Professional Documents
Culture Documents
SIFANG CSC-200 Instruction Manual (0SF.451.045E) V2.07
SIFANG CSC-200 Instruction Manual (0SF.451.045E) V2.07
MANUAL
CSC-200 NUMERICAL PROTECTION
MANUAL
Version: V2.07
WARNING
1) During operation of electrical equipment, certain parts of this equipment are
under high voltage. Severe personal injury or significant equipment damage
could result from improper behavior.
2) Only qualified personnel should work on this equipment or in vicinity of the
equipment. These persons must be familiar with warning & service procedure
described in this manual, as well as with safety regulations.
3) Prerequisites to proper & safety operation of the equipment are proper
storage, setup, installation, operation & maintenance of the equipment.
4) In particularly cases, the general rules & safety regulations according to
relating standards (e.g. IEC, National standards or other International
standards) for work with high voltage equipment must be observed.
COPYRIGHT
All rights reserved.
Registered trademark
® are registered trademark of Beijing Sifang Automation Co., Ltd.
CONTENTS
Part I Technical Instruction of Equipment ............................................................................................ 1
1 General ........................................................................................................................................... 1
12.1 Application....................................................................................................................................... 1
12.2 Main features ................................................................................................................................... 2
2 Technical Conditions .................................................................................................................... 3
3 Hardware ........................................................................................................................................ 4
3.1 Structure ........................................................................................................................................... 4
3.2 Overview of function module .......................................................................................................... 5
3.3 AC module (AC) .............................................................................................................................. 6
3.4 CPU module (CPU) ......................................................................................................................... 6
3.5 Logic module (LOG) ....................................................................................................................... 6
3.6 Digital output module (DO) ............................................................................................................. 6
3.7 Communication module (COM) ...................................................................................................... 7
3.8 Man-machine interface (MMI) ........................................................................................................ 7
3.9 Power supply module (POW) .......................................................................................................... 7
3.10 Module layout .................................................................................................................................. 7
4 Measurement and control function ............................................................................................. 8
4.1 Measurement meter .......................................................................................................................... 8
4.2 Breaker control ................................................................................................................................ 9
4.3 Operation mode control ................................................................................................................... 9
4.4 Programmable logic control ............................................................................................................. 9
4.5 Accident recording and analysis ...................................................................................................... 9
4.6 Communication .............................................................................................................................. 10
4.7 Test function................................................................................................................................... 11
4.8 EPPC® debugging and analysis software ....................................................................................... 11
5 CSC-211 numerical line protection measurement control equipment................................. 13
5.1 Introduction .................................................................................................................................... 13
5.2 Protection component .................................................................................................................... 14
5.3 Setting and description ................................................................................................................... 25
5.4 Terminal figure............................................................................................................................... 32
5.5 Wiring illustration .......................................................................................................................... 33
6 CSC-221 numerical capacitor protection measurement control equipment ...................... 34
6.1 Introduction .................................................................................................................................... 34
6.2 Protection component .................................................................................................................... 35
6.3 Setting and setting description ....................................................................................................... 40
6.4 Terminal figure............................................................................................................................... 44
6.5 Wiring figure .................................................................................................................................. 45
7 CSC-231 numerical reactor protection measurement control equipment .......................... 46
7.1 Application..................................................................................................................................... 46
7.2 Main functions ............................................................................................................................... 46
7.3 Protection component .................................................................................................................... 46
7.4 Setting and setting description ....................................................................................................... 50
I
7.5 Terminal figure ...............................................................................................................................53
7.6 Wiring figure and wiring description ............................................................................................. 54
8 CSC-241E numerical earthing transformer protection measurement control equipment 55
8.1 Introduction .................................................................................................................................... 55
8.2 Protection component .....................................................................................................................55
8.3 Setting and description ................................................................................................................... 58
8.4 Terminal figure ...............................................................................................................................62
8.5 Wiring figure and wiring description ............................................................................................. 63
9 CSC-298 numerical VT protection measurement control equipment .................................. 64
9.1 Introduction .................................................................................................................................... 64
9.2 Main functions................................................................................................................................ 64
9.3 Protection component .....................................................................................................................64
9.4 Setting and description ................................................................................................................... 66
9.5 Terminal figure ...............................................................................................................................68
9.6 Wiring figure and wiring description ............................................................................................. 69
10 Automatic bus transfer equipment(ABTE).......................................................................... 70
10.1 Introduction .................................................................................................................................... 70
10.2 Standby principle............................................................................................................................ 70
10.3 Introduction of line standby scheme .............................................................................................. 71
10.4 Protection and auxiliary monitoring function of line standby ........................................................82
10.5 Setting and setting description ....................................................................................................... 85
10.6 Introduction of main transformer standby scheme ......................................................................... 88
10.7 Main transformer backup protection and auxiliary monitoring function .......................................90
10.8 Setting description .......................................................................................................................... 92
11 CSC-241C numerical power plant (substation) transformer protection measurement
control equipment .................................................................................................................................. 96
12.2 Introduction .................................................................................................................................... 96
12.2 Protection component .....................................................................................................................97
11.3 Setting and description ................................................................................................................. 101
11.4 Terminal figure ............................................................................................................................. 104
11.5 Wiring illustration ........................................................................................................................ 105
12 CSC-237A numerical motor protection measurement control equipment ........................ 106
12.1 Introduction .................................................................................................................................. 106
12.2 Protection function ....................................................................................................................... 106
12.3 Setting and description ................................................................................................................. 121
12.4 Terminal figure ............................................................................................................................. 123
13 CSC-237C Digital motor protection measurement control IED .......................................... 124
13.1. IED Introduction .......................................................................................................................... 124
13.2. Main Functions............................................................................................................................. 124
13.3. Protection Elements...................................................................................................................... 125
13.4. Setting Value and Setting Specifications ..................................................................................... 134
13.5. IED terminal diagram ................................................................................................................... 138
13.6. Connection Schematic diagram and Specification ....................................................................... 139
Part II User Installation and Operation................................................................................................... 140
II
14 Box opening check ................................................................................................................... 140
15 Installation and debugging....................................................................................................... 140
15.1. Installation ................................................................................................................................... 140
15.2. Check before power on ................................................................................................................ 140
15.3. Insulation resistance measurement............................................................................................... 140
15.4. Check of equipment power on ..................................................................................................... 140
15.5. Check of sampling precision ........................................................................................................ 141
15.6. Digital input and digital output check .......................................................................................... 141
15.7. Trip and close current keeping test .............................................................................................. 141
15.8. In-station communication test ...................................................................................................... 142
15.9. Protection function test ................................................................................................................ 142
15.10. Phase sequence check ............................................................................................................ 142
16 Man machine interface and its operation .............................................................................. 142
16.1. Front layout of equipment ............................................................................................................ 142
16.2. Display under normal operation................................................................................................... 144
16.3. Equipmentmenu ........................................................................................................................... 145
16.4. Description of menu function ...................................................................................................... 146
17 Operation and maintenance .................................................................................................... 149
17.1. Equipment operation .................................................................................................................... 149
17.2. Equipment operation .................................................................................................................... 149
17.3. Notices in operation ..................................................................................................................... 149
17.4. Equipment maintenance ............................................................................................................... 150
17.5. Operation environment ................................................................................................................ 150
18 Transport and storage .............................................................................................................. 150
III
CSC-200 numerical protection measurement control equipment Manual
1. General
CSC-200 numerical protection measurement
control equipment is applicable to the power
system of under 110kV power grid and power
plant, it includes complete protection,
measurement, control and monitoring function,
provides complete solution for the protection and
control of the power system of the low-voltage
power grid and power plant, and can powerfully
guarantee the secure and stable operation of the
power system of the low-voltage power grid and
power plant.
1.1. Application
This instruction includes CSC-200 equipments and their applications, as shown in the table 1-1.
a) Embedded 32-bit microprocessor and 14-bit data collection system, is powerful in data
processing.
b) Flexible programmable protection and control logic, graphic editing of the protection and control
scheme, meet the personalized requirement.
c) Virtual test function, Automatic point synchronization of remote signals, automatic trigger of
SOE event, fault simulation, and online simulation of control scheme.
e) Complete records of operation information and fault information, supply enough data for
operation optimization and accident analysis.
f) High-precision measurement meter system independent of the CPU system, meet the
requirement for operation monitoring and remote automatic meter reading.
g) Perfect software and hardware self-check function, adjustment-free circuit design, is easy to be
installed and debugged.
h) Friendly man-machine interface, simple operation, 11 indicators indicating the operation status
of the equipment.
i) Network time synchronization, GPS impulse time synchronization, IRIG-B code time
synchronization, possess hardware clock system.
j) PC-based auxiliary analysis software, realize the protection and control logic customization,
accident analysis and virtual test easily.
l) Can be centrally grouped as screen, or be installed on the switch cabinet indoors or outdoors.
2
CSC-200 numerical protection measurement control equipment Manual
2. Technical Conditions
DC voltage: 220V/110V
phase voltage: 100V
Rated inputs Open-delta voltage:300V
AC current: 1A/5A
Frequency: 50Hz
Current: ≤ 3%
Accuracy Voltage: ≤ 5%
Direction: ≤ ±2
o
DC circuit: ≤ 35W
Power
AC current: phase ≤ 1VA (In=5A) or ≤ 0.5VA (In=1A)
consumption
3
CSC-200 numerical protection measurement control equipment Manual
3. Hardware
3.1 Structure
According to IEC60297-3 standard, enclosure is 4U high and 19 wide. It adopts whole built-in mode
2
and is wired in the rear. The dimension of the installation is shown as the figure 3-1.
4
CSC-200 numerical protection measurement control equipment Manual
5
CSC-200 numerical protection measurement control equipment Manual
It is the core module of equipment, including CPU system, data sampling system, switch input/output
system, real time hard-clock system and high-speed communication system. The multi-layer printed
circuit and surface mount technology are used, including multiple anti-disturbance methods.
The logic module provides the protection trip and close control, remote trip and close control,
action/alarm signal output, and has an effect of electric isolation. Wherein, to avoid misoperation caused
by component damage, all important output can be executed after the QD relay is open.
6
CSC-200 numerical protection measurement control equipment Manual
trip and close keeping and trip prevention. The keeping current of the trip and close is self-adapted within
0.5 ~ 4A, so the electric parameters of the loop can not be changed. The trip and close operation loop of
this module can be cancelled according to the technical requirement of users.
COM module is mainly used for the fiber communication and communication extension and is the
optional module. It consists of a pair of fiber interface for receiving and transmission (wavelength: 850nm,
fiber interface: ST interface, receiving sensibility: -34.4dBm, transmission power: >-15.6dBm), a
LonWorks interface, and IRIG-B code timing connection.
7
CSC-200 numerical protection measurement control equipment Manual
b) Voltage Ua,Ub,Uc
h) Monitoring
8
CSC-200 numerical protection measurement control equipment Manual
The breaker can be normally closed and opened via the communication interface, operation handle on
the screen cabinet or operation interface of equipment. The equipment provides the interval lock function
to prevent from misoperation, and its interval lock logic can be customized via the logic editor.
The remote control is allowed upon “remote/local” digital input high level, the remote control is locked
upon low level, the onsite operation function is not affected by this digital input.
The equipment provides 32-group setting management function, which will not be lost upon cut off and
can meet the operation mode change’s need in most cases.
Soft switch of the main protection component is provided. The user can starts up/shuts down part of the
protection components via the communication interface or operation interface to meet the operation
requirement and the status will not be lost upon cut off.
9
CSC-200 numerical protection measurement control equipment Manual
d) Operation setting
EPPC tool software is used to call the recording wave, the operation steps are as follows: under the
debugging mode, to click main menu\accident record\record duplication, select the accident record SN to
view in the record duplication dialog, click “copy” to copy the records to the debugging window, right click
this record, and pop up the shortcut menu, to click “wave recording data”, the recording wave figure is
called.
4.6 Communication
The equipment is equipped with a RS232 debugging port on the front panel to connect PC. The PC can
set parameters, test functions, download software and analyze data via the EPPC. The signal definitions
of the debugging port are shown as the figure 4-2.
DB9/M DB9
Pin Signal Pin Signal
2 RXD 2 RXD
3 TXD 3 TXD
5 GND 5 GND
Debugging port of
equipment PC RS232
10
CSC-200 numerical protection measurement control equipment Manual
To meet the networking requirement of the automated system, the equipment provides the following
communication ports for the user to select, refer to equipment wiring figure for Ethernet interface and 485
interface.
The equipment supports IEC60870-5-103 and CSC-2000 communication protocol. It can transmit real
time operation information (such as measurement data, switch location and event records) to the station
monitoring or SCADA system via the communication port and corresponding communication protocol.
The station-level devices can distribute the control command to the equipment or remotely manage the
protection information via the communication interface.
The user can check the important hardware loop via the test command provided by the equipment, such
as AC loop, digital input loop and digital output loop.
To cooperate the implementation of the automated system engineering, the equipment provides the
remote point testing function to quickly inspect the information library of local monitoring and remote
main station, which makes the monitoring and remote communication personnel free of trivial manual
point testing operation, including remote signal point aiming, remote measurement point aiming, alarm
event point aiming and action event point aiming. To check the communication status of the equipment
and find the possible communication bug of the equipment and its located network, the operation
statistics information of related communication ports is provided as the network diagnosis data.
EPPC debugging analysis software package will be issued together with the equipment, it runs under
Windows 98/2000/NT/XP environment, is easy for installation and operation. The hardware test,
protection configuration and monitoring and control of the equipment can be easily realized by using
RS232 debugging port of the front panel and PC advantage in resource.
