Professional Documents
Culture Documents
SIFANG CSC 211 Multifunction Protection Ied Technical Application Manual
SIFANG CSC 211 Multifunction Protection Ied Technical Application Manual
Note: the company keeps the right to perfect the instruction. If equipment does not agree with
the instruction at anywhere, please contact our company in time. We will provide you with
corresponding service.
®
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and
dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.
The data contained in this manual is intended solely for the IED description and is not to be
deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards
as a result it is possible that there may be some differences between the hardware/software
product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
This manual describes the functions, operation, installation, and placing into
service of IED CSC-211. In particular, one will find:
Target audience
This manual mainly face to installation engineer, commissioning engineer and
operation engineer with perfessional electric and electrical knowledge, rich
experience in protection function, using protection IED, test IED, responsible
for the installation, commissioning, maintenance and taking the protection
IED in and out of normal service.
Technical support
In case of further questions concerning the CSC family, please contact
SiFang compay or your local SiFang representative.
Safety information
Avoid to touching the circuitry when covers are removed. The IED
contains electirc circuits which can be damaged if exposed to static
electricity. Lethal high voltage circuits are also exposed when covers
are removed
Using the isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present
Changing the setting value group will inevitably change the IEDs
operation. Be careful and check regulations before making the
change
Contents
Chapter 1 Introduction .......................................................................................................................1
1 Overview ...........................................................................................................................................2
2 Features ............................................................................................................................................3
3 Functions ..........................................................................................................................................5
3.1 Protection functions .........................................................................................................5
3.2 Control functions ..............................................................................................................6
3.3 Monitoring functions ........................................................................................................6
3.4 Station communication....................................................................................................7
3.5 IED software tools............................................................................................................7
Chapter 2 General IED application ..................................................................................................8
1 Display on LCD screen ...................................................................................................................9
1.1 LCD screen display function ..........................................................................................9
1.2 Analog display function ...................................................................................................9
1.3 Report display function ...................................................................................................9
1.4 Menu dispaly function .....................................................................................................9
2 Report record .................................................................................................................................10
3 Disturbance recorder.....................................................................................................................10
3.1 Introduction .....................................................................................................................10
3.2 Fault recording ...............................................................................................................10
3.3 Wave recording ..............................................................................................................11
3.4 Sequence of event record ............................................................................................11
3.5 Operation record ............................................................................................................11
4 Self-supervision function ..............................................................................................................12
4.1 Introduction .....................................................................................................................12
4.2 Self-supervision principle..............................................................................................12
4.3 Self-supervision report ..................................................................................................13
5 Time synchroniation function .......................................................................................................15
5.1 Introduction .....................................................................................................................15
5.2 Synchronization principle..............................................................................................15
5.2.1 Synchronization from IRIG ...........................................................................................16
5.2.2 Synchronization via PPS or PPM ................................................................................16
5.2.3 Synchronization via SNTP ............................................................................................16
6 Setting .............................................................................................................................................17
6.1 Introduction .....................................................................................................................17
6.2 Operation principle ........................................................................................................17
7 Authorization...................................................................................................................................18
Chapter 3 Over current protection .................................................................................................19
1 Overcurrent protection ..................................................................................................................20
1.1 Introduction .....................................................................................................................20
1.2 Protection principle ........................................................................................................21
1.2.1 Time characteristics ...................................................................................... 21
1.2.2 Inrush restraint function ................................................................................ 23
1.2.3 Low voltage component................................................................................ 23
1.2.4 Direction determination feature ................................................................... 24
1.2.5 Logic diagram................................................................................................. 27
1.3 Input and output signals ............................................................................................... 29
1.4 Setting parameters ........................................................................................................ 30
1.5 Reports............................................................................................................................ 33
1.6 Technical data................................................................................................................ 34
Chapter 4 Earth fault protection ..................................................................................................... 35
1 Earth fault protection ..................................................................................................................... 36
1.1 Introduction ..................................................................................................................... 36
1.2 Protection principle........................................................................................................ 37
1.2.1 Time characteristic ........................................................................................ 37
1.2.2 Inrush restraint ............................................................................................... 38
1.2.3 Direction determination feature ................................................................... 39
1.2.4 Logic diagram................................................................................................. 44
1.3 Input and output signals ............................................................................................... 46
1.4 Setting parameters ........................................................................................................ 47
1.5 IED reports ..................................................................................................................... 50
1.6 Technical data................................................................................................................ 50
Chapter 5 Sensitive earth fault protection .................................................................................... 52
1 Sensitive overcurrent protection ................................................................................................. 53
1.1 Introduction ..................................................................................................................... 53
1.2 Protection principle........................................................................................................ 53
1.2.1 Time characteristic ........................................................................................ 53
1.2.2 Direction determination feature ................................................................... 55
1.2.3 Logic diagram................................................................................................. 59
1.3 Input and output signals ............................................................................................... 60
1.4 Setting parameters ........................................................................................................ 61
1.5 IED reports ..................................................................................................................... 64
1.6 Technical data................................................................................................................ 64
Chapter 6 Negative-sequence overcurrent protection ............................................................... 66
1 Negative-sequence overcurrent protection ............................................................................... 67
1.1 Introduction ..................................................................................................................... 67
1.2 Protection principle........................................................................................................ 67
1.2.1 Protection function description .................................................................... 67
1.2.2 Logic diagram................................................................................................. 69
1.3 Input and output signals ............................................................................................... 69
1.4 Setting parameters ........................................................................................................ 70
1.5 IED reports ..................................................................................................................... 72
1.6 Technical data................................................................................................................ 73
Chapter 7 Thermal overload protection ........................................................................................ 74
1 Thermal overload protection ........................................................................................................ 75
9
1.1 Introduction .....................................................................................................................75
1.2 Protection principle ........................................................................................................75
1.3 Input and output signals................................................................................................77
1.4 Setting parameters ........................................................................................................77
1.5 IED reports......................................................................................................................78
1.6 Technical data ................................................................................................................78
Chapter 8 Swtich on to faulty..........................................................................................................79
1 Swtich on to faulty protection .......................................................................................................80
1.1 Introduction .....................................................................................................................80
1.2 Protection principle ........................................................................................................80
1.2.1 Protection function description .....................................................................80
1.2.2 Logic diagram .................................................................................................81
1.3 Input and output signals................................................................................................81
1.4 Setting parameters ........................................................................................................82
1.5 IED reports......................................................................................................................82
Chapter 9 Overvoltage protection ..................................................................................................84
1 Overvoltage protection ..................................................................................................................85
1.1 Introduction .....................................................................................................................85
1.2 Protection principle ........................................................................................................85
1.2.1 Time characteristics .......................................................................................85
1.2.2 Overvoltage protection principle ..................................................................87
1.2.3 Voltage connection ........................................................................................87
1.2.4 Logic diagram .................................................................................................88
1.3 Input and output signals................................................................................................89
1.4 Setting parameters ........................................................................................................90
1.5 IED reports......................................................................................................................91
1.6 Technical data ................................................................................................................91
Chapter 10 Undervoltage protection................................................................................................92
1 Undervoltage protection................................................................................................................93
1.1 Introduction .....................................................................................................................93
1.2 Protection principle ........................................................................................................93
1.2.1 Protection function description .....................................................................93
1.2.2 Voltage connection ........................................................................................94
1.2.3 Depending on the VT location......................................................................95
1.2.4 Logic diagram .................................................................................................96
1.3 Input and output signals................................................................................................97
1.4 Setting parameter ..........................................................................................................98
1.5 IED reports......................................................................................................................99
1.6 Technical data ..............................................................................................................100
Chapter 11 Displacement voltage protection ...............................................................................101
1 Displacement voltage protection ...............................................................................................102
1.1 Introduction ...................................................................................................................102
1.2 Protection principle ......................................................................................................102
1.2.1 Displacement voltage input ........................................................................102
10
1.2.2 Protection description ................................................................................. 103
1.2.3 Logic diagram............................................................................................... 104
1.3 Input and output signals ............................................................................................. 105
1.4 Setting parameter ........................................................................................................ 106
1.5 IED reports ................................................................................................................... 107
1.6 Technical data.............................................................................................................. 107
Chapter 12 Negative-sequence over voltage protection ............................................................ 108
1 Negative-sequence over voltage protection ............................................................................ 109
1.1 Introduction ................................................................................................................... 109
1.2 Protection function description .................................................................................. 109
1.2.1 Negative-sequence voltage input.............................................................. 109
1.2.2 Protection description ................................................................................. 109
1.2.3 Logic diagram............................................................................................... 110
1.3 Input and output signals ............................................................................................. 110
1.4 Setting parameter ........................................................................................................ 111
1.5 IED reports ................................................................................................................... 111
1.6 Technical data.............................................................................................................. 111
Chapter 13 Circuit breaker failure protection ............................................................................... 112
1 Circuit breaker failure protection ............................................................................................... 113
1.1 Introduction ................................................................................................................... 113
1.2 Protection principle...................................................................................................... 113
1.2.1 Protection description ................................................................................. 113
1.2.2 Current criterion evaluation ........................................................................ 114
1.2.3 Circuit breaker auxiliary contact evaluation ............................................. 114
1.2.4 Logic diagram............................................................................................... 115
1.3 Input and output signals ............................................................................................. 116
1.4 Setting parameter ........................................................................................................ 117
1.5 IED reports ................................................................................................................... 117
1.6 Technical data.............................................................................................................. 118
Chapter 14 Dead zone protection .................................................................................................. 119
1 Dead zone protection.................................................................................................................. 120
1.1 Introduction ................................................................................................................... 120
1.2 Protection principle...................................................................................................... 120
1.2.1 Function description .................................................................................... 120
1.2.2 Logic diagram............................................................................................... 121
1.3 Input and output signals ............................................................................................. 122
1.4 Setting parameter ........................................................................................................ 122
1.5 IED reports ................................................................................................................... 123
1.6 Technical data.............................................................................................................. 123
Chapter 15 STUB protection .......................................................................................................... 124
2 STUB protection .......................................................................................................................... 125
2.1 Introduction ................................................................................................................... 125
2.2 Protection principle...................................................................................................... 125
2.2.1 Function description .................................................................................... 125
11
2.2.2 Logic diagram ...............................................................................................126
2.3 Input and output signals..............................................................................................126
2.4 Setting parameters ......................................................................................................127
2.5 Reports ..........................................................................................................................127
2.6 Technical data ..............................................................................................................127
Chapter 16 Synchro-check and energizing check function ........................................................128
1 Synchro-check and energizing check function ........................................................................129
1.1 Introduction ...................................................................................................................129
1.2 Function principle.........................................................................................................129
1.2.1 Synchro-check mode...................................................................................130
1.2.2 Energizing check mode...............................................................................131
1.2.3 Override mode..............................................................................................132
1.2.4 Logic diagram ...............................................................................................132
1.3 Input and output signals..............................................................................................133
1.4 Setting parameter ........................................................................................................133
1.5 IED reports....................................................................................................................134
1.6 Technical data ..............................................................................................................135
Chapter 17 Autoreclosing function .................................................................................................136
1 Autoreclosing function.................................................................................................................137
1.1 Introduction ...................................................................................................................137
1.2 Function principle.........................................................................................................137
1.2.1 Auto-reclosing initiation modules ...............................................................137
1.2.2 Autoreclosing logic.......................................................................................138
1.3 Input and output signals..............................................................................................141
1.4 Setting parameter ........................................................................................................143
1.5 IED reports....................................................................................................................145
1.6 Technical data ..............................................................................................................146
Chapter 18 Under current monitoring ............................................................................................147
1 Under current monitoring ............................................................................................................148
1.1 Introduction ...................................................................................................................148
1.2 Protection principle ......................................................................................................148
1.2.1 Function description ....................................................................................148
1.2.2 Logic diagram ...............................................................................................148
1.3 Input and output signals..............................................................................................149
1.4 Setting parameter ........................................................................................................149
1.5 IED reports....................................................................................................................150
Chapter 19 Over-frequency protection ..........................................................................................151
1 Over-frequency protection ..........................................................................................................152
1.1 Introduction ...................................................................................................................152
1.2 Protection principle ......................................................................................................152
1.2.1 Function description ....................................................................................152
1.2.2 Logic diagram ...............................................................................................152
1.3 Input and output signal................................................................................................153
1.4 Setting parameter ........................................................................................................153
12
1.5 IED reports ................................................................................................................... 154
Chapter 20 Rate of change of frequency protection ................................................................... 155
1 Rate of change of frequency protection ................................................................................... 156
1.1 Introduction ................................................................................................................... 156
1.2 Protection principle...................................................................................................... 156
1.2.1 Function description .................................................................................... 156
1.2.2 Logic diagram............................................................................................... 157
1.3 Input and output signal ............................................................................................... 157
1.4 Setting parameter ........................................................................................................ 158
1.5 IED reports ................................................................................................................... 158
Chapter 21 Load shedding protection ........................................................................................... 159
1 Low frequency load shedding protection ................................................................................. 160
1.1 Introduction ................................................................................................................... 160
1.2 Protection principle...................................................................................................... 160
1.2.1 Function description .................................................................................... 160
1.2.2 Logic diagram............................................................................................... 162
1.3 Input and output signals ............................................................................................. 162
1.4 Setting parameter ........................................................................................................ 163
1.5 IED reports ................................................................................................................... 163
2 Low voltage load shedding protection ...................................................................................... 164
2.1 Introduction ................................................................................................................... 164
2.2 Protection principle...................................................................................................... 164
2.2.1 Funciton description .................................................................................... 164
2.2.2 Logic diagram............................................................................................... 166
2.3 Input and output signals ............................................................................................. 166
2.4 Setting parameter ........................................................................................................ 167
2.5 IED reports ................................................................................................................... 168
3 Overload load shedding protection ........................................................................................... 169
3.1 Introduction ................................................................................................................... 169
3.2 Protection principle...................................................................................................... 169
3.2.1 Fucntion description .................................................................................... 169
3.2.2 Logic diagram............................................................................................... 170
3.3 Input and output signals ............................................................................................. 170
3.4 Setting parameter ........................................................................................................ 171
3.5 IED reports ................................................................................................................... 172
3.6 Technical data.............................................................................................................. 172
Chapter 22 Super load shedding protection ................................................................................ 173
4 Super Low frequency load shedding protection ..................................................................... 174
4.1 Introduction ................................................................................................................... 174
4.2 Protection principle...................................................................................................... 174
4.2.1 Function description .................................................................................... 174
4.2.2 Logic diagram............................................................................................... 176
4.3 Input and output signals ............................................................................................. 177
4.4 Setting parameter ........................................................................................................ 177
13
4.5 IED reports....................................................................................................................179
5 Super Low voltage load shedding protection ..........................................................................180
5.1 Introduction ...................................................................................................................180
5.2 Protection principle ......................................................................................................180
5.2.1 Funciton description ....................................................................................180
5.2.2 Logic diagram ...............................................................................................182
5.3 Input and output signals..............................................................................................183
5.4 Setting parameter ........................................................................................................183
5.5 IED reports....................................................................................................................184
6 Super Overload load shedding protection ...............................................................................185
6.1 Introduction ...................................................................................................................185
6.2 Protection principle ......................................................................................................185
6.2.1 Fucntion description ....................................................................................185
6.2.2 Logic diagram ...............................................................................................186
6.3 Input and output signals..............................................................................................187
6.4 Setting parameter ........................................................................................................187
6.5 Technical data ..............................................................................................................188
Chapter 23 Fast busbar protection scheme .................................................................................189
1 Fast busbar protection scheme .................................................................................................190
1.1 Input and output signals..............................................................................................191
1.2 IED reports....................................................................................................................192
Chapter 24 Secondary system supervision ..................................................................................193
1 Current circuit supervision ..........................................................................................................194
1.1 Function principle.........................................................................................................194
1.1.1 Function description ....................................................................................194
1.1.2 Logic diagram ...............................................................................................194
1.2 Input and output signals..............................................................................................194
1.3 Setting parameter ........................................................................................................195
1.4 IED reports....................................................................................................................195
2 Fuse failure supervisionVT .........................................................................................................196
2.1 Introduction ...................................................................................................................196
2.2 Function principle.........................................................................................................196
2.2.1 Logic diagram ...............................................................................................198
2.2.2 Input and output signals ..............................................................................198
2.3 Setting parameter ........................................................................................................199
2.4 IED reports....................................................................................................................200
2.5 Technical data ..............................................................................................................200
Chapter 25 Monitoring function ......................................................................................................201
1 Switching devices status monitoring .........................................................................................202
2 Self-supervision ...........................................................................................................................202
Chapter 26 Station communication................................................................................................203
1 Overview .......................................................................................................................................204
1.1 Protocol .........................................................................................................................204
1.1.1 IEC61850-8 communication protocol........................................................204
14
1.1.2 IEC60870-5-103 communication protocol ............................................... 204
1.2 Communication port .................................................................................................... 205
1.2.1 Front communication port .......................................................................... 205
1.2.2 RS485 communication ports...................................................................... 205
1.2.3 Ethernet communication ports ................................................................... 205
1.3 Technical data.............................................................................................................. 205
1.4 Typical substation communication scheme ............................................................. 207
1.5 Typical time synchronizing scheme .......................................................................... 207
Chapter 27 Hardware ...................................................................................................................... 208
1 Introduction................................................................................................................................... 209
1.1 IED structure ................................................................................................................ 209
1.2 IED module arrangement ........................................................................................... 209
2 Local human-machine interface ................................................................................................ 210
2.1 Liquid crystal display (LCD) ....................................................................................... 210
2.2 Man-Machine Interface Module (MMI) ..................................................................... 210
2.3 IED menu ...................................................................................................................... 214
2.3.1 Menu construction ....................................................................................... 214
2.3.2 Operation status .......................................................................................... 215
2.3.3 Settings ......................................................................................................... 215
2.3.4 QueryRpt....................................................................................................... 215
2.3.5 DevSetup ...................................................................................................... 216
2.3.6 Print ............................................................................................................... 216
2.3.7 Testing ........................................................................................................... 216
2.3.8 DevInfo .......................................................................................................... 217
2.3.9 Connector ..................................................................................................... 217
3 Analog input module ................................................................................................................... 217
3.1 Introduction ................................................................................................................... 217
3.2 Technical data.............................................................................................................. 219
4 Binary Input & Output module ................................................................................................... 220
4.1 Terminals figure of IED ............................................................................................... 221
4.2 Technical data.............................................................................................................. 223
5 CPU module ................................................................................................................................. 225
5.1 Introduction ................................................................................................................... 225
5.2 Terminals of CPU module .......................................................................................... 226
5.3 Technical data.............................................................................................................. 227
6 Power supply module ................................................................................................................. 229
6.1 Introduction ................................................................................................................... 229
6.2 Terminals of power supply module ........................................................................... 229
6.3 Technical data.............................................................................................................. 230
6.4 Type tests ..................................................................................................................... 231
6.5 IED design .................................................................................................................... 235
6.6 CE certificate ................................................................................................................ 235
Chapter 28 Appendix ....................................................................................................................... 236
1 General setting list ...................................................................................................................... 237
15
1.1 Setting list for CSC-211(F11) .....................................................................................237
1.2 Setting list for CSC-211(L11) .....................................................................................249
2 General report list ........................................................................................................................254
2.1 Event report list ............................................................................................................254
2.2 Alarm report list ............................................................................................................256
3 Typical connection .......................................................................................................................258
4 Time inverse characteristic.........................................................................................................274
4.1 11 kinds of IEC and ANSI inverse time characteristic curves ...............................274
4.2 User defined characteristic .........................................................................................274
4.3 Typical inverse curves ................................................................................................276
5 CT Requirement...........................................................................................................................288
5.1 Overview .......................................................................................................................288
5.2 Current transformer classification .............................................................................288
5.3 Abbreviations (according to IEC 60044-1, -6, as defined).....................................289
5.4 General current transformer requirements ..............................................................290
5.4.1 Protective checking current ........................................................................290
5.4.2 CT class.........................................................................................................291
5.4.3 Accuracy class .............................................................................................292
5.4.4 Ratio of CT ....................................................................................................293
5.4.5 Rated secondary current ............................................................................293
5.4.6 Secondary burden .......................................................................................293
5.5 Rated equivalent secondary e.m.f requirements ....................................................294
5.5.1 Definite time overcurrent protection and earth fault protection .............294
5.5.2 Inverse time overcurrent protection and earth fault protection .............295
16
Chaper 1 introduction
Chapter 1 Introduction
1
Chaper 1 introduction
1 Overview
CSC-211 series are selective, reliable and high speed multifunction
protection IED (Intelligent Electronic Device), which are able to be applied
for protection, control and measurement for following applications:
2
Chaper 1 introduction
2 Features
Extensivemultifunction IED including protection, control and monitoring
functions
Undercurrent protection(37)
High frequencyprotection(81H)
3
Chaper 1 introduction
CB status supervision
4
Chaper 1 introduction
3 Functions
Voltage protection
3U>
Overvoltage protection 59 PTOV
3U>>
3U<
Undervoltage protection 27 PTUV
3U<<
Displacement voltage protection 64 VE>
Negative-sequence overvoltage
47 PPBV U2>
protection
Breaker protection and control function
3I> BF
Breaker failure protection 50BF RBRF I0>BF
I2>BF
Dead zone protection 50SH-Z
5
Chaper 1 introduction
Other functions
Fast busbar protection using reverse
interlocking
Description
Self-supervision
Fault recorder
6
Chaper 1 introduction
Description
Communication protocols
Functions
Setting
IED testing
IED configuration
Printing
7
Chaper 2 General IED application
8
Chaper 2 General IED application
The analog display includes measured Ia, Ib, Ic, 3I0, Is0, Ua, Ub, Uc, U4,
Mea Ia, Mea Ib, Mea Ic, Mea Ua, Mea Ub, Mea Uc, Mea Uab, Mea Ubc
and Mea Uca.
