Half Cell Potential Studies for Durability Studies of


Concrete Structures in Coastal Environment

V L Satish1,
Engineer SF- ISRO, SDSC SHAR, Sriharikota & Research Scholar JNTU College of Engg Kakinada,
isrosatish@gmail.com
More info about this article: http://www.ndt.net/?id=26122

Abstract: The aspects of concrete durability and performance have become a major subject of discussion especially when the
concrete is subjected to severe environment. Due to the saline and aggressive atmospheric conditions at SHAR (Sriharikota, AP,India,
the only Space port of India), the durability of structures has become a matter of concern. Reinforced concrete is one of the most
common materials used in most of the structures here. The Non Destructive Test (NDT) studies viz, Rebound hammer test, UPV test,
Core test, Half cell survey, Chlorides, sulpahtes, Carbonation test etc were conducted on some old buildings at Sriharikota island.
Half – cell potential (HCP) survey using Copper-Copper sulphate half-cell was conducted on RCC members, where corrosion
symptoms were observed. The HCP values observed indicated Probability of different corrosion stages in reinforcement present in
the structure. Studies revealed that Chloride induced reinforcement corrosion is the predominant reason for the early deterioration of
RC structures here.

This paper attempts to present the results of NDT studies conducted on old buildings at SHAR island with emphasis on the Half-cell
Potential Test studies.

Keywords: NDT, Coastal environment, Half-cell potential Test, Chloride content, Corrosion.

1. Introduction
Durability of cement concrete is defined as its ability to resist weathering action, chemical attack, abrasion or any other
process of deterioration. Durable concrete will retain its original form, quality and serviceability when exposed to
environment.” [1]. Deterioration of reinforced concrete structures results from external factors or causes within the
concrete itself. Deterioration rate of structures depends on the exposure conditions and extent of maintenance. External
chemical attack occurs mainly through the action of aggressive ions, such as chlorides, sulphates or carbon dioxide, as
well as many natural or industrial liquids and gases. Corrosion of steel bars is a main factor affecting both the concrete
durability and strength. Usually, there are two major factors which cause corrosion of rebars in concrete structures,
carbonation and ingress of chloride ions. When chloride ions penetrate in concrete more than the threshold value or
when carbonation depth exceeds concrete cover, then it initiates the corrosion of RC structures.

Concrete normally provides a high degree of protection to the reinforcing steel against corrosion, by virtue of the high
alkalinity (pH 13.5) of the pore solution. Under high alkalinity steel remains passivized. In addition, well consolidated
and purely cured concrete with low water cement ratio has a low permeability, which minimizes the penetration of
corrosion inducing agents such as chlorides, CO2, moisture etc. to steel surfaces.

After the initiation of corrosion in steel rebars, products of corrosion tend to expand and occupy a volume of about 6–
10 times greater than that of steel resulting in the formation of cracks and finally spalling of concrete surfaces occurs as
shown in Figures 1 and 2.
2 NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . .

Fig 1: Cracks in beams indicate corrosion of reinforcement Fig 2 : Spalling of cover concrete & severe corrosion in
beams

In a study by Elsener et al., 2003 [2], the evaluation parameters that are required to ensure a sound decision on repair
scheme/ developing a maintenance strategy are as follows:
 Reasons for damage or loss of protection –
 degree and amount of damage –
 progress of damage with time –
 effect of damage on structural behaviour and serviceability.
Obtaining reliable information on stage and rate of deterioration is done during regular inspections relying on visual
examination of the whole structure. If no reliable conclusion on the state of the structure can be obtained, an additional
inspection (verification) including non-destructive testing is warranted.

Due to the saline and aggressive atmospheric conditions at SHAR (Sriharikota), the durability of structures has become
a major concern. As per the report of CECRI Karaikudi, the region of Sriharikota is one of the extremely corrosive
places in India. Sriharikota is the most corrosive area with corrosion rate of mild steel of 1.6 mm per year [3].

