent on Personal dimming control gives occupants 10 – 20%
each floor, or linked the ability to adjust the light level.
Full On Dim Lighting
via Vive wireless hubs.
5 – 15%
HVAC integration controls heating,
ventilation, and air conditioning systems
Heating Cooling through contact closure or BACnet protocol. HVAC
Saving Saving
System Optimization service from Lutron identifies
important lighting control adjustments to save additional
60 70
Variable
% %
Occupancy and
daylight sensors
Or
Vive wireless hub
Or
Communication protocols
6 | Lutron Lutron | 7
Selecting and installing wireless controls is easy
Area Control
Step 1 Switching
Step 2
Control your lights Switching
where you need to
• Wireless devices can be mounted
to any surface with no wiring needed
• Pico controls communicate wirelessly Dimming
to the controls in the ceiling
• 10-year battery life
Pico wireless remotes
Scene
Step 3
Add sensors to your job Corner
8 | Lutron Lutron | 9
Selecting and installing wireless controls is easy
Area Control
Step 4
Add daylight harvesting
to meet code and
save energy Daylight sensor
Step 5 (optional)
System software
and control
• Timeclock
• Demand response
• BACnet and API integration
• Energy and occupancy information
10 | Lutron Lutron | 11
Selecting and installing wireless controls is easy
Individual Fixture Control
Step 1
Simply count the fixtures—
the technology is built in
• Visit lutron.com/hpfl for a list of fixtures that
come with Vive wireless technology built in
• Fixture are shipped with occupancy, vacancy
and daylight sensing already installed
Occupancy/vacancy sensors
Switching
Control your lights
where you need to
• Wireless devices can be mounted to
any surface with no wiring needed
Dimming
• Pico controls communicate wirelessly
to the controls in the ceiling
• 10-year battery life
Scene
Step 3 (optional)
System software
and control
• Timeclock
• Demand response
• BACnet and API integration
• Energy and occupancy information See easy system
programming on
• Proactive maintenance alerts
pages 16 and 17
Vive software
12 | Lutron Lutron | 13
Simple to design Easily meet code
Access to tools and resources is at your fingertips. Summary of code requirements for lighting control
Get access and quick answers to keep your project moving. Vive wireless solutions ensure you can meet new construction and retrofit (lighting alterations)
code requirements for three major energy codes: ASHRAE, IECC, and Title 24.
For specific commercial building code lighting requirements in your state, please visit lutron.com/energycodes.
Code Comp
liance | Lightin
g Controls
ions
Vive Solut Commercial Application Guide
Vive Soluti
Code Compliance | Lighting Controls
Title 24-2 ons
n Guide ANSI/ASHRAE/IES 90.1– 2016 019
ial Applicatio Commerc
allows you to design a Lutron Vive lighting control system with visual Code Comp
liance | Lightin
g Controls
Code Comp
Vive So
liance | Lightin
g Controls
application guides that include examples of different spaces and corresponding
Lutron products for those spaces. Guides show you how you can use Lutron
ons IECC 201 lutions
Vive So5luti
“drag and drop” layout and connections. It also allows you to generate
8
Commerc
IECC 201 n Guide
ial Applicatio
n Guid
Wireless
ial Applicatio eload
controls
Commerc
In-wall
controls Wireless
remotes Wireless
( ) ( )
ZONE X ( )
ZONE X ( ) ( ) SWITCHED POWER ( ) ( )
P P
RF
VAC
SWITCHED POWER (8A MAX)
(1A MAX)
Controlled
Controlled
0-10V DIM
On/Off On/Off
0-10V DIM
LUTRON LUTRON
(60 mA MAX)
(6 mA MAX) PJ2-3BRL-GWH-XXX PJ2-3BRL-GWH-XXX
LRF2-VCR2B-P-WH RMJS-8TN-DV-B LRF2-OKLB-P-WH
CAR2S-20-STR-WH 3 BUTTON CONTROL LRF2-DCRB-WH POWPAK DIMMING MODULE CAR2S-20-STR-WH 3 BUTTON CONTROL
VACANCY SENSOR CORNER MOUNTED
20A TAMPER RESISTANT, WITH RAISE/LOWER DAYLIGHT SENSOR 120/277V~, 50/60 Hz 20A TAMPER RESISTANT, WITH RAISE/LOWER
FCJS-010 OCCUPANCY SENSOR
SPLIT DUPLEX RECEPTACLE SHOWN WITH CW-1-WH W/ 0-10 V CONTROL SPLIT DUPLEX RECEPTACLE SHOWN WITH CW-1-WH
POWPAK WIRELESS 90° COVERAGE
HALF SWITCHING CLARO WALLPLATE DIMENSIONS: HALF SWITCHING CLARO WALLPLATE
FIXTURE CONTROL
3.42"(H) X 2.82"(W) X 1.25"(D)
FOR 0-10 V CONTROL
(87mm X 72mm X 32mm)
TYPICAL OPEN OFFICE - 0-10V DIMMING TYPICAL MULTI-STALL BATHROOM - 0-10V DIMMING
TYPICAL 0-10V POWPAK(S) TYPICAL FOR RECEPTACLE CONTROL TYPICAL OCCUPANCY SENSOR TYPICAL DAYLIGHT SENSOR TYPICAL 0-10V POWPAK(S) TYPICAL MANUAL OVERRIDE TYPICAL OCCUPANCY SENSOR
(1 PER ZONE REQUIRED) (SEE CODE COMPLIANCE TABLE FOR APPLICABILITY) TYPICAL MANUAL OVERRIDE @ EACH ENTRY (REFER TO PLANS FOR LOCATIONS & QUANTITIES) (REFER TO PLANS FOR LOCATIONS & QUANTITIES) (1 PER ZONE REQUIRED) (AS REQUIRED - REFER TO PLANS FOR LOCATIONS) (REFER TO PLANS FOR LOCATIONS & QUANTITIES)
Get access to Lutron Vive videos 24/7. Step-by-step setup, Specifying wireless lighting control reduces design time and allows flexibility for changes
ZONE X ( ) ZONE X
SWITCHED POWER ( ) ( ) ( ) SWITCHED POWER ( ) ( )
P P
RF
Controlled
0-10V DIM 0-10V DIM
On/Off
LUTRON LUTRON
( )
(LSC-OS-PROG4-SP)
ZONE X ZONE X NUMBER OF 4-HOUR VISITS PURCHASED.