The Mea means that the measurement analogue quantity, for example,
Mea Ia, means the measurement current for phase A.
The menu dispaly includes main menu and debugging menu, see chapter
Chapter 27 for detail.
9
Chaper 2 General IED application
2 Report record
The report record includes tripping, alarm and operation reports. See
Chapter 28 general report list for detail.
3 Disturbance recorder
3.1 Introduction
To get fast, complete and reliable information about fault current, voltage,
binary signal and other disturbances in the power system is very important.
This is accomplished by the disturbance recorder function and facilitates a
better understanding of the behavior of the power system and related
primary and secondary equipment during and after a disturbance. An
analysis of the recorded data provides valuable information that can be
used to explain a disturbance, basis for change of IED setting plan,
improvement of existing equipment etc.
The IED can save the latest 40 fault records in case of power
disconnection, which can be read via the IED operation interface or
communication port. The fault record consists of the following information:
Operation setting
10
Chaper 2 General IED application
Recording function is used to capture the analog data and status data on
the amount of predefined length before or after an event, reappearing the
protection device running track events before or after the change of status
apparatus, internal logic element and the switches can be used to trigger
recording function. Recorder contain analog channel, digital channel
(binary input/output, protection element status and etc.) and time
sequence information.Device can be record 40 points per cycle, each
recordingtotal length up to 10s, and it can save 8 recent protection
operation informationand 5 protection pickup information, total of 13 times
recorders. Recording can be read through CSC-200 software tools from
the device Ethernet port (COMTRADE universal format), also through the
station communication network upload to engineer station, for the analysis
of protection operation.
IED real time monitor to record the operation event, alarm event, binary
input, binary output and function on or off, these state changes information
total 256, record of events time, causes and current status, and it will
transfer to the station control centerby the communication port. Device can
save the recent startup and operation event, and it canprint drawings
through the HMI or export electronic files by software tool of CSC-200.
Fault wave recorder with great capacity, can record full process of any fault,
and can save the corresponding records. Optional data format or wave
format is provided, and can be exported through serial port or Ethernet port
by COMTRADE format.
4 Self-supervision function
4.1 Introduction
The IED can be self diagnosis and self monitoring operation is achieved by
means of soft hardware self-test and monitoring, to ensure the high
reliability of operation through the Power on. Self check includes the key
components of hardware (such as analog input , Binary output, RAM,
ROM), hardware assisted components (such as communication interface)
and the important operating parameters (such as the set value, the soft
switching plate), in addition, device built in two level software monitor
which is used to monitor the operation conditions of the software. When
the device detectsany is abnormal, it will record the corresponding
abnormal events and drive the related signal node and the LED indicating
lamp, for the key abnormal, device will lock protection function and
important binary output , to prevente misoperation.
Users can also check the hardware by use the device that it is provide
inspection device, such as AC circuit, binary input and binary outp , and so
on.
12
Chaper 2 General IED application
14
Chaper 2 General IED application
5.1 Introduction
Time definitions
The error of a clock is the difference between the actual time of the clock,
and the time the clock is intended to have. The rate accuracy of a clock is
normally called the clock accuracy and means how much the error
increases, i.e. how much the clock gains or loses time. A disciplined clock
is a clock that “knows” its own faults and tries to compensate for them, i.e.
a trained clock.
Synchronization principle
The built in GPS clock module receives and decodes time information from
the global positioning system. The module is located on the CPU Module.
The GPS interfaces to the IED supply two possible synchronization
methods, IRIGB and PPS (or PPM).
The IED accepts PPS or PPM to the GPS interfaces on the CPU Module.
These pulses can be generated from e.g. station master clock. If the
station master clock is not synchronized from a world wide source, time will
be a relative time valid for the substation. Both positive and negative edges
on the signal can be accepted. This signal is also considered as a fine
signal.
16
Chaper 2 General IED application
6 Setting
6.1 Introduction
Settings are divided into separate lists according to different functions. The
setting consists of two parts -setting list and communication parameters.
The setting procedure can be ended at any the time by the key “SET” or
“QUIT”. If the key “SET” is pressed, the display shows the content of
“Select”. The range of setting zone is from 1 to 16. After confirming with the
setting zone-key “SET”, those new settings will be valid. If key “QUIT” is
pressed instead, all modifications which have been changed will be
ignored.
17
Chaper 2 General IED application
7 Authorization
To safeguard the interests of customers, both the IED and the tools that
are accessing the IED are protected, subject of authorization handling. The
concept of authorization, as it is implemented in the IED and the
associated tools is based on the following facts:
There are different levels (or types) of guest, super user and
protectionengineerthat can access or operate different areasof the
IED and tools functionality.
18
Chaper 3 Over current protection
19
Chaper 3 Over current protection
1 Overcurrent protection
1.1 Introduction
Overcurrent have four stages, 1st stage is definite time stage, 2nd , 3rd
and 4th stages can be set definite or inverse time stage by control
word “OC2 Inv On” “OC3 Inv On” and “OC4 Inv On” .
20
Chaper 3 Over current protection
Overcurrent have four stages, 1st stage is definite time stage, 2nd 3rd and 4th
stages can be set definite or inverse time stage by control word “OC2 Inv
On” “OC3 Inv On” and “OC4 Inv On”
Each stage can operate in conjunction with the integrated inrush restraint
and directional functions and operate based on measured phase current.In
addition, an undervoltage control feature is provided which can be used for
definite overcurrent stages.
Pickup value for the definite stage can be set in setting value. Each phase
current is compared with the corresponding setting value with delay time. If
currents exceed the associated pickup value, after expiry of the time delay,
the trip command or alarm signal is issued.The dropout value of the
definite stages is approximately equal to the system setting “High Relay
Ret”of the pickup value for I/In ≥ 0.5. The condition for delay time starting is
expressed in the following formula:
IΦ > Iset (Φ = a, b, c)
Equation 3-1
The delay time can be set for each definite stage individually in setting.
After the delay time elapsed, a trip command or alarm signal is issued.
For the delay time of inverse time characteristic, which is calculated here
based on the type of the set characteristic, the magnitude of the current
and a time multiplier, both ANSI and IEC based standard curves are
available, and any user-defined characteristic can be defined using
following formula:
= ( )K_OC
( )
Equation 3-2
21
Chaper 3 Over current protection
where:
22
Chaper 3 Over current protection
The protection IED may detect large magnetizing inrush currents during
transformer energizing. In addition to considerable unbalance fundamental
current, inrush current comprises large second harmonic current which
does not appear in short circuit current. Therefore, the inrush current may
affect the protection functions which operate based on the fundamental
component of the measured current. Accordingly, inrush restraint logic is
provided to prevent overcurrent protection from maloperation.
The inrush restraint function has a maximum inrush current setting. Once
the measuring current exceeds the setting, the overcurrent protection will
not be blocked any longer.
The logic of inverse time don’t judge undervoltage component when 2nd 3rd
and 4thstages set inverse time
23
Chaper 3 Over current protection
Table 3-2 Voltage and current measurement used for direction determination
A Ia U bc
B Ib U ca
C Ic U ab
As can be seen from Table 3-2, the healthy voltages are used in direction
determination. This allows for a correct direction determination even if the
fault voltage has collapsed entirely because of a single-phase short-line
fault. With three-phase short-line faults, memory voltage values from three
last cycles are used to clearly determine the direction, if the magnitudes of
24
Chaper 3 Over current protection
Forward 90° IA
Bisector
Φ
0°
U BC_Ref
5°
-IA
25
Chaper 3 Over current protection
90° IA
Bisector
Reverse
Φ
0°
U BC_Ref
-IA 5°
where:
26
Chaper 3 Over current protection
Ib2/Ib1 > OR
t<
Cross BLK
Cross BLK
Cross BLK
27
Chaper 3 Over current protection
{Uab,Ubc,Uca}Min<
1Ph V Connect & OC1_V Blk On
MV For OC 1
U_OC UnBlk>0
OC2_V Blk On
MV For OC 2
{Uab,Ubc,Uca}Max< & ≥
OC2_V Blk On
1Ph V Connect MV For OC 3
OC32_V Blk On
U2> MV For OC 4
1Ph V Connect &
U2_OC UnBlk>0
Ia >
VT Fail
&
Blk Fun_VTFail
&
&
VT Fail
≥
Phase A Forward
&
OC1 Dir On ≥ & DEF A OK
≥
OC1 Dir On &
MV For OC 1
& OC1 Dir On
OC1_V Blk On ≥ &
OC1_V Blk On
OC1_V Blk On
OC1 2H_Blk On
≥
< I_2H_UnBlk
&
Ia2/Ia1>
DEF A OK T Func_OC1
BI_Blk OC1 & Trip/Alarm
Cross BLK
&
OC1 2H_Blk On
≥
28
Chaper 3 Over current protection
Ia Inverse
VT Fail
&
Blk Fun_VTFail
&
&
VT Fail
≥
Phase A Forward
&
OC2 Dir On ≥ & INV A OK
≥
OC2 Dir On
OC2 Dir On
OC2 2H_Blk On
≥
< I_2H_UnBlk
&
Ia2/Ia1>
INV A OK Func_OC2
& Trip/Alarm
Cross BLK
&
OC2 2H_Blk On
≥
IP1 OC1_Trip
IP2 OC2_Trip/Alarm
IP3
OC3_Trip/Alarm
UP1
OC4_Trip/Alarm
UP2
UP3
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
IP3 Signal for current input 3
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
29
Chaper 3 Over current protection
Signal Description
OC1_Trip Overcurrent protection stage 1 trip
OC2_Trip Overcurrent protection stage 2 trip
OC3_Trip Overcurrent protection stage3 trip
OC4_Trip Overcurrent protection stage4 trip
OC2 Alarm Overcurrent protection stage 2alarm
OC3 Alarm Overcurrent protection stage 3alarm
OC4 Alarm Overcurrent protection stage 4alarm
30
Chaper 3 Over current protection
2: IEC VI
3: IEC EI
4: IEC LTI
5: ANSI MI
6: ANSI VI
7: ANSI EI
8:ANSI INV
9:ANSI SI
10:ANSI LI
11:ANSI DI
10 K_OC3 Inv 0.025~1.5
Overcurrent setting for
11 I_OC4 0.05~100 A
stage 4
Overcurrent Time setting
12 T_OC4 0.00~100.00 s
for stage4
0: Defined by user
1:IEC NI
2: IEC VI
3: IEC EI
4: IEC LTI
5: ANSI MI
13 OC4 Inv CRV SEL 0~11
6: ANSI VI
7: ANSI EI
8:ANSI INV
9:ANSI SI
10:ANSI LI
11:ANSI DI
14 A_OC4 Inv 0.001~1000 s
15 P_OC4 Inv 0.01~10.00
Inverse characteristic
16 B_OC4 Inv 0.000~60.00 s
17 K_OC4Inv 0.025~1.5
Low voltage blocking for
18 U_OC_UnBlk 1.00~120.0 V
Overcurrent.
19 U2_OC_UnBlk 1.00~120.0 V
Overcurrent setting for
20 Angle_OC 0.00~90.00 degree
directional element
21 I_2H_UnBlk 0.05~100 A
22 Ratio_I2/I1 0.07~0.50
31
Chaper 3 Over current protection
32
Chaper 3 Over current protection
1-On;0-Off.
Direction toward for overcurrent stage
17 OC4 Dir FWD 1/0 0
4. 1-Forward; 0-Reverse.
Low voltage blocking for overcurrent
18 OC4 VBlk On 1/0 0
stage 4. 1-On; 0-Off.
Low voltage blocking for overcurrent
19 OC4 2H_Blk On 1/0 0
stage4 Inverse. 1-On; 0-Off.
Select the overcurrent stage 2 trip or
20 OC2 Trip On 1/0 0
alarm. 1-Trip; 0-Alarm.
Select the overcurrent stage 3 trip or
21 OC3 Trip On 1/0 0
alarm. 1-Trip; 0-Alarm.
Select the overcurrent stage 4 trip or
22 OC4 Trip On 1/0 0
alarm. 1-Trip; 0-Alarm.