In the present study, to assess the condition of buildings using the Visual observations and the Non-Destructive (ND)
tests, such as Profometer survey, Rebound Hammer test and Ultrasonic pulse velocity test were carried out. Also, the
other Partially Destructive tests like Core sampling, Evaluation of Electrochemical parameters of concrete (pH, S, Cl-),
Half-cell potential survey etc. were carried out. The details of the Half-cell potential studies, analysis and conclusions
are presented in the subsequent sections.

2 Coastal Concrete Structures and Chloride effect


Structures in coastal areas are prone to corrosion related problems. Corrosion destructs the parent material by reaction
with its environment and it constitutes one of the basic factors of degradation of reinforced concrete structures. The
presence of coastal environment, which is rich in chloride ions, is considered as one of the major external factors
inducing damage on reinforced concrete structures. The fundamental problem corresponding to the chloride movement
is the initial concentration of chlorides when spread in the concrete.
NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . . 3

Fig. 3 Chloride concentration at different depths for bridges exposed to sea (Source: Mohammed, 2018)

The general plot of the curve of the changing chloride concentration with depth in the concrete is explained in Figure
3. From this figure, we note that the concentration of chlorides is reduced rapidly whenever propagation occurs inside
the concrete. It can also be seen that the chloride concentration with depth varies as a simple parabolic curve.

Fig. 4 Structure Corrosion Risk based on the distance from coast (Source: Mohammed, 2018)

Chloride can be in the form of a spray in the air when the coastal environment surrounds the structure. For example
we can consider a structure or a building under construction near the shore in a coastal area wherein the chloride effect
can be seen clearly. Figure 4 shows the intensity of risk posed to a structure according to its location in terms of its
distance from the coast and also in terms of height. However, these data shall not be taken as it is, but only as a guide
to determine the degree of risk, depending on the climatic conditions of the region [4].

3 Half – Cell Electrical Potential Method to measure Corrosion of Reinforcement in Concrete


(ASTM C 876- 91)

Since 1978 Half Cell Potential mapping [5] is in vogue for detecting corroding areas on concrete structures in Denmark.
The Half Cell Potential Testing method is suggested for diagnosing the probability of reinforcement corrosion in turn
which is used for assessment of the durability of reinforced concrete [5,6]. Corrosion inspection of steel can be
conducted by many different techniques. Non-destructive technique such as half-cell potential measurement (HCP) is a
well known technique for investigation of corrosion in steel [7]. Even though there are many methods for evaluating
4 NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . .

the corrosion, half-cell potential has been considered useful by many researchers as the main method to detect the
corrosion activity in RC structures [8].

3.1 Description of method:

Corrosion of steel can be assessed by Half-Cell Potential (HCP) measurement by an electrochemical process as per
ASTM C87. In this method, the electrical potential difference between the upper steel rebars and a standard portable
reference electrode in contact with the concrete surface is measured. The half-cell is made by a Copper/ Copper Sulphate
or Silver/ Silver Chloride cell but other combinations are also used. The concrete acts as an electrolyte and the risk of
corrosion of steel reinforcement in immediate region of the test location may be related empirically to the measured
potential difference.

The schematics of the test and equipment is shown Fig. 5. It consists of a rigid tube composed of dielectric material that
is non-reactive with copper or copper sulphate, a porous wooden or plastic plug that remains wet by capillary action,
and a copper rod that is immersed within the tube in a saturated solution of copper sulphate. The schematics of the
electrode is shown in figure 6. The reference electrode is connected to the positive end of the high impedance voltmeter
and the steel reinforcement to the negative. At the anode, the ferrous ions (Fe++) are dissolved and electrons are set
free. These electrons drift the steel to the cathode, where they form hydroxide (OH-). This principle creates a potential
difference that can be measured by the half-cell method.

Fig 5 Schematics showing the Half Cell Potential Measurement Technique (www.proceq.be)
NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . . 5

Fig.6. Schematic of Copper Sulphate electrode

The reliability of half-cell potential measurement as an indication of corrosion potential has evolved by the good results
during the bridge deck corrosion surveys. An indication of the relative probability of corrosion activity was empirically
obtained through measurements during the 1970s [9]. This work formed the basis of the ASTM standard C876, which
provides general guidelines for evaluating corrosion in concrete structures as outlined in Table 1:

Table 1. Probability of Corrosion according to half-cell potential values

Half Cell Potential Value ( mV) Corrosion activity

More negative than -350 mV >95%

-200 mV to -350 mV 50%

More Positive than -200 mV <5%

Measured half-cell potential values can be plotted to obtain the potential contour for the surface of reinforced concrete
structure and this potential contour map as shown in Figure 7 can be used to evaluate the probability of corrosion at
different areas on the surface of the concrete structures. Portions of the structures where high corrosion activity is
prevalent can be obtained and identified by their high negative potentials.
6 NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . .

Fig. 7. Half Cell Potential Contour

3.2 Equipment Used

Following are the equipment used for corrosion monitoring of reinforcement in concrete (Fig. 8& 9). The measurement
of HCP values carried out at site is shown in figure 10.

Fig. 8. Basic Half cell survey equipment Fig. 9. Reference electrode(CuSo4)

Fig. 10. HCP measurement at site


NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . . 7

3.3 Precautions for Taking Half-Cell Potential Measurements

A reliable half-cell potential survey for assessing the corrosion damage of a reinforced concrete structure requires
good planning and preparation, careful measurement and data correlation. The method specified by ASTM C876 is a
satisfactory measurement procedure to follow.
The following data should be taken before starting the HCP measurement:
• Basic information about the structure such as structural drawings, mix design details, concrete admixture details,
cover meter survey details etc.,
• The history of previous repair and rehabilitation including patch repair
• Earlier conducted condition survey details, visual examination data and delamination survey results, and chloride
content analysis.
The half-cell potential data should always be validated by other testing methods before an interpretation of corrosion
probability is made. Many methods are commonly used along with the half-cell potential technique in field assessment
of corrosion like visual inspection, delamination survey, chloride content measurement, concrete resistance
measurement, concrete cover-depth survey, carbonation profile determination etc.,

4 Present Study

Under this study some buildings which are having an age of approximately 40 years were selected to assess the structural
condition of the buildings. The buildings are located at Sriharikota Island, India. It is prone to severe weather phenomena
like tropical cyclones, thunderstorms, and squally weather. SHAR being a coastal area, it experiences sea breeze and
land breeze also. The half cell potential studies conducted on these buildings are presented and analysed in this paper.

4.1 Case study 1 (Colony PHC). Under this study some residential buildings which were built approximately 40 years
back were selected to check the corrosion potential. The buildings are located at Sriharikota Island. These buildings are
built during the year approximately during 1975-76. The building units are Ground + 2 units with Load bearing structure
with RCC roof slab and other RCC elements like staircase, chajjas etc. The Grade of concrete adopted during
construction is M15.

Rebound hammer Test and UPV Values. Rebound hammer test values (RHV) on the surface at grid points and on
the surface (at Random locations) in the slab portions, wherever taken are uniform. However higher compressive
strength in some RCC members indicated carbonated cover concrete. The average compressive strength is about 25
N/Sqmm. It is observed from the Ultrasonic pulse velocity test results that the Slabs, columns & beams tested, have
concrete integrity range from doubtful to good. Some of the UPV values indicate that the concrete possess voids (honey
combed in the interior portions).

Core Test. The mean compressive strength of cubes obtained is about 16 N/ Sqmm which is satisfactory with respect
to the design strength of 15 N/ sqmm.

Carbonation test & Chloride Tests. The in-situ carbonation tests on Slabs, Beam, and column indicate that
reinforcements are corroded due to carbonated layer reaching up to concrete cover thickness after the carbonation test.
In the quarters, out of 14 tests, about 9 samples have shown signs of carbonation. The Chloride content as Cl- in the
reference quarter is about 0.8 to 1%. The Chloride content as Cl- in the WTP is about 0.6 to 5%.

Results of Half –Cell Potential (HCP) Survey (Colony PHC).


Half – cell potential survey using Copper-Copper sulphate half-cell was conducted on RCC members, where corrosion
symptoms were observed. The HCP values observed show 50% probability of corrosion in some of the quarters tested.
8 NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . .

A total of 18 data sets were collected for reference quarter building. The measurements were taken at random spots over
the different structural elements. Refer to Table 2 data showing the minimum and maximum values obtained at the
various locations.
Table 2: Maximum and minimum values of the HCP readings (Qrtr Building).