11
CSC-200 numerical protection measurement control equipment Manual
b) Connector setup, setting zone switching, time setup, and signal reset
f) Quick update and upgrade support of configuration scheme and protection software
g) Monitoring and testing of equipment AC loop, digital input and digital output loop
12
CSC-200 numerical protection measurement control equipment Manual
5.1 Introduction
CSC-211 is line protection measurement control equipment that is applicable to neutral indirect ground
system of under 110kV and can be installed inside the switch cabinet on the spot.
b) Three-zone zero-sequence over current protection (EF) with definite-time (via direction lock),
wherein Ⅲ can be set as reverse-time zone (Once set as reverse-time, definite-time
zero-sequence over current II and Ⅲ exit automatically).
b) Remote control of open and close for small current-grounded detection, remote control of open
and close for normal breaker
c) Remote measurement of Ua, Ub, Uc, Ia, Ic, P, Q, cosϕ and F analog
13
CSC-200 numerical protection measurement control equipment Manual
e) 32 setting-group
a) MAX ( Ia, Ib, Ic) > Idzn , Idzn is the current setting of the nth zone;
b) Delay expiration
c) The low-voltage component and the direction component meet the operation conditions
The three-zone over current protection starts up/shuts down via a soft connector, when the rear board
terminal X5.7 is used as the common remote signal. The software and hardware combined connector
mode can be selected. Here, the X5.7 is the hard contact digital input of the three-zone over current
protection. The direction component and low-voltage component can be quit or adopted via the control
word. When the direction or low-voltage lock condition starts up, the protection logic is affected by the VT
disconnection and control word KG1.13; when the direction and low-voltage lock condition do not
operate, the protection logic is not affected by VT disconnection. The following figure shows the A phase
over current protection logic with the direction and low-voltage lock condition.
The over current Ⅲ zone can be set as the reverse-time (here, the over current II and Ⅲ zone exit), the
logic figure is shown as follows (taking A phase reverse-time over current as one example):
14
CSC-200 numerical protection measurement control equipment Manual
The low-voltage component can be quit or adopted via the control word.
b) Delay expiration
The three-zone zero-sequence over current protection starts up/shuts down via a soft connector, and the
zero-sequence direction component can be quit or adopted via the control word. When the direction
component starts up, the protection logic is affected by the VT fail and control word KG1.13,or the
protection logic is not affected by VT fail.
The three-zone zero-sequence over current with definite-time protection logic is shown as follows (taking
zero-sequence over current I zone as one example):
15
CSC-200 numerical protection measurement control equipment Manual
The zero-sequence over current Ⅲ can be set as the reverse-time (here, the zero-sequence over current
II and Ⅲ zone shuts down), and the protection logic is shown as follows:
< 30o (as shown in the figure 5-5), the error is smaller than ±2°, and sensibility angle is -30°.
U
−90o < arg
I
To eliminate the dead area, the direction component has memory function.
3I 0
The action zone of the zero-sequence direction component is 120 < arg < 240o , 3U0 is the
o
3U 0
self-generation zero-sequence voltage, the external 3I0 terminal wiring is not reverse, and the blurry
angle error of the edge is smaller than ±5°(as shown in the figure 5-6).
16
CSC-200 numerical protection measurement control equipment Manual
Action 120o
zone
3U0
3I0 120o
Note: when the onsite test condition is not met, only the analogue phase sequence is validated, and the
direction action zone is not validated.
If there is no main station system, it is judged as the ground line as the 3U0 is higher than 18V upon
close, 3U0 is smaller than 18V after the onsite test trip and open,. The alarm message “local line
ground“ is reported. After trip test, the equipment will automatically reclose.
In addition, the equipment includes the trip test and line selection function. The on-duty person
makes the trip operation at the monitoring main station to identify the ground line. The test trip
provides the automatic reclose function. (When the reclose starts up and the hide trip reclosing
control word starts up)
17
CSC-200 numerical protection measurement control equipment Manual
c) Extreme reverse-time: t = 80
Tp
I 2
( ) −1
Ip
Wherein: Tp is the time coefficient, ranges from 0.05 to 1; Ip is the basic current, I is the fault current, and t
is the trip time.
Deducted from above equation, the reverse time limit feature expression of this equipment is written as
the equation 5-1:
Tinv
t= (equation 5-1)
I
( ) Exp − 1
Ip
The reverse-time index setting is the Exp value of the equation 5-1 in the setting list. The reverse-time
time setting is the Tinv in the equation 5-1. it is the product of the numerator in the above three IEEE
expressions and the unit is second.
18
CSC-200 numerical protection measurement control equipment Manual
The inter-phase current and zero-sequence current of the equipment includes the fixing and reverse time
protection function. The related bits of the control word can be set to select the definite-time or
reverse-time limit. When the reverse time is selected, the definite-time over current II and III zone and
zero-current II and III zone component will automatically shuts down, the function connector of the
inter-phase current III zone and zero-sequence current III zone becomes the connector of the
inter-phase current reverse-time and zero-sequence current reverse-time function.
d) The breaker changes from open to close and closes at the fault.
2.The breaker keeps open means TWJ of the device is close which is the actual location of the
breaker.
a) MAX ( Ia, Ib, Ic) > Idz ,Idz is acceleration current setting:
b) Delay expiration
The over current acceleration low-voltage lock can operate and exit via the control word. When the
low-voltage lock starts up, the protection logic is affected by VT fail and control word KG1.13,or the
protection logic is not affected by VT fail.
a) The zero-sequence current is higher than the zero-current acceleration current setting;
b) Delay expires
The logic of the manual close over current acceleration protection is shown as follows:
19
CSC-200 numerical protection measurement control equipment Manual
The logic of the manual close zero current protection is shown as follows:
a) Protection trip
When the breaker closes, the reclosing starts to be charged, the charging duration is 15 s. The green
reclosing indicator will flicker during charging. The green indicator will keep on after the reclosing is
charged fully. When any condition is met, the reclosing starts to discharge.
20
CSC-200 numerical protection measurement control equipment Manual
b) The spring non energy storage terminal is at high level and is discharged after 2 s delay.
d) After permanent trip (such as under-frequency, under-voltage action, and over-load action )
b) Check no voltage
c) Check synchronization
d) If check no voltage fails, the reclosing will automatically enter into the check synchronization.
The reclosing function starts up/shuts down via the soft connector; the reclosing mode and
synchronization phase selection are set via the control word. For check no voltage mode, when the
control word KG2.9=0, and the line extraction voltage is lower than 0.3Un, it is judged as no voltage;
when the control word KG2.9=1, no bus voltage or no line extraction voltage is met, it is judged as no
voltage.
Note: when the PT is not installed on the line side, the reclosing mode should be non synchronization
mode.
The reclosing mode, synchronization phase selection uses the same control word and setting of
Sync-Check with three phase first reclosing. For “DI4 manual digital input“ is at the high level , check
whether the close condition is met during extension period 9s, if it is met, equipment puts the spare exit 2
out.
When the manual close digital input keeps a high level for 10s, an alarm “manual close digital input
error“ is reported.
Action condition:
b) Delay expiration.
Lock condition:
a) The minimum line voltage is lower than the lock voltage setting;
d) When the load current < Idz(this condition is optional via the control of the control word);
e) VT disconnect;
Idz is the under-frequency current setting, its setting range is from 0 to 10.0In, it is recommend to be over
0.1In.
The under frequency load shedding component starts up/shuts down via a soft connector, the rear
terminal X5.6 is used as the common remote communication. If the software and hardware combined
connector mode be selected, the X5.6 is the hard contact digital input of this component.
Note: the under frequency signal indicator (red indicator) of the panel can be used as the under
voltage action indicator.
Action condition:
b) Delay expiration:
Lock condition:
22
CSC-200 numerical protection measurement control equipment Manual
a) ΔU/Δt > lock setting of voltage change rate, wherein ΔU/Δt is change rate of any line voltage;
b) Three-phase current is lower than 0.1In(this condition is optional via the control of the control
word);
f) VT disconnection;
The low-voltage separation protection equipment function starts up/shuts down via the control word.
Note: the under-frequency signal indicator(red indicator) of the panel can be used as the under-voltage
action indicator.
Max(Uab,Ubc,Uca)<Udz
ΔU/Δt >(du/dt)dz
U2 > 5V
VT Fail
On unclosed status
a) MAX ( Ia, Ib, Ic) > Idz , Idz is the over-load current setting;
b) Delay expiration;
The over-load function starts up/shuts down via the soft connector and the control word is used to
decide whether to trip.
Note: this equipment considers that generally the over-load time is long delay, and the protection exit
delay is the practical setting time, but the report does not embody it.
23
CSC-200 numerical protection measurement control equipment Manual
Wherein Ttz is the over-load trip time and Tgj is the over load alarm time.
a) If the self-generated 3U0 is smaller than 8V, the three-phase voltage is smaller than 8V, and
the current is over no current threshold (the default is 0.125 A), it is judged as three phase
voltage loss.
b) If the self-generated 3U0 is higher than 8V, and the minimum line voltage is lower than 16V,
it is judged as two-phase failure.
c) If the self-generated 3U0 is higher than 8V and the difference between the maximal line
voltage and minimal line voltage is higher than 16V, it is judged as single phase VT failure.
After the equipment detects VT failure, it can exit the protection with direction component or voltage
component via the control word, or select to shut down the direction components and voltage
components.
If the analog self-check function and reclosing function operate, and the reclosing selects the check
no voltage or check synchronization mode, when the line voltage is lower than 0.3Un and any phase
current is higher than the default 0.125A (no current value can be changed in the factory setting).
The line VT fail is reported after 9-second delay, the alarm signal is given, and the automatic
reclosing is locked. When the line voltage recovers to normal status, the reclosing will automatically
recover to normal status.
VT loop monitoring function starts up/shuts down via the analog self-check control word.
24
CSC-200 numerical protection measurement control equipment Manual
No current
Ux<0.3Uxn
ARC Sync-Check
& 9S Report“Ux VT Fail”
≥1 KG1.15=1
ARC Check LU
Relay start up
factory setting.
Name Function
OC Ⅰ OC Ⅰ ON/OFF
OC Ⅱ OC Ⅱ ON/OFF
OC Ⅲ OC Ⅲ ON/OFF
EF Ⅰ EF Ⅰ ON/OFF
EF Ⅱ EF Ⅱ ON/OFF
25
CSC-200 numerical protection measurement control equipment Manual
Name Function
EF Ⅲ EF Ⅲ ON/OFF
0.25~100(In=5A)
4 OC Ⅰ I A
0.05~20(In=1A)
5 OC Ⅰ T 0.0~32.00 s
0.25~100(In=5A)
6 OC Ⅱ I A
0.05~20(In=1A)
7 OC Ⅱ T 0.1~32.00 s
0.25~100(In=5A)
8 OC Ⅲ I A
0.05~20(In=1A)
9 OC Ⅲ T 0.1~32.00 s
0.25~100(In=5A)
11 EF Ⅰ I A
0.05~20(In=1A)
26
CSC-200 numerical protection measurement control equipment Manual
12 EF Ⅰ T 0.0~32.00 s
0.25~100(In=5A)
13 EF Ⅱ I A
0.05~20(In=1A)
14 EF Ⅱ T 0.1~32.00 s
0.25~100(In=5A)
15 EF Ⅲ I A
0.05~20(In=1A)
16 EF Ⅲ T 0.1~32.00 s
OC ACC I
0.25~100(In=5A)
17 A
0.05~20(In=1A)
OC ACC T
18 0.0~3.00 s
EF ACC I
0.25~100(In=5A)
19 A
0.05~20(In=1A)
EF ACC T
20 0.0~3.00 s
0.25~100(In=5A)
21 OC INV I A
0.05~20(In=1A)
22 OC INV T 0.005~250 s
0.25~100(In=5A)
23 EF INV I A
0.05~20(In=1A)
24 EF INV T 0.005~250 s
0.25~100(In=5A)
26 Overload I A
0.05~20(In=1A)
27
CSC-200 numerical protection measurement control equipment Manual
27 OL Alarm T 6~6000 s
28 OL Trip T 0.1~6000 s
30 ARC T 0.2~32.0 s
31 UF F 45.0~49.5 Hz
32 UF T 0.0~32.0 s
0~50(In=5A)
35 BLK UF I A
0~10(In=1A)
37 UV split T 0.1~32.0 s
14 CT Rated 5A CT Rated 1A
28
CSC-200 numerical protection measurement control equipment Manual
29
CSC-200 numerical protection measurement control equipment Manual
3 Reclosing phase
1
Reclosing mode
0
Note:To separate the reclosing signal node from the protection action signal node, the enhanced
CSC211 terminal X6-19 and X6-20 can be used as the reclosing action signal contact. This contact
can act as the reclosing action signals or spare exit 4 via the control word KG2.10 in the software. If
this node is used as the reclosing action signal contact in the engineering, please set the control
word KG2.10 as the “1”.
1 0 ARC Check LU
0 0 0 /
0 0 1 Syn-Check UA
30
CSC-200 numerical protection measurement control equipment Manual
0 1 0 Syn-Check UB
0 1 1 Syn-Check UC
1 0 0 None
1 0 1 Syn-Check UAB
1 1 0 Syn-Check UBC
1 1 1 Syn-Check UCA
2 EF CT Rated 1A EF CT Rated 5A
b) CT change ratio is special for measurement; it is set via dividing the change ratio by 1000.
c) All protection function can start up/shut down via the soft connector or control word.
31
POWER TRIP LOGIC CPU COM AC2 AC2 AC1
X8 X7 X6 X5 X4 X3 X2 X1
1 DI1 BLK ARC 1 1 Common 1 Rem/Loc 1 Ua 1 1
2 DI2 CB unpower 2 2 Trip1 2 Reset 2 Ub 2 2
3 3 3 Close1 3 Overhaul 3 Uc 3 3
4 4 4 Common 4 4 Un 4 4
5 5 5 Trip2 5 -24V 5 Ux 5 5
6 6 6 Close2 6 UF/P 6 Ux' 6 6
5.4 Terminal figure
7 7 7 Common 7 OC/Q 7 7
8 8 8 Remote trip 8 Common- 8 8
9 9 9 Remote close 9 9 9
10 (-) 10 10 Common 10 10 10
11 11 11 Operation 11 11 11
12 12 12 Alarm 12 12 12 Ib'
13 13 13
Backup1
14 Failure 14 14
15 15 15
Backup2
16 16 16
CSC-200 numerical protection measurement control equipment
17 17 17
Backup3
32
18 18 18
19 19 19
20 20 20
33
CSC-200 numerical protection measurement control equipment Manual
6.1 Introduction
It is applicable to 66kV and lower capacitor protection and measurement and control and can be installed
at the switch cabinet.
d) Over-voltage protection(OV)
e) Under-voltage protection(UV)
d) Over-voltage protection
e) Under-voltage protection
b) Remote control of open and close for small current-grounded detection, remote control of open
and close for normal breaker
c) Remote measurement of Ua, Ub, Uc, Ia, Ib, Ic, P, Q and cosϕ
d) Forward/reverse re power
c) CB unpower alarm
34
CSC-200 numerical protection measurement control equipment Manual
MAX(IΦ) > MIN(Id ); Id is n-zone over current setting, IΦ is phase current (terminal X2-1~6).