1.5 Reports
Information Description
OC1 Trip Overcurrent protection stage 1 issues trip command
OC2 Trip Overcurrent protection stage 2 issues trip command
OC3 Trip Overcurrent protection stage 3 issues trip command
OC4 Trip Overcurrent protection stage 4 issues trip command
Information Description
OC2 Alarm Overcurrent protection stage 2issues alarm signal
OC3 Alarm Overcurrent protection stage 3 issues alarm signal
OC4 Alarm Overcurrent protection stage 4 issues alarm signal
OC Inrush Blk Inrush is detected to block function.
33
Chaper 3 Over current protection
Long inverse
ANSI Inverse; ≤ ±5% setting + 40ms, at 2
Short inverse; <I/ISETTING < 20, in
with IEC60255-151
Time factor of inverse time, A 0.005 to 200.0s, step 0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
set time Multiplier for step n: k 0.05 to 999.0, step 0.01
Minimum operating time 20ms
Maximum operating time 100s
Reset mode instantaneous
Reset time approx. 40ms,
Directional element
Operating area range ≤ ±3°, at phase to phase
Characteristic angle 0°to 90°, step 1° voltage >1V
34
Chapter 4 Earth fault protection
35
Chapter 4 Earth fault protection
1.1 Introduction
Earth fault protection have four stages, 1st stage is definite time stage, 2nd ,
3rd , and 4th stages can be set definite or inverse time stage by control
word “EF2 Inv On” “EF3 Inv On” and “EF4 Inv On” .
The second,third and fourth stage can be set individually to alarm or trip
Earth fault protection have four stages, 1st stage is definite time stage, 2 nd 3rd
and 4th stages can be set definite or inverse time stage by control word “EF2
Inv On” “EF3 Inv On” and “EF4 Inv On”
Each stage can operate in conjunction with the integrated inrush restraint and
directional functions and operate based on measured phase current
The earth fault protection can operate with the measured or calculated zero
sequence current (zero-sequence current IN measured from earth phase CT
or zero-sequence current 3I0 calculated by the summation of three phase
currents, 3I0=IA+IB+IC). These two types of measured quantity can be enabled
or disabled via binary setting”EF 3I0 Calculated”. If setting “EF 3I0 Calculated”
is set as “0”, the function will operate based on the measured zero-sequence
current, whereas, the “EF 3I0 Calculated”is set as “1”, the zero-sequence
current is calculated from the summation of three phase currents.
Pickup value for the definite stage can be set in setting value. The measured
or calculated zero-sequence current is compared with the corresponding
setting value with delay time. If zero-sequence current exceed the associated
pickup value, after expiry of the time delay, trip command is issued. The
condition for delay time start is expressed in the following formula
Equation 4-1
The time delay can be set for each definite stage individually in setting. After
the delay time elapsed, trip command or alarm signal is issued. The drop out
value of the definite stages is approximately equal to the system setting “High
Relay Ret” of the pickup value for 3I0/In≥0.5.
The time delay of inverse time characteristic is calculated based on the type
37
Chapter 4 Earth fault protection
of the set characteristic, the magnitude of the current and a time multiplier.
For the inverse time characteristic, both ANSI and IEC based standard curves
are available, and any user-defined characteristic can be defined using the
following equation:
= ( E )K_EF
( )
E
Equation 4-2
where:
The time is set to count up for a user-defined time delay. The time delay can
be set for each definite stage individually through corresponding settings.
After the user-defined time delays elapsed, a trip command is issued.
The protection IED may detect large magnetizing inrush currents during
transformer energizing. In addition to considerable unbalance fundamental
current, inrush current comprises large second harmonic current which does
not appear in short circuit current. Therefore, the inrush current may affect the
protection functions which operate based on the fundamental component of
the measured current. Accordingly, inrush restraint logic is provided to
prevent earth fault protection from maloperation.
The integrated earth fault protection may detect large magnetizing inrush
currents when a power transformer installed at downstream path is energized.
The inrush current may be several times of the nominal current, and may last
from several tens of milliseconds to several seconds. Inrush current
comprises second harmonic as well as a considerable fundamental
component. It is possible to apply the inrush restraint feature separately to
each definite stage and inverse time-current stage of earth fault element by
38
Chapter 4 Earth fault protection
using binary setting “EF1 2H_Blk On”, “EF2 2H_Blk On” , “EF3 2H_Blk On”
and “EF4 2H_Blk On”. By applying setting “1” to each of the mentioned binary
setting, no trip command or alarm signal would be possible by corresponding
stage, if an inrush condition is detected. Since the inrush current contains a
relatively large second harmonic component which is nearly absent in fault
current, the inrush restraint operates based on the evaluation of the second
harmonic content which is present in the phase currents.
Generally, inrush restraint for earth fault protection is performed based on the
second harmonic contents of three phase currents. However, it is possible to
use the IED only for earth fault protection and therefore, the phase currents
may be not connected to the IED. In such cases, if the binary setting of “EF
Chk I02/I01” is set as “1”, second harmonic content of zero sequence current
is considered if the zero sequence current is measured from neutral CT. As
mentioned previously, the binary setting of “3I0 Measured” is enabled for this
situation. So, the inrush condition is recognized if the ratio of second
harmonic content of measured zero sequence current to its fundamental
component exceeds corresponding setting value.
On the contrary, if binary setting of “EF Chk I02/I01” is set as “0”, the inrush
condition is recognized if the ratio of second harmonic content in each phase
current to their fundamental component exceeds setting value.
39
Chapter 4 Earth fault protection
Figure 4-1.
40
Chapter 4 Earth fault protection
3I 0 90°
10°
0°
3U 0_Ref
Φ0
Forward Bisector
-3 I 0
3I 0 90°
Reverse
10°
0°
3U 0_Ref
Φ0
Bisector
-3 I 0
where:
The fault current -3I2 is in phase opposition to the fault current 3I2 and lags
from the voltage 3V2 by the fault angle Φ2. To satisfy different applications, the
reference voltage can be rotated by adjustable angle between 0°and 90°in
clockwise direction (negative sign) to be closely adjusted to the vector of fault
current -3I2. This would provide the best detection result for direction
determination. The rotated reference voltage defines the forward and reverse
area. The forward area is in range of ±80°around the rotated reference
voltage. If the vector of fault current -3I2 is in this area, the fault condition is
detected as forward direction. The negative sequence direction detection
characteristic is shown in
Figure .
42
Chapter 4 Earth fault protection
3I 2 90°
10°
0°
3U 2-Ref
Φ0
Forward Bisector
-3 I 2
3I 2 90°
Reverse
10°
0°
3U 2-Ref
Φ2
Bisector
-3 I 2
where:
43
Chapter 4 Earth fault protection
I02/I01 >
Figure 4-3 Logic diagram for inrush restraint based on measured zero sequence current
Max(Ia1,Ib1,Ic1) >I_2H_UnBlk
Ia2/Ia1 >
Ib2/Ib1 > ≥
Ic2/Ic1 >
Figure 4-4 Logic diagram for inrush restraint based on based on phase currents
44
Chapter 4 Earth fault protection
Blk Fun_VTFail
&
VT Fail ≥
&
Blk Fun_VTFail
&
U0/I0-φ
3U0>2V
≥
& Forward/Reverse
U2/I2-φ
& &
EF U2/I2 Dir
EF 3I0 Calculated
Blk Fun_VTFail
&
≥
VT Fail &
&
Blk Fun_VTFail
Blk Fun_VTFail
&
V1p VT Fail ≥
&
Blk Fun_VTFail
&
U0/I0-φ
3U0>2V
≥
& Forward/Reverse
U2/I2-φ
& &
EF U2/I2 Dir
EF 3I0 Calculated
Blk Fun_VTFail
&
≥
V1p VT Fail &
&
Blk Fun_VTFail
3I0 >
BI_Blk EF1
EF1 Dir On
≥
&
Forward/Reverse
Figure 4-6 Logic diagram for first definite stage of earth fault protection
45
Chapter 4 Earth fault protection
3I0 Inverse
BI_Blk EF2
EF2 Dir On
≥
Forward/Reverse &
Figure 4-7 Logic diagram for inverse time stage of earth fault protection
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
IP3 Signal for current input 3
IP0 Signal for current input 0
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
UP0 Signal for voltage input 0
Signal Description
EF1 Trip Earth fault protection stage 1 trip
EF2 Trip Earth fault protection stage 2 trip
EF3 Trip Earth fault protection stage 3 trip
EF4 Trip Earth fault protection stage 4 trip
EF2 Alarm Earth fault protection stage 2alarm
EF3 Alarm Earth fault protection stage 3 alarm
EF4 Alarm Earth fault protection stage 4alarm
46
Chapter 4 Earth fault protection
47
Chapter 4 Earth fault protection
48
Chapter 4 Earth fault protection
1-Calculated; 0-Measured.
Select the Earth fault stage 2 trip or
21. EF2 Trip On 1/0 0
alarm. 1-Trip; 0-Alarm.
Select the Earth fault stage 3 trip or
22. EF3 Trip On 1/0 0
alarm. 1-Trip; 0-Alarm.
Select the Earth fault stage 1 trip or
23. EF4 Trip On 1/0 0
alarm. 1-Trip; 0-Alarm.
Information Description
EF1 Trip Earth fault protection stage 1 issues trip command
EF2 Trip Earth fault protection stage 2 issues trip command
EF3 Trip Earth fault protection stage 3 issues trip command
EF4 Trip Earth fault protection stage 4 issues trip command
Information Description
EF2Alarm Earth fault protection stage 2issues an alarm signal
EF3 Alarm Earth fault protection stage 3 issues an alarm signal
EF4 Alarm Earth fault protection stage 4 issues an alarm signal
EF Inrush Blk Inrush is detected to block function.
50
Chapter 4 Earth fault protection
Long inverse
ANSI Inverse; ANSI/IEEE C37.112,
Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic IEC60255-151
T=( )k
( )P ≤ ±5% setting + 40ms, at 2
SET
<I/ISETTING< 20
Time factor of inverse time, A 0.005 to 200.0s, step
0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
set time Multiplier for step n: k 0.05 to 999.0, step 0.01
Minimum operating time 20ms
Maximum operating time 100s
Reset mode instantaneous
Reset time approx. 40ms
Directional element
Operating area range of zero ≤ ±3°, at 3U0≥1V
sequence directional element
Characteristic angle 0°to 90°, step 1°
Operating area range of negative ≤ ±3°, at 3U2≥2V
sequence directional element
Characteristic angle 50°to 90°, step 1°
51
Chapter 5 Sensitive earth fault protection
52
Chapter 5 Sensitive earth fault protection
1.1 Introduction
In networks with high impedance earthing, the phase to earth fault current is
significantly smaller than load current and phase to phase short circuit currents.
Another difficulty for earth fault protection is that the magnitude of the phase to
earth fault current is almost independent of the fault location in the network.
Sensitive earth fault protection can be used to detect and give selective trip of
phase to earth faults in isolated or compensated networks. The protection
function also can be applied to detect high impedance earth faults in solidly or
low-resistance earthed networks.
Sensitive earth fault protection integrated in the IED provides following features:
Sensitive overcurrent have four stages, 1st stage is definite time stage, 2nd
3rd and 4th stages can be set definite or inverse time stage by control word
“SEF2 Inv On” “SEF3Inv On” and “SEF4 Inv On”.
11 kinds of IEC and ANSI inverse time characteristic curves as the standard
curves for 2ndand 3rdstages. And the standard curves as well as optional
user defined characteristic for 4thstage.
The second, third and fourth can be set individually to alarm or trip
Dedicated sensitive CT
Sensitive overcurrent have four stages, 1st stage is definite time stage, 2nd 3rd
53
Chapter 5 Sensitive earth fault protection
and 4th stages can be set definite or inverse time stage by control word “SEF2
Inv On” “SEF3Inv On” and “SEF4 Inv On”
Each stage can operate in conjunction with the integrated directional functions
and operate based on measured phase current which is injected from the
dedicated sensitive current transformer.
Furthermore, each stage is independent from each other and can be combined
as desired.
Pickup value for the definite stage can be set in setting value. The measured
current from sensitive CT input is compared with the corresponding setting value
with delay time. If the measured current exceeds the associated pickup value,
after expiry of the time delay, the trip command or alarm signal is issued. The
dropout value of the definite stages is approximately equal to the system setting
“High Relay Ret”.
The time delay of inverse time characteristic is calculated based on the type of
the set characteristic, the magnitude of the current and a time multiplier. For the
inverse time characteristic, both ANSI and IEC based standard curves are
available, and any user-defined characteristic can be defined using the following
equation:
= ( SE )K_SEF
( )
SE
Equation 5-1
where:
54
Chapter 5 Sensitive earth fault protection
55
Chapter 5 Sensitive earth fault protection
Contrary to the directional phase elements, which work with the un-faulted
voltage as reference voltage, the fault voltage itself is the reference voltage for
the directional sensitive earth fault protection. Depending on the connection of
voltage transformer (setting “SEF 3U0 Calculated”), the setting “0” or “1” is
corresponding to voltage U4 or 3U0 (3U0=VA+VB+VC).
56
Chapter 5 Sensitive earth fault protection
90°
Forward
10°
- I NS
Bisector
Φd 0°
3U0_Ref
I NS
90°
- I NS
10°
Bisector
Φd 0°
3U0_Ref
Reverse
I NS
Figure 5-1 Direction detection characteristic of the sensitive earth fault directional
element by U0/I0-Φ
where:
ФNS: The settable characteristic angle
57
Chapter 5 Sensitive earth fault protection
voltage defines the forward and reverse area. The forward area is in range of
±80°around the rotated reference voltage. If the vector of the fault current -Is is
in this area, the device detects forward direction. Figure 5-1 shows an example
of direction determination. As can be seen from the figure, fault current -Is leads
residual sequence voltage 3U0 by Φd, which is the setting value of “Angle_SEF”.
The reference voltage 3V0 is rotated by this angle to be closely matched to -IS
current. Furthermore, the forward area is depicted in the figure.
58
Chapter 5 Sensitive earth fault protection
IS 90°
Forward 0°
3U0_Ref
- IS
IS 90°
Reverse 0°
3U0_Ref
- IS
Figure 5-2 Direction detection characteristic of the sensitive earth fault directional
element by Cos Φ
U0/I0-φ
3U0> & Forward/Reverse
SEF Chk U0/I0
Figure 5-3 Logic diagram for direction determination based on U0/I0-Φ measurement
59
Chapter 5 Sensitive earth fault protection
IsCOSφ
3U0> & Forward/Reverse
SEF Chk U0/I0
Figure 5-4 Logic diagram for direction determination based on Cos Φ measurement
VT Fail
&
Blk Fun_VTFail
≥
&
VT Fail &
Forward/Reverse
≥ Forward/Reverse Release
3U0 Calculated
Forward/Reverse
VT Fail &
Blk Fun_VTFail
≥
&
&
VT Fail
Figure 5-5 Influence of VT failure on direction determination of sensitive earth fault protection
Is >
Func_SEF1
BI_Blk SEF1 & T Trip/Alarm
SEF1 Dir On
≥
&
Forward/ Reverse Release
Figure 5-6 Logic diagram for the first definite stage of sensitive earth fault protection
Is Inverse
Func_SEF2
BI_Blk SEF1 & Trip/Alarm
SEF2 Dir On
≥
Forward/ Reverse Release &
Figure 5-7 Logic diagram for the inverse time stage of sensitive earth fault protection
IS SEF1 Trip
UP1 SEF2 Trip/ Alarm
UP2 SEF3 Trip/ Alarm
UP3 SEF4 Trip/ Alarm
60
Chapter 5 Sensitive earth fault protection
Signal Description
Is Signal for sensitive current input
UP1 Signal for voltage input 2
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
Signal Description
SEF1 Trip Sensitive earth fault protection stage 1 trip
SEF2 Trip Sensitive earth fault protection stage 2 trip
SEF3 Trip Sensitive earth fault protection stage 3 trip
SEF4 Trip Sensitive earth fault protection stage 4 trip
SEF2 Alarm Sensitive earth fault protection stage 2 alarm
SEF3 Alarm Sensitive earth fault protection stage 3alarm
SEF4 Alarm Sensitive earth fault protection stage 4alarm
Table 5-3 Function setting list for sensitive earth fault protection
11:ANSI DI
20 U_3V0_SEF 2.00~100.0 V
Table 5-4 Logical linker list for sensitive earth fault protection
Table 5-5 Binary setting list for sensitive earth fault protection
63
Chapter 5 Sensitive earth fault protection
Information Description
SEF1 Trip Sensitive earth fault protection stage 1 issues trip command
SEF2 Trip Sensitive earth fault protection stage 2 issues trip command
SEF3 Trip Sensitive earth fault protection stage 3 issues trip command
SEF4 Trip Sensitive earth fault protection stage 4 issues trip command
Information Description
SEF2Alarm Sensitive earth fault protection stage 2issues an alarm signal
SEF3 Alarm Sensitive earth fault protection stage 3issues an alarm signal
SEF4 Alarm Sensitive earth fault protection stage 4 issues an alarm signal
Long inverse
ANSI Inverse; ≤ ±5% setting + 40ms, at 2
Short inverse; <I/ISETTING < 20, in
64
Chapter 5 Sensitive earth fault protection
Very inverse;
Extremely inverse;
Definite inverse
user-defined characteristic ≤ ±5% setting + 40ms, at 2
T=( )k <I/ISETTING< 20, in accordance
( )P
SET
with IEC60255-151
Time factor of inverse time, A 0.005 to 200.0s, step 0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
set time Multiplier for step n: k 0.05 to 999.0, step 0.01
Minimum operating time 20ms
Maximum operating time 100s
Reset mode instantaneous
Reset time approx. 40ms
Directional element for sensitive earth-fault protection
principles I cos Φ
Φ (V0 / I0)”
Direction measurement IE and VE measured
or 3V0 calculated
3U0 Minimum voltage threshold 2.00 to 100.00 V, step 0.01 V ≤ ±3 % setting for measured
voltage;
≤ ±5 % setting for calculated
voltage
Characteristic angle Φ_SEFChar 0.0°to 90.0°, step 1° ≤ ±3°
Operating area range ≤ ±3°
65
Chapter 6 Negative-sequence overcurrent protection
Chapter 6 Negative-sequence
overcurrent protection
66
Chapter 6 Negative-sequence overcurrent protection
1 Negative-sequence overcurrent
protection
1.1 Introduction
Equation 6-1
67
Chapter 6 Negative-sequence overcurrent protection
Individual pickup value for each definite stage can be set in setting value.