SWITCHED POWER ( ) ( ) ( ) SWITCHED POWER ( ) ( ) REMOTE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUS HOURS
P P
RF
Controlled
- 4 HOUR BLOCK
installation, and programming help whenever you need it. during the project without the need to make revisions. Vive wireless specification
CONTRACTOR OVER THE PHONE. THE SYSTEM WILL BE PROGRAMMED
0-10V DIM 0-10V DIM
On/Off
(LSC-RMT-PROG4-SP)
PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE
LUTRON LUTRON
TYPICAL 0-10V POWPAK(S) TYPICAL FOR RECEPTACLE CONTROL TYPICAL OCCUPANCY SENSOR TYPICAL DAYLIGHT SENSOR
(1 PER ZONE REQUIRED) (SEE CODE COMPLIANCE TABLE FOR APPLICABILITY) TYPICAL MANUAL OVERRIDE @ EACH ENTRY (REFER TO PLANS FOR LOCATIONS & QUANTITIES) (REFER TO PLANS FOR LOCATIONS & QUANTITIES)
ZONE X ( )
SWITCHED POWER ( ) ( ) ( )
P
RF
(8A MAX)
TYPICAL VIVE HUB TYPICAL VIVE HUB
Egress Corridor | New Construction
Controlled
0-10V DIM FOR SYSTEM PROGRAMMING, DEMAND FOR SYSTEM PROGRAMMING, BMS INTEGRATION,
On/Off
LUTRON
(60 mA MAX)
PJ2-3BRL-GWH-XXX RESPONSE, AND TIMECLOCK DEMAND RESPONSE, AND TIMECLOCK
RMJS-8TN-DV-B LRF2-OKLB-P-WH
LRF2-DCRB-WH (OTHER OPTIONS AVAILABLE) (OTHER OPTIONS AVAILABLE)
POWPAK DIMMING MODULE
120/277V~, 50/60 Hz
CAR2S-20-STR-WH
20A TAMPER RESISTANT,
3 BUTTON CONTROL
WITH RAISE/LOWER
CORNER MOUNTED
OCCUPANCY SENSOR
DAYLIGHT SENSOR ASHRAE 90.1-2010 by
typicals allow for quick and easy design of many applications. Simply copy and paste
SHOWN WITH CW-1-WH
lutron.com/viveresources
W/ 0-10 V CONTROL SPLIT DUPLEX RECEPTACLE 90° COVERAGE
DIMENSIONS: HALF SWITCHING CLARO WALLPLATE
120V/277V 120V/277V
3.42"(H) X 2.82"(W) X 1.25"(D)
(87mm X 72mm X 32mm)
HJS-0-FM HJS-2-FM
VIVE HUB PREMIUM VIVE HUB
W/ CLEAR CONNECT & TIMECLOCK W/ CLEAR CONNECT, TIMECLOCK, & BACNET
24V POWER SUPPLY & ADAPTER INCLUDED 24V POWER SUPPLY& ADAPTER INCLUDED
SEE SPEC SHEET FOR MOUNTING REQUIREMENTS SEE SPEC SHEET FOR MOUNTING REQUIREMENTS
COMMUNICATES W/ CLEAR CONNECT COMMUNICATES W/ CLEAR CONNECT
DEVICES WITHIN 71'[22m] RADIUS DEVICES WITHIN 71'[22m] RADIUS
ALCR DEVICE FOR CONTROL OF BOTH NORMAL AND EMERGENCY 0-10V LOADS
WIRING LEGEND: SPEC:
REGULAR Neutral
INPUT POWER (NORMAL)
1-WAY RF COMMUNICATION
WIRELESS NETWORK:
A. RF FREQUENCY: 434 MHZ; OPERATE IN FCC GOVERNED FREQUENCY SPECTRUM FOR To emergency power
IECC 2018
UTILITY POWER 2 #12AWG (4 mm2)
UL 1008
TRANSFER SWITCH
Normal/Emergency Power 20A CIRCUIT PERIODIC OPERATION; CONTINUOUS TRANSMISSION SPECTRUM IS NOT PERMITTED.
1. WIRELESS SENSORS, WIRELESS KEYPADS AND WIRELESS LOAD CONTROL DEVICES VIVE TYPICAL
Line/Hot (Blue) 0-10V SIGNAL: 2 #18AWG (1.0 mm2)
OR EQUAL NORMAL/EMERGENCY 2-WAY RF COMMUNICATION DO NOT OPERATE IN THE NOISY 2.4 GHZ FREQUENCY BAND WHERE HIGH
EMERGENCY CIRCUIT PANEL POTENTIAL FOR RF INTERFERENCE EXISTS.
POWER SOURCE B. LOCAL ROOM DEVICES COMMUNICATE DIRECTLY WITH EACH OTHER (AND NOT Line-voltage Low-voltage Clear Connect
wiring wiring RF Communication
SYMBOL LEGEND: THROUGH A CENTRAL HUB OR PROCESSOR) TO ENSURE:
the typicals into drawing packages for complete design, layout, and BOM information.
1. RELIABILITY OF SYSTEM PERFORMANCE.
WIRELESS OCCUPANCY SENSOR WHEN POWER IS APPLIED TO AND REMOVED FROM LOAD CIRCUITS.
Red 2 Violet (+) Gray (-)
Control
P4 2. RATED FOR SWITCHING OF GENERAL PURPOSE LOADS.