Two-zone over current protection starts up/shuts down via the soft connector.
Action condition:
Two-zone zero-sequence over current protection starts up/shuts down via a soft connector.
The zero-sequence rated current is 1A or 5A and can be set via the internal parameters.
35
CSC-200 numerical protection measurement control equipment Manual
b) The three phase current of this line is lower than the setting
c) The line voltage exists for over 2s, namely the voltage reduction edge action
The under-voltage protection starts up and shuts down via a soft connector. When the mode is “soft and
hard combination”, the hard connector (5X-7) should operate.
b) T > setting;
c) Breaker is closed;
The over-voltage protection starts up/shuts down via the soft connector.
0.14 13.5 80
t= tp t= tp t= tp
(I Ip) −1
0.02
(I Ip) −1 (I Ip) −1
2
Wherein: tp is the time coefficient, ranges from 0.05 to 1; Ip is the basic current, I is the fault current, and t
is the trip time.
Deducted from above equation, the reverse time limit feature expression of this equipment is written as
Tinv
t=
(I Ip)Exp−1
the equation.
The reverse-time index setting is the Exp value of the equation. The reverse-time time setting is the Tinv,
it is the product of the numerator in the above three IEEE expressions and the unit is second.
The inter-phase current and zero-sequence current of the equipment includes the fixing and reverse time
protection function. The related bits of the control word can be set to select the definite-time or
reverse-time limit. When the reverse time is selected, the definite-time over current II zone and
zero-current II zone component will automatically shuts down, the function connector of the inter-phase
current II zone and zero-sequence current II zone becomes the connector of the inter-phase current
reverse-time and zero-sequence current reverse-time function.
a) Any one (three phase) of three phase imbalanced input (terminal X1-1 ~ 6) is higher than the
imbalanced setting
b) Breaker is closed
Note: If the imbalanced analog only includes one phase, connect the three phase imbalanced input
terminal to get any phase.
37
CSC-200 numerical protection measurement control equipment Manual
a) Any one of three line voltages is higher than the automatic switching over-voltage setting;
a) Three line voltage is lower than the automatic switching low-voltage setting and is higher than
64V
38
CSC-200 numerical protection measurement control equipment Manual
To prevent capacitor from closing upon fault, manual trip, remote trip or protection lock occurs, this
protection automatically shuts down “Autoswitch” soft connector. Therefore, the spare action signal
contact should feed back to connect to lock digital input.
a) If the three phase voltage is lower than 8V and the current of a phase (a or c phase) is
higher than 0.25A (set), it is judged as the three phase voltage loss.
b) If the sum of the three phase voltage is higher than 8V and the minimal line voltage is lower
than 16V, it is judged as the two-phase VT failure.
c) If the sum of the three phase voltage is higher than 8V and the difference between
maximum and minimum line voltage is higher than 16V, it is judged as the single phase VT
failure.
VT loop monitoring function starts up/shuts down via the self-check control word. When KG1.15
(D15)=1, VT detection function starts up;
39
CSC-200 numerical protection measurement control equipment Manual
The protection type of the CSC-221A and CSC-221B capacitor is 41H in hexadecimal, CSC-221A setting
type is 91H, and the CSC-221B setting type is 92H.
Name Function
OC Ⅰ OC Ⅰ ON/OFF
OC Ⅱ OC Ⅱ ON/OFF
EF Ⅰ EF Ⅰ ON/OFF
EF Ⅱ EF Ⅱ ON/OFF
OV OV ON/OFF
UV UV ON/OFF
Connector8 Backup
Connector9 Backup
0.25~100(In=5A)
3 OC Ⅰ I A
0.05~20(In=1A)
4 OC Ⅰ T 0.0~32.00 S
0.25~100(In=5A)
5 OC Ⅱ I A
0.05~20(In=1A)
40
CSC-200 numerical protection measurement control equipment Manual
6 OC Ⅱ T 0.1~32.00 S
0.25~100(In=5A)
7 EF Ⅰ I A
0.05~20(In=1A)
8 EF Ⅰ T 0.0~32.00 S
0.25~100(In=5A)
9 EF Ⅱ I A
0.05~20(In=1A)
10 EF Ⅱ T 0.1~32.00 S
0.25~100(In=5A)
11 OC INV I A
0.05~20(In=1A)
12 OC INV T 0.005~120 S
0.25~100(In=5A)
13 EF INV I A
0.05~20(In=1A)
14 EF INV T 0.005~120 S
16 Imbalanced 0.25~100(In=5A)
A CSC221B: Imbalanced I
0.05~20(In=1A)
17 Imbalanced T 0.0~32.0 S
18 OV V 70~130.0 V Phase-to-phase
19 OV T 0.0~100.0 S
20 UV V 10~110.0 V Phase-to-phase
21 UV T 0.0~100.0 S
41
CSC-200 numerical protection measurement control equipment Manual
0.25~100(In=5A)
22 BLK UV I A
0.05~20(In=1A)
26 Auto On T 0.1~100.0 S
Mea CT
27 0.001~7.0 Primary Mea CT/1000
Ratio(kA/A)
Mea VT
28 0.01~2.0 Primary VT/1000
Ratio(kV/V)
D5 OV Trip OV Alarm
D4 EF Ⅱ Trip EF Ⅱ Alarm
D3 EF Ⅰ Trip EF Ⅰ Alarm
42
CSC-200 numerical protection measurement control equipment Manual
D0 OV 3X1~4 OV Clearance
2. When the over-voltage is the bus voltage (KG1.0=0), the bus voltage is connected to the terminal
X3-1~4; when the over-voltage is the clearance voltage (KG1.0=1), the clearance voltage is connected to
the terminal X1-3 ~ 6, and any voltage of two channels is higher than the over-voltage setting, action
occurs.
b) CT change ratio is special for measurement, and is set via dividing the change ratio by 1000.
c) All protection equipment function can start up/shut down via the soft connector or control word.
e) The above part lists the standard configuration. If the content is not consistent with the
equipment list, refer to the practical equipment.
43
POWER TRIP LOGIC CPU COM AC2 AC2 AC1
X8 X7 X6 X5 X4 X3 X2 X1
1 DI1 1 1 Common 1 Rem/Loc 1 Ua 1 1
2 DI2 CB unpower 2 2 Trip1 2 Reset 2 Ub 2 2
3 3 3 Close1 3 Overhaul 3 Uc 3 3
4 4 4 Common 4 4 Un 4 4
5 5 5 Trip2 5 -24V 5 5 5
6 6 6 Close2 6 OV/P 6 6 6
7 7 7 Common 7 UV/Q 7 7
6.4 Terminal figure
17 17 17
Backup
18 18 18
44
19 19 19
Backup
20 20 20
Wiring note: if only one imbalanced analog input is provided, the A phase X3-1 and X3-2 of the three
phase imbalance at the X3 terminal is connected. If the automatic voltage switching function of this
equipment is not used, the action signal contact of the X6-19~20 is not connected to the X5-4. Generally
the strong current digital input 1 (X8-1) is used as the remote communication of the entity. After the entity
action is expanded by the external relay, the connection equipment trips and the digital input makes a
remote communication.
45
CSC-200 numerical protection measurement control equipment Manual
7.1 Application
CSC-231 is applicable to 66kV and lower low-voltage reactor protection and can be installed at the
switch cabinet.
b) Ratio restraint differential protection with secondary harmonic restraint reacts on inner-faults
d) Non-electric protection
c) Remote measurement of analog Ua, Ub, Uc, Ia, Ic, P, Q and COSф
46
CSC-200 numerical protection measurement control equipment Manual
If the above two equations are met, the ration differential components will act. Wherein, Id is the
differential current, Ir is the restraint current, Kcd is the ratio coefficient, Icd is the threshold setting of
differential current, and Ir0 is the inflexion current.
Id =∣ I&1 + I&2 ∣
Kc
Icd
0 Ir0 I
Wherein, I&1 and I&2 are the currents on two sides of the reactor, its forward direction is the flow-in
direction of the reactor.
The current inductor on two sides of the reactor has same polarity in the reactor direction.
Wherein Id2 is the secondary harmonic of the three differential current, Id is the corresponding phase
differential current, and Kxb is the secondary harmonic coefficient. Any phase of the three current meets
the above condition, the three phase ratio differential protection is locked. The secondary harmonic
break components can starts up/shuts down via the control word.
The CT disconnection is judged via checking whether one phase or two phases have no current but have
differential current.
47
CSC-200 numerical protection measurement control equipment Manual
2) One or two of three phase have no current on local side, but the three phase currents of other
side do not change.
When the above condition is met, the CT secondary loop disconnection is judged.
After CT secondary disconnection, the alarm signal is given; you can select to lock or not to lock
differential protection.
If the differential current is higher than the differential current ex-limit alarm setting, the alarm is given
after the judgement exceeds 10s, the differential current ex-limit is reported, but differential protection is
not locked. This function can be used to monitor the AC sampling loop of the protection equipment.
OC
Iψ>Idz Td Trip
Note: Idzn is the n-zone current setting, IΦ is the phase current, and Tdn is the n-zone time delay setting.
EF
I0>Idz Td Trip
48
CSC-200 numerical protection measurement control equipment Manual
The control word can determine the over load trip or alarm.
When KG1.10=1, the HWJ of this equipment is not used, the control loop disconnection report is not sent;
at this time, DI4 is used as the HWJ digital input and the high bit indicates the close status.
If the non non-electric directly puts out and gives the signal via the relay reclosing box, the non
non-electric is not connected to this equipment.
49
CSC-200 numerical protection measurement control equipment Manual
The protection type of the CSC-231 is 42H in hexadecimal, CSC-231 setting type is 93H.
Name Function
Diff
Differential protection ON/OFF
Fast Diff
Fast differential protection ON/OFF
OC Ⅰ
OC Ⅰ ON/OFF
OC Ⅱ
OC Ⅱ ON/OFF
EF
EF ON/OFF
Non-electric
Non-electric ON/OFF
Overload
Over load ON/OFF
UV
UV ON/OFF
Connector9
Backup
Connector10
Backup
0.05~4(In=1A)
3 Diff Startup I A (0.2~2.0)Ie
0.25~20(In=5A)
0.05~4(In=1A)
4 Restraint I A (0.8~3.0)Ie
0.25~20(In=5A)
0.05~20(In=1A)
7 Fast Diff I A (1.0~15)Ie
0.25~100(In=5A)
0.05~4(In=1A)
8 Diff Ex-limit A
0.25~20(In=5A)
0.05~20(In=1A)
9 OC Ⅰ I A
0.25~100(In=5A)
50
CSC-200 numerical protection measurement control equipment Manual
10 OC Ⅰ T 0.0~32.00 s
0.05~20(In=1A)
11 OC Ⅱ I A
0.25~100(In=5A)
12 OC Ⅱ T 0.10~32.00 s
0.05~20(In=1A)
13 EF I A
0.25~100(In=5A)
14 EF T 0.04~32.0 s
0.05~20(In=1A)
15 Overload I A
0.25~100(In=5A)
16 Overload T 0.10~9000.00 s
17 UV V 10~120.0 V Phase-to-phase
18 UV T 0.0~32.0 s
0.05~4(In=1A)
19 BLK UV I A
0.25~20(In=5A)
51
CSC-200 numerical protection measurement control equipment Manual
b) CT change ratio is special for measurement, and is set via dividing the change ratio by 1000.
c) All protection equipment function can start up/shut down via the soft connector or control word.
e) It lists the standard configuration. If the content is not consistent with the equipment list, refer to
the practical equipment.
52
7.5
POWER TRIP LOGIC CPU COM AC2 AC2 AC1
X8 X7 X6 X5 X4 X3 X2 X1
1 1 1 Common 1 Rem/Loc 1 Ua 1 1
2 2 2 Trip1 2 Reset 2 Ub 2 2
3 3 3 Close1 3 Overhaul 3 Uc 3 3
4 4 4 Common 4 Backup 4 Un 4 4
5 5 5 Trip2 5 -24V 5 5 5
6 6 6 Close2 6 P 6 6 6
7 7 7 Common 7 Q 7 7
8 8 8 Remote trip 8 Common- 8 8
9 9 9 Remote close 9 9 9
10 (-) 10 10 Common 10 10 10
11 11 11 Operation 11 11 11
12 12 12 Alarm 12 12 12
Terminal figure
13 13 13
Backup
14 Failure 14 14
15 15 15
Backup
16 16 16
17 17 17
Backup
18 18 18
CSC-200 numerical protection measurement control equipment
19 19 19
Backup
20 20 20
53
11 RS485A 11 RS485A 11 RS485A 11 RS485A 11 RS485A
12 RS485B 12 RS485B 12 RS485B 12 RS485B 12 RS485B
13 Resistance 13 Lon-A 13 Lon-A
14 RS485A 14 Lon-B 14 Lon-B
15 RS485B 15 Not used 15 Lon-A
16 Resistance 16 Not used 16 Lon-B
A
+24V(X8.11)
B X5
DI1
C Remote/Local 1
Reset DI2
2
Spare DI3
3
Spare DI4
4
X2 -24V 5 -24V(X8.12)
P +24V
1 Ia1 6
2 Ia1’ Q 7
Ib1 COM- 8 -24V
3
4 Ib1’ SYNA+ 9 Pluse
5 Ic1 SYNA- 10 -24V
Pro.CT 6 Ic1’ RS485A 11
7 I0 RS485B 12
IEC60870-5-103
Zero CT 8 I0' X6
9 Ia COM 1 +KM
10 Ia' Trip1 2 X7.3
Mea.CT
11 Ic Close1 3 X7.7
12 Ic' COM 4
Trip2 5
X3
1 Ua Close2 6
2 Ub COM 7 +KM
3 Uc Remote trip 8 X7.2
4 Un Remote close 9 X7.7
5 COM 10 +XM
6 Operation 11 Operation
Alarm 12 Alarm
+KM X8 13
DI1 Backup1
1 DI1 14
DI2 2 DI2 15
DI3 Backup2
3 DI3 16
DI4 17
4 DI4 Backup3
DI5 18
5 DI5
DI6 19
6 DI6 Backup4
DI7 20
7 DI7
DI8
8 DI8
DI9 X7
9 DI9
+KM 1 +KM
-KM 10 DI(-) Manual Trip 2 X6.8
11 +24V
Relay Trip 3 X6.2
12 -24V
Open winding 4 Trip
13 DC
signal Failure Close winding 5 Close
14
Short to CW 6
15 Not uesd
Close 7 X6.3
(+) 16 DC(+) X6.9
220/110 -KM 8 -KM
17 Not used
DC supply COM 9 +XM
(-) 18 DC(-)
TWJ 10 G
19 Not used
HWJ 11 R -XM
20 GND
12
CC broken
13
UTP5 Eth 14
HUB/SWITCH 1 Event Spare
RJ45-1 15
Out for 16
Spare
manual trip 17
Eth 18
HUB/SWITCH 2 RJ45-2
19
20
54
CSC-200 numerical protection measurement control equipment Manual
e) Non-electric protection
control
c) 32 setting-group
55
CSC-200 numerical protection measurement control equipment Manual
a) I0> I0dz, I0dz is the zero sequence current setting, I0 is zero sequence current.