The calculated negative sequence current from Equation -1 is compared
separately with the corresponding setting value with delay time. If the
calculated negative-sequence current exceeds the associated pickup value,
after expiry of the time delay, the trip command or alarm signal is issued.
The drop out value of the definite stages is approximately equal to the
system setting “High Relay Ret” of the pickup value for I/In≥0.5.
The time delay of inverse time characteristic is calculated based on the type
of the set characteristic, the magnitude of the current and a time multiplier.
For the inverse time characteristic, both ANSI and IEC based standard curves
are available and any user-defined characteristic can be defined using the
following equation:
= ( S )K_NSOC
( )
S
Equation 6-2
where:
68
Chapter 6 Negative-sequence overcurrent protection
CT Fail
Func_NSOC1 On T1 NSOC1 Trip
&
I2 > I2_NSOC1
BI_Blk NSOC1
Func_NSOC2 On
T2 NSOC2
&
I2 > I2_NSOC2 Trip/Alarm
BI_Blk NSOC2
Func_NSOC3 On
T3 NSOC3
&
I2 > I2_NSOC3 Trip/Alarm
BI_Blk NSOC3
Func_NSOC4 On T4 NSOC4
& Trip/Alarm
I2 > I2_NSOC4
BI_Blk NSOC4
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
IP3 Signal for current input 3
69
Chapter 6 Negative-sequence overcurrent protection
Signal Description
NSOC1 Trip Negative sequence overcurrent protection stage 1 trip
NSOC2Trip Negative sequence overcurrent protection stage 2 trip
NSOC3Trip Negative sequence overcurrent protection stage 3trip
NSOC4 Trip Negative sequence overcurrent protection stage 4 trip
NSOC2 Alarm Negative sequence overcurrent protection stage 2 alarm
NSOC3 Alarm Negative sequence overcurrent protection stage 3 alarm
NSOC4 Alarm Negative sequence overcurrent protection stage 4 alarm
6: ANSI VI
7: ANSI EI
8:ANSI INV
9:ANSI SI
10:ANSI LI
11:ANSI DI
10 K_NSOC3 Inv 0.025~1.5
11 I2_NSOC4 0.05~100.00 A Earth fault current setting for stage 3
12 T_NSOC4 0.00~100.00 s Earth fault Time setting for stage3
0: Defined by user
1:IEC NI
2: IEC VI
3: IEC EI
4: IEC LTI
NSOC4 Inv CRV 5: ANSI MI
13 0~11
SEL 6: ANSI VI
7: ANSI EI
8:ANSI INV
9:ANSI SI
10:ANSI LI
11:ANSI DI
14 A_NSOC4 Inv 0.001~1000 s
15 P_NSOC4 Inv 0.01~10.00 Inverse characteristic
16 B_NSOC4 Inv 0.000~100.00 s
17 K_NSOC4 Inv 0.025~1.5
71
Chapter 6 Negative-sequence overcurrent protection
Information Description
NSOC1 Trip Negative sequence current protection stage 1 issues trip command
NSOC2 Trip Negative sequence current protection stage 2 issues trip command
NSOC3 Trip Negative sequence current protection stage 3 issues trip command
NSOC4 Trip Negative sequence current protection stage 4 issues trip command
Information Description
NSOC2Alarm Negative sequence current protection stage 2issues an alarm signal
NSOC3 Alarm Negative sequence current protection stage 3 issues an alarm signal
NSOC4 Alarm Negative sequence current protection stage 4 issues an alarm signal
72
Chapter 6 Negative-sequence overcurrent protection
Long inverse
ANSI Inverse; ≤ ±5% setting + 40ms, at 2
with IEC60255-151
Time factor of inverse time, A 0.005 to 200.0s, step 0.001s
Delay of inverse time, B 0.000 to 60.00s, step 0.01s
Index of inverse time, P 0.005 to 10.00, step 0.005
set time Multiplier for step n: k 0.05 to 999.0, step 0.01
Minimum operating time 20ms
Maximum operating time 100s
Reset time approx. 40ms
73
Chapter 7 Thermal overload protection
74
Chapter 7 Thermal overload protection
1.1 Introduction
The IED calculates the temperature rise of the protected equipment in each
phase, based on following differential equation:
𝑑𝛩 𝐼 2
τ Θ =( )
𝑑𝑡 𝐼𝜗
Equation 7-1
where:
τ:is thermal time constant of heating for the protected object, in seconds. It is usually
75
Chapter 7 Thermal overload protection
I: is the measured fundamental current flowing through each phase of the protected
object.
Θ: is temperature rise of the protected object in per unit of the final temperature rise
at maximum allowed phase currentIϑ .
𝐼 2 𝐼 2
( ) − ( 𝑃)
𝐼
𝜗 𝐼 𝜗
= τ ln [ 2 ]
𝐼
( ) − 1
𝐼 𝜗
Equation 7-2
where:
𝐼 2
( )
𝐼𝜗
= τ ln [ ]
𝐼 2
( ) − 1
𝐼 𝜗
Equation 7-3
From the Equation 7.2 and Equation 7-3 can be seen, the cold curve
provides no memory regarding to previous thermal condition of the protected
object, hereas, by using the hot curve, the protection function is able to
represent a memorized thermal profile of the protected object. Thermal will be
resetby binary input, when binary input value is "1" , the thermal
accumulationis reset, the thermal accumulated calculation formula is
76
Chapter 7 Thermal overload protection
Signal Description
IP1 Signal for current input 1
IP2 Signal for current input 2
IP3 Signal for current input 3
Signal Description
Thermal OL Trip Thermal overload protection trip
Thermal OL Alarm Thermal overload protection alarm
1 I_Therm OL 0.10~10.00 A
2 T_Const Therm 6~9999 S
3 Ratio_Cool 0.1~10
4 Ratio_Alarm 0.5~1
77
Chapter 7 Thermal overload protection
Information Description
Therm OL Trip Thermal overload protection issues trip command
Information Description
Therm OL Alarm Thermal overload protection issues an alarm signal
I eq2
IEC cold curve t ln 2 2
IEC 60255–8,
I eq I ≤ ±5% setting or +40ms
I eq2 I P2
IEC hot curve t ln 2 2
IEC 60255–8,
I eq I ≤ ±5% setting or +40ms
78
Chapter 8 Switch on to faulty
79
Chapter 8 Switch on to faulty
1.1 Introduction
Through measuring the current value in a time with MCB close, the protection
switch to faulty issures the line whether being fault or not. When the control
word SOTF Chk MC is On is be on, and in the time of T_MC Chk Fault the
rising edge of coming of input BI_MC begins to time, the 3-pahse current in
higher than I_SOTF or the measured earth current is higher than 3 I0_SOTF,
the relay operates. The input BI_MC can be defined by users in the LOGIC
file. When the input BI_MC is be set 1 for more than 10s, the relay will alarm
and show the report MC Error.
While the control word SOTF Chk CB On is be on, after conforming the CB
positing going by the relay time T_SOTF Chk CB, and 3-phase current is
higer than the setting I_SOTF or the measured earth current is more than 3
I0_SOTF, the relay operates.
80
Chapter 8 Switch on to faulty
10s
BI MC
& &
SOTF Chk MC On &
T_MC Chk Fault
SOTF Chk CB On
≥ CB Status
&
TWJ
T_SOTF Chk CB
&
HWJ
CB Status
BI_Blk SOTF
& 40ms SOTF OC Trip
Func_SOTF
Ia2/Ia1 >
Ib2/Ib1 > ≥
Ic2/Ic1 >
Ia2/Ia1 >
Ib2/Ib1 > ≥ &
Ic2/Ic1 >
Calculated 3I0>“3I0_SOTF”
BI_Blk SOTF
& 40ms SOTF EF Trip
Func_SOTF
CB Status
Signal Description
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
81
Chapter 8 Switch on to faulty
Signal Description
SOTF OC Trip SOTF protection OC stage Trip
SOTF EF Trip SOTF protection EF stage Trip
1 I_SOTF 0.05~10 A
2 3I0_SOTF 0.05~10 A
3 T_SOTF Chk CB 0~100 s
Information Description
SOTF OC Trip SOTF OC protection issues trip command
SOTF EF Trip SOTF EF protection issues trip command
Information Description
SOTF Inrush Blk Inrush is detected to block function.
82
Chapter 8 Switch on to faulty
83
Chapter 9 Overvoltage protection
84
Chapter 9 Overvoltage protection
1 Overvoltage protection
1.1 Introduction
First stage and inverse time stage can be set to alarm or trip
The relay provide 2 stages definite time and a inverse time Overvoltage
protection. The delay time can be set for each definite stage individually in
setting. After the delay time elapsed, a trip command or alarm signal is
issued.
For the delay time of inverse time characteristic, which is calculated here
based on the type of the set characteristic, the magnitude of the current and
85
Chapter 9 Overvoltage protection
a time multiplier, both ANSI and IEC based standard curves are available,
and any user-defined characteristic can be defined using following formula:
= ( )K_OV
( )
Equation 9-1
where:
86
Chapter 9 Overvoltage protection
Overvoltage protection element provides two definite time stages and one
inverser time stage which can be enabled or disabled separately according
to the user’s requirement using dedicated binary setting “Func_OV1”,
“Func_OV2” and “Func_OV INV”. The first stage and inverse timestage can
be used for tripping or alarming, whereas the second stage is dedicated for
tripping purposes. It is possible to select the operation mode of the first
stage of overvoltage protection using binary setting “OV1 Trip” and “OV Inv
Trip” as “1”. As expected, When the setting “OV1 Trip” and “OV Inv”as
“0”makes it work as an alarming stage, while by applying “OV1 Trip” and
“OV Inv Trip” as “1”, it is possible to use the first stage as a tripping stage.
Voltage thresholds and time delays can be set individually for each element.
Overvoltage protection can operate based on phase to earth voltages VA-N,
VB-N, VC-N or phase to phase voltage VA-B, VB-C, VC-A. The IED is
informed about user’s preference by binary setting “OV PP/OV PE”. By
setting “OV PP”, calculation would be based on phase to phase voltages.
However, by setting “OV PE”, phase to ground voltages would be employed
in calculation.
A A
B B
C C
VA VA
VB VB
VC VC
VN VN
CSC-211 CSC-211
Case A Case B
A A
B B
C C
VA VA
VB VB
VC VC
VN VN
CSC-211 CSC-211
Case C Case D
87
Chapter 9 Overvoltage protection
Ua>
Ub> ≥
&
Uc> Func_OV1
≥
OV Chk PE
& T1 Trip/Alarm
Uab>
&
Ubc> ≥
BI_Blk OV1
Uca>
88
Chapter 9 Overvoltage protection
Ua>>
Ub>> ≥
&
Uc>> Func_OV2
≥
OV Chk PE
& T2 Trip/Alarm
Uab>>
&
Ubc>> ≥
BI_Blk OV2
Uca>>
Ua Inverse
Ub Inverse ≥
&
Uc Inverse Func_OV Inverse
≥
OV Chk PE
& Trip/Alarm
Uab Inverse
&
Ubc Inverse ≥
BI_Blk OV Inverse
Uca Inverse
UP1 OV1_Trip/Alarm
UP2 OV2_Trip
UP3 OV Inv Trip/Alarm
Signal Description
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
Signal Description
OV1 Alarm Overvoltage protection stage 1 alarm
OV Inv Alarm Overvoltage protection stage 2 alarm
OV1Trip Overvoltage protection stage 1 trip
OV2Trip Overvoltage protection stage 2 trip
OV Inv Trip Overvoltage protection stage 2 trip
89
Chapter 9 Overvoltage protection
1 U_OV1 40.00~200.0 V
2 T_OV1 0.00~120.00 S
3 U_OV2 40.00~200.0 V
4 T_OV2 0.00~120.00 S
Earth fault Time setting for
5 T_OV Inv 40.00~200.0 s
stage3
0: Defined by user
1:IEC NI
6 OV Inv CRV SEL 0~4 2: IEC VI
3: IEC EI
4: IEC LTI
7 A_OV Inv 0.001~1000 s Inverse characteristic
8 P_OV Inv 0.01~10.00
9 B_OV Inv 0.000~60.00 s
10 K_OV Inv 0.025~1.5
11 Dropout_OV 0.90~0.99
90
Chapter 9 Overvoltage protection
Information Description
OV1 Trip Overvoltage protection stage 1 issues trip command
OV2 Trip Overvoltage protection stage 2 issues trip command
OV Inv Trip Overvoltage protection inverse stage issues trip command
Information Description
OV1 Alarm Overvoltage protection stage 1 issues an alarm signal
OV Inv Alarm Overvoltage protection stage 1 issues an alarm signal
91
Chapter 10 Undervoltage protection
92
Chapter 10 Undervoltage protection
1 Undervoltage protection
1.1 Introduction
Undervoltage protection element provides two definite time stages which can
be enabled or disabled separately according to the user’s requirement using
dedicated binary settings “Fun_UV1” and “Fun_UV2”. The first stage can be
used for tripping or alarming, whereas the second stage is dedicated for
tripping purposes. It is possible to select the operation mode of the first stage
of undervoltage protection using binary setting “UV1 Trip On”. As expected,
setting “UV1 Trip On” set as “0” makes it work as an alarming stage, while by
applying “UV1 Trip On” set as “0”it is possible to set the first stage as a
tripping undervoltage stage. Voltage thresholds and time delays can be set
individually for each element. Thus, alarming or tripping can be
time-coordinated depending on how severe the voltage collapses are. In this
context, settings “U_UV1” and “T_UV1” correspond to the voltage threshold
and time delay of the first stage. Similarly, settings “U_UV2” and “T_UV2” are
related to the second stage. The dropout ratio for both the undervoltage
stages can be set through setting “Dropout_UV”.
93
Chapter 10 Undervoltage protection
A A
B B
C C
VA VA
VB VB
VC VC
VN VN
CSC-211 CSC-211
Case A Case B
A A
B B
C C
VA VA
VB VB
VC VC
VN VN
CSC-211 CSC-211
Case C Case D
94
Chapter 10 Undervoltage protection
95
Chapter 10 Undervoltage protection
out when circuit breaker is opened. This feature can be enabled by applying
setting “UV Chk CB On” as “1”in binary setting. This is mainly useful when
voltage transformer is installed on load side. However, if the voltage
transformer is installed on the source side and it is not desired to check circuit
breaker position in undervoltage protection, setting “UV Chk CB On” as
“0”should be applied in binary setting.
Ua <
≥
Ub < &
Uc <
UV Chk 1Ph ≥
Ua <
&
Ub < & &
Uc <
UV Chk PE
≥ UV stg1
Uab <
≥
Ubc < &
Uca < &
UV Chk 1Ph ≥
Uab <
&
Ubc < &
Uca <
Ua <<
≥
Ub << &
Uc <<
UV Chk 1Ph ≥
Ua <<
&
Ub << & &
Uc <<
UV Chk PE
≥ UV stg2
Uab <<
≥
Ubc << &
Uca << &
UV Chk 1Ph ≥
Uab <<
&
Ubc << &
Uca <<
96
Chapter 10 Undervoltage protection
UV stg1
& &
Max(Uab/Ubc/Uca)>U_UV1
T1 Trip/Alarm
1Ph V Connect T1+2s
&
Umax>U_UV1
UV Chk CB On
&
TWJ
Imax>I_Chk_UV ≥
VT fail
UV stg2
BI_Blk UV2
&
Max(Uab/Ubc/Uca)>U_UV2
& Fun_UV2
1Ph V Connect T2+2s
T2 Trip
&
Umax>U_UV2
UV Chk CB On
&
TWJ
Imax>I_Chk_UV ≥
VT fail
TWJ
97
Chapter 10 Undervoltage protection
Signal Description
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
Signal Description
TWJ Open status of CB
Signal Description
UV1 Alarm Undervoltage protection stage 1 alarm
UV1_Trip Undervoltage protection stage 1 trip
UV2_Trip Undervoltage protection stage 2 trip
1 U_UV1 5.00~150 V
2 T_UV1 0.00~120.0 S
3 U_UV2 5.00~150 V
4 T_UV2 0.00~120.0 S
5 I_Check UV 0.0~10 A
6 Dropout_UV 1.01~2.00
98
Chapter 10 Undervoltage protection
Information Description
UV1 Trip Undervoltage protection stage 1 issues trip command
UV2 Trip Undervoltage protection stage 2 issues trip command
Information Description
UV1 Alarm Undervoltage protection stage 1 issues an alarm signal
99
Chapter 10 Undervoltage protection
100
Chapter 11 Displacement voltage protection
101
Chapter 11 Displacement voltage protection
1.1 Introduction
Two definite time stages and one inverse time stage,The inverse time
stage provide 4 fixed curves and a user-define curve.
