EFFICIENCY AT FINGERTIPS
Sr Deviation descriptions Effect on Approx Monetary
No Heat Rate loss per day (Rs) for
200MW 500MW
1 1 Degree rise in CW inlet temp deteriorates 5.2 Kcal/Kwhr 23400 55000
condenser vacuum by 4 mmHg
2 1 mmHg deterioration of condenser vacuum 1.8 Kcal/Kwhr 8100 20000
3 3 TPH increase in RH Spray 1 kcal/kwhr 4500 11000
4 25 TPH of SH Spray 1 kcal/kwhr 4500 11000
5 1 Degree deviation in MS Temperature 0.7 Kcal/Kwhr 3150 7700
6 1 Degree deviation in HRH Temperature 0.5 Kcal/Kwhr 2250 5500
7 1 Degree deterioration in FW Temp at Eco inlet 1 kcal/kwhr 4500 11000
Must Know:
Heat Rate is energy required to generate one unit of electricity
(Kcal/kwhr)
Gross Heat rate is Turbine Heat rate per unit of Boiler efficiency
Net Heat rate Gross Heat rate/(1-APC). PAT target is monitored in
terms of NHR
1 Kcal/Kwhr Heat rate deterioration in 500 MW emits additional 4 Tons
CO2 in a day
CRH temperature after attemperation must be more than 10 degree
Superheat. Two phase flow of steam may damage the boiler tubes
Air ingress in Boiler through Peep holes/manholes/SB glands leads to
increase in FGET and thus reduction in Boiler efficiency
For proper combustion, Wind Box DP should be maintained around
design
5 Degree increase in all running Mill outlet Temp may reduce FGET by
around 1 deg C and thus improved Heat rate
Increased TTD (Saturation temp corresponding to condenser vacuum –
CW outlet temp) indicates tube deposits and thus vacuum deterioration
Air suction depression more than 5 degree (Hotwell Temp – Air suction
Temp to vacuum Pump) is the indication of air ingress in Condenser
Increased DO in condenser may be due to air ingress through various
water lines (CEPs/Flash Tank drains/level Standpipes/drains etc)
connected to Condenser
Sudden decrease in FW outlet Temp at HPH outlet may be indication of
parting plane leakage. This will also increase the TTD of HPH
Increased Drain Cooler Approach (DCA = Drain out Temp – Feed water
inlet temp) indicates low Heater Level. Very low heater level may have
impact on tube failure and have less heat transfer in drain cooling Zone
of heater
In case of unidentified condenser air ingress and vacuum loss more than
3 mmHg it is advisable to keep both Vacuum pump in service
Increased air pre heater seal leakages may result into increased draft
Power
By-
M K JHA
AGM (EEMG)