LUT-ALCR-D 3. MOTOR RATING OF 0.5 HP AT 120 V FOR 15 A RECEPTACLES, AND 1 HP AT 120 V FOR
Normal Voltage Sense State Sense
LVS CONTROLS ALCR DEVICE EMERGENCY LOAD 20 A RECEPTACLES.
FOR USE WITH 0-10V LOADS
Switched Hot WIRELESS KEYPADS
Symbol Model Number Description Qty
A. DOES NOT REQUIRE EXTERNAL POWER PACKS, POWER OR COMMUNICATION WIRING.
Neutral Project Number: N/A
Normal Hot
Violet (+)
B. ALLOWS FOR EASY REPROGRAMMING WITHOUT REPLACING UNIT.
C. INCLUDES LED TO INDICATE BUTTON PRESS OR PROGRAMMING MODE STATUS. RMJS-8T-DV-B PowPak dimming module with 0-10 V 1
REGULAR
20A CIRCUIT D. MOUNTING: Drawn By: ER
Gray (-) 1. CAPABLE OF BEING MOUNTED WITH A TABLE STAND OR DIRECTLY TO A WALL
UTILITY POWER NORMAL Normal Neutral UNDER A FACEPLATE, BACKBOX OPTIONAL. Radio Powr
Drawing Savr wireless hallway
Revision:
CIRCUIT PANEL
NORMAL LOAD
E. 10 YEAR BATTERY LIFE LRF2-OHLB-P-WH 0 1
occupancy sensor
Drawing Date: 05.28.2020
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control
Sheet: 1 OF 1 2
RMJS-8TN-DV-B PICO-WBX-ADAPT Pico wallbox adapter 2
POWPAK DIMMING MODULE
WITH 8A, 0-10 V CONTROL
Occupant Enters:
All lights automatically turn on to maximum light level. Maximum light level is set to 80%.
When Occupied:
I
Code Notes: Verify that the egress fixtures go to full output upon loss of control signal. For projects that require UL 924 compliance, provide an
automatic load control relay (ALCR) per load controller connected to emergency fixtures. Add a daylight sensor for corridors with daylight zones.
Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details.
This solution requires 0-10 V enabled ballasts and drivers by others.
14 | Lutron Lutron | 15
Easy system programming
Simple setup and programming options with the Vive wireless hub For systems without a Vive wireless hub
Wireless dimmer
Occupancy sensor
16 | Lutron Lutron | 17
Save energy and improve building performance
Quickly view and display energy- Easily set lighting reduction levels Use a 365-day calendar to Create and configure scenes to Directly adjust the light levels remotely View proactive alerts that show
usage information to drive decision that automatically respond during automatically adjust lights based control individual devices, areas, from any smart device. Easily respond issues such as low batteries or
making and demonstrate savings. peak electricity usage times. on time of day, including single-day or groups of areas on demand. to occupant requests without needing inactive devices to help improve
and holiday events. to be in the physical space. building maintenance efficiency.
API integration, native on the Vive hub, enables integration with third-party devices, HVAC Audio & Video IT
systems, and software. RESTful APIs are available over the ethernet.
18 | Lutron Lutron | 19
A smart building is now simple
20 | Lutron Lutron | 21
Enterprise Vue – connected campus
22 | Lutron Lutron | 23
Lutron system security Lutron reliability
Clear Connect
Clear Connect being used to access the corporate
network to gain confidential information Continuous monitoring
2. A distributed security architecture — each hub and improvements
has its own unique keys Security is a constantly moving target. Lutron uses Other frequency bands
a dedicated security team to continuously monitor the
3. NIST-recommended best practices for securing
market for potential threats and, when needed, send out
passwords, including salting and use of SCrypt
security patches to update installed systems.
4. AES 128-bit encryption for network communications
24 | Lutron Lutron | 25
Vive product catalog
Wireless
hub
page 28
Load
controllers
page 30
In-wall
controls
page 50
Wireless
remotes
page 54
Wireless
sensors
page 58
Vive Installation
Suncrest Bank — Visalia, California
26 | Lutron Lutron | 27
Vive Wireless hub
Wireless hub
• Communicates with controls on a floor using Lutron wireless All wireless devices to be associated to the Vive wireless hub must be within 71 ft (22 m)
Clear Connect technology (range radius of 71 ft [22 m]) of the Vive wireless hub and must be on the same floor as the Vive wireless hub.
• Distributed system architecture
- Pico remote controls and sensors communicate directly with the
load devices they control and must be located within 30 ft (9 m) Conference Room
PowPak dimming module
of the device with which they are associated
Vive hub
• Supports timeclock events based on both sunrise and sunset RF coverage
or fixed time of day
• Two contact closure inputs to enable load shed from other devices Private Office
Maestro wireless
for Title 24 compliance and utility integration dimmer 30 ft (9 m) 30 ft (9 m)
Vive wireless hub Maximum Maximum Note: A minimum distance of 10 ft (3 m)
• OpenADR 2.0b compatible for integration with utilities for demand
between Vive wireless hubs on the same
response/loadshed and code compliance
Dimensions floor is required.
• Each hub provides an individual dashboard for its coverage area and Note: Vive wireless hub must be
W: 6.5" (165 mm)
allows you to link to other hub dashboards from the mobile application 71 ft (22 m)
mounted a minimum of 10 ft (3 m) from
H: 1.5" (38 mm) Maximum
D: 2.8" (71 mm) • API integration, native on the Vive hub, to enable integration with a Wi-Fi router or access point.
third-party devices, systems, and software. RESTful APIs are available
over the ethernet.
30 ft (9 m) 30 ft (9 m)
• Proactive alerts, i.e. low battery or possible device malfunction, help to Maximum Maximum
ensure system operates as expected
• Override and lockout support for emergency devices to send the
emergency lights to defined levels and lock out controls in the case Setup, Monitor
and Control 100 ft (30 m)
of a fire alarm, power loss, or security incident. This may be activated
Vive hub
manually or with an integration.