The first and Inverse time stage can be set to alarm or trip
The displacement voltage 3V0 can be directly applied to the IED or can be
calculated based on the connected three phase to ground voltages
(3V0=VA+VB+VC). In the latter case, the three voltage inputs must be
connected to voltage transformers in a ground-wye configuration. If the IED is
only provided with phase to phase voltages or provided only one phase to
earth or phase to phase voltage, it is not possible to calculate a displacement
voltage. In this case, the direction cannot be determined for earth fault or
sensitive earth fault protection.
If the displacement voltage is directly applied to the IED and the binary setting
“3U0 Calculated” is set as “0”, it is not affected by VT fail detection on
three-phase connected voltage. Similarly, if the displacement voltage is
calculated based on the three-phase voltages and the binary setting “3U0
Calculated” is set as “1”, it would not be blocked as a result of failure
detection in U4 voltage transformer. However, in case of a failure in U4
voltage transformer, the displacement voltage protection based on measured
value 3V0 would be blocked.
102
Chapter 11 Displacement voltage protection
Individual pickup value for each definite stage can be defined by setting
“U_3V01”, “U_3V02” and “U_3V0 Inv”. With these settings, the measured or
calculated displacement voltage is compared separately with the setting
value for each stage. If the respective value is exceeded, a trip or alarm time
delay timer is started. Each timer is set to count up to a user-defined time
delay. The time delay can be set for each definite stage individually via
settings “T_3V01” and “T_3V02”. After the user-defined time delays elapsed,
a trip command or an alarm signal is issued by respective stage.
The pickup value for the inverse time-voltage stage can be defined by setting
“U_3V0 Inv”. The displacement voltage 3U0 is compared with corresponding
setting value. If it exceeds the setting value, the inverse displacement voltage
protection stage picks up and the tripping or alarming time is calculated from
the displacement voltage, using the selected tripping or alarming curve. The
tripping or alarming curve can be selected from IEC standard curves, or a
user-defined characteristic can be used alternatively. Application of each
curve is possible by setting respective coefficients of following formula:
t B K
A
U P
1
Us
Equation 11-1
103
Chapter 11 Displacement voltage protection
3V0 1 OP
BLK 3V0
Func_3V01
3U0> & T1 Trip/Alarm
BI_Blk 3V01
Func_3V02
3U0>
& T2 Trip
BI_Blk 3V02
Func_3V Inv
3U0>
& Trip/Alarm
BI_Blk 3V0 Inv
104
Chapter 11 Displacement voltage protection
3V0 1 OP
VA>U_Phase up
& Gnd A
VA<U_Phase low
VB>U_Phase up
& Gnd B
VB<U_Phase up
VC>U_Phase up
& Gnd C
VC<U_Phase up
Signal Description
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
UP4 Signal for voltage input 4
Signal Description
Displacement voltage protection stage 1
3V01 Alarm
alarm
Displacement voltage protection stage 2
3V0 InvAlarm
alarm
3V01Trip Displacement voltage protection stage 1 trip
3V02Trip Displacement voltage protection stage 2 trip
Displacement voltage protection inverse time
3V0 Inv Trip
stage trip
105
Chapter 11 Displacement voltage protection
1 U_3V01 2.00~100.0 V
2 T_3V01 0.00~120.00 s
3 U_3V02 2.00~100.0 V
4 T_3V02 0.00~120.00 s
5 U_3V0 Inv 2.00~100.0 V
0: Defined by user
1: IEC NI
6 3V0 Inv CRV SEL 0~4 2: IEC VI
3: IEC EI
4: IEC LTI
7 A_3V0 Inv 0.001~1000 s Inverse characteristic
8 P_3V0 Inv 0.01~10.00
9 B_3V0 Inv 0.000~100.00 s
10 K_3V0 Inv 0.025~1.5
11 U_Phase low 10.00~100.0 V
12 U_Phase up 40.00~100.0 V
106
Chapter 11 Displacement voltage protection
Information Description
3V01 Trip Voltage displacement protection stage 1 issues trip signal
3V02 Trip Voltage displacement protection stage 2 issues trip signal
3V0 Inv Trip Voltage displacement protection inverse time stage issues trip signal
Information Description
3V01 Alarm Voltage displacement protection stage 1 issues an alarm signal
3V0 InvAlarm Voltage displacement protection inverse timestage issues an alarm signal
PhA Grounded Phase A is grounded
PhB Grounded Phase B is grounded
PhC Grounded Phase C is grounded
107
Chapter 12 Negative-sequence over voltage protection
108
Chapter 12 Negative-sequence over voltage protection
1.1 Introduction
The relay provide one stage negative-sequence over voltage protection with
definite time delay characteristic, and it can be controlled on or off by the
connector “Fun_NSOV”.
Voltage thresholds and time delays can be set individually for the protection.
Thus, tripping can be time-coordinated depending on how severe the
voltage collapses are, in this context, setting “U2_NSOV” and “T_NSOV”.
109
Chapter 12 Negative-sequence over voltage protection
U2>
Func_U2
BI_Blk U2 & T Trip
1Ph V Connect
UP1 U2 Trip
UP2
UP3
BI_Blk NSOV
Signal Description
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
Signal Description
BI_Blk NSOV The signal input for blocking the ptotection.
Signal Description
Negtive-sequence obervoltage protection
U2 Trip
stage trip
110
Chapter 12 Negative-sequence over voltage protection
Table 12-4 Function setting list for negative-sequence over voltage protection
1 U2_NSOV 2~100 V
2 T_NSOV 0~120 s
Table 12-5 Logical linker list for negative-sequence over voltage protection
Information Description
NSOV Trip Negtive-sequence voltage protection issues trip signal
111
Chapter 13 Circuit breaker failure protection
112
Chapter 13 Circuit breaker failure protection
1.1 Introduction
The circuit breaker failure protection is able to detect a failure of the circuit
breaker during a fault clearance. It ensures fast back-up tripping of
surrounding breakers by tripping relevant bus sections.
In the event of a circuit breaker failure with a busbar fault, a transfer trip
signal is issued to trip the remote end circuit breaker of the feeder.
The current criteria are in combination with three phase currents, zero and
negative sequence current t achieve a higher security.
The function can be set to give three phase re-trip of the own breaker to avoid
unnecessary tripping of surrounding breakers at an incorrect starting due to
mistakes during testing.
Circuit breaker failure protection can be enabled or disabled in the IED via
binary setting “Func_CBF”. If setting “ON” is applied, CBF protection would
be enabled. In this case, by operation of a protection function, and
subsequent CBF initiation by respective protection function, a programmed
timer runs toward a preset time delay limit. This time delay is set by user
113
Chapter 13 Circuit breaker failure protection
under the settings “T_CBF1”. If the circuit breaker has not been opened after
expiration of the preset time limit, the circuit breaker failure protection issues
a command to trip circuit breaker (e.g. via a second trip coil). If the circuit
breaker doesn’t respond to the repeated trip command, until another preset
delay time which is set at “T_CBF2”, the protection issues a trip command to
isolate the fault by tripping other surrounding backup circuit breakers (e.g. the
other CBs connected to the same bus section as the faulty CB).
Initiation of CBF protection can be performed by both the internal and external
protection functions. If it is desired to initiate the CBF protection by means of
external protection functions, specified binary inputs (BI) should be
marshaled. Internal protection functions can initiate the CBF protection
integrated in the IED.
For protection functions where the tripping criterion is not depend on current,
current flow is not a suitable criterion for proper operation of the breaker. In
this case, the position of the circuit breaker auxiliary contact should be used
to determine if the circuit breaker properly operated. It is possible to evaluate
the circuit breaker operation from its auxiliary contact status. A precondition
for evaluating circuit breaker auxiliary contact is that open status of CB should
be marshaled to binary inputs.
114
Chapter 13 Circuit breaker failure protection
HWJ
& 20ms CB Status
TWJ
Ia>
&
Ib> ≥
Ic>
&
I2>
≥
3I0>
≥ Curr.Crit
Ia>
&
Ib>
Ib>
& ≥
Ic>
Ia>
&
Ic> &
115
Chapter 13 Circuit breaker failure protection
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
3I0 signal for zero sequence current input
Signal Description
Signal Description
CBF1Trip Circuit breaker failure protection stage 1 trip
CBF2 Trip Circuit breaker failure protection stage 2 trip
116
Chapter 13 Circuit breaker failure protection
Table 13-4 Function setting list for circuit breaker failure protection
2 I_CBF 0.05~100 A
3 3I0_CBF 0.05~100 A
4 I2_CBF 0.05~100 A
5 T1_CBF 0~100 s
6 T2_CBF 0~100 s
Table 13-5 Logical linker list for circuit brea ker failure protection
Table 13-6 Binary setting list for circuit breaker failure protection
Information Description
CBF T1 Trip The first stage CBF issues trip command
CBF T2 Trip The second stage CBF issues trip command
Faulty CBF Initiate CBF function is initiate by faulty
Ext CBF Initiate CBF function is initiated by BI
117
Chapter 13 Circuit breaker failure protection
118
Chapter 14 Dead zone protection
119
Chapter 14 Dead zone protection
1.1 Introduction
The IED provides this protection function to protect the area between circuit
breaker and CT in the case that CB is open, namely dead zone. Therefore,
by occurrence of a fault in dead zone, the short circuit current is measured
by protection IED while CB auxiliary contacts indicate the CB is open.
When one bus side CT of feeder is applied, once a fault occurs in the dead
zone, the IED trips the relevant busbar zone. Tripping logic is illustrated in
Figure 14-1.
trip
Bus
IFAULT
Legend:
Opened CB
Closed CB
When one line side CT is applied, when a fault occurs in the dead zone,
protection relay sends a transfer trip to remote end relay to isolate the fault.
Tripping logic is illustrated in Figure 14-2.
Inter trip
Busbar
IFAULT
Trip
Relay
Legend:
Opened CB
Closed CB
HWJ
& 20ms CB Open
TWJ
BI_Init DZ 20ms
& Ext DZ Initiate
Func_DZ
& ≥ DZ Start
BI_Blk DZ
Ia>
Ib> ≥
Ic>
DZ Start
121
Chapter 14 Dead zone protection
IP1 DZ Trip
IP2
IP3
DZ Init
TWJ
HWJ
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
Signal Description
DZ Init DZ initiation
TWJ Three phase CB open
HWJ Three phase CB Close
Signal Description
DZ Trip Dead Zone protection trip
1 I_DZ 0.05~10 A
2 T_DZ 0~100 s
122
Chapter 14 Dead zone protection
Information Description
DZ Trip The dead zone function issues trip command
123
Chapter 15 STUB protection
124
Chapter 15 STUB protection
2 STUB protection
2.1 Introduction
Capacitor Voltage Transforemers (CVTs) are commonly installed at the line side
of transmission lines. Therefore, for the cases that transmission line is taken out
of service and the line disconnector is open, the distance protection will not be
able to operate and must be blocked.
The STUB protection protects the zone between the CTs and the open
disconnector. The STUB protection is enabled when the open position of the
disconnector is informed to the IED through connected binary input. The
function supports one definite stage with the logic shown inbelow figure.
Busbar A
CB1
CT1
Stub fault Feeder1
Disconnector1
CB3
CT3
Feeder2
Disconnector2
CT2
CB2
Busbar B
If IED detects short circuit current flowing while the line disconnector is open,
STUB fault is detected for the short circuit in the area between the current
125
Chapter 15 STUB protection
transformers and the line disconnector. Here, the summation of CT1 and CT3
presents the short circuit current.
Ia>I_STUB
Ib>I_STUB ≥
Ic>I_STUB
BI_STUB Enable
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
Signal Description
BI_STUB Enable STUB protection enabled
Signal Description
STUB Trip STUB Trip
126
Chapter 15 STUB protection
Name Description
STUB Enable Enable or disable STUB protection
Func_STUB Stub protection operating mode
2.5 Reports
Table 15-6 Event report list
Information Description
STUB Trip STUB protection trip
127
Chapter 16 Synchro-check and energizing check function
128
Chapter 16 Synchro-check and energizing check function
1.1 Introduction
The synchronism and voltage check function ensures that the stability of the
network is not endangered when switching a line onto a busbar. The voltage
of the feeder to be energized is compared to that of the busbar to check
conformances in terms of magnitude, phase angle and frequency within
certain tolerances.
The synchro-check function checks whether the voltages on both sides of the
circuit breaker are synchronizing, or at least one side is dead to ensure
closing can be done safely.
When comparing the two voltages, the synchro check uses the voltages from
busbar and outgoing feeder. If the voltage transformers for the protective
functions are connected to the outgoing feeder side, the reference voltage
has to be connected to a busbar voltage.
The external automatic reclosing and manual closing are initiated through
corresponding binary input respectively. When a synchronization request is
received, it can work based on different close permission criteria. The criteria
can be selected for auto reclosure or manual closure separately. The binary
settings are“AR_Override”, “AR_Syncheck”, “AR_EnergChkDLLB”,
“AR_EnergChkLLDB”, “AR_EnergChkDLDB” for auto reclosure, and
“MC_Override”, “MC_Syn check”, “MC_EnergChkDLLB”,
“MC_EnergChkLLDB”, “MC_EnergChkDLDB” are settable for manual closure.
The meaning of each operation mode is as follows:
Syn check: by applying this setting, with any synchronization request, the
129
Chapter 16 Synchro-check and energizing check function
130
Chapter 16 Synchro-check and energizing check function
At the end of the dead time, synchronization request will be initiated and the
synchronization conditions are continuously checked to be met for a certain
time during maximal extended time “T_Syn Chk”. By satisfying synch-check
condition in this period, the monitor timer will stop and close command will be
issued for AR.
Energizing check for dead line and live bus for AR enabled or disabled,
when the control word “AR_EnergChkDLLB” is on
131
Chapter 16 Synchro-check and energizing check function
Energizing check for live line and live bus for AR enabled or disabled,
when the control word “AR_EnergChkLLDB” is on
Energizing check for dead line and live bus for AR enabled or disabled,
when the control word “AR_EnergChkDLDB” is on
U4>Umax_Energ
Anglediff<Angle_Syn Diff
AND
Freqdiff<Freq_Syn Diff AR_Override On
T_MaxSynExt
AND AND Synchr-check fail
Udiff<U_Syn Diff
U4 >Umax_Energ
AND
U4 for Ux
T_Syn Check Synchr-check meet
AR_EnergChkLLDB on
Umax<Umin_Syn
AND
AND
1Ph V Connect on
AND
corresponding Phase<Umin_Syn
OR
AR_EnergChkDLDB on
AND
1Ph V Connect on
AND MC BO
AND HWJ
corresponding Phase<Umin_Syn
U4 <Umin_Syn
AND
U4 for Ux Synchr-check fail
AND
T_MaxSynReq
MC_Override On
AR_EnergChkDLLB on
AND
Func_MC
Umin>Umax_Energ
AND AND BI_Req Syn
1Ph V Connect on
Syn Request
AND
Corresponding Phase>Umax_Energ
132
Chapter 16 Synchro-check and energizing check function
UP1
UP2
UP3
UP4
BI_Req Syn
Signal Description
UP1 Signal for voltage input 1
UP2 Signal for voltage input 2
UP3 Signal for voltage input 3
UP4 Signal for voltage input 4
Signal Description
BI_Req Syn Binary input Initiation autoreclosing
133
Chapter 16 Synchro-check and energizing check function
Table 16-5 Logical linker list for synchro-check and energizing check protection
Table 16-6 Binary setting list for synchro-check and energizing check protection
Information Description
Syn Ok Synchronization check OK
Syn Request Check synchronization
Syn Vdiff fail Voltage difference for synchronization check fail
Syn Ang fail Angle difference for synchronization check fail
Syn Fdiff fail Frequency difference for synchronization check fail
Syn Failure Synchronization check timeout
134
Chapter 16 Synchro-check and energizing check function
135
Chapter 17 Autoclosing function
136
Chapter 17 Autoclosing function
1 Autoreclosing function
1.1 Introduction
Internal/external AR initiation
CB ready supervision
In the Table 17-1, the first and second columns show the protection
functions, respectively, while the third column introduces the binary setting
which is possible to set protection functions to work in conjunction with AR.