56
CSC-200 numerical protection measurement control equipment Manual
zero sequence over current protection starts up/shuts down via the soft connector.
Figure 8-3 Zero sequence over current protection at high voltage side logic
Figure 8-4 Zero sequence over current protection at low voltage side logic
a) U0>U0dz,U0dz is the zero sequence voltage setting, U0 is zero sequence voltage of external
input.
57
CSC-200 numerical protection measurement control equipment Manual
The protection type of the CSC-241E is 47H and the setting type is 9AH.
58
CSC-200 numerical protection measurement control equipment Manual
Name Function
Fast OC Fast over current
OC Over current
Zero sequence over current protection at
HV NOC
high voltage side
Zero sequence over current protection at
LV NOC
low voltage side
ND 3U0 Zero sequence over voltage protection
HG Heavy gas
LG Light gas
OT Over temperature
Connector9 Backup
Connector10 Backup
59
CSC-200 numerical protection measurement control equipment Manual
D9 OT Alarm OT Trip
D8 Backup Backup
D7 HG Alarm HG Trip
60
CSC-200 numerical protection measurement control equipment Manual
D3 OC T4 Off OC T4 On
D2 OC T3 Off OC T3 On
D1 OC T2 Off OC T2 On
D0 OC T1 Off OC T1 On
b) All protection function can start up/shut down via the soft connector or control word.
61
POWER LOGIC CPU COM/AO/DIO AC2 AC1
TRIP
X8 X7 X6 X5 X4 X3 X2 X1
1 Heavy gas 1 1 Common 1 Rem/Loc 1 1 1
2 CB unpower 2 2 2 Reset 2 2 2
3 Light gas 3 3 3 Overhaul 3 3 3
4 Over temper. 4 4 Common 4 Backup 4 4 4
5 5 5 Trip1-2 5 -24V 5 5 5
6 6 6 6 6 6 6
7 7 7 Common 7 7 7
8 8 8 Remote trip 8 8 8
8.4 Terminal figure
19 19 19
Output5
20 GND 20 20
62
11 RS485A 11 RS485A 11 RS485A 11 RS485A 11 RS485A
12 RS485B 12 RS485B 12 RS485B 12 RS485B 12 RS485B
13 Resistance 13 Lon-A 13 Lon-A
14 RS485A 14 Lon-B 14 Lon-B
15 RS485B 15 Not used 15 Lon-A
16 Resistance 16 Not used 16 Lon-B
Manual
CSC-200 numerical protection measurement control equipment Manual
63
CSC-200 numerical protection measurement control equipment Manual
e) Non-electric protection
a) All of the three phase-to-phase voltage is lower than under voltage setting.
b) The voltage reduction edge action.
64
CSC-200 numerical protection measurement control equipment Manual
a) If the self-generated 3U0 is smaller than 8V, the three-phase voltage is smaller than 8V, and the
current is over no current threshold (the default is 0.125 A), it is judged as three phase voltage
loss.
65
CSC-200 numerical protection measurement control equipment Manual
b) If the self-generated 3U0 is higher than 8V, and the minimum line voltage is lower than 16V, it is
c) If the self-generated 3U0 is higher than 8V and the difference between the maximal line voltage
and minimal line voltage is higher than 16V, it is judged as single phase VT failure.
VT loop monitoring function starts up/shuts down via the analog self-check control word. VT1 and VT2
function can be quit or adopted via KG1.15 and KG1.14 respectively.
9.3.5 Non-electric protection
The equipment includes single non-electric protection. The time delay can be set, trip or alarm is optional.
When choose trip mode, non-electric action will output spare exit 2 (6X15~6X16).
KG Trip
Non-electric 1
Ttz Trip
"1" 0
KG Alarm
1 Alarm
"0" 0
66
CSC-200 numerical protection measurement control equipment Manual
If special measurable current is not used,CT change ratio is insignificant. It can be set 0.1 as
default value.
b) All protection equipment function can start up/shut down via the soft connector or control word.
67
POWER LOGIC CPU AC2 AC1
X8 X6 X5 X3 X2
1 1 Common 1 Rem/Loc 1 1
2 2 Trip1-1 2 Reset 2 2
B us 1
3 3 3 UV HardCon 3 3 B us 2
DI( 24 V)
4 4 Common 4 Backup 4 4
9.5 Terminal figure
5 5 Trip1-2 5 -24V 5 5
3 V0
6 6 6 Backup 6 6
Co nt ac t output
Ba ckup
8 8 Trip3 8 8
9 9 9 9
S yn
10 (-) 10 Common 10 10
CSC-200 numerical protection measurement control equipment
11 11 Operation 11 11
68
S i g nal
2 4V
Com
12 12 Alarm 12 12
13 13
DC Failure Backup1
Si gn
14 14
15 Not used 15
Backup2
16 16
11 RS485A 11 RS485A 11 RS485A 11 RS485A 11 RS485A
17 Not used 17 12 RS485B 12 RS485B 12 RS485B 12 RS485B 12 RS485B
Backup3 13 Resistance 13 Lon-A 13 Lon-A
14 RS485A 14 Lon-B 14 Lon-B
E t h e rnet
18 18
P ower
15 RS485B 15 Not used 15 Lon-A
19 Not used 19 Backup4 16 Resistance 16 Not used 16 Lon-B
20 GND 20
Manual
CSC-200 numerical protection measurement control equipment Manual
Note:
6X1~6X2,6X4~6X5: The output contact of UV stage1 protection.
6X7~6X8: The output contact of UV stage2 and UV stage3 protection.
6X13~6X14: The output contact of ND 3U0 protection.
6X15~6X16: The output contact of Non-electric protection
6X17~6X18: The output contact of OV protection.
69
CSC-200 numerical protection measurement control equipment Manual
70
CSC-200 numerical protection measurement control equipment Manual
71
CSC-200 numerical protection measurement control equipment Manual
LineⅠ LineⅡ
UL1 UL2
IL1 IL2
CB1 CB2
2#Bus
1#Bus VT
VT
Equipment 2
72
CSC-200 numerical protection measurement control equipment Manual
d) Current setting Idz1: Ⅰ line no current setting, used for I bus voltage loss judgement (different
from VT fail);
e) Current setting Idz2: Ⅱ line no current setting, used for II bus voltage judgement (different from
VT fail);
f) Current setting Idz3: Ⅰ line over-load I zone setting, used for first-round load of joint operation
g) Current setting Idz4: Ⅱ line over-load I zone setting, used for joint operation first-round of load
h) Current setting Idz5: Ⅰ line over-load II zone setting, used for second-round load of joint
operation.
i) Current setting Idz6: II line over-load II zone setting, used for second-round load of joint
operation;
j) Time setting T1: delay of CB1 trip;
k) Time setting T2: delay of CB2 trip;
l) Time setting T3: delay of CB3 close.
m) Time setting T4: first-round of joint operation load delay .
n) Time setting T5: second-round of joint operation load delay.
10.3.2 Scheme 2
Applicable to: in line backup self-operation, in line I and in line II back up for each other, and the wiring is
shown as the equipment 1 of the figure 10-3.
The PT of two lines has a voltage under normal operation, two buses have a voltage, one switch of CB1
and CB2 is closed, another switch is open. CB3 is closed.
Work line is cut off, the work line trips when the backup line has a voltage, and the backup power supply is
closed.
When the bus joint makes a hide trip and leads to the bus voltage loss, the backup line switch is closed
when the backup line has a voltage.
To prevent the backup automatic start-up from making a mistaken action upon VT fail, the line current is
used as the lock judgement of the line voltage loss.
The 1# and 2# transformer main protection and high-voltage backup protection give signal to digital input
7 and digital input 8. The main protection and high-voltage backup protection action does not lock the
in-line switch standby of the other side.
For example: a) CB1, CB3 operate and CB2 backup: after the charge is full, if 1# transformer differential
action trip CB1, CB3 switch and low-voltage switch of 1# transformer, the equipment closes the CB2
switch, and 2# transformer starts up. When any main transformer acts, if it is required that the standby is
locked, the action node is connected to the digital input 9 to lock the ABTE.
b) CB1 and CB3 starts up, CB2 backup: after the charge is full, if 2# transformer makes a differential
action, the standby is locked.
74
CSC-200 numerical protection measurement control equipment Manual
LineⅠ LineⅡ
UL1 UL2
IL1 IL2
CB1 CB2
1#Bus VT 2#Bus VT
Equipment2
75
CSC-200 numerical protection measurement control equipment Manual
Note 1: as shown in the figure, when an in-line trips, the reclosing time of the equipment on other side
should be considered.
Note 2: when CB1 makes a hide trip, the continued actions of the ABTE is selected via the control word
KG2.14. If “KG2.14=0 switch hide trip standby continues”, after the switch makes a trip, the equipment
closes the CB2 after T8. CB1 makes a hide trips and leads to T8 bus voltage loss time; if “KG2.14=1,
switch makes a hide trip, and makes a trips”, after the switch makes a hide trip, the equipment trips CB1
after T5; after CB1 trips, the CB3 is closed after T8, so CB1 makes a hide trip and leads to T5+T8 bus
voltage loss.
Note 3: when CB2 makes a hide trip, the continued actions of the ABTE is selected via the control word
KG2.14. if “KG2.14=0 switch hide trip standby continues”, after the switch makes a trip, the equipment
closes the CB1 after T6. CB2 makes a hide trips and leads to T6 bus voltage loss time; if “KG2.14=1,
switch makes a hide trip, and makes a trips”, after the switch makes a hide trip, the equipment trips CB2
after T7; after CB2 trips, the CB1 is closed after T6, so CB2 makes a hide trip and leads to T7+T6 bus
voltage loss.
Note 4: the ABTE can expand node to cut operation capacitor group, or coordinate the voltage loss
protection time setting via time setting, and the capacitor protection equipment remove the capacitor
group.
Note 5: when CB1 runs and CB2 is for backup, 1# transformer action (digital input 7) does not lock the
ABTE, 2# transformer action (digital input 8) locks the standby equipment. Similarly, when CB2 runs and
CB1 is for backup, 2# transformer action (digital input 8) does not lock the ABTE, 1# transformer action
(digital input 7) locks the standby equipment. if any main transformer action will lock the standby, the
digital input 7 and digital input 8 are not connected, the action node is connected to the digital input 9 of
the standby general lock.
Scheme 2 “charging” condition
a) I bus and II bus have a voltage, and the line UL1 and UL2 have a voltage.
b) One of CB1 and CB2 switch is closed, another is open, and the CB3 is closed.
c) The scheme 2 control word starts up;
d) The standby connector starts up;
Scheme 2 “discharge” condition:
a) Standby protection action exit:
b) External lock signal
10.3.2.2 Terminal wiring
a) Voltage input terminal X3-1,X3-2,X3-3: connect I zone bus voltage , Ua1,Ub1,Uc1;
b) Voltage input terminal X3-4,X3-5,X3-6: connect II zone bus voltage ,Ua2,Ub2,Uc2;
c) Voltage input terminal X1-3,X1-4: connect line I voltage, line voltage or phase voltage
d) Voltage input terminal X1-5,X1-6: connect line II voltage, line voltage or phase voltage;
e) Current input terminal X2-7,X2-8: connect line I current
f) Current input terminalX1-1,X1-2: connect line II current;
g) Digital input terminal X8-1: connect CB1 trip TWJ constant open contact;
h) Digital input terminal X8-2: connect CB2 trip TWJ constant open contact;
i) Digital input terminal X8-3: connect CB3 trip TWJ constant open contact (if no CB3, it keeps
empty)
j) Digital input terminal X8-7: 1# transformer fails *;
k) Digital input terminal X8-8: 2# transformer fails *;
76
CSC-200 numerical protection measurement control equipment Manual
IL1 IL2
CB1 CB2
Bus
Bus VT
Uab1,Ubc1
77
CSC-200 numerical protection measurement control equipment Manual
1 runs, CB2 is open, and in-line 2 is for backup. The standby normally acts upon power loss. On the
contrary, if CB1 is open, CB2 is close, and the in line 2 runs, the standby does not act upon power loss.
The in-line 1 must be identified as power supply in the engineering design and the control word KG1.9=1
is set.
a) Control word: set to the scheme 2
b) Voltage setting Udz1: I bus or II bus voltage loss threshold;
c) Voltage setting Udz2: I bus or II bus voltage threshold;
d) Voltage setting Udz3: I line or II line has voltage threshold, it is recommended that the in-line
voltage is set as 70V;
e) Current setting Idz1: I line no current setting, used for I bus voltage loss judgement (different
from VT fail)
f) Current setting Idz2: II line no current setting, used for II bus voltage loss judgement (different
from VT fail)
g) Time setting T5: CB1 trip delay of exit 5
h) Time setting T6: CB1 close delay of exit 6
i) Time setting T7: CB2 trip delay of exit 7
j) Time setting T8: CB2 close delay of exit 8
Note: the joint operation function shuts down when the scheme 2 is used; the exit 6 and exit 8 are used to
close CB1 and CB2
10.3.3 Scheme 3
Applicable to: automatically recognize the bus joint self-operation and mutual operation of line switch
according to the operation status, usually it is used for 110kV, the wiring form is shown as the figure 8-6.
LineⅠ LIneⅡ
UL1 UL2
IL1 IL2
CB1 CB2
1#Bus CB3
1#Bus VT 2#Bus VT
79
CSC-200 numerical protection measurement control equipment Manual
f) Current setting Idz2: II line no current setting, used for bus voltage loss judgement (different
from VT fail)
g) Time setting T1: CB1 trip delay when the mode 1 automatically recognized.;
h) Time setting T2: CB2 trip delay when the mode 1 automatically recognized;
i) Time setting T3: CB3 trip delay when the mode 1 automatically recognized;
j) Time setting T5: CB1 trip delay when the mode 2 automatically recognized;
k) Time setting T6: CB1 close delay when the mode 2 automatically recognized
l) Time setting T7: CB2 close delay when the mode 2 automatically recognized
m) Time setting T8: CB2 trip delay when the mode 2 automatically recognized
10.3.4 Scheme 1+balanced load function
Applicable to: the balanced load bus joint standby. The wiring form is shown as the following figure.