Product options
Vive hub power supply Vive wireless hub models
Range with multiple Vive hubs
Dimensions Starter (up to 75 devices)
W: 4.0" (102 mm) HJS-0-FM Flush mount
H: 1.7" (43 mm)
71 ft (22 m)
D: 2.8" (71 mm) Standard Maximum
100 ft 71 ft (22 m)
(30 m) Maximum
HJS-2-SM Surface mount Note: A corporate Wi-Fi network can interfere with the Wi-Fi on the Vive wireless hub. Where a corporate Wi-Fi network
exists, it is recommended to do the following: Connect the Vive wireless hub to the corporate network using the Ethernet
HJS-UPDATE Software upgrade license to add BACnet and API connection on the hub, and disable the hub’s Wi-Fi.
Software upgrade license expands device
HJS-DEVICES
28 | Lutron Lutron | 29
limit to 700 devices
Load controllers: J-box mounted switches and dimmers
Load controllers
•
Product options
16 A models
RMJS-16R-DV-B
5 A models
RMJS-5R-DV-B
30 | Lutron Lutron | 31
Load controllers: J-box mounted switches and dimmers
Load controllers
•
0-10 V control wires be installed using NEC Class 1 or Class 2 wiring methods.
with 0-10 V control 0-10 V Link: Communicates with up to 60 mA of fixtures
•
Dimensions
W: 2.89" (48 mm) Product options
H: 3.44" (87 mm)
D: 1.25" (32 mm) 8 A models with 0-10 V control
RMJS-8T-DV-B
Wiring Schematic
RMJS-8TN-DV-B Junction Box* Junction Box*
Line / Hot Line / Hot
Switched Line / Hot Switched Line / Hot
To Fluorescent To Fluorescent
Neutral Neutral Ballasts / LED Neutral Neutral Ballasts / LED
Drivers Drivers
−
0–10 V- to
+ Fluorescent
Ballasts / LED
Drivers
FCJS-ECO FCJS-ECO
120 – 277 V~ 50 / 60 Hz 1 A 120 – 277 V~ 50 / 60 Hz 1 A
PowPak® PowPak®
UL 2043 UL 2043
Plenum Rated Plenum Rated
12 V-- 25 mA 12 V-- 25 mA
® ®
lutron.com IEC SELV / NEC® Class 2 lutron.com IEC SELV / NEC® Class 2
1.844.LUTRON1 Sensor | Détecteur 1.844.LUTRON1 Sensor | Détecteur
México: México:
1.888.235.2910
lutron.com 1.888.235.2910
lutron.com
RMJS-8T-DV-B RMJS-8TN-DV-B
−
+ 0–10 V- to Fluorescent
Ballasts / LED Drivers
OTE: The control module mounts to the exterior of a U.S.-style junction box.
* N
32 | Lutron Lutron | 33
4.53 1.80
(114.90) (45.60)
50 ft (15.2 m)
60 ft (18 m) PowPak 30 ft (9 m)
LED bulbs, self-ballasted lamps (reverse-phase) 450 VA
Load controllers
450W/VA PowPak Phase Select maximum module maximum
line of sight through walls
dimming module LED NEMA SSL 7A-2015 (forward-phase) B, H 200 W Radio Powr Savr Pico remote
occupancy sensor control
Incandescent/halogen 450 W
Dimensions
ELV (reverse-phase) 450 W
W: 4.53" (114.90 mm)
H: 4.53" (114.90 mm) Fluorescent (forward-phase) 400 VAF
60 ft (18 m)
D: 1.80" (45.60 mm) Neon/cold cathode, MLV C, D 400 VAF (320 W)
•
Input: 120V/277V
Product options
box. NOTE: Must use metal junction
box, minimum depth 2.125 in (53.975 Dimensions
mm). Adding an extension ring is S P E Cas:
Dimensions are® shown IFICinAT I O N S U B M I T TA L
(mm) Page
450W/VA PowPak Phase Select dimming module
recommended for junction box depth Job Name: Model Numbers:
extension. See installation guide
RMJS-PNE-DV
041808 for additional information.
Job Number:
3.37
4.53 (85.75)
(114.90)
4.53 1.80
(114.90) (45.60)
1.90 3.37
(48.20) (85.75)
Range Diagram
PowPak module Contact Lutron first for applications using
foil-backed or metallic ceiling tiles.
5.2 m)
Load controllers: 4x4 box-mounted switches and dimmers
Load controllers
Dimensions 0-10 V Link: Communicates with up to 60 mA of fixtures
• 347V Relay module
0-10 V control
Dimensions are shown as: in (mm)
Dimensions Product options
Dimensions Product options W: 4.53" (114.90 mm)
W: 4.53" (114.90 mm) 5 A relay module
H: 4.53" (114.90 mm)
H: 4.53" (114.90 mm) 5 A model with 0-10 V control
D: 1.80" (45.60 mm)
D: 1.80" (45.60 mm) RMJS-5R-347
5 A switching only
RMJS-5T-347
0-10 V- dimming and
5 A switching
3.37
Mounting:
4.53 Mounts in a standard 4 in (85.75) Mounting: Mounts in a standard 4 in
(114.90)
x 4 in (101.6 mm x 101.6 mm) junction Divider for Class 1 & Class 2 separation x 4 in (101.6 mm x 101.6 mm) junction
box. NOTE: Must use metal junction box. NOTE: Must use metal junction
box, minimum depth 2.125 in (53.975 5T-347-DIVIDER box, minimum depth 2.125 in (53.975
mm). Adding an extension ring is mm). Adding an extension ring is
recommended for junction box depth recommended for junction box depth
extension. See Installation guide extension. See installation guide
041773 for additional information.