138
Chapter 17 Autoclosing function
is not still detected by the IED, AR function would be blocked for duration of
AR reset time which is defined by “T_AR Reset”. In this case, reclosing
attempt would be announced as unsuccessful (annunciation “AR Failure”).
If circuit breaker failure protection (internal or external) is used for the CB,
monitoring time “T_Max CB Open” should be set shorter than the delay time
for detection of circuit breaker failure. By doing so, make sure that no
reclosing takes place for a faulty circuit breaker. No reclosing would take
place for CBF stage 2 or dead zone function operation.
Regarding the close command, it has a pulse nature which lasts for 500ms
at most. As expected, no synchronization check takes place during this
pulse time. If during this pulse time, the auxiliary contact of CB indicates
that the CB has been closed or a current flow is detected by the IED, the
close command pulse will be reset.
Once the close command pulse is issued (rising edge) to close the circuit
breaker, reclaim time “T_Reclaim” is started, within this time it is checked
whether the reclosing attempt is successful. If no fault occurs before the
reclaim time elapses, it is thought that fault is cleared. In this case, at the
end of reclaim time, reset time “T_AR Reset” is started. During reset time
AR function is blocked. If a new fault occurs before the reclaim time elapses,
it results in reset of the reclaim time and starting of next reclosing shot. This
procedure can be repeated until the maximum number of reclosure shots is
reached.
If none of the reclosing shots is successful, and therefore the fault is still
139
Chapter 17 Autoclosing function
remained after the last shot, final trip takes place. Furthermore, AR function
would be blocked for a time period defined by “T_AR Reset ”, and
annunciation “AR Failure” is issued.
There may be cases when it is already obvious that CB cannot perform any
reclosing attempt. For such cases, binary input “BI2/CB Faulty” is
considered which indicates that CB is not ready for reclosing. CB Faulty
should be checked with a time delay “T_CB Faulty”, which is set according
to the characteristic of circuit breaker. AR function would be blocked if the
IED detects activation of “BI2/CB Faulty”, even the AR function would not be
initiated. AR is blocked until the BI disappears. Furthermore, this condition
is checked whenever a close command is received from AR function.
Single-shot reclosure
Multi-shot reclosure
140
Chapter 17 Autoclosing function
different dead time. This procedure can be repeated until the whole
reclosing shots which are set inside the IED is performed. Different dead
times can be set for various shots of AR function. This can be performed
through settings “T_3P AR1”, “T_3P AR2”, “T_3P AR3” and “T_3P AR4”. If
one of the preset reclosure shots is successful, AR function would be reset
after expiration of the reclaim time. However, if none of reclosing shots is
successful, i.e. the fault doesn’t disappear after the last programmed shot, a
final trip is issued, and reclosing attempts are announced to be
unsuccessful.Figure 17-1 illustrates the operation method of two shots
reclosure.
Trip Command
CB Open
AR Initiate
Figure 17-1 Timing diagram showing two reclosure shots, first unsuccessful, second successful
IP1 AR Close
IP2 AR Not Ready
IP3 AR Final Trip
UP1 AR Successful
UP2 AR Fail
UP3
UP4
BI1/AR Off
BI2/CB Faulty
BI3/Init AR
BI4/MC CLS
BI8 CB Open
BI9 CB Close
141
Chapter 17 Autoclosing function
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
UP4 signal for voltage input 4
Signal Description
BI1/AR Off Binary input 1/AR function off
BI2/CB Faulty Binary input 2/CB Faulty
BI3/Init AR Binary input 3/Initiation AR function
BI4/MC CLS Binary input 4/manual closing
MC/AR Block AR block
BI8 CB Open Binary input 8 CB Open
BI9 CB Close Binary input 9 CB Close
Signal Description
AR Close AR Close
AR Not Ready AR Not Ready
AR Final Trip AR Final Trip
AR Successful AR Successful
AR Fail AR Fail
142
Chapter 17 Autoclosing function
143
Chapter 17 Autoclosing function
144
Chapter 17 Autoclosing function
Information Description
AR in progess AR is initiated by internal or external function
Syn Request Check synchronization
Syn OK Synchronization check OK
1st Reclose The first shot reclosing
2nd Reclose The second shot reclosing
3rd Reclose The third shot reclosing
4th Reclose The fourth shot reclosing
AR Success AR successful
AR Failure AR unsuccessful
Syn Vdiff fail Voltage difference for synchronization check fail
Syn Ang fail Angle difference for synchronization check fail
Syn Fdiff fail Frequency difference for synchronization check fail
Syn Failure Synchronization check timeout
Information Description
CB Not Ready BI2 is active to show CB is not ready
145
Chapter 17 Autoclosing function
146
Chapter 18 Under current protection
147
Chapter 18 Under current protection
1.1 Introduction
The following figure shows the logic diagram of the undercurrent ptotection.
Ia<
Ib< &
Ic< Fun_UC
T Trip
HWJ &
BI_Blk OF
148
Chapter 18 Under current protection
IP1 UC Trip
IP2
IP3
HWJ
BI_Blk UC
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
Signal Description
HWJ The binary input of CB Close
BI_Blk UC The binary signal for blocking the protection
Signal Description
UC Trip Under current monitoring function trip
Table 18-4 Function setting list for under current monitoring function
149
Chapter 18 Under current protection
Table 18-5 Logical linker list for under current monitoring function
Information Description
UC Trip Under current protection issues trip command
150
Chapter 19 Over-frequency protection
151
Chapter 19 Over-frequency protection
1 Over-frequency protection
1.1 Introduction
Over frequency protection provide a trip stage. When the detected frequency
is more than the threshold, and the CB position is be colsed, the function will
be pickup, and it will be operate after the delay time . This protection will be
blocked by VT fail or the minimum Vph-ph is less than function setting value.
When a phase voltage input, the Control word “1 Ph V Connection” being “1”,
the protection will be blocked if the maximum Vph-ph is less than the function
setting value.
F>
VT fail Fun_OF
Umin>
&
1Ph V Connect ≥
&
Umax>
152
Chapter 19 Over-frequency protection
UP1 OF Trip
UP2
UP3
TWJ
BI_Blk OF
Signal Description
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
Signal Description
TWJ The binary input of CB Open
BI_Blk OF The signal input for blocking the ptotection.
Signal Description
OF Trip Over-frequency protection function trip
Table 19-4 Function setting list for under current monitoring function
153
Chapter 19 Over-frequency protection
Information Description
HF Trip Over-frequency protection issues trip command
154
Chapter 20 Rate of change of frequency protection
155
Chapter 20 Rate of change of frequency protection
1.1 Introduction
156
Chapter 20 Rate of change of frequency protection
|df/dt|>Setting
Dir model
df/df Startup
Check U On
Upp>Setting
F normal>2s
Signal Description
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
Signal Description
BI_Blk ROCOF The signal input for blocking the ptotection.
Signal Description
ROCOF Trip The rate of change of frequency protection function trip
157
Chapter 20 Rate of change of frequency protection
Table 20-4 Function setting list for under current monitoring function
Information Description
ROCOF Trip The rate of change of frequency protection issues trip command
158
Chapter 21 Load shedding protection
159
Chapter 21 Load shedding protection
1.1 Introduction
Undervoltage checking
CB position checking
160
Chapter 21 Load shedding protection
begins to run toward a pre-defined time limit which is the time delay of the
protection (setting “T_LF LS”). When the time delay elapsed, the trip
command is issued.
Since the protection based on power frequency from the connected voltages,
the protection should be blocked if some conditions are satisfied as following:
161
Chapter 21 Load shedding protection
F<F_LF LS
AND
Func_LF LS
F<55HZ
AND
VT fail
OR
TWJ
AND T_LF LS LF LS Shedding Trip
BI_Blk LF LS
OR
Imax<I_Block_LS
Uppmax<U_Block_LS
AND
1Ph V Connect
AND
Uppmin<U_Block_LS
OR
dF/dt On
AND
|Df/dt|>dF/dt_LS
Figure 21-1 Logic diagram for low frequency load shedding protection
IP1 LF LS Trip
IP2
IP3
UP1
UP2
UP3
TWJ
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
162
Chapter 21 Load shedding protection
Signal Description
TWJ Binary input of CB open
Signal Description
LF LS Trip Low frequency load shedding trip
1 F_LF LS 45.00~60.0 Hz
2 T_LF LS 0.10~100.00 S
3 dF/dt_LS 0.30~20.00 Hz/s
4 U_Block_LS 10.00~120.00 V
5 I_Block_LS 0.00~10.0 A
Table 21-5 Logical linker list for low frequency load shedding protection
Table 21-6 Binary setting list for low frequency load shedding protection
1 dF/dt On 1/0 0
Information Description
LF LS Trip Low frequency load shedding function issues trip command
163
Chapter 21 Load shedding protection
2.1 Introduction
Undervoltage checking
CB position checking
Low voltage load shedding is provided based on “bay load shedding” principle.
This means that the protection function is implemented in each bay separately,
instead of being applied in an incoming bay and sending trip command to
various outgoing bays. In this regard, coordination between the low voltage
load shedding protection functions applied at various bays can be achieved
by selecting appropriate settings for pickup threshold and time delay of the
protection in various bays. The protection function can be enabled or disabled
via binary setting “Func_LV LS”. Based on the “bay load shedding” principle,
only one trip stage is provided for the protection. This protection can operate
based on both three-phase and single-phase voltage input configurations.
The voltage connection is set in the IEDby binary setting “3Ph V Connect/1Ph
164
Chapter 21 Load shedding protection
165
Chapter 21 Load shedding protection
Uppmax<U_LV LS
AND
1Ph V Connect
OR
AND AND
Uppmin<U_LV LS
Func_LV LS
VT fail
OR
TWJ
BI_Blk LV LS
1Ph V Connect
OR OR
AND
Uppmin<U_Block_LS
AND
U2>5V
Imax<I_Block_LS OR
dU/dt On
AND
|dUpp/dt|max>dU/dt_LS
Figure 21-2 Logic diagram for low voltage load shedding protection
IP1 LV LS Trip
IP2
IP3
UP1
UP2
UP3
TWJ
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
166
Chapter 21 Load shedding protection
Signal Description
TWJ Binary input of CB open
Signal Description
LF LS Trip Low voltage load shedding trip
Table 21-11 Function setting list for low frequency load shedding protection
Table 21-12 Logical linker list for low frequency load shedding protection
Table 21-13 Binary setting list for low frequency load shedding protection
167
Chapter 21 Load shedding protection
Information Description
LV LS Shedding Trip Low voltage load shedding function issues trip command
168
Chapter 21 Load shedding protection
3.1 Introduction
The IED provides a load shedding function based on the load current
passing through feeder. This function will be essential in conditions that
feeder is connected to a huge network with constant frequency and
additional AVR is continuously used for voltage regulation. In this case, load
shedding protection should be done based on load currentand monitoring of
following items
Undervoltage checking
If the voltage connected to the IED and the binary setting “OL LS Chk V On”
is set in binary setting “OL LS Chk V Off/OL LS Chk V On”, the protection
would be blocked as following conditions:
169
Chapter 21 Load shedding protection
Imax>I_OL LS
Func_OL LS AND
BI_Blk LV LS
or
TWJ
VT fail
Uppmax<U_Block_LS
AND
|df/dt|>dF/dt_LS
AND
dF/dt On
dU/dt On
AND
|dUpp/dt|max>dU/dt_LS
OLLS Chk V On
IP1 OL LS Trip
IP2
IP3
UP1
UP2
UP3
TWJ
170
Chapter 21 Load shedding protection
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
Signal Description
TWJ Binary input of CB open
Signal Description
OL LS Trip Overload load shedding trip
Table 21-18 Function setting list for overload load shedding protection
Table 21-19 Logical linker list for overload load shedding protection
171
Chapter 21 Load shedding protection
Table 21-20 Binary setting list for overload load shedding protection
Information Description
OL LS Trip Overload load shedding function issues trip command
172
Chapter 22 Super load shedding protection
173
Chapter 22 Super load shedding protection
4.1 Introduction
Super under frequency load shedding protection provides four trip stages.
Each stage can be implemented when both joint linker and respective linker
are switched on. All the four stages will be disabled when the joint linker is
switched off. The first three stages can be tripped by turns, vie control word
‘LF joint Cut On/Off’, i.e. the second stage can’t be tripped only after the first
stage actuation, and the third stage can’t be tripped only after the second
stage actuation. When this control word is enabled, a certain stage can trip
even previous linker is switched off. The fourth stage is special. It can operate
regardless of previous three.
The acceleration stage is also provided. When the frequency is less than the
first stage setting ‘’f_LF LS1’’, and frequency change rate is more than
‘’df/dt_ACC1/2’’ and less than ‘’df/dt_LF LS’’, serious overloading is
considered. In this condition, the IED will shed load fast, and trip the first two
or three stages. The acceleration stage can be disable by control word “ACC
LF1&2 On/Off”or “ACC LF1&2 &3On/Off’’.
Blocking:
1. The frequency is considered abnormal when it is less than 45Hz for 50Hz
system, or less than 55Hz for 60Hz system. In this condition, the function will
be blocked instantly, and alarm will be reported after 5s time delay. The block
will be released after the frequency is considered normal.
174
Chapter 22 Super load shedding protection
checking. When the frequency difference more than 0.5Hz, blocking this
function immediately. If the value less than 0.5Hz, it will be automatic
unblocking.
5. The minimum magnitude among of the connected voltages is lower than the
threshold defined by “U_Check”.
6. Load current is lower than setting “I_Check”. This condition is mainly useful
when the voltage transformer is connected at source side. The setting applied
at “I_Check” corresponds to minimum load current which may flow when
circuit breaker is closed. It is possible to disable this feature by applying
setting 0 to “I_Check”.
8. The system action process load shedding in the Low-frequency, active power
maybe occur before the previous stage operation after the system is no longer
vacancy. Frequency begin to rebound, but this knee point maybe within the
next stage pickup value. For example, after the 1st stage load shedding
operation, the frequency will be slowly rise, but the 2nd stage will be operate
when the 2nd stage pickup value constant under longer than this stage
operate delay time, not necessary the part load shedding. The over shedding
phenomenon easily in the area occurred in the small grid. Therefore, the
blocking criterion df/dt≥0 add in the each stage , can be effectively prevent
the over shedding phenomenon, and this function alsoo can be put on/off
ctrlword “Trend BLKF On/Off”.
175
Chapter 22 Super load shedding protection
F<55Hz &
System Frequency=60Hz Y
F<45Hz &
System Frequency=50Hz Y
VT fail >=1
>=1 0
0
Block
U2>5V & Y 0 Y
Y
1Ph V Connect
U_Check<
I_Check<
Trend BLKF On
df/dt≥0
Func_LF LS On
&
f≤f_Startup LF LS startup
Y
Block ≥1
df/dt On
H
df/dt_LF LS >
LF LS startup &
Tf_ACC1
ACC LF1&2 On ACC LF1&2 Trip
df/dt_ACC1≤df/dt Y
<df/dt_LF LS
LF LS startup &
Tf_ACC2
ACC LF1&2&3 On ACC LF1&2&3 Trip
df/dt_ACC1≤df/dt Y
<df/dt_LF LS
Func_LF LS1 On
&
T_LF LS1
LF LS startup LF LS1 Trip
Y
f≤f_LF LS1
Func_LF LS2 On
f≤f_LF LS2
Func_LF LS3 On
f≤f_LF LS3
Func_LF LS4 On
&
T_LF LS4
LF LS_Startup LF LS4 Trip
Y
f≤f_LF LS4
176
Chapter 22 Super load shedding protection
IP1 LF LS Trip
IP2
IP3
UP1
UP2
UP3
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
Signal Description
LF LS Trip Low frequency load shedding trip
Table 22-3 Function setting list for low frequency load shedding protection
177
Chapter 22 Super load shedding protection
9. T_LF LS4 the time delay settings for LF LS4 S 0.10 100.0
df/dt_ACC1 the df/dt setting for Hz/s
10. 0.300 20.00
LFLSaccelerate1
Tf_ACC1 the time delay setting for S
11. 0.10 100.0
LFLSaccelerate1
df/dt_ACC2 the df/dt setting for Hz
12. 0.300 20.00
LFLSaccelerate2
Tf_ACC2 the time delay setting for S
13. 0.10 100.0
LFLSaccelerate2
14. df/dt_LF LS the df/dt setting for LFLS blocking Hz/s 0.300 20.00
Table 22-4 binary settings list for low frequency load shedding protection
178
Chapter 22 Super load shedding protection
Information Description
LF LS Trip Low frequency load shedding function issues trip command
179
Chapter 22 Super load shedding protection
5.1 Introduction
Super under voltage load shedding protection provides four trip stages. Each
stage can be implemented when both joint linker and respective linker are
switched on. All the four stages will be disabled when the joint linker is
switched off. The first three stages can be tripped by turns, via control word
‘LV Joint Cut On/Off’, i.e. the second stage can’t be tripped only after the first
stage actuation, and the third stage can’t be tripped only after the second
stage actuation. When this control word is enabled, a certain stage can trip
even previous linker is switched off. The fourth stage is special. It can operate
regardless of previous three.