Two sets of equipments coordinate to complete the required functions. The wiring of each set is
marked as the following figure.
80
CSC-200 numerical protection measurement control equipment Manual
The mark in the bracket is another standby wiring and relative location.
The above process can be divided into the following action logic:
a) Action logic 1:the lock requires that CB2 is at trip; II bus voltage loss and the II in line current
lower than current setting Idz2 are the start condition; the CB2 trips after T2 delay.
b) Action logic 2: the lock requires that I bus voltage is lower than Udz2; II bus voltage loss and CB2
trip location are the start condition; CB3 is closed after T3 delay.
c) Action logic 3: the lock requires that CB1 is at the trip; I bus voltage loss and I in line current
lower than the current setting Idz1 are the start condition; CB1 trips after T1 delay.
d) Action logic 4: the lock requires that II bus voltage is lower than Udz2; I bus voltage loss and CB1
trip are the start condition; the CB3 is closed after T3 delay.
e) Action logic 5: the lock requires that CB4 is at a trip and IV bus voltage are lower than Udz3; CB1
trip and CB3 trip are the start condition; CB4 trips after T8 delay. CB4 rejects to trip, the load is
emergently cut off, and the exit 8 acts.
f) Action logic 6: the lock requires that CB6 is at the trip; the CB4 trip is the start condition, CB6 is
closed after T3 delay. This set of the equipment uses the single logic action scheme, this action
logic is realized by another auxiliary equipment.
10.3.4.2 Terminal wiring
The wiring of the two sets of equipments is similar, and the mark with a bracket is the wiring mark of
another set of equipment.
a) Voltage input terminal X3-1,X3-2,X3-3: connect I bus voltage, Ua1,Ub1,Uc1
b) Voltage input terminal X3-4,X3-5,X3-6: connect II bus voltage,Ua2,Ub2,Uc2
c) Current input terminal X2-7,X2-8: connect I in line current;
d) Current input terminal X1-1,X1-2: connect II in line current;
e) Voltage input terminal X1-3,X3-4: connect IV bus voltage,Uab4;
f) Voltage input terminal X1-5,X3-6: connect IV bus voltage,Ubc4;
g) Current input terminal X2-1,X2-2: Connect bus joint or bridge switch current Ia;
h) Current input terminal X2-3,X2-4: Connect bus joint or bridge switch current Ib;
i) Current input terminal X2-5,X2-6: Connect bus joint or bridge switch current Ic;
j) Digital input terminal X8-1: connect CB1 trip TWJ constant open contact;
k) Digital input terminal X8-2: connect CB2 trip TWJ constant open contact;
l) Digital input terminal X8-3: Connect CB3 trip TWJ constant open contact;
m) Digital input terminal X8-4: connect CB4 trip TWJ constant open contact;
n) Digital input terminal X8-9: Connect external lock backup self-operation;
o) Contact output terminal X6-1,X6-2: connect to trip input of the CB3 operation box;
p) Contact output terminal X6-1,X6-3: connect to close input of CB3 operation box;
q) Contact output terminal X6-13,X6-14: connect to trip input of CB1 operation box;
r) Contact output terminal X6-15,X6-16: connect to trip input of CB4 operation box;
s) Contact output terminal X6-17,X6-18: connect to trip input of CB2 operation box;
t) Contact output terminal X6-19,X6-20: emergent joint cut load output after CB4 rejects a trip.
10.3.4.3 Description of related settings
a) Control word: “KG1.0=1 mode 1 operation”, “KG1.7=1 mode 1 with balance load”
81
CSC-200 numerical protection measurement control equipment Manual
82
CSC-200 numerical protection measurement control equipment Manual
{Ⅰ bus U2>“negative sequence voltage lock value”, orⅡ bus U2>“negative sequence voltage lock value”}
Note: the compound voltage lock is not applicable to “only one bus PT operation”, the solution is to
connect the Ua, Ub and Uc of PT to the voltage terminal of the I bus and II bus.
The over current I zone protection starts up/shuts down via the over current I zone connector.
10.4.2 Over current II zone protection with multiple voltage lock
If the protected switch current is higher than the over current II zone setting, the protection starts.
If the control word is “KG2.2=0 II zone compound voltage lock exit”, the exit will trip after over current II
zone delay and the standby brake will be locked.
If the control word is “KG2.2=1Ⅱzone compound voltage lock operation”, the coordinated control word
KG2.4 includes two cases, similar to the over current I zone, it will not be described in detail;
The over current II zone protection starts up/shuts down via the over current II zone connector.
10.4.3 Zero-current I and II zone protection
The protected switch zero-sequence self-generated current is higher than zero-current I zone setting, the
protection starts, the exit trips after current I zone delay, and the standby is locked. The zero-current I
zone protection starts up/shuts down via the zero-current I zone connector.
The protected switch zero-sequence self-generated current is higher than zero-current II zone setting, the
protection starts, the exit trips after current II zone delay, and the standby is locked. The zero-current II
zone protection starts up/shuts down via the zero-current II zone connector.
10.4.4 Over current or zero-current acceleration protection
To validate that fault occurs when device closes, the zero-current or over current acceleration includes
condition “switch keep open for 30 second”, this condition is met, then switch changes from the open
status to closed status, the charging protection last for 3s. If the charging protection does not start, it will
exit after 3s.
The protected switch current is higher than “zero-current or over current acceleration zone current” setting,
the charge protection starts.
The zero-current is higher than the acceleration zone current setting, the exit trips after the zero-current
acceleration zone delay.
For the over current acceleration protection, if the control word is “KG2.3=0 charge compound voltage
lock exit”, the exit will trip after over current acceleration zone delay and the backup automatic start-up
close is locked.
For the over current acceleration, if the control word “KG2.3=1 charge compound voltage lock operation”,
the coordination control word KG2.4 includes two cases. Similar to the over current I zone, it will not be
described.
The zero-current acceleration zone protection starts up/shuts down via the zero-current acceleration zone
connector, and the over current acceleration zone protection starts up/shuts down via the over current
acceleration zone connector.
10.4.5 Over-load joint cut
The joint cut logic 1: I line current (I L1) is higher than the current setting Idz3, or II line current (I L2) is
higher than the current setting Idzd4, the first-round joint cut operates (exit 6) after T4 delay.
The joint cut logic 2: I line current (I L1) is higher than the current setting Idz5, or II line current (I L2) is
higher than the current setting Idzd6, the second-round joint cut operates (exit 8) after T5 delay.
The over-load joint cut function shuts down/starts up via the joint cut connector.
10.4.6 Control circuit broken monitoring
If the operation box inside the equipment is used to control CB3 in the scheme 1, it is necessary to detect
the control loop disconnection according to the breaker trip and close status. When the control circuit of
83
CSC-200 numerical protection measurement control equipment Manual
the equipment is not used in other schemes, the control circuit detection function is not required generally.
The alarm judgement is listed as follows;
a) TWJ and HWJ do not act
b) The time exceeds 10s
The control circuit detection function starts up/shuts down via the control word KG1.13.
10.4.7 VT fail monitoring
VT fail is divided into the bus disconnection, bus voltage loss, and in-line voltage loss, they starts
up/shuts down via the control word separately. The judgement logic is shown as the following figure.
84
CSC-200 numerical protection measurement control equipment Manual
EF Ⅰ EF Ⅰ ON/OFF
EF Ⅱ EF Ⅱ ON/OFF
85
CSC-200 numerical protection measurement control equipment Manual
9 Idz1 0.02 ~ 20 A
10 Idz2 0.02 ~ 20 A
11 Idz3 0.1 ~ 20 A
12 Idz4 0.1 ~ 20 A
13 Idz5 0.1 ~ 20 A
14 Idz6 0.1 ~ 20 A
15 Idz7 0.1 ~ 20 A
16 Idz8 0.1 ~ 20 A
17 T1 0.0 ~ 60.0 s
18 T2 0.0 ~ 60.0 s
19 T3 0.0 ~ 60.0 s
20 T4 0.0 ~ 60.0 s
21 T5 0.0 ~ 60.0 s
22 T6 0.0 ~ 60.0 s
23 T7 0.0 ~ 9000.0 s
24 T8 0.0 ~ 9000.0 s
0.1 ~ 100(In=5A)
25 OC Ⅰ I A
0.02 ~ 20(In=1A)
26 OC Ⅰ T 0.0 ~ 32.0 s
0.1 ~ 100(In=5A)
27 OC Ⅱ I A
0.02 ~ 20(In=1A)
28 OC Ⅱ T 0.1 ~ 32.0 s
86
CSC-200 numerical protection measurement control equipment Manual
0.1 ~ 100(In=5A)
33 EF Ⅰ I A
0.02 ~ 20(In=1A)
34 EF Ⅰ T 0.0 ~ 60.0 s
0.1 ~ 100(In=5A)
35 EF Ⅱ I A
0.02 ~ 20(In=1A)
36 EF Ⅱ T 0.0 ~ 60.0 s
0.1 ~ 100(In=5A)
37 EF ACC I A
0.02 ~ 20(In=1A)
87
CSC-200 numerical protection measurement control equipment Manual
I1 I2 I1 I2
88
CSC-200 numerical protection measurement control equipment Manual
89
CSC-200 numerical protection measurement control equipment Manual
n) Contact output terminal X6-15,X6-16: connect to close input of CB3 operation box;
o) Contact output terminal X6-17,X6-18: Connect to trip input of CB4 operation box;
p) Contact output terminal X6-19,X6-20: connect to close input of CB4 operation box.
10.6.1.3 Description of related settings
a) Control word: set as the scheme 5
b) Voltage setting Udz1: bus voltage loss threshold
c) Voltage setting Udz2: voltage threshold of high voltage side of I main transformer or high voltage
side of II main transformer
d) Current setting Idz1: no current setting on low voltage side of I main transformer, used for bus
voltage loss judgement (different from VT fail);
e) Current setting Idz2: no current setting on low voltage side of II main transformer, used for bus
voltage loss judgement (different from VT fail)
f) Time setting T1: CB1 trip delay;
g) Time setting T1: CB3 trip delay;
h) Time setting T2: CB2 close delay;
i) Time setting T3: CB4 close delay;
j) Time setting T4: CB2 trip delay;
k) Time setting T4: CB4 trip delay;
l) Time setting T5: CB1 close delay;
m) Time setting T6: CB3 close delay .
90
CSC-200 numerical protection measurement control equipment Manual
KG1.11Bus VT Loss
Bus 1: V<70V Alarm
& “1”
≥1
Line IL1 have 10S VT Fail
Y
current H
≥1 “0”
line IL2 have H
current
91
CSC-200 numerical protection measurement control equipment Manual
Note 2: at the bottom of circularly displays, the item “★” indicates that the standby scheme is charged
fully, the item “☆” indicates that the standby is not charged fully, and you should check whether the
charging conditions of the standby is met. (V2.00 program and higher version include this function).
Connector2 Backup
OC Ⅰ OC Ⅰ ON/OFF
OC Ⅱ OC Ⅱ ON/OFF
EF Ⅰ EF Ⅰ ON/OFF
EF Ⅱ EF Ⅱ ON/OFF
Connector9 Backup
Connector10 Backup
9 Idz1 0.02 ~ 20 A
10 Idz2 0.02 ~ 20 A
11 Idz3 0.1 ~ 20 A
92
CSC-200 numerical protection measurement control equipment Manual
12 Idz4 0.1 ~ 20 A
13 Idz5 0.1 ~ 20 A
14 Idz6 0.1 ~ 20 A
15 Idz7 0.1 ~ 20 A
16 Idz8 0.1 ~ 20 A
17 T1 0.0 ~ 60.0 s
18 T2 0.0 ~ 60.0 s
19 T3 0.0 ~ 60.0 s
20 T4 0.0 ~ 60.0 s
21 T5 0.0 ~ 60.0 s
22 T6 0.0 ~ 60.0 s
23 T7 0.0 ~ 9000.0 s
24 T8 0.0 ~ 9000.0 s
0.1 ~ 100(In=5A)
25 OC Ⅰ I A
0.02 ~ 20(In=1A)
26 OC Ⅰ T 0.0 ~ 32.0 s
0.1 ~ 100(In=5A)
27 OC Ⅱ I A
0.02 ~ 20(In=1A)
28 OC Ⅱ T 0.1 ~ 32.0 s
0.1 ~ 100(In=5A)
29 OC ACC I A
0.02 ~ 20(In=1A)
0.1 ~ 100(In=5A)
33 EF Ⅰ I A
0.02 ~ 20(In=1A)
34 EF Ⅰ T 0.0 ~ 60.0 s
93
CSC-200 numerical protection measurement control equipment Manual
0.1 ~ 100(In=5A)
35 EF Ⅱ I A
0.02 ~ 20(In=1A)
36 EF Ⅱ T 0.0 ~ 60.0 s
0.1 ~ 100(In=5A)
37 EF ACC I A
0.02 ~ 20(In=1A)
94
CSC-200 numerical protection measurement control equipment Manual
D11
D9
D8
D7 Refer to 10.8.4.2
D6
D5 Backup Backup
D4 Backup Backup
10.8.4.1 Selection of digital input for CB service in main transformer standby logic
1 1 1 None
95
CSC-200 numerical protection measurement control equipment Manual
8 7 6
e) Zero sequence over current protection (EF) with definite time or reversetime which is optional
g) Non-electric protection
96
CSC-200 numerical protection measurement control equipment Manual
97
CSC-200 numerical protection measurement control equipment Manual
transformer. The component is used as backup protection which acts when transformer load fuse refuse
to action.
Zero sequence over current protection at high voltage side adopts definite time mode, the action condition
are:
a) 3I0g>Ig0dz.Ig0dz is current setting, 3I0g is the zero sequence current at high voltage side.
b) T>Tg0. Tg0 is the time setting.
98
CSC-200 numerical protection measurement control equipment Manual
Figure 11-4 Definite time zero sequence over current protection logic
Zero sequence over current protection at low voltage side can adopt definite time mode or reverse time
mode via control word, the action condition of the protection with definite time are
a) 3I0d>Id0dz.Id0dz is current setting; 3I0d is the zero sequence current at low voltage side.
b) T>Td0. Td0 is the time setting.