Ref Quarter HCP Value ( mV) Data sets


Bldg collected
Max Min
Room 1 -177 -290 6
Room 2 -126 -169 6
Room 3 -7 -74 6

Table 3: Maximum and minimum values of the HCP readings (Treatment Plant Building).
HCP Value ( mV) Data sets
WTP Bldg
Max Min collecetd

Chemical room -102 -176 6


Clarifier -24 -45 6
Flocculator -282 -313 6
Entry area -282 -313 6

It can be seen that the readings ranged from -7 mV to -290 mV. All the data obtained has also been plotted in a histogram
shown in Fig. 11. The mean half-cell potential reading was -135 mV for quarter building and -195 for the WTP building.
The HCP values observed in SHAR CAMPUS the readings showed more positive. The HCP values of the WTP building
indicates Probability of 50% corrosion activity present in the reinforcement.

14
12
10
8
Count

6
4
2
0
-350 -300 -250 -200 -150 -100 -50 0
HCP Values (mV)

Fig 11: Histogram of the half-cell potential measurements data (PHC)


4.2 CASE STUDY 2 (Colony DOS- A type qrtr buildings):
These are residential buildings which were built approximately 40 years back were selected to check the corrosion
potential. The buildings are located at Sullurupeta town which is near by Sriharikota Island. The building units are
Ground + 2 units with Load bearing structure with RCC roof slab and other RCC elements like staircase, chajjas etc.
The Grade of concrete adopted during construction is M15 to M20.
NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . . 9

Rebound hammer Test and UPV Values. Rebound hammer test values indicated higher compressive strength in some
RCC members. The average compressive strength is about 27 N/Sqmm. It is observed from the Ultrasonic pulse velocity
test results ranged about 2 km/s indicating doubtful integrity of concrete.

Results of Chloride content Tests DOS).The Chloride content as Cl- are very high in some quarters 0.4 to 1% even
after hydration. The chloride are normally contributed by added water in the concrete mix.

Results of Half –Cell Potential (HCP) Survey (Colony DOS). A total of 90 data sets were collected for reference
quarter building (DOS- A type qrtr buildings). The measurements were taken at random spots over the different
structural elements. Refer to Table 4 data showing the minimum and maximum values obtained at the various locations.
It can be seen that the readings ranged from -130 mV to -408 mV. All the data obtained has also been plotted in a
histogram shown in Fig. 12. The mean half-cell potential reading was -294 mV for these quarter buildings. The HCP
values indicates Probability of 50% to 95% corrosion activity present in the reinforcement.

Table 4: Maximum and minimum values of the HCP readings (A type Qrtrs- DOS).

Ref Quarter HCP Value ( mV) Data sets


Bldg collected
Max Min
A26 to A30 -264 -385 18
A4 to A26 -190 -408 42
A26 to A30
staircases -130 -357 12
A2 to A16 -237 -349 18

50

40

30
Count

20
Frequency
10

0
-400 -300 -200 -100 0 50 More
HCP Values (mV)

Fig. 12. Histogram of the half-cell potential measurements data (DOS)

4.3 CASE STUDY 3 (Storage Bldgs I & II)


Under this study two industrial buildings which are used for Storage & integration activities in the initial days (year
1980). The building consists of two independent shed structures namely -I & II. The shed structures consist of R.C.C.
column – beam framework and are covered with roofing sheets supported on structural steel trusses and purlins. The
space available in between two sheds is covered with R.C.C. slab and merged with two sheds. The Grade of concrete
adopted during construction is M 20 to M 25.
10 NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . .

Results of Half –Cell Potential (HCP) Survey (Storage Bldgs I & II). Half-cell Potentiometer test is performed at
103 numbers of test locations on columns and east side RCC wall cladding of buildings-I & II. Refer to Table 5 data
showing the minimum and maximum values obtained at the various locations. It can be seen that the readings ranged
from -11 mV to -198 mV. All the data obtained has also been plotted in a histogram shown in Fig. 13. The mean half-
cell potential reading was -90 mV for these quarter buildings. The HCP values indicates 10 % probability (mild risk) of
active corrosion.