The acceleration stage is also provided. When the voltage is less than the
first stage setting ‘’U_LV LS1’’, and frequency change rate is more than
‘’du/dt_ACC1’’ and less than ‘du/dt_LVLS’’, serious overloading is considered.
In this condition, the IED will shed load fast, and trip the first two or three
stages. The acceleration stage can be disabled by control word “ACC LV1&2
Off”or “ACC LV1&2&3 Off’’.
Blocking:
180
Chapter 22 Super load shedding protection
181
Chapter 22 Super load shedding protection
U2>5V &
Y
1Ph V Connect
>=1
VT fail 0
0
Block
Y
U_Check<
I_Check<
Trend BLKV On
du/dt≥0
Func_LV LS On
&
U≤U_Startup LV LS startup
Y
Block ≥1
du/dt On
H
du/dt_LV LS >
LV LS startup &
Tv_ACC1
ACC LV1&2 On ACC LV1&2 Trip
du/dt_ACC1≤du/dt Y
<du/dt_LV LS
&
LV LS startup Tv_ACC2
ACC LV1&2&3 Trip
ACC LV1&2&3 On Y
du/dt_ACC1≤du/dt
<du/dt_LV LS
Func_LV LS1 On
&
T_LV LS1
LV LS startup LV LS1 Trip
Y
U≤U_LF LS1
Func_LV LS2 On
U≤U_LV LS2
Func_LV LS3 On
U≤U_LV LS3
Func_LV LS4 On
&
T_LV LS4
LV LS Startup LV LS4 Trip
Y
U≤U_LV LS4
182
Chapter 22 Super load shedding protection
IP1 LV LS Trip
IP2
IP3
UP1
UP2
UP3
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
Signal Description
LF LS Trip Low voltage load shedding trip
Table 22-8 Function setting list for low frequency load shedding protection
183
Chapter 22 Super load shedding protection
Table 22-9 Binary setting list for low voltage load shedding protection
Information Description
Func_LV LS Disable or enable the low voltage load shedding
184
Chapter 22 Super load shedding protection
6.1 Introduction
The IED provides a super load shedding function based on the load current
passing through feeder. This function will be essential in conditions that
feeder is connected to a huge network with constant frequency and
additional AVR is continuously used for voltage regulation. In this case, load
shedding protection should be done based on load current and monitoring
of following items
If there is voltage connection to the device and the device is informed about
it by setting “OL LS Chk V On” to control word “OL LS Chk V Off/OL LS Chk
V On”, the protection would be blocked in following conditions:
VT fail
U_Check<
F<F_Startup
& Block
Y Y
Y
du/dt_OL LS >
>=1
&
Upp<U_Startup
Y
Y
Func_OL LS On
&
I≥I_Startup OL LS startup
Y
Block
Func_OL LS1 On
&
T_OL LS1
OL LS startup OL LS1 Trip
Y
I≥I_OL LS1
Func_OL LS2 On
I≥I_OL LS2
Func_OL LS3 On
I≥I_OL LS3
Func_OL LS4 On
&
T_OL LS4
OL LS_Startup OL LS4 Trip
Y
I≥I_OL LS4
186
Chapter 22 Super load shedding protection
IP1 OL LS Trip
IP2
IP3
UP1
UP2
UP3
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
Signal Description
OL LS Trip Overload load shedding trip
Table 22-13 Function setting list for overload load shedding protection
187
Chapter 22 Super load shedding protection
Table 22-14 Binary setting list for overload load shedding protection
188
Chapter 23 Fast busbar protection scheme
189
Chapter 23 Fast busbar protection scheme
A
Relay A
B
Trip
Relay C
If the fault occurs on outgoing feeder C, the protection IED C will trip and
send block messenger to IED A to block IED A relevant protection function.
190
Chapter 23 Fast busbar protection scheme
A
Relay A
Trip
Relay B
Relay C
Once the fault located on the busbar, protection IEDs of outgoing feeder do
not trip and therefore there is no any blocking signal. So the IED A will trip
and clear off the fault with short time delay.
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
191
Chapter 23 Fast busbar protection scheme
Information Description
OC Startup Three stages over current protections startup
OC Startup Back Three stages over current protections return
192
Chapter 24 Secondary system supervision
193
Chapter 24 Secondary system supervision
To prevent the IED from wrong trip, interruptions in the secondary circuits of
current transformers is detected and reported by the UED. When the zero
sequence current is always larger than the setting value “3I0_CT Fail” for
12s, “CT Fail” will be reported and each stage of zero sequence current
protection will be blocked if setting “Blk EF_CT Fail” is selected.
IP1 CT Fail
IP2
IP3
IN
194
Chapter 24 Secondary system supervision
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
IN signal for zero sequence current input
Signal Description
CT Fail CT Fail
Table 24-3 Function setting list for current circuit supervision protection
Table 24-4 Binary setting list for current circuit supervision protection
Information Description
CT Fail CT failure in circuit of current transformer
195
Chapter 24 Secondary system supervision
The calculated zero sequence voltage 3U0 is more than the setting of
“Upe_VT Fail”. This condition may correspond to single or two-phase
broken fault in secondary circuit of the voltage transformer, if the system
196
Chapter 24 Secondary system supervision
The calculated zero sequence voltage 3U0 is more than the setting of
“Upe_VT Fail”, and at the same time, the difference between the maximum
and minimum phase-to-phase voltages is more than the setting of “Upp_VT
Fail”. This condition may correspond to single or two-phase broken fault in
secondary circuit of the voltage transformer, if the system starpoint is
isolated or resistance earthed.
Without relay pickup, minimum phase voltage becomes more than setting of
“Upe_VT Normal” for 500ms.
While the protection which relates to current is detected pick up, it will block
the VT failure supervision.
Without relay pickup, minimum phase voltage becomes more than setting of
“Upe_VT Normal” and at the same time, the calculated zero sequence or
negative sequence current of corresponding side becomes more than the
setting of “3I02_ VT Fail”.
197
Chapter 24 Secondary system supervision
Max(Ia,Ib,Ic)>I_ VT Fail
Solid Earth on OR
AND
Max{Uab,Ubc,Uca}-Min{Uab,Ubc,Uca}> Upp_VT Fail
1Ph V Connect
AND
Relay Pickup OR
VT Fail Detected
IP3
IN
UP1
UP2
UP3
Signal Description
IP1 signal for current input 1
IP2 signal for current input 2
IP3 signal for current input 3
IN Signal for zero sequence current input
UP1 signal for voltage input 1
UP2 signal for voltage input 2
UP3 signal for voltage input 3
UP4 signal for voltage input 4
198
Chapter 24 Secondary system supervision
Signal Description
V3P MCB Fail Three phase MCB VT fail
V1P MCB Fail Single phase MCB VT fail
Signal Description
VT Fail VT fail
V1P MCB Fail Single phase MCB VT fail
Table 24-9 Function setting list for fuse failure supervision protection
Table 24-10 Binary setting list for fuse failure supervision protection
199
Chapter 24 Secondary system supervision
Information Description
VT Fail VT failure in circuit of voltage transformer
V1P VT Fail VT failure in circuit of the forth voltage transformer
Minimum zero or negative 0.08Ir to 0.20Ir, step 0.01A ≤ ±5% setting or ±0.02Ir
sequence current
Maximum phase to earth voltage 7.0V to 20.0V, step 0.01V ≤ ±3% setting or ±1 V
Maximum phase to phase 10.0V to 30.0V, step 0.01V ≤ ±3% setting or ±1 V
voltage
Normal phase to earth voltage 40.0V to 65.0V, step 0.01V ≤ ±3% setting or ±1 V
200
Chapter 25 Monitoring function
201
Chapter 25 Monitoring function
2 Self-supervision
All modules can perform self-supervision to its key hardware components
and program as soon as energizing. Parts of the modules are
self-supervised in real time. All internal faults or abnormal conditions will
initiate an alarm. The fatal faults among them will result in the whole IED
blocked
202
Chapter 26 Station communication
203
Chapter 26 Station communication
1 Overview
Each IED is provided with a communication interface, enabling it to connect
to one ormany substation level systems or equipment.
1.1 Protocol
IEC 61850-8-1 allows two or more intelligent electronic devices (IEDs) from
one orseveral vendors to exchange information and to use it in the
performance of their functionsand for correct co-operation.
There is a RJ45 port on the front plate of all the IEDs. Through this port, the
IED can be connected to the personal computer for setting, testing, and
configuration using the dedicated Sifang software tool.
Item Data
Number 1
Connection A RJ45 for software tools
Communication speed 100Mbit/s
205
Chapter 26 Station communication
Item Data
Number 1, only
Connection 2-wire connector
Rear port in communication module
Max. length of communication cable 1.0 km
Test voltage 500 V AC against earth
For IEC 60870-5-103 protocol
Communication speed Factory setting 9600 baud,
Min. 1200 baud, Max. 19200 baud
Item Data
Ethernet communication port
Number 3 RJ45 or 2 optical
Connection RJ45 connector or optical interface
Rear port in communication module
Max. length of communication cable 100m
For IEC 61850 protocol
Communication speed 100 Mbit/s
For IEC 60870-5-103 protocol
Communication speed 100 Mbit/s
Item Data
Mode Pulse mode or optical signal
IRIG-B signal format IRIG-B000
Connection 2-wire connector or optical fiber
Rear port in communication module
Voltage levels differential input
206
Chapter 26 Station communication
Switch
Work Station 3
Gateway Switch
or
converter
Chapter 27 Hardware
208
Chapter 27 Hardware
1 Introduction
1.1 IED structure
The modules can be combined through the bus on the rear board. Both
the IED and the other system can be combined through the rear
interfaces.
X1 X2 X3 X4 X5 X6 X7
POWER OUT DIO CPU DIO AC AC/DIO
When operating keys are pressed or in the case of IED alarming or operating
report appearance, theback light will turn on automatically until the preset
time delay elapse after the latest operation or alarm.
There are 16 LEDs on the panel; they will show the normal/abnormal state of
the equipment. There are 6 Local function buttons on the bottom of the panel,
which are designed for the user for more convenient circuit breaker control in
local mode.
After loading the CPU programme, you should switch the language you want
the relay to display, then press set button, after the relay rebooting, the
language of the relay will be set successfull.
210
Chapter 27 Hardware
1 2
7 Run
3
Alarm
4
5
State Indication LED (From left to right, 1st line, and followed by 2nd line)
There are 16 LEDs, and the function of the LED1 and LED9 are fixed. They
are introduced as following. LED2 ~ LED8, LED10~LED16 are configurable
and can be defined by users and these LEDs can be marshaled in the
following property.
211
Chapter 27 Hardware
Run (LED1) -- The first LED indicator is “Run” indicator, generally the “Run”
indicator keeps constant green and shows that the equipment can work
normally; the green indicator flickers after the protection startup, and the
indicator recovers to constant green after protection equipment is reset; And
when the relay is switched to Unlock state, the “Run” indicator will flicker in
green.
Alarm (LED9) -- When protection operates, this indicator will be light in red.
The LED is latched. The LED does not extinguish until reset is coming even
though the relay was powered off.
QUIT--Quit the sub-menu and return to the upper level menu, or to cancel the
present operation.
Sifang Keyboard--Operation keys. They make the cursor move up, down, left
and right in the menu. The up/down buttons have the ‘+’/ ‘-’ function on
numbers.
LCD--It displays the present measurement, the switch-on connectors and the
single-line diagram of the Bay when there is no operation on the buttons.
These kinds of information are renewed every some seconds. Users can lock
one of them by pressing QUIT button and press it again to return to the cycle
display state. When there is no button pressed on menu operation for 5
minutes the LCD will return to the state of cycle display.
Debug Ethernet port-- PC uses the tool software CSmart Assistant to set the
parameters, test the function, download software and analyze the data. IP
address 196.178.180.66, this IP address cannot be modify
212
Chapter 27 Hardware
The keyboard has the same look and feel in CSC family. As shown in Table
27. The keyboard is divided into Arrow keys, Reset key, Quit key and Set
key. The specific instructions on the keys as the following table described:
Key Function
Up arrow key Move up in menu
Page up between screens
Increase value in setting
Down arrow key Move down in menu
Page down between screens
Decrease value in setting
Left arrow key Move left in menu
Right arrow key Move Right in menu
Reset key Reset the LEDs
Return to normal scrolling display state directly
Set key Enter main menu or submenu
Confirm the setting change
Quit key Back to previous menu
Cancel the current operation and back to previous menu
Return to scrolling display state
Lock or unlock current display in the scrolling display state
(the lock state is indicated by a "solid diamond" type icon
on the botton right corner of the LCD)
213
Chapter 27 Hardware
SecValue DevSta
PryValue Calculate
OpStatus AnalyHarm M&C Link
DI State Sub DI
DO
ViewSet SwSetGr
Settings
WriteSet DelSetGr
EventRpt StartRpt
SOERpt RemCtrRpt
CalRpt
MainMenu
EquipPara OpStatus
ProtSet RePort
CalSetting
Eth 1# Serial
Monitor
Test BO SimuTest
Testing
Test LED GOOSE Test
214
Chapter 27 Hardware
2.3.3 Settings
2.3.4 QueryRpt
215
Chapter 27 Hardware
2.3.5 DevSetup
2.3.6 Print
2.3.7 Testing
216
Chapter 27 Hardware
2.3.8 DevInfo
2.3.9 Connector
3.1 Introduction
The analogue input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers.
217
Chapter 27 Hardware
218
Chapter 27 Hardware
219
Chapter 27 Hardware
36 binary inputs and 24 binary output relays are provided in this module. They
are shown in the terminal figure 27-4 and figure 27-5 below.
The binary inputs relay of input and the pulse width of binary output can be
set in the setting by user themselfs. The range of the setting is from 0s to 10s.
The two binary outputs X5-B06-1/2 and X5-B071/2 are each closure. Take
the binary output X5-B06-1/2 for example, while X5-B06-1 is open, the
X5-B06-2 is close; while X5-B06-1 is close, the X5-B06-2 is open.
220
Chapter 27 Hardware
221
Chapter 27 Hardware
223
Chapter 27 Hardware
224
Chapter 27 Hardware
5 CPU module
5.1 Introduction
The CPU module handles all protection functions and logic, hardware
self-supervision and performs communication and information exchange
between the protection system and external equipments such as HMI, PC,
monitor, control system, substation automation system, engineer station,
RTU and printer, etc. Additionally, the CPU module transmits remote
metering, remote signaling, SOE, event reports and record data. The module
also provides binary inputs, synchronization and communication ports.
The pulse, IRIG-B or SNTP mode can be applied for time synchronization.
225
Chapter 27 Hardware
Terminal Definition
01 485-1A/B+
02 485-1A/B-
03 COM
04 485-2A
05 485-2B
Ethernet Port A Optional optical fiber or RJ45 port for station automation system
Ethernet Port B Optional optical fiber or RJ45 port for station automation system
IRIG-B Optical IRIG-B for station automation system
226
Chapter 27 Hardware
Item Data
Number 1
Connection A RJ45 for software tools
Fixed IP address 196.178.180.66
Communication speed 100 Mbit/s
Item Data
Number 2
Connection 2-wire connector
Rear port in communication module
Max. length of communication cable 1.0 km
Test voltage 500 V AC against earth
For IEC 60870-5-103 protocol
Communication speed Factory setting 9600 baud,
Min. 1200 baud, Max. 19200 baud
Item Data
Electrical communication port
Number 0 to 3
Connection RJ45 connector or optical interface
Rear port in communication module
Max. length of communication cable 100m
For IEC 61850 protocol
Communication speed 100 Mbit/s
For IEC 60870-5-103 protocol
Communication speed 100 Mbit/s
227
Chapter 27 Hardware
Item Data
Mode Pulse mode or optical IRIG-B
IRIG-B signal format IRIG-B000
Connection 2-wire connector or fiber connector
Rear port in communication module
Voltage levels differential input
228
Chapter 27 Hardware
6.1 Introduction
The power supply module is used to provide the correct internal voltages
and full isolation between the terminal and the battery system.The module
provides 9 binary input channels as well.
229
Chapter 27 Hardware
Terminal Definition
230
Chapter 27 Hardware
231
Chapter 27 Hardware
GB/T 15145-2001
DL/T 478-2001
Protective bonding resistance IEC60255-27 ≤ 0.1Ω
Fire withstand/flammability IEC60255-27 Class V2
232
Chapter 27 Hardware
233
Chapter 27 Hardware
234
Chapter 27 Hardware
Item Data
-10 °C to +55°C (Legibility of display may be
Recommended permanent operating temperature
impaired above +55 °C /+131 °F)
Storage and transport temperature limit -25°C to +70°C
Permissible humidity 95 % of relative humidity
Item Data
Case size 4U×1/2 19inch
Weight ≤ 5kg
6.6 CE certificate
Item Data
EN 61000-6-2 and EN61000-6-4 (EMC Council
EMC Directive
Directive 2004/108/EC)
Low voltage directive EN 60255-27 (Low-voltage directive 2006/95 EC).