4.53 1.80 041828 for additional information.
(114.90) (45.60)
1.90 3.37
(48.20) (85.75)
60 ft (18 m) PowPak 30 ft (9 m)
maximum module maximum
3.37
line of sight through walls 4.53 (85.75)
Radio Powr Savr Pico remote (114.90)
occupancy sensor control
60 ft (18 m)
4.53 1.80
(114.90) (45.60)
36 | Lutron Lutron | 37
1.90 3.37
(48.20) (85.75)
Load controllers: J-box mounted switches and dimmers
Product options
Cooling Supply
Standard Filter coil fan
Load controllers
PowPak contact C
closure output module RMJS-CCO1-24-B Contact closure output
Dimensions
C
W: 2.89" (48 mm)
H: 3.44" (87 mm) Note: If using a relay module with the contact closure output, you do
D: 1.25" (32 mm) not need to add a contact closure output module unless a second
contact closure output is needed. VAV Damper open VAV Damper closed
Occupied Unoccupied
38 | Lutron Lutron | 39
Load controllers: Plug load control
20 A models
Load controllers
PowPak relay module
General purpose switch
RMJS-20R-DV-B
Dimensions 120-277 V receptacles
W: 2.89" (48 mm)
H: 3.44" (87 mm) General purpose switch
RMJS-20RCCO1-DV-B
D: 1.25" (32 mm) 20 A, 120-277 V receptacles
with one contact closure output
20 A 20 A
Occupied Unoccupied
One wireless receptacle can also control standard The occupancy/vacancy sensor wirelessly communicates room occupancy to the wireless receptacle.
receptacles wired downstream Based on the occupancy status received, the wireless receptacle switches the power on or off, reducing the
amount of energy consumed. The wireless receptacle will control normal receptacles downstream.
•
Input: 120 V
Load controllers
RF receptacle with
top controlled
Product options
15 A models
Dimensions
W: 2.94" (75 mm) CAR2S-15-STR - 15 A
Split (half switching;
H: 4.69" (119 mm) single pole/downstream)
D: 1.4" (36 mm)
CAR2S-15-DTR - 15A Duplex (dual switching;
single pole/downstream)
20 A models
CAR2S-20-STR - 20A
Split (half switching;
single pole/downstream)
CAR2S-20-DTR - 20A
Duplex (dual switching;
single pole/downstream)
20 A 20 A
Occupied Unoccupied
Load controllers
Vive Integral Fixture Control
Product options Vive Wireless fixture controller
Product options
Wireless individual in-fixture control Sensor Dimensions 0-10 V control models
Dimensions
W: .827" (21 mm) DFCSJ-OEM-RF Clear Connect (RF) only W: 2.89" (48 mm)
FCJS-010
H: 2.477" (62.9 mm) H: 3.44" (87 mm)
Clear Connect (RF) and occupancy/
DFCSJ-OEM-OCC D: 1.25" (32 mm)
FCJS-010-BULK8 8-pack
daylight sensing
Dimensions
with occupancy/daylight sensor ontact your local fixture representative and ask for a Vive-enabled
C
EcoSystem control models
W: .927" (23.5 mm) fixture or visit lutron.com/findafixture
H: 2.577" (65.4 mm) Note: Wireless sensors and controls must be located within 60 ft (18 m)
How it works FCJS-ECO
line of sight, or 30 ft (9 m) through walls, of each other.
Install the fixture control directly to a FCJS-ECO-BULK8 8-pack
fixture or on a junction box nearest
to the fixture. Install the sensor on the
Clear Connect (RF) + Sensing ceiling near the fixture to optimize Sensor models
coverage in the desired area.
FC-SENSOR Occupancy/daylight sensor
Note: Avoid mounting the fixture
Clear Connect (RF) Only sensor in direct sunlight or in the light FC-VSENSOR Vacancy/daylight sensor
which is cast from the fixture.
30 ft (9 m) 9 ft
(2.7 m)
Maximum
Link
Test
Pico
Pico remote control Radio Powr Savr Radio Powr Savr
Remote
Control Floor
(up to 10) occupancy sensor daylight sensor 12.0 ft
15 ft 9 ft 3 ft 0 3 ft 9 ft 15 ft
(up to 10) (1 maximum) (3.65 m)
(4.6 m) (2.7 m) (0.9 m) (0.9 m) (2.7 m) (4.6 m)
12.0 ft
(3.65 m)
44 | Lutron Lutron | 45
Load controllers: Emergency-rated wireless controllers
Load controllers
Emergency PowPak modules • 8 A: 0-10 V controlled fixtures and switches compatible with
Dimensions third-party 0-10 V fluorescent ballasts, LED drivers, and fixtures
W: 2.89" (48 mm) •
0-10 V link: Communicates with up to 60 mA of fixtures
H: 3.44" (87 mm)
D: 1.25" (32 mm) Fixture control:
• 1 A of load or up to 3 drivers and ballasts
System Wiring Diagram (Vive Hub with Emergency PowPak)
•
Input (all models): 120/277 V
Normal/Emergency
Circuit Panel
Product options
Regular
Utility Third-party OEM fixture with DFCJ-OEM
Power
Normal Power Normal / Emergency EcoSystem Driver
ULR 1008 Normal / Emergency Power
Emergency Power Transfer
Switch
Relay RMJS-16R-DV-B-EM DFCSJ-OEM-OCC/
RF
Inverter by
1- or 3-phase others**
Normal Power
Sense Pins 7&8 50019164a lutron.com
Regular
Utility
Power All Emergency
PowPak units
Red wires
Pins 1&7 Normal/Emergency
Pins 3&4 or 5&6 Light Fixture
Normally Open
Pins 3&4
Optional Fire Alarm Normally Closed
connection Pins 5&6
RADIOTOUCH
CONTACTS
CONTACTS
´FACP´ N/O
´FACP´ N/C
NOT USED
LED3
LED1
LED2
COMMON
+24VFW
SENSE
DRAIN
MUX
MUX
PHASE
FACF
TEST
GND