180
160
140
120
100
Count

80
60 Frequency
40
20
0
-50

50
0
-250
-200
-150
-100

Half Cell potential Values (mV) More

Fig 13: Histogram of the half-cell potential measurements data (Storage Bldgs I & II)

Results of Chloride content Tests (Storage Bldgs I & II). Chlorides: As per IS: 456:2000, Clause 8.2.5.2, Table 7,
limit of chloride content of concrete (maximum total acid soluble chloride content) is 0.025%. The chemical analysis
of 13 nos. of concrete powder samples out of 20 samples of VIB-I & II indicates chloride content of 0.1%.

5 Discussions & Conclusions:

 The corrosion rate is the main factor to be taken into consideration in framing up the maintenance strategy.
 The Half Cell Potential Testing method is a technique, used for assessment of the durability of reinforced
concrete and helps in diagnosing reinforcement corrosion. A more negative reading of potential is generally
considered to indicate a higher probability of corrosion.
 In both the housing units (case study 1 & case study 2) the half-cell potential values indicate 50% probability
for corrosion. This can be attributed to the inadequate cover to reinforcement, or lack of compaction of cover
concrete resulting in porous micro structure which is visible in the site. Also, there are many leakage areas which
might have contributed to the local corrosion spots. There is possibility of chlorides permeate into concrete from
its ingredients or penetrated from the surrounding chloride laden environment.
 In case study 3 the half-cell potential values indicate 10% probability for corrosion. For this structure which is
of age equal to the housing units, the corrosion level is very low. This can be attributed to the adequate cover
and well finished and hard surfaces.
 The HCP survey values correlate to the chloride content tested in the concrete
 Several research studies revealed that half-cell potential measurement only indicates the corrosion probability at
a given location and time. Long-term testing by measuring the half-cell potential values may be appropriate.
 Corrosion rate in a concrete structure is governed by several parameters such as moisture content, availability
of oxygen, temperature etc. Hence, for genuine assessment, it may be appropriate to repeat corrosion rate
measurements in regular time intervals considering the environmental factors.
NDE2020, 013, v1: ’Half Cell Potential Studies for Durability Studies of Concrete Structu . . . 11

References

1. American Concrete Institute (2001), “Guide to Durable Concrete”, ACI COMMITTEE REPORT.
2. B. Elsener, C. Andrade, J. Gulikers, R. Polder and M. Raupach (2003) “Half-cell potential measurements- Potential
mapping on reinforced concrete structures” Materials and Structures / Matrriaux et Constructions, Vol. 36, pp 461-471
3. Natesan, Venkatachari and N Palaniswamy ; (2005) “Corrosivity and durability maps of India” 2004, CECRI, Karaikudi,
lndia.,e- library krc.cecri.res.in/ro_2005/013-2005
4. Mohammed Abdallah El-Reedy, (2018) Steel-Reinforced Concrete Structures Assessment and Repair of Corrosion Second
Edition, CRC Press
5. ASTM C 876-91 (Reapproved 1999), “Standard Test Method for Half-cell Potentials of Uncoated Reinforcing Steel in
Concrete,” Annual Book of ASTM Standards, 03.02 (2006), 11-16.
6. RILEM TC 154-EMC, “Electrochemical Techniques for Measuring Metallic Corrosion” Recommendations, “Halfcell
potential measurements – Potential mapping on reinforced concrete structures,” Materials and Structures. 36 August -
September (2003), 461-471.
7. Chansuriyasak , Wanichlamlart , Sancharoen, Kongprawechnon and Tangtermsiriku (2010), Comparison between half-cell
potential of reinforced concrete exposed to carbon dioxide and chloride environment, Songklanakarin J. Sci. Technol. 32
(5), 461-468
8. Song H and V. Saraswathy, “Corrosion monitoring of reinforced concrete structures—a review,” International Journal of
Electrochemical Science, vol. 2, pp. 1–28, 2007.
9. Ping Gu and J.J. Beaudoin(1998) “Obtaining Effective Half-Cell Potential Measurements in Reinforced Concrete
Structures” Construction Technology Update No. 18, http://irc.nrc-cnrc.gc.ca