In order to realize the coordination of time characteristic of fuse blowing, protection of neutral current or
zero sequence current at low voltage side can adopt reverse time mode. The feature equation is shown
as follows:
t =τ×IeL/(I0L- IRE)
Where:
Zero sequence over current component starts up/shuts down via the soft connector
than the setting voltage, whether to excise load can be judged automatically. The action condition are
a) The line voltage exists for over 2s, namely the voltage reduction edge action ever have voltage.
b) All of the three line voltages are lower than under voltage load dropping setting.
c) Current exists
99
CSC-200 numerical protection measurement control equipment Manual
100
CSC-200 numerical protection measurement control equipment Manual
d) If voltages of three phase all are under 8v, and one phase current (phase A or phase C) is over
no current threshold (the default is 0.25 A), it is judged as three phase voltage loss.
e) If the self-generated 3U0 is higher than 8V, and the minimum line voltage is lower than 16V, it
is judged as two-phase failure.
f) If the self-generated 3U0 is higher than 8V and the difference between the maximal line
voltage and minimal line voltage is higher than 16V, it is judged as single phase VT failure.
11.2.9 Control circuit disconnection detection
The integrity of the control circuit can be judged according to the contact location of the relay HWJ
and TWJ. When the contact location of HWJ and TWJ is open, the equipment will actively display “CC
broken” alarm after delay confirmation. The alarm indicator of the panel is lighted and the alarm signal
is given. The control bus disconnection is confirmed within the default 10s.
The control circuit disconnection detection function can starts up/shuts down via the control word
11.2.10 CB unpower alarm
When the “CB unpower” digital input is at the high level, the equipment will actively display “CB
unpower” after delay confirmation, the alarm indicator of the panel is on, and the alarm signal is given.
The CB unpower digital input is confirmed within the default 10s.
Name Function
101
CSC-200 numerical protection measurement control equipment Manual
6 OC T 0.1~32.00 s
0.25~15(In=5A)
7 Overload I A
0.05~3(In=1A)
8 OL Alarm T 1~6000 s
9 OL Trip T 1~6000 s
0.25~100(In=5A)
10 HV EF I A
0.05~20(In=1A)
11 HV EF T 0~32.0 s
0.25~100(In=5A)
12 LV EF I A
0.05~20(In=1A)
13 LV EF T 0~32.0 s
14 LV Rated I 0.2~10.0 A
0.25~50(In=5A)
15 EF INV I A
0.05~10(In=1A)
0.25~100(In=5A)
16 ACC I A
0.05~20(In=1A)
17 ACC T 0.0~3.00 s
18 UV V 2.0~100.0 V Phase-to-phase
19 UV T 0.1~32.0 s
20 Non-elec 1 T 0~32.0 s
21 Non-elec 2 T 0~32.0 s
22 Non-elec 3 T 0~32.0 s
23 Non-elec 4 T 0~32.0 s
24 Mea CT Ratio 0.001~7.0 none Primary Mea CT/1000
25 Mea VT Ratio 0.01~2.0 无 Primary VT/1000
102
CSC-200 numerical protection measurement control equipment Manual
D1 LV EF DEF LV EF INV
D0 Overload Alarm Overload Trip
D1 LV EF Trip LV EF Alarm
D0 HV EF Trip HV EF Alarm
103
POWER TRIP LOGIC CPU COM/AO/DIO AC2 AC1
X8 X7 X6 X5 X4 X3 X2 X1
1 No-elec 1 1 1 Common 1 Rem/Loc 1 1 1
2 CB unpower 2 2 Trip1-1 2 Reset 2 2 2
3 No-elec 2 3 3 3 Overhaul 3 3 3
4 No-elec 3 4 4 Common 4 Non-elec 1 4 4 4
5 No-elec 4 5 5 Trip1-2 5 -24V 5 5 5
6 DI6/Fuse Trip 6 6 6 P/Fast OC 6 6 6
7 7 7 Common 7 Q/OC 7 7
8 8 8 Remote trip 8 8 8
9 9 9 Remote close 9 9 Mea Ia 9
10 (-) 10 10 Common 10 10 Mea Ia' 10
11.4 Terminal figure
19 19
20 Trip5
20 GND 20
104
11 RS485A 11 RS485A 11 RS485A 11 RS485A 11 RS485A
12 RS485B 12 RS485B 12 RS485B 12 RS485B 12 RS485B
13 Resistance 13 Lon-A 13 Lon-A
14 RS485A 14 Lon-B 14 Lon-B
15 RS485B 15 Not used 15 Lon-A
16 Resistance 16 Not used 16 Lon-B
11.5Wiring illustration
A
B
C
+24V(X8.11)
X2 X5
DI1
1 Ia Remote/Local 1
Reset DI2
2 Ia’ 2
Backup DI3
3 Ib 3
DI4
4 Ib’ Non-elec1 HardCon 4
5 Ic -24V 5 -24V(X8.12)
Pro.CT +24V
6 Ic’ Fast OC/P 6
9 Ia OC/Q 7
10 Ia' COM- 8 -24V
X1 SYNA+ 9 Pluse
11 Ib SYNA- 10 -24V
12 Ib' RS485A 11
X2 12
RS485B
11 Ic
Mea.CT
12 Ic' X6
X1 COM 1 +KM
1 Trip1 2 X7.3
Zero CT
2 Close1 3 X7.7
COM 4
Trip2 5
Close2 6
COM 7 +KM
X3
1 Remote trip 8 X7.2
Ua
2 Ub Remote close 9 X7.7
COM 10 +XM
3 Uc
Operation 11 Operation
4 Un
Alarm 12 Alarm
5 U0
13
6 U0’
14
X2 15
7
Zero CT 8 16
+KM 17
X8
DI1 18
1 Non-elec 1
DI2 DI2 CB unpower 19
2 ARC(holdin) Spare
DI3 20
3 Non-elec 2
DI4 X7
4 Non-elec 3
DI5 +KM 1 +KM
5 Non-elec 4
DI6 Manual Trip 2 X6.8
6 DI6
DI7 7 Relay trip 3 X6.2
DI7
DI8 Open winding 4 Trip
8 DI8
DI9 9 Close winding 5 Close
DI9
-KM 10 DI(-) Short to CW 6
X6.3
11 +24V Close 7
X6.9
12 -24V -KM 8 -KM
13 COM 9 +XM
signal DC Failure
14 TWJ 10 G
15 Not uesd HWJ 11 R -XM
16 DC(+) 12
220/110 (+) CC Broken
17 Not uesd 13
DC supply
(-) 18 Not uesd 14
Event Spare
19 Not uesd 15
20 GND 16
Out for manual trip Spare
17
Eth
UTP5 18
HUB/SWITCH 1 RJ45-1
19
20
105
CSC-200 numerical protection measurement control equipment Manual
selected)
e) Overheat protection (Overheat tripping, overheat alarm and heat accumulation memorizing)
selected)
g) Earth fault protection (Zero sequence over-current protection, trip or alarm can be selected)
106
CSC-200 numerical protection measurement control equipment Manual
120
Ie
10
Table - 3 Seting-parameters
107
CSC-200 numerical protection measurement control equipment Manual
Rated current of
26 0.1~20.0 A
motor
Startup time of
27 0.100~300.0 S
motor
Ieq= K 1 I 1 + K 2 I 2
2 2
Where:
Ieq-Equivalent current
I1-Positive sequence current
I2-Negative sequence current
K1-Heat coefficient of positive sequence current. 0.5 for motor startup process and 1.0 for motor startup
end.
K2-Heat coefficient of the negative sequence current
According to the heat model of the motor, the characteristic curve between the operation time of the motor
and the equivalent current Ieq is calculated by the following formula:
2
I eq-I 2p
t=τ×ln
2
I eq-I ∞2
Where:
Ip-load current before overload. Ip is 0 if it is in the cool status before overload.
The criterion fully considers the heat process of the motor rotor and the heat state before overload.
Equivalent Trip
current
108
CSC-200 numerical protection measurement control equipment Manual
will restart. In emergency, it is needed to start up instantly, and then the heat resetting can be operated.
The overheat block is enabled or disabled by the control word 1.1, it also provides the function of
overheating alarm which is enabled or disabled by the control word 1.0. Users can select whether to trip
or not for overheating by Linker, but the overheating alarm or block function are not controlled by Linker.
The heat time constantτshould be provided by the motor factory. If the constantτis not provided, it can
be estimated by the following methods:
a) If the motor is provided with heat limit curve or a group of load capability data, theτcan be calculated
by the following formula to obtain a group of values and select the minimum value.
t
τ=
I2
ln 2 2
I -I ∞
b) If the rotation block current I and the allowed rotation block time t are known, theτcan estimated by
the following formula:
t
τ=
I2
ln 2 2
I -I ∞
c) Theτcan be calculated by the following formula:
θ e × K 2 × Tstart
τ=
θ0
Where
θe is the rated value of temperature rising, K is the multiple of startup current, θ0 is the value of
temperature rising by starting and Tstart is the startup time of the motor.
Table – 6 Seting-parameters
Overheat startup
18 (0.05~4.0)In A
current
109
CSC-200 numerical protection measurement control equipment Manual
Heat time
19 6~3000 S
constant τ
Negative sequence
20 heat effect 3~10 Generally 6
coefficient
Heat disperse
22 1~5τ multiple Generally 4.0
multiple
110
CSC-200 numerical protection measurement control equipment Manual
I > Isdg
&
The motor is starting. Y
≥
H
I > Isdd &
&
Y Y
The motor is starting.
≥
Tsd Trip
H
PT fails
&
Y
Any phase(IOC) meets direction element.
A Ia Ubc
B Ib Uca
C Ic Uab
111
CSC-200 numerical protection measurement control equipment Manual
90o
125o
operation area
I
O Uφφ
-35o
Table - 10 Seting-parameters
112
CSC-200 numerical protection measurement control equipment Manual
I>Igl
-automatic startup
is running...
113
CSC-200 numerical protection measurement control equipment Manual
Detection Detection
Table - 13 Seting-parameters
Setting value of
6 (0.05~20.0)In A (0.08~20)Ie
over-current
Time of
7 0.2~6000 S
over-current
Select Alarm
Bit of control
Definition of setting as 0 Definition of setting as 1 Remark
word
Table - 16 Seting-parameters
Sequence
Setting name Range Unit Remark
Number
114
CSC-200 numerical protection measurement control equipment Manual
Setting value of
8 zero sequence (0.05~20.0)In A
current
Time of zero
9 0.1~32.00 S
sequence current
80tp
t=
I 2
( ) −1
Ip
The setting value of “NS INV T” is the numerator (80tp) in the expression above. The range of Ip is(0.2~
1.7 I e ).
When the IED fault occurs externally, the feedback negative sequence current of the motor may result in
mal-operation caused by negative sequence over current protection. According to different ratio of I2/I1
for asymmetry faults occurring in internal or external of the asynchronous motor, the negative sequence
over current protection will be blocked if I2≥1.125I1 is satisfied. I1 is the positive sequence current and I2
is the negative sequence current. However, when the fault occurs in the motor, the condition will be not
satisfied and the block will be released automatically which assures the reliability of the protection. The
condition of block can be enabled or disabled by the control word. If it is used for synchronous motor
protection, the function can be disabled.
trip
KG selected inverse time
characteristic
115
CSC-200 numerical protection measurement control equipment Manual
Linker Function
I2≥1.125I1 I2≥1.125I1
KG1.11 non-block negative block negative sequence
sequence protection protection
Table - 19 Seting-parameters
Setting value of
10 negative sequence (0.05~20.0)In A
over-current
Time of Negative
11 sequence definite 0.1~32.00 S
time stage
Time of Negative
Extremely
12 sequence inverse 4.000~80.00 S
inverse
time stage
When the protection CT is the way of two phases, it will affect the calculation of negative sequence
current in software, so it is needed to synthesize the B phase current by line connection.
12.2.7 Under voltage protection
In order to assure safe production, for the motor which is not allowed to startup automatically, the under
voltage protection issue trip command after the voltage of the power supply disappears or decreases,
which will switch off the motor from the power network automatically.
When the measured line-to-line voltage is lower than the setting value, the switch or the contactor is in the
close position and the falling edge is present, the undervoltage protection issues trip command. In order
to prevent tripping the motor due to PT failure, under voltage protection will be blocked when PT fails.
116
CSC-200 numerical protection measurement control equipment Manual
Uab<Udz
&
Ubc<Udz Y
Uca<Udz
&
PT failure
Y Td Trip
close position, HWJ
line-to-line voltage
>Udz 2s
Td
Bit of Remark
Definition of setting as 0 Definition of setting as 1
control word
Table - 22 Seting-parameters
Time of under
17 0.1~32.0 S
voltage
117
CSC-200 numerical protection measurement control equipment Manual
KG selects Tripping.
KG selects Alarm.
Bit of Remark
Definition of setting as 0 Definition of setting as 1
control word
Table - 25 Seting-parameters
Current setting of
13 (0.05~4.0)In A (0.08~20)Ie
overload
Time delay of
14 0.2~6000 S
overload tripping
Time delay of
15 0.2~6000 S
overload alarm
118
CSC-200 numerical protection measurement control equipment Manual
Table - 27 Seting-parameters
Setting value of
28 (0.05~20.0)In A (1~20)Ie
F-C lock current
Table - 29 Seting-parameters
Time delay of
23 External BI→BO 0.0~100.0 S
protection 1
Time delay of
24 External BI→BO 0.0~100.0 S
protection 1
Time delay of
25 External BI→BO 0.0~100.0 S
protection 1
119
CSC-200 numerical protection measurement control equipment Manual
Test steps:
a) Switch the grade of universal meter to 20mA, and connect it to terminals of equipment channel
adjusted. Enter into Main Menu/ DevSetup/20mA, select channel, and calibrate coefficients of
“4.5mA Out” by LEFT and RIGHT keys. If the measuring value of universal meter is 4.5mA, that
is OK. The “19mA Out” is the same as “4.5mA Out”. If AO module has several 4-20mA channels,
all adjustments can be finished in turn in such menu. After calibration, press SET key to confirm
it, and the IED will reboot so the calibration will operate.
b) 4-20mA output is response to the metering of equipment, which can be selected by entering into
Main Menu/ComConf/20mA Set. If “Mea Ia” is selected, Input 3.0A and the 4-20mA output
should be 12±0.1mA. This is the situation of 5A CT(Control word select “CT Rated 5A”),
“4-20mA output” corresponds to “0-6A input”. Some equipments select 1A CT, in this instance,
“4-20mA output” corresponds to “0-1.2A input”.If AC input is 0.6A, DC output should be 12±
0.1mA.