12 11 10 9 8 7 6 5 4 3 2 1 S1
Power Supply
Fire Alarm Control 24 V-
CLASS 2 LOW VOLTAGE WIRING
lutron.com
1.844.LUTRON1
®
12 V-- 25 mA
IEC SELV / NEC® Class 2
Sensor | Détecteur
HJS-x
México:
1.888.235.2910
lutron.com
46 | Lutron Lutron | 47
Load controllers: Emergency-rated wireless controllers
Load controllers
347 V emergency
lighting module
•
Input: 347 V
Product options
Dimensions
W: 4.53" (114.90 mm)
H: 4.53" (114.90 mm) 5 A model with 0-10 V control
D: 1.80" (45.60 mm)
System Wiring Diagram (Vive hub with 347V emergency dimming module)
RMJS-5T-347-EM Normal/Emergency
Circuit Panel
Regular
Utility
5 A model Power
Normal Power
Third-party OEM fixture with DFCJ-OEM
Normal / Emergency EcoSystem Driver
ULR 1008 Normal / Emergency Power
Emergency Power Transfer
RMJS-5R-347-EM Switch
DFCSJ-OEM-OCC/
RF
DFC-OEM-DBI
Wiring Schematic
How to design and120/277
specify
Emergency Normal Circuit
Power Panel* NOTE: Solution is not applicable for an
V~ Uninterruptable Power Supply (UPS)
Power Pack
Normal Feed Neutral (N) 24 V- backup system. RMJS-PNE-DV-EM
PP-DV
•
One dimming module for phase control
Neutral (N) Common must see a complete change-over of
Inverter by
For each controlled phase dimmable lighting zone in the space. power from
1- or normal to emergency others**
3-phase for
Normal Power
•
Regular the unitSense
to go into emergency
Pins 7&8 mode.
Control
50019164a lutron.com
Regular
Utility Power Utility
LED drivers (reverse-phase) 450 VA
Line / Hot (L) Junction Box Power Junction Box All Emergency
PowPak units
Red wires To additional
Pins 1&7 Normal/Emergency
Neutral (N) RMJS-PNE-DV
Lutron Hi-lume 1% 2-wire LED driver A 3 A (13 drivers max) Pins 3&4 or 5&6
units
Light Fixture
RADIOTOUCH
CONTACTS
CONTACTS
´FACP´ N/O
´FACP´ N/C
NOT USED
LED3
LED1
LED2
COMMON
+24VFW
SENSE
DRAIN
MUX
MUX
PHASE
FACF
TEST
Phase Select dimming module LED NEMA SSL 7A-2015 (forward-phase) B, H 200 W
GND
Power Supply
12 11 10 9 8 7 6 5 4 3 2 1 S1
UL 2043
Plenum Rated
1.888.235.2910
lutron.com
12 V-- 25 mA
IEC SELV / NEC® Class 2
Sensor | Détecteur
lutron.com
HJS-x
In-wall controls
Dual Voltage No Neutral switches MRF2S-6CL-XX 150 W dimmable CFL/LED,
MRF2S-8S-DV-XX
8 A lighting, 1/10 HP fan @ 120 V only, 600 W incandescent/halogen
50 | Lutron Lutron | 51
In-wall controls: switches and dimmers
In-wall controls
• Select appropriate model based on type of load:
- 120 – 277 V~ 8 A Electronic fluorescent ballast or LED drivers
- Controls up to 50mA of 0-10 V fixtures, sink only
)
(0-10 V dimmer version)
- Neutral required
• Add additional Pico remotes for rooms with multiple switches
for a single zone
• Add additional wireless occupancy and/or daylight sensors )
for additional coverage area and functionality
Product options
Vertical Beam Diagram
Standard
(For Reference Only)
MRF2S-8SD010-XX 0-10 V wallbox occupancy/vacancy
sensor dimmer
Wireless remotes
W: 1.28" (33 mm) PJ2-2B-XXX-L01 2-button wireless remote
H: 2.60" (66 mm)
D: 0.33" (8 mm) PJN-2B-GXX-L01 Nightlight 2-button wireless remote
PJ2-3BRL-XXX-L01
3-button with raise/lower
wireless remote
and Scene control keypads (-L31, -S31) are available but require
a different set of button marking codes when ordering
•
Select one Pico wallbox adapter for each Pico that you
Note: 2-Group (-L21, -S21, -LS21) would like wall mounted with a Claro-style wallplate
controls are not offered with the custom engraving option).
• Select one Claro wallplate (up to 4-gang) for all Pico and
Maestro Wireless wall-mounted control locations where
Wireless remotes
Claro style is desired
Standard Custom
Button Marking Codes Engraving Engraving
Zone Control Product options
Lights -L01 -EL1 Wall-mount accessories
Shades -S01 -ES1
PICO-WBX-ADAPT Pico wallbox adapter
Scene Control
CW-1-WH Claro 1-gang wallplate
Lights -L31 -EL2
Shades -S31 -ES2 CW-2-WH Claro 2-gang wallplate
Wall-mount accessories
Pico wallplate adapter and
Claro wallplate
Dimensions
W: 2.94" (75 mm)
H: 4.69" (119 mm)
56 | Lutron D: 1.44" (38 mm) Lutron | 57
Wireless sensors: Ceiling occupancy/vacancy sensors
H: 3.57" (91 mm) 15 ft 12 ft 9 ft 6 ft 3 ft 0 ft 3 ft 6 ft 9 ft 12 ft 15 ft
LRF2-OCR2B-P-WH Occupancy/vacancy Floor (4.6 m) (3.7 m) (2.7 m) (1.8 m) (0.9 m) (0 m) (0.9 m) (1.8 m) (2.7 m) (3.7 m) (4.6 m)
D: 1.13" (29 mm) 15 ft 12 ft 9 ft 6 ft 3 ft 0 ft 3 ft 6 ft 9 ft 12 ft 15 ft
(4.6 m) (3.7 m) (2.7 m) (1.8 m) (0.9 m) (0 m) (0.9 m) (1.8 m) (2.7 m) (3.7 m) (4.6 m)
LRF2-VCR2B-P-WH Vacancy only
Top view
Accessories
L-CMDPIRKIT Ceiling-mount sensor lens masking kit
9 ft 6 ft 3 ft 0 ft 3 ft 6 ft 9 ft
(2.7 m) (1.8 m) (0.9 m) (0 m) (0.9 m) (1.8 m) (2.7 m)
9 ft 6 ft 3 ft 0 ft 3 ft 6 ft 9 ft
Wireless sensors
(2.7 m) (1.8 m) (0.9 m) (0 m) (0.9 m) (1.8 m) (2.7 m)
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 and 8 ft (1.6 and 2.4 m).