235
Chapter 27 Appendix
Chapter 28 Appendix
236
Chapter 27 Appendix
237
Chapter 27 Appendix
238
Chapter 27 Appendix
stage 1. 1-On;0-Off.
Second harmonic Blocking for
4. OC1 2H_Blk On 1/0 0
overcurrent stage 1. 1-On;0-Off.
5. OC2 Inv On
Direction for overcurrent stage 1
6. OC2 Dir On 1/0 0
1-On;0-Off.
Direction toward for overcurrent
7. OC2 Dir FWD 1/0 0
stage 1. 1-Forward; 0-Reverse.
Low voltage blocking for overcurrent
8. OC2 V_ Blk On 1/0 0
stage 1. 1-On;0-Off.
Second harmonic Blocking for
9. OC2 2H_Blk On 1/0 0
overcurrent stage 1. 1-On;0-Off.
10. OC3 Inv On
Direction for overcurrent stage 1
11. OC3 Dir On 1/0 0
1-On;0-Off.
Direction toward for overcurrent
12. OC3 Dir FWD 1/0 0
stage 1. 1-Forward; 0-Reverse.
Low voltage blocking for overcurrent
13. OC3 V_ Blk On 1/0 0
stage 1. 1-On;0-Off.
Second harmonic Blocking for
14. OC3 2H_Blk On 1/0 0
overcurrent stage 1. 1-On;0-Off.
15. OC4 Inv On
Direction for overcurrent stage 1
16. OC4 Dir On 1/0 0
1-On;0-Off.
Direction toward for overcurrent
17. OC4 Dir FWD 1/0 0
stage 1. 1-Forward; 0-Reverse.
Low voltage blocking for overcurrent
18. OC4 V_ Blk On 1/0 0
stage 1. 1-On;0-Off.
Second harmonic Blocking for
19. OC4 2H_Blk On 1/0 0
overcurrent stage 1. 1-On;0-Off.
20. OC2 Trip On 1/0 0
21. OC3 Trip On 1/0 0
22. OC4 Trip On 1/0 0
23. EF1 Dir On 1/0 0
24. EF1 Dir FWD 1/0 0
25. EF1 2H_Blk On 1/0 0
26. EF2 Inv On 1/0 0
27. EF2 Dir On 1/0 0
28. EF2 Dir FWD 1/0 0
239
Chapter 27 Appendix
240
Chapter 27 Appendix
On
242
Chapter 27 Appendix
243
Chapter 27 Appendix
for stage4
0: Defined by user
1:IEC NI
2: IEC VI
3: IEC EI
4: IEC LTI
5: ANSI MI
13. OC4 Inv CRV SEL 0~11
6: ANSI VI
7: ANSI EI
8:ANSI INV
9:ANSI SI
10:ANSI LI
11:ANSI DI
14. A_OC4 Inv 0.001~1000 s
15. P_OC4 Inv 0.01~10.00
Inverse characteristic
16. B_OC4 Inv 0.000~100.00 s
17. K_OC4 Inv 0.025~1.5
Low voltage blocking for
18. U_OC_UnBlk 1.00~120.0 V
Overcurrent.
19. U2_OC_UnBlk 1.00~120.0 V
Overcurrent setting for
20. Angle_OC 0.00~90.00 degree
directional element
21. I_2H_UnBlk 0.05~100 A
22. Ratio_I2/I1 0.07~0.50
23. T2H_Cross_Blk 0.00~100.0 s
24. 3I0_EF1 0.05~100 A
25. T_EF1 0.00~100.0 s
26. 3I0_EF2 0.05~100 A
27. T_EF2 0.00~100.0 s
28. EF2 Inv CRV SEL 1~11
29. K_EF2 Inv 0.025~1.5
30. 3I0_EF3 0.05~100 A
31. T_EF3 0.00~100.0 s
32. EF3 Inv CRV SEL 1~11
245
Chapter 27 Appendix
246
Chapter 27 Appendix
247
Chapter 27 Appendix
248
Chapter 27 Appendix
249
Chapter 27 Appendix
5. CT Fail On
250
Chapter 27 Appendix
1 F_Startup 45.00~60 Hz
2 F_LF LS1 45.00~60 Hz
3 T_LF LS1 0.100~100.0 s
4 F_LF LS2 45.00~60 Hz
5 T_LF LS2 0.100~100.0 s
6 F_LF LS3 45.00~60 Hz
7 T_LF LS3 0.100~100.0 s
8 F_LF LS4 45.00~60 Hz
9 T_LF LS4 0.100~100.0 s
10 df/dt_ACC1 0.300~20 Hz/s
11 Tf_ACC1 0.100~100.0 s
12 df/dt_ACC2 0.300~20 Hz/s
13 Tf_ACC2 0.100~100.0 s
14 df/dt_LF LS 0.300~20 Hz/s
15 U_Startup 30.00~110 V
16 U_LV LS1 30.00~110 V
17 T_LV LS1 0.100~100.0 s
18 U_LV LS2 30.00~110 V
19 T_LV LS2 0.100~100.0 s
20 U_LV LS3 30.00~110 V
21 T_LV LS3 0.100~100.0 s
22 U_LV LS4 30.00~110 V
23 T_LV LS4 0.100~100.0 s
24 du/dt_ACC1 1.00~200.0 V/s
25 Tv_ACC1 0.100~100.0 s
26 du/dt_ACC2 1.00~200.0 V/s
27 Tv_ACC2 0.100~100.0 s
28 du/dt_LV LS 1.00~200.0 V/s
251
Chapter 27 Appendix
29 I_Startup 30.00~110 A
30 I_OL LS1 30.00~110 A
31 T_OL LS1 0.100~100.0 s
32 I_OL LS2 30.00~110 A
33 T_OL LS2 0.100~100.0 s
34 I_OL LS3 30.00~110 A
35 T_OL LS3 0.100~100.0 s
36 I_OL LS4 30.00~110 A
37 T_OL LS4 0.100~100.0 s
38 df/dt_OL LS 0.3~20.0 Hz/s
39 du/dt_OL LS 1.00~200.0 V/s
40 U_Chk 10.00~120.00 V
41 I_Chk 0.00~20.00 A
42 T_CB Faulty 0.100~100.0 S
252
Chapter 27 Appendix
253
Chapter 27 Appendix
254
Chapter 27 Appendix
255
Chapter 27 Appendix
Two kinds of alarm report are included in the IED, which are shown in the
following table:
Alarm I is severe alarm. When alarm I happens, the alarm LED on the
front panel of the IED will flash, all of protection function will be out of
service and the trip power of protection will be blocked by the IED.
Alarm II is other alarm. When alarm II happens, the alarm LED on the
front panel of the IED will flash (except “BI Set SetGr2” and “BI Set
SetGr1”), and will not block the trip power of protection.
256
Chapter 27 Appendix
257
Chapter 27 Appendix
3 Typical connection
A. For incoming or outgoing feeder protection or line backup
protection
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
Figure 28-1 Application of feeder protection to measure three phase and earth currents
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
Figure 28-2 Application of feeder protection to measure three phase and earth currents and
three phase voltages (bus side)
258
Chapter 27 Appendix
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
Figure 28-3 Application of feeder protection to measure three phase and earth currents and
three phase voltages (line side)
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
259
Chapter 27 Appendix
Figure 28-4 Application of feeder protection to measure three phase and earth currents and
single phase voltage (Ph-Ph) (bus side)
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
Figure 28-5 Application of feeder protection to measure three phase and earth currents and
single phase voltage (Ph-E) (bus side)
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
I01
*
I1
I02
260
Chapter 27 Appendix
Figure 28-6 Application of feeder protection to measure three phase currents, earth current,
and sensitive earth current
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08
IN
AIM1
I01
*
I1
I02
Figure 28-7 Application of feeder protection to measure three phase currents, earth current
and sensitive earth current, and three phase voltages (bus side)
261
Chapter 27 Appendix
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM1
* I01
I1
I02
Figure 28-8 Application of feeder protection to measure three phase currents, earth current
and sensitive earth current, and three phase voltages (line side)
262
Chapter 27 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I1
I02
Figure 28-9 Application of feeder protection to measure three phase currents, earth current
and sensitive earth current, and single phase voltage (Ph-Ph) (bus side)
263
Chapter 27 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I1
I02
Figure 28-10 Application of feeder protection to measure three phase currents, earth
current, and sensitive earth current, and single phase voltage (Ph-E) (bus side)
264
Chapter 27 Appendix
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02
I1
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
265
Chapter 27 Appendix
A
B
C
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM1
* I01
I02 I1
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
266
Chapter 27 Appendix
A
B
C
AIM2
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
AIM1
* I01
I02 I1
A
B
C
A
B
C
AIM2
U05
U4
U06
U01
UA
U02
UB
U03
UC
U04
UN
267
Chapter 27 Appendix
A
B
C
AIM2
U05
U4
U06
U01
UA
U02
UB
U03
UC
U04
UN
AIM2
I01
I02 IA
I03
I04 IB
* * * I05
I06 IC
I07
I08 IN
Figure 28-17 Typical connection for synch-check and feeder current protection
268
Chapter 27 Appendix
A
B
C
I04 IC1
* I05
I06
IC2
* I07
I08 IC3
Figure 28-18 Typical connection for capacitor bank unbalanced current protection with
three current inputs
A
B
C
U06 UC2
U07
U08 UC3
Figure 28-19 Typical connection for capacitor bank unbalanced voltage protection with
three voltage inputs
269
Chapter 27 Appendix
A
B
C
I04 IC1
*
I05
I06
IC2
I07
I08 IC3
Figure 28-20 Typical connection for capacitor bank unbalanced current protection with one
current input
A
B
C
AIM1
Capacitor bank U03
U04 UC1
U05
U06 UC2
U07
U08 UC3
Figure 28-21 Typical connection for capacitor bank unbalanced voltage protection with one
voltage input
270
Chapter 27 Appendix
A A
B
B C
C
I1
I1 I2
I3
A A
B B
C C
U1
I1
A A
B
B C
C
U1
I1
Figure 28-24 Neutral current protection Figure 28-27 Neutral voltage unbalanced
for ungrounded split-Wye capacitor bank detection for ungrounded split-Wye
capacitor bank
271
Chapter 27 Appendix
A A
B
C B
C
U1
U1
U1 U1
U2
U3
Figure 28-29 Neutral voltage unbalance
Figure 28-31 Three unbalanced voltages
detection by 3VTs for unrounded Wye
detection for Capacitor Bank
capacitor bank
272
Chapter 27 Appendix
273
Chapter 27 Appendix
8 ANSI MODERATELY
0.0103 0.02 0.0228
INV.
= ( )T
()
274
Chapter 27 Appendix
where:
275
Chapter 27 Appendix
0.001
0.0001
1 10 100
Id/I_Inv
276
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC INV. Curve in the
following figure:
1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1.0
K=1.25
0.1
0.01
1 10 100
I/Is
277
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC VERY INV. Curve in
the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
278
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC EXTREMELY INV.
Curve in the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
279
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the IEC LONG INV. Curve in
the following figure:
1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.1
0.01
1 10 100
I/Is
280
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ASNI INV. Curve in the
following figure:
10
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
281
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI SHOTR INV.
Curve in the following figure:
0.1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
0.0001
I/Is
282
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI LONG INV. Curve
in the following figure:
1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
K=1.5
0.1
0.01
1 10 100
I/Is
283
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI MODETATELY INV.
Curve in the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
284
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSIVERY INV. Curve
in the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
285
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI EXTREMELY INV.
Curve in the following figure:
0.1
Time in Seconds
K=0.025
K=0.2
K=0.5
K=1
0.01
K=1.5
0.001
1 10 100
0.0001
I/Is
286
Chapter 27 Appendix
Where K=0.025, K=0.2, K=0.5, K=1 and K=1.5 the ANSI DEFINITE INV.
Curve in the following figure:
1
Time in Seconds
K=0.025
0.1 K=0.2
K=0.5
K=1
K=1.5
0.01
0.001
1 10 100
I/Is
287
Chapter 27 Appendix
5 CT Requirement
5.1 Overview
In practice, the conventional magnetic- core current transformer (hereinafter
as referred CT) is not able to transform the current signal accurately in whole
fault period of all possible faults because of manufactured cost and
installation space limited. CT Saturation will cause distortion of the current
signal and can result in a failure to operate or cause unwanted operations of
some functions. Although more and more protection IEDs have been
designed to permit CT saturation with maintained correct operation, the
performance of protection IED is still depended on the correct selection of CT.
Class P CT
Class PR CT
CT with limited remanence factor for which, in some cased, a value of the
secondary loop time constant and/or a limiting value of the winding
resistance may also be specified.
Class PX CT
Class TPS CT
Class TPX CT
288
Chapter 27 Appendix
Class TPY CT
Class TPZ CT
289
Chapter 27 Appendix
For different protections, Ipcf is the selected fault current in proper fault
position of the corresponding fault, which will flow through the verified CT.
Lastbut not least, Ipcf calculation should be based on the future possible
system power capacity
𝐼
=
𝐼
[ 𝑡 𝑑 ]
>
[ 𝑡 𝑑 ]
290
Chapter 27 Appendix
5.4.2 CT class
The selected CT should guarantee that the error is within the required
accuracy limit at steady symmetric short circuit current. The influence of short
circuit current DC component and remanence should be considered, based
on extent of system transient influence, protection function characteristic,
consequence of transient saturation and actual operating experience. To fulfill
the requirement on a specified time to saturation, the rated equivalent
secondary e.m.f of CTs must higher than the required maximum equivalent
secondary e.m.f that is calculated based on actual application.
For TPS class CT, Eal (rated equivalent secondary limiting e.m.f) is generally
determined as follows:
= 𝐼 ( 𝑡 )
Where
For TPX, TPY and TPZ class CT, Eal (rated equivalent secondary limiting
e.m.f) is generally determined as follows:
= 𝑡𝑑 𝐼 ( 𝑡 )
Where
291
Chapter 27 Appendix
For the CTs applied to 110 - 220kV voltage level transmission line protection,
110 - 220kV voltage level transformer differential protection, 100-200MW
generator-transformer set differential protection, and large capacity motor
differential protection, the influence of system transient state to CT is so less
that the CT selection is based on system steady fault state mainly, and leave
proper margin to tolerate the negative effect of possible transient state.
Therefore, P, PR, PX class CT can be always applied.
For P class and PR class CT, Esl (the rated secondary limited e.m.f) is
generally determined as follows:
= 𝐼 ( 𝑡 )
= 𝐼 ( 𝑡 )
For the CTs applied to protection for110kV voltage level and below system,
the CT should be selected based on system steady fault state condition. P
class CT is always applied.
The CT accuracy class should guarantee that the protection relay applied is
able to operate correctly even at a very sensitive setting, e.g. for a sensitive
residual overcurrent protection. Generally, the current transformer should
have an accuracy class, which have an current error at rated primary current,
that is less than ±1% (e.g. class 5P).
If current transformers with less accuracy are used it is advisable to check the
actual unwanted residual current during the commissioning.
292
Chapter 27 Appendix
5.4.4 Ratio of CT
The current transformer ratio is mainly selected based on power system data
like e.g. maximum load. However, it should be verified that the current to the
protection is higher than the minimum operating value for all faults that are to
be detected with the selected CT ratio. The minimum operating current is
different for different functions and settable normally. So each function should
be checked separately.
Too high flux will result in CT saturation. The secondary e.m.f is directly
proportional to linked flux. To feed rated secondary current, CT need to
generate enough secondary e.m.f to feed the secondary burden.
Consequently, Higher secondary burden, need Higher secondary e.m.f, and
then closer to saturation. So the actual secondary burden R’b must be less
than the rated secondary burden Rb of applied CT, presented
Rb > R’b
The CT actual secondary burden R’b consists of wiring loop resistance Rlead
and the actual relay burdens Zb in whole secondary circuit, which is
calculated by following equation
R’b = Rlead + Zb
= 2
𝐼
Where
Sr: the burden of IED current input channel per phase, in VA;
For earth faults, the loop includes both phase and neutral wire, normally twice
the resistance of the single secondary wire. For three-phase faults the neutral
current is zero and it is just necessary to consider the resistance up to the
293
Chapter 27 Appendix
point where the phase wires are connected to the common neutral wire. The
most common practice is to use four wires secondary cables so it normally is
sufficient to consider just a single secondary wire for the three-phase case.
protection
> { , " , }
Where
𝐼
=
𝐼
𝐼"
" =
𝐼
> 𝑡𝑑 𝐼 ( 𝑡 )
Where
294
Chapter 27 Appendix
[ 𝑡 ]
>
[ 𝑡 ]
Where
= { , " , }
𝐼
=
𝐼
𝐼"
" =
𝐼
> = 𝐼 [ 𝑡 ]
Where
> = 𝐼 [ 𝑡 ]
Where
protection
>
Where
𝐼
=
𝐼
> 𝑡𝑑 𝐼 ( 𝑡 )
295
Chapter 27 Appendix
Where
[ 𝑡 ]
>
[ 𝑡 ]
Where
𝐼
=
𝐼
> = 𝐼 [ 𝑡 ]
Where
> = 𝐼 [ 𝑡 ]
Where
296