120
CSC-200 numerical protection measurement control equipment Manual
121
CSC-200 numerical protection measurement control equipment Manual
122
POWER TRIP LOGIC CPU COM/AO/DIO
AC2 AC1
X8 X7 X6 X5 X4 X2 X1
1 DI1 1 +KM 1 Common 1 1
1 Rem/Loc Ia
2 DI2 CB unpower 2 Manual trip(in) 2 Trip1 2 Reset
Backup 2 Ia' 2
3 DI3 3 Relay trip(in) 3 Close1 Backup 3 Ib 3
3 UV
4 DI4(HWJ) 4 To trip coil 4 Common 4 Ib' 4
4 Heating Reset Backup
5 DI5 5 To close coil 5 Trip2 5 Ic 5
5 -24V
6 DI6 6 Short to X7-5 6 Close2 Backup/P
Backup 6 Ic' 6
6
7 DI7 7 Close(in) 7 I0 7
7 Common 7 Backup/Q Backup
8 DI8 8 8 I0' 8
-KM 8 Remote trip 8 COM-
12.4Terminal figure
15 2 Ub
16 DC(+) 16 Output for Backup2
Manual trip 16 R 3 Uc
17 Not used 17
123
17 4 Un
18 DC(-) 18 + 2YJJ Full-U T
18 2RJ45 5
19 Not used 19
2YJJ (out) 19 6
20 GND 20 CB Close Blk.
20
This IED is applicable to all kinds of 10kV and below neutral non-direct grounded system, which is used
for internal fault differential protection of large and medium-sized asynchronous motor (above hundreds
of kilowatt), phase-to-phase fault, overload, locked-rotor and other integrated protections, and it can be
locally installed in switch cabinet.
Differential protection with ratio restraint reflect the fault in protected area
Long-starting protection
Overheat protection (overheat tripping, overheat alarming, heat accumulation memory function)
Ground protection (earth fault protection, tripping or only alarm signalling can be selected)
Under-voltage protection
Non-elec protection
Tele-metering of Ua, Ub, Uc, Ia, Ic, P, Q, COSф and other analog quantity
124
CSC-200 numerical protection measurement control equipment Manual
SOE of all event, etc
When differential current of any phase is greater than setting value of instantaneous differential
protection, operate from the output relay and is used for quickly disconnecting the motor in case of
serious fault in motor differential area.
In order to ensure sensitive operation of differential protection during internal fault and simultaneously
prevent the maloperation caused by transient unbalance current during external fault when motor
starting, this IED adopts treble slope percent differential principle, the operation equation is as follows:
Wherein, Icd is the setting value of starting current of differential protection, Id is differential current, Ir is
restraint current, Ir1 is the current setting value of the first break point, Ir2 refers to the current
(regularly adopting 2Ie for the internal) of the second break point, K1 is the settable slope of restraint
curve, and K2 is internal fixed coefficient (adopting 0.7).
Wherein, I1 and I2 respectively refer to the current on both sides of the motor and all take flowing into the
motor as forward direction. Current transformers on both sides of the motor take directing to the motor as
homopolarity.
Action area
125
CSC-200 numerical protection measurement control equipment Manual
Icd and Ir1 are generally set as 0.3-1.2 Ie and 0.8-1.2 Ie respectively, K1 is generally set as 0.2-0.7, Ir 2
adopts 2Ie, and K2 adopts 0.7. (Ie is rated current of the motor)
This protection operates with 1h delayduring motor starting in order to avoid transient peak current at
the moment of starting.
Under normal circumstances, for discriminating CT failure, to detect that there is no current but
differential current exists on one or two of all phases current, then it is discriminated as CT failure.
2) There is no current in one or tow of three phases on this side, and there is no change on three-phase
current on opposite side
After CT secondary circuit failure, issue alarming signal, and select differential protection exit either
locking or non-locking.
DIFF action
DIFF
Ratio lock & Trip
Harm lock ≥1
KG1.1
CT fail
1
0
“0”
If the differential current is large than 25% differential setting current, issue alarming signal with 10s for
discrimination, and also report differential current is over-limit, but don’t differential protection. This
function is used fo monitoring AC sampling circuit of protection IED
The method of the IED measuring motor starting time-Tstart: when the maximum phase current of the
motor sudden-changes from 0 to 10%Ie, start timing and stop when starting current drops to 120%Ie
126
CSC-200 numerical protection measurement control equipment Manual
after passing peak value, the duration between which is called Tstart. (Ie is rated current of the motor.)
Over long starting time of the motor will make rotor overheating; when measured starting time of the IED
exceeds permissible setting starting time Tstart, the protection operates to trip, and the long-starting
protection can be enabled or disabledby binary setting "Motor Start Dsicrimination".
In order to lower starting current and reduce reactive power impact to power grid, large-sized
asynchronous motor is usually connected with reactor or the resistance in series so as to carry out lower
voltage starting; after starting, short circuit the series reactor or resistance. Dedicated binary setting is
used for thisIED, if selecting "Enable Lower Voltage Starting", then the IED will issue a pair of "Enable
Full Voltage" contact after starting in order to timely connecting to voltage-division reactor in short-circuit
to make the motor operate under rated voltage.
In order to test conveniently, when CSC 237A protection IEDdetects that the motor is "In the process of
Starting" (i.e. the period of Tstart time shown in the figure above), indicating green LED (spare) at the
bottom of panel HMI is on. And the IED also has the function of motor start recording, which is enabled
or disabled by setting value "Motor Starting Wave Recording". Analog quantity of the IED wave recording
refers to all electrical quantities directly connected to all IEDs: IA, IB, IC, I0, UA, UB and UC, from the
time of beginning start, the IED records the waveform once every 70ms and simultaneously reports the
message "Motor Start Operating" so as to check the analog variation at the moment of motor starting
operation during field testing. And Tstart and Istart of last motor starting operation time can be inquired
from measured value of IED operating condition; Istart is the maximum current during starting operation.
Overheat Protection takes into account of heat effect produced by positive and negative-sequence
current of the motor, provides protection for overheating caused by various overloads of the motor, and
also used as the back-up of short circuit, over long starting time and locked rotor of the motor.
Using equivalent current Ieq to simulate heating effect of the motor, that is:
127
CSC-200 numerical protection measurement control equipment Manual
I1-positive-sequence current
I2-negative-sequence current
K1-heating coefficient of positive-sequence current, respectively set as 0.5 during motor starting and
1.0 after motor starting
According to heating model of the motor, characteristic curve of motor operating time t and equivalent
operation current Ieq is given by following formula:
I∞-starting current, that is, the required current limit value for protection don’t operate, and I∞ can be
set as 0.80-1.30 times rated current Ie ;
This criterion takes into account of heating process of motor stator and the heat state before
overloading.
This criterion takes into account of heating process of motor stator and the heat state before
overloading.
Equivalent Trip
current
Based on the principle that the motor can be contiguously started twice, heat accumulation during each
starting should not exceed 50% of the tripping value, so when the value of heat accumulation is over
50%, closing-blocking contact of the IED operate. The value of heat accumulation can be inquired from
measured value of IED operating condition and also can be viewed from cyclical display on the panel.
After overheat protection tripping, memory function of the IED startup, closingblocking output contact
isholding, and overheat closing-blocking contact will return till heat accumulation value drops to below
50%, at that time the motor can newly startup. In case of immediately startup under the condition of
emergency, carry out heat resetting operation for the IED. And overheat blocking can be enabled or
disabled by binary setting "Overheat Blocking", moreover, it also has the function of overheat alarming,
which is enabled or disabled by binary setting "Overheat Alarming". And the user can select the
overheat function for tripping or not by enabling or disabling the linker, but overheat alarming and
blocking function can not be controlled by linker.
Heating time constant T should be provided by motor manufacturer; if not, it can be estimated by using
one of the following methods
128
CSC-200 numerical protection measurement control equipment Manual
1、If the manufacturer provides heat limit curve of the motor or a group of data relating to overloading
capacity, calculate T as the formula shown below:
2、If locked-rotor current I and permissible locked-rotor time t are given, τ can be estimated as the
formula shown below:
Wherein: θe is rated temperature rising of the motor, K is the multiple of starting current, θ0 is
temperature rising during motor starting, and Tstart is starting time of the motor.
High set value of instantaneous current Isdg which is the setting value of instantaneous protection during
motor starting and is set to avoid maximum starting current of motor starting normally. Low set value of
instantaneous current Isdd which is set by two-phase short-circuit current of motoroperating under the
minimum operation mode divided by certain sensitivity coefficient.
If the"Enable Motor Starting discrimination" is seleted in binary setting, instantaneous current protection
operates with high set value Isdg during motor starting; after the process of motor starting is finished,
instantaneous current protection operates with low set value Isdd in order to improve the sensitivity of
instantaneous current protection during motor running normally. If the"Disable Motor Starting
discrimination" is seleted in binary setting, the motor will not distinguish starting process, the
instantaneous current protection operates with low set value Isdd and overcurrent protection is enabled
all the time.
Operating conditions:
The operating time Tsd of instantaneous current protection can be set, the operating time can be set as
extremely short (e.g. 0ms) for the motor controlled by breaker and longer time delay (e.g. 0.3s) for the
motor controlled by contactor.
129
CSC-200 numerical protection measurement control equipment Manual
Instantaneous current protection logic diagram is as follows:
I>Isdg
&
Motor starting IOC
Tsd
≥1 Trip
I>Isdd
≥1
Motor running
Notes: Isdg refers to high set value of instantaneous current (setting value of instantaneous current
protection during motor starting);
Isdd refers to low set value of instantanesous current (setting value of instantaneous current
protection during the operation after motor starting);
The overcurrent protection is used for locked-rotor protection with one definite time stage, and the
operating time is set to avoid maximum permissible locked-rotor time. Overcurrent protection is disabled
automatically while motor starting and automatically enabled after the motor starting. When the "Disable
Motor Start Discrimination", is selected in binary setting, the IED does not distinguish motor starting and
doesn’t block overcurrent protection. For locked-rotor occurring during motor starting, long-starting
protection can operate, at the moment, the actual operating time may be longer than setting time of
locked-rotor.
When short-time power supply source interruption or external fault causes terminal voltage of the motor
reduction, motor slip ratio gradually increase and rotor speed will decrease; when power supply is
recovered or external fault is cleared, terminal voltage of the motor returns to normal and come into the
process of self-starting; if terminal current before self-starting is greater than the minimum current of
starting discrimination, starting discrimination will not discriminate the process of self-starting, and for
some large-sized motors or the motors adopting reduced-voltage starting, starting current at this time is
still very large (corresponding to full voltage starting if terminal voltage drops greatly), which always
causes the maloperation of overcurrent protection. In the IED, the software distinguishes the process of
self-starting through detecting rising edge of voltage while the current is greater than 1.2 times rated
current of the motor. During self-starting, disable the overcurrent protection, which will automatically
enabled after starting; self-starting discrimination can be ienabled or disabled by setting value, and when
"Disable Self-starting Discrimination" is selected, the IED does not distinguish self-starting and doesn’t
block overcurrent protection.
130
CSC-200 numerical protection measurement control equipment Manual
I>Igl OC
Tgl
Motor starting & Trip
Self starting
The magnitude of motor grounding current depends on grounding mode of power system. In
ungrounded or high resistance grounding system, the fault current is only several ampere, hundreds of
ampere in neutral resistance grounding system and much larger in direct grounding system. For the
system with higher ground fault current, if three phases are all equipped with current transformer,
zero-sequence current can be obtained through the current sum of three phases. In most conditions, in
order to detect low grounding current, usually zero-sequence current is from zero-sequence current
transformer. Therefore, this protection can be used with either the mode of two-phase current
transformer plus zero-sequence current transformer, or the mode of three-phase current transformer.
Sel Trip
EF
T0
I0>I0dz Trip
Sel Alarm
T0
Alarm
Negative-sequence protection is mainly used for non-grounded asymmetrical faults, such as: when any
phase failure happens of the motor, the magnitude of negative sequence component is different due to
load rate before the fault, when load rate is over 0.7, healthy phase can cause overcurrent, thus, general
protection cannot effectively protect asymmetrical faults. As to operating time, there are two kinds of time
characteristics can be seleted, definite time stage and inverse time stage, extremely inverse time stage
131
CSC-200 numerical protection measurement control equipment Manual
I is negative-sequence fault current
t tripping time
For setting value, "The Time of Negative-sequence Inverse Time stage " is product value of numerator
(80tp) in the expression above, and its unit is s. Ip setting range is (0.2-1.7 Ie), and it is suitable to select
1.0 Ie setting value in order to protect locked-rotor of phase failure or reversed phase of the motor.
When exteral fault occurs, feedback negative-sequence current of the motor may cause the
maloperation of negative-sequence current protection. Based on the different ratios of I2/I1 of
asynchronous motor when asymmetrical faults occurs externally or internally ,is the following conditions
are met, the negative-sequence current protection will be blocked: I2≥1.125I1, wherein, I1 refers to
positive-sequence current, and I2 is negative-sequence current. While short circuit fault occurs inside
the motor, this condition is not met; the blocking is automatically released, which ensures operation
reliably. The Blocking condition can beenabled or disabled through binary setting, i.e., disabled the
protection while used as synchronous motor protection.
KG1.10=0
I2> T
KG1.10=1 ≥1
I2FSX> ∫
UV
& Trip
KG1.11
I2≥1.2I1
1
0
“0”
When external protection CT is two-phase, it may affect the calculation of negative-sequence current of
internal software, so B-phase current needs to be combined through wiring connetion.
In order to ensure production safely, for the motor which is not allowed to self-starting, after the
powersupply disappears or reduces, under voltage protection operate with tripping to make the motor
self-disconnect from power grid.
When measuring line voltage U is lower than setting value, the switch or contactor is in the closing stage
and there is falling edge, under voltage protection operate. In order to prevent PT failure from
mis-disconnectin the motor, this protection is equipped with the function to block under voltage
protection by the negative-sequence voltage caused by single-phase, two-phase or three-phase VT
failure.