** 12 ft (3.7 m) is the maximum mounting height allowed.
58 | Lutron Lutron | 59
Wireless sensors: Wall-/Hall-/Corner-mount occupancy/vacancy sensors
Dimensions (4.6 m)
H: 4.35" (110 mm)
LRF2-VWLB-P-WH
0 ft
Corner-mount sensors 15 ft
(4.6 m)
0 ft
LRF2-OKLB-P-WH Occupancy/vacancy (0 m)
0 ft 35 ft 50 ft
(0 m) (10.7 m) (15.2 m)
H: 2.18" (55 mm) 0 ft
LRF2-OHLB-P-WH Occupancy/vacancy (0 m)
5 ft
Wireless sensors
(1.5 m)
LRF2-VHLB-P-WH Vacancy only 10 ft
(3.0 m)
0 ft 150 ft
(0 m) (45.7 m)
Accessories
LRF-ARM-WH
Flexible armature mounting kit for Radio
Powr Savr wall, hall, corner sensors Hallway sensor maximum recommended length chart
(sensor centered within hallway)
Wire cage guard L-WIRECAGE-C Wire guard for ceiling-mount sensor
Dimensions Width of hallway Length of hallway
L-WIRECAGE-W Wire guard for in-wall sensor
W: 7.0" (178 mm) 6 ft (1.6 m) or less 50 ft (15.2 m)
H: 5.75" (146 mm)
D: 4.5" (114 mm) 8 ft (2.4 m) 100 ft (30.5 m)
10 ft (3.0 m) or more 150 ft (45.7 m)
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 and 8 ft (1.6 and 2.4 m).
** 12 ft (3.7 m) is the maximum mounting height allowed.
60 | Lutron Lutron | 61
Wireless sensors: Daylight sensors
Bottom of sensor
Loc
Bottom of sensor (cor
Location for narrow areas Loc
Arro
Wireless sensors
(corridors, private offices) by th
(cor
Arrow points towards the area viewed by the (awa
Arro
sensor (away from window).
by th
(awa
62 | Lutron Lutron | 63
Lutron service solutions
when you need them during the construction timeline us do the setup for you.
• Choose the amount of time you need • Includes a Commercial System Limited Warranty
Service solutions
LSC-SPV-DOC System performance—
LSC-PRG-AST-RMTE Remote programming assistance verification documentation
64 | Lutron Lutron | 65
Lutron service solutions Vive warranty and technology support
Commercial System
Support Options Limited Warranty Silver (TSP) Gold (TSP) Platinum (TSP)
Service solutions
Diagnostic Labor— 72-Hour Response •
Diagnostic Labor— 48-Hour Response •
Diagnostic Labor — 24-Hour Response •
Priority Support Line •
Annual Preventive Maintenance Visit • •
66 | Lutron Lutron | 67
Ordering information
Model Number Description List Price (US) Model Number Description List Price (US)
Note: Pricing accurate as of 07/10/2022. For up to date pricing, contact your Lutron sales representative. * Contact your local fixture representative and ask for a Vive-enabled fixture or visit lutron.com/findafixture; fixture
adders may vary.
Note: Pricing accurate as of 07/10/2022. For up to date pricing, contact your Lutron sales representative.
68 | Lutron Lutron | 69
Ordering information
Model Number Description List Price (US) Model Number Description List Price (US)
* ( XX in the model number represents color/finish code; use WH for White; please visit lutron.com for other color choices.) * (XX in the model number represents color/finish code; use WH for White; please visit lutron.com for other color choices.)
Price indicated for gloss finish products. Price indicated for gloss finish products.
Note: Pricing accurate as of 07/10/2022. For up to date pricing, contact your Lutron sales representative. ** (XX in the model number represents color/finish code; use WH for White; please visit lutron.com for other color choices.)
Price indicated for White finish products.
Note: Pricing accurate as of 07/10/2022. For up to date pricing, contact your Lutron sales representative.
70 | Lutron Lutron | 71
Ordering Information
Model Number Description List Price (US) Model number Description List Price (US)
L-CMDPIRKIT Sensor lens masking kit for Radio Powr Savr ceiling sensor 15.00 LSC-SPV-DOC-T24 Title 24 acceptance test visit
L-CRMK-WH Recess-mounting bracket for Radio Powr Savr ceiling sensor 21.50
LRF-ARM-WH Flexible armature mounting kit for Radio Powr Savr 74.00 Vive setup support services
wall, hall, corner sensors
LSC-OS-PROG8-SP Onsite programming — 8-hour block
L-WIRECAGE-WBX Wire guard for in-wall sensor, white 80.00
L-WIRECAGE-C Wire guard for ceiling-mount sensor, white 80.00 LSC-OS-PROG4-SP Onsite programming —4-hour block
L-WIRECAGE-W Wire guard for wall-mount and hallway sensors, white 80.00 Remote programming —8-hour block
LSC-RMT-PROG8-SP
Contact Lutron
LSC-PREWIRE Prewire visit
sales for a quote
Radio Powr Savr daylight sensor
LSC-TRAINING Customer-site solution training
LRF2-DCRB-WH Ceiling-mount daylight sensor 150.00
LSC-AF-VISIT Onsite scene and level tuning
72 | Lutron Lutron | 73
In-wall: Occupancy/vacancy switches Standalone Solutions
Standalone
Standalone solutions are not compatible with the Vive hub
•
•
Lutron XCT technology for superior sensitivity prevents false
ONs and false OFFs
• Automatically turns lights OFF when space is unoccupied
• Easy to install; directly replaces an existing control
•
Lutron Smart Ambient Light Detection learns your
Maestro sensor
preferences over time and adapts accordingly
Dimensions •
Lutron Adaptive Zero-Cross Switching extends relay lifetime
W: 2.94" (75 mm) • 180° sensor field-of-view; must have unobstructed view
H: 4.69" (119 mm)
D: 1.44" (38 mm)
•
Up to 900 ft2 major motion coverage and 400 ft2 minor
motion coverage
• Adjustable timeout—1-, 5-, 15-, 30-minutes
Vacancy/partial-ON models available to meet
Other energy-saving
•
CA Title 24 requirements
•
Dual-circuit sensors provide bi-level control of two circuits, as
required by specific energy codes
74 | Lutron Lutron | 75
In-wall: Occupancy/vacancy switches Standalone Solutions
Standalone
Standalone solutions are not compatible with the Vive hub
• • Standalone solutions are not compatible with the Vive hub
• L
utron XCT technology greatly enhances the performance •
Lutron XCT technology for superior sensitivity
of dual-technology sensors, enabling them to detect very prevents false ons and false offs
fine motion like typing • Automatically turns lights off when space is unoccupied
• Automatically turns lights off when space is unoccupied • Easy to install; directly replaces an existing control
• Easy to install; directly replaces an existing control •
Lutron Smart Ambient Light Detection learns your
Maestro dual-technology Lutron Smart Ambient Light Detection learns your preferences Maestro 0-10V dimmer sensor
•
preferences over time and adapts accordingly
sensor switch over time and adapts accordingly
Dimensions • 180° sensor field-of-view; must have unobstructed view
Dimensions • Lutron Adaptive Zero-Cross Switching extends relay lifetime W: 2.94" (75 mm) •
Up to 900 ft2 major motion coverage and 400 ft2 minor
W: 2.94" (75 mm) 180° sensor field-of-view; must have unobstructed view H: 4.69" (119 mm)
•
motion coverage
H: 4.69" (119 mm) D: 1.44" (38 mm)
• Up to 900 ft2 major motion coverage and 400 ft2 minor Adjustable timeout—1-, 5-, 15-, 30-minute
D: 1.44" (38 mm) •
motion coverage
•
Vacancy models available to meet CA Title 24
• Adjustable timeout—1-, 5-, 15-, 30-minute requirements
• Vacancy models available to meet CA Title 24 requirements • Controls electronic LED drivers and fluorescent ballasts
• Dual-circuit sensors provide bi-level control of two circuits, as • Miswire and load incompatibility alert —lens will
required by specific energy codes flash red if control is miswired or connected to an
incompatible fixture
MS-A202-XX** 6 A lighting per circuit, 120-277 V
dual-tech occupancy/vacancy, 4.4 A
fan (120 V only) per circuit; single pole,
neutral optional
*
For dual-tech or 0-10 V vacancy models, *
For dual-tech or 0-10 V vacancy models,
Add “-V-” before the color code (XX). MS-B202-XX** 6 A lighting per circuit, 120-277 V
Add “-V-” before the color code (XX).
** (XX in the model number represents dual-tech occupancy/vacancy ** (XX in the model number represents
color/finish code; use WH for Whites.) sensor, 4.4 A fan (120 V only) per color/finish code; use WH for White.)
See Maestro colors on page 70. See Maestro colors on page 70.
circuit; 3-way, neutral required
76 | Lutron Lutron | 77
In-wall: Occupancy/vacancy switches
• Standalone solutions are not compatible with the Vive hub Sensor switches *
• LED+ dimmer for control of LED lighting MS-OPS2-XX 2 A lighting, 120 V PIR occupancy/vacancy; single pole,
neutral optional 31.10
Sensor dimmers * *
MS-Z101-XX 8 A lighting 120-277 V; occupancy/vacancy; multi-location/
3-way/single pole 120.00
MSCL-OP153M-XX LED+ dimmer with PIR sensor; occupancy/vacancy;
single pole/3-way/multi-location; 150 W CFL/LED,
600 W incandescent/halogen 57.20
(1.5 m)
(1.5 m)
(9 m)
(6 m)
(3 m)
(3 m)
(6 m)
(9 m)
30 ft
30 ft
20 ft
20 ft
10 ft
10 ft
(6 m)
(6 m)
(3 m)
(3 m)
10 ft
10 ft
5 ft
20 ft
20 ft
5 ft
0
Lutron | 79
78 | Lutron
For a list of all Vive wireless solutions Questions?
product model numbers and pricing call us 24*7
1.844.588.7661
see lutron.com/vive
Contact Lutron
lutron.com/service
Lutron Electronics Co., Inc., 7200 Suter Road, Coopersburg, PA 18036-1299
Customer Assistance
Online: lutron.com/help
Email: support@lutron.com
Phone: 1.844.LUTRON1 (588.7661) — includes 24/7 technical support
I
© 02/2023 Lutron Electronics Co., Inc. P/N 367-2597 REV W
The Lutron logo, the Starburst logo, Lutron, Maestro, PowPak, Quantum, Radio Powr Savr, and Vive are
trademarks or registered trademarks of Lutron Electronics Co., Inc., in the U.S. and/or other countries.