132
CSC-200 numerical protection measurement control equipment Manual
Uab>Udz
Ubc>Udz &
Uca>Udz
UV
VT broken
& Td
Trip
HWJ
2s
max(Uxx)>Udz
Td
Overload element monitors the current of three phases, the operating conditions are: MAX(IΦ)>Ifh and
time delay elapse; wherein, Ifh refers to setting value of overload current. Tripping or only alarming
signal given can be selected by binary setting for overload protection operation. Overload tripping time
should be set to tavoid the time of motor starting.
Overload KG1.12=1
Ttz
MAX(IΦ)>Ifh Trip
KG1.12=0
Tgj
Alarm
Note: this IED takes into account of the time delay is longer for overload protection and protection output
is actual setting value, but the message does not reflect it.
For the motor controlled by F-C (high-voltage fuse - contactor), if fault current of any phase exceeds
breaking current of the contactor, protection output is blocked, the fuse is responsible for clearing the
fault. If the fuse can not clear the fault in time and the fault current remains, if the time delay of other
protection of this IED elapse, then the message relating to other protection is still reported, but no
operate actually.
Connect fusing contact of external fuse to IED 8X2, the IED issues alarming signal of DI2, and tripping or
not can be selected by binary setting ( Non-elec2 ).
3-channel binary input DI1, I2, DI3 of Non-elec protection protection to are provided, respectively
corresponding to rear terminals 8X1, 8X2 and 8X3. After receiving DI signal from switch cabinet, if
133
CSC-200 numerical protection measurement control equipment Manual
relevant Non-elec binary setting is enabled, trip the corresponding CB and record the event, and the
record can be uploaded to background computer through network port or fieldbus.
VT circuit monitoring is used for detecting single-phase failure, two-phase failure and three-phase
voltage loss fault of VT circuit; if any one of the following three conditions is met, the IED will report the
event of "VT filure or voltage loss" and drive corresponding signal node and LED indicator.
The voltage of all three phases is less than 8V and the current of any phase (a or c) is greater than
non-current threshold (can be set by internal setting value), discriminated as three-phase voltage
loss.
The voltage sum of all three phases is greater than 8V and the minimum line voltage is less than
16V, discriminated as two-phase VT failure.
The voltage sum of all three phases is greater than 8V and the voltage difference between
maximum line voltage and minimum line voltage is greater than 16V, discriminated as single-phase
PTfailure.
2) The time exceeds setting value. (Internal parameter can be set, the default is 10s)
The function of control circuit failure monitoring is enabled or disabled by setting value "Control Circuit
Failure".
134
CSC-200 numerical protection measurement control equipment Manual
Notes:
¾ The functions not used can be completely disabled with corresponding logical linker or binary
setting. Spare bit in binary setting is set as 0.
137
POWER TRIP LOGIC CPU AC2 AC2 AC1
X8 X7 X6 X5 X3 X2 X1
1 DI1Non-elec1 1 +KM 1 Common 1 Rem/Loc 1 Ua 1 Ia1 1 Ia2
2 DI2Non-elec2 2 Manual trip(in) 2 Trip1 2 Reset 2 Ub 2 Ia1' 2 Ia2'
3 DI3Non-elec3 3 Relay trip(in) 3 Close1 3 Overhaul 3 Uc 3 Ib1 3 Ib2
4 DI4HWJ 4 To trip coil 4 Common 4 Heating Reset 4 Un 4 Ib1' 4 Ib2'
5 DI5 5 To close coil 5 Trip2 5 -24V 5 5 Ic1 5 Ic2
6 DI6 6 Short to X7-5 6 Close2 6 UV/P 6 6 Ic1' 6 Ic2'
7 DI7 7 Close(in) 7 Common 7 DIFF/Q 7 I0 7
8 DI8 8 8 Remote trip 8 COM- 8 I0' 8
-KM
9 DI9 9 Common 9 Remote close 9 SYNA+ 9 Mea Ia 9
TWJ 10 Common 10 SYNA- 10 Mea Ia' 10
13.5. IED terminal diagram
10 DI (-) 10
11 +24V 11 HWJ 11 Operation 11 RS485A 11 Mea Ic 11 Mea Ib
12 -24V 12 12 Alarm 12 RS485B 12 Mea Ic' 12 Mea Ib'
13 13
CC broken 13
DC Backup1
CSC-200 numerical protection measurement control equipment
14 Failure 14 14
Event 1RJ45
15 Not used 15 15
138
Backup2
16 DC(+) 16 Output for 16
Manual trip
17 Not used 17 17
Full-U
18 DC(-) 18 + 2YJJ 18
2RJ45
19 Not used 19 19
CB Close Blk.
20 GND 20 2YJJ (out) 20
Connection specification: Input current analog used for measurement through dedicated measuring CT
(A and C phases) to ensure adequate accuracy; input the voltage used for measurement and protection
voltage for using in common. When external protection CT is two-phase, because it will affect the
calculation of negative-sequence current of internal software, B-phase current needs to be combined
through wiring, the wiring is as follows: connect external Ia of IED to 2X1, external Ic to 2X5, external Ia'
and Ic' to 2X3, and connect other current terminals 2X2, 2X4 and 2X6 in short circuiting. It had better to
connect zero-sequence current with dedicated zero-sequence current transformer, if there is no such
transformer, use the sum of three-phase current, namely, neutral current of CT on the premise of
ensuring that zero-sequence current can meet selectivity requirements of small grounding current
system protection. Blocking-closing contact can be bridged to closing circuit as required, the method is:
connect 6X.19 to 7X.7 and 6X.20 to 6X.9 as well as KKJ manual closing output contact of switch cabine.
139
CSC-200 numerical protection measurement control equipment Manual
15.1. Installation
a) The equipment should be solidly fixed on the screen (cabinet) and all connection screws of the
equipment should be fixed.
b) The equipment ground and screen (cabinet) ground are reliably grounded with the system
ground and bus bar.
c) The wiring of the equipment should meet the requirement in the wiring drawing.
a) Plug all modules and check whether the mechanical parts and components of the modules are
loose, fall off, or mechanically damaged. Whether the wiring is solid.
b) Check whether the connectors of all modules are inserted in place and lock is reliable.
c) Check whether the man-machine interface (MMI) and panel are connected reliably.
Before you make an insulation check, you should guarantee that the equipment terminal has no electric
connection with the onsite secondary loop. Respectively short-connect the AC voltage loop, AC current
loop, DC power loop, switch/signal input loop, switch/signal output loop, use 500V meter to measure
insulation resistance of all loops to ground or to each other, which is required to be higher than 100MΩ.
After the equipment powers on, the steps are followed to check whether the equipment is normal.
140
CSC-200 numerical protection measurement control equipment Manual
d) Check that the software information and configuration information of the equipment should be
consistent with the equipment type.
e) Check that the calendar clock of the equipment should be accurate and whether calibration is
required.
f) Enter the settings to the corresponding zone according to the setting list and switch the running
setting zone to the required one.
g) To set various protection functions via the link, the equipment should display no exceptional
information.
h) Check whether the modules of the factory menu are consistent with detailed engineering
technical requirements. For inconsistent contents, know the user requirement and make correct
setup.
The sampling precision of this equipment require no adjustment and the sampling error should not be
higher than 2%. Generally, the protection tester is used for qualitative calibration. For strict requirement,
the phase current input terminals of the equipment can be serial connected with 5A/1A current. The
phase PT is parallel connected with 50V voltage. The equipment should accurately display the input, the
value of all phase should be consistent, the phase of the analog channels should be correct.
Digital input loop calibration can be made via the digital input test commands on the operation interface
of the equipment.
Digital output loop calibration can be made via the digital output test commands on the operation
interface of the equipment, or made together with the setting calibration. Each channel of contact output
is checked for one time, for other tests, the signal indicators and LCD are observed. The close and trip
should be tested with breaker to validate that the breaker can correctly act.
Simulate a fault to make the protection act and trip, validate that the close and trip current keeps a
normal status. The manual close and open operation is made to validate the integrity of this loop..
141
CSC-200 numerical protection measurement control equipment Manual
If the equipment is connected to the local monitoring or SCADA system, test whether the communication
network between the local monitoring or SCADA system and equipment is perfect and the information
transmission is correct. The test is made via the remote communication test function on the operation
interface of the equipment, setting validation or secondary wiring calibration can be made at the same
time.
The protection function and action logic of the equipment are tested via simulation and other tests. The
onsite debugging is only used to validate the validity of all settings, others can be reliably guaranteed.
Observe whether all phase currents, voltages and other phase angles displayed by the LCD of the
equipment is consistent with the practical operation results after the line is powered.
a) The function definition of the keyboard meets the operation habits, the keyboard is used to
browse information, modify the setting and complete the corresponding control in the function
menu conveniently.
b) Monitor operation and control or operate operation mode simply and quickly.
c) Provide customization function of the display control image to meet the operation habit of the
142
CSC-200 numerical protection measurement control equipment Manual
user.
a) Circularly display the current time, measurement value, operating soft connector, and current
setting zone under the general status.
b) When the equipment starts up exceptionally or the protection acts, the background light of the
display screen is enhanced to actively display the event information via a highlighted mode.
c) Respond to the keyboard command and enhance the background light of the display screen to
display the man-machine dialog interface via the highlighted mode.
d) LCD is divided into LCD (320*240) and LCD(160*80), refer to the practical object for detailed
configuration.
16.1.2 Keyboard
The keyboard consists of [↑], [↓], [→], [←], [SET] and [QUIT] keys and can be used to complete all
man-machine dialog operations.
[SET] key
a) To press “SET” key, activate the main menu under circular display status.
b) When you make the operations such as switching link, setting, switching setting zone, setting
time, setting equipment address. “SET” key is equivalent to press Enter key. To press “SET” key,
you can confirm the execution.
[QUIT] key
a) Clear screen
b) When you operate the menu, to press “QUIT” key, you can cancel the operation, or return to the
higher menu.
b) When you enter a digit, you can use [←] and [→] key to move the cursor left and right to a digit,
and use [↑] and [↓] to increase or decrease the digit.
The first indicator of the CSC-200 equipment is “run /alarm” indicator, generally the “run/alarm” indicator
143
CSC-200 numerical protection measurement control equipment Manual
keeps constant green and shows that the equipment can work normally; the green indicator flickers after
the protection starts, and the indicator recovers to constant green after protection equipment is reset; the
indicator keeps constant red on when the equipment gives an alarm, and the indicator will recover to
constant green on status when the equipment resets.
Wherein 10 green indicators indicate “XXX protection function connector operate” and the red indicator
indicates that the protection function acts.
Special example:
a) The “reclosing” indicator for CSC-211 keeps constant green on and shows that the reclosing
function starts up and is fully charged; when the green indicator flickers, it shows that the equipment
is being charged; when the red indicator is constant on, it indicates the reclosing exit.
b) “Under-frequency load dropping” indicator and under-voltage load dropping (separation) of the
CSC-211 are common.
144
CSC-200 numerical protection measurement control equipment Manual
16.3. Equipmentmenu
When the equipment normally starts up, the default image will circularly display current time,
measurement value, computation value, link status, and operation setting zone. when the protection acts
or the alarm occurs, the equipment will automatically pop up the event information image. The equipment
can respond to the keyboard commands and display the tree menu or operation interface.
As shown in the figure 11-2, the equipment menu consists of main menu and multi-level sub-menu, the
menu at different levels is different in operation right. The information monitoring does not require
password validation, such as the operation information monitoring, setting view, and history report view.
The parameter setup and test control operation of the equipment such as the setting, link
commission/cease, and operation setting zone switching require the password validation to avoid
accidental modification to the important operation parameters of the equipment which leads to the
operation exceptionally of the equipment or mistaken action or rejection of the protection. The operation
password is 【8888】.
145
CSC-200 numerical protection measurement control equipment Manual
146
CSC-200 numerical protection measurement control equipment Manual
147
CSC-200 numerical protection measurement control equipment Manual
Note 1: 【Print Setup】 now the equipment support the network to share the print and 485 share print,
only a special print server is provided, the MMI print function can be used.
Note 2: 【Equipment Test】 when the digital output test and precision test command are used, to
prevent the equipment from leading to unnecessary information interference, the protection will
automatically exit. In principle, the equipment can be tested when it shuts down the operation.
Note 3: 【Measurement Calibration】 it is mainly used for the precision calibration of the measurement
module, a precise standard voltage power supply is required for coordination. If no special requirement ,
generally this operation is not executed at the site, otherwise, it may lead to insufficient precision of the
measurement module.
148
CSC-200 numerical protection measurement control equipment Manual
The following items should be carefully checked before the equipment starts up.
c) The settings of the equipment should be consistent with the setting list.
d) The operation setting zone and protection commission/cease link of the equipment should meet
the operation requirement.
The breaker location and other auxiliary switch locations of the equipment should be consistent with the
practical locations.
Because the equipment has a perfect software and hardware self-check function, the effective routine
maintenance means is to monitor the signal node and LED status of the equipment. Combining with the
LED and LCD under the normal operation, the equipment can show comprehensive operation status and
practical operation data of the equipment without manual interference.
If the protection action occurs, the corresponding saved fault records and recording wave data should be
called in time for accident analysis. After the accident is processed, the action signal contact and related
LED should be reset.
If the alarm call exception occurs, the event should be focused. The observed phenomena should be
recorded in detail. if it is the equipment operation exception (such as load and zero-current alarm), the
corresponding operation regulation is used for processing. If it is the key part exception of the equipment,
the equipment should stop for overhaul. After the alarm reason is eliminated, the alarm signal contact
and related LED of the equipment should be reset.
c) Do not modify the important operation parameters of the equipment during operation such as
the hardware test and setting to avoid the incorrect action of the equipment or influences on the
whole performance.
If the equipment encounters an exception which can not be solved, you should contact us as early as
possible, do not disassemble and repair it by self.
149
CSC-200 numerical protection measurement control equipment Manual
a) The repair must comply with the local or power regulations after the equipment starts up.
b) The repair must be performed by the professionals after the equipment starts up.
e) Do not make digital input drive, switch setting zone, change setting, switch link, and change
equipment address at random during operation.
f) When the alarm indicator of the equipment is on, you should instantly notify the relay protection
equipment staff to process.
b) The air does not include erosive materials such as acid and alkali.
c) The equipment can normally operate under -10℃ ~ +55℃ (in Celsius degree) temperature, if
the temperature is beyond this scope and is within -25℃ ~ +70℃, the LCD may display
exception and blurry front, but the protection is not affected, and the action deviation will not
exceed the allowed range.
150