You are on page 1of 1

Test Type Inlet Oily WastewaterThe outlet specification of outlet waste water

pH 8.5 6 - 9.5

T.D.S. ppm 251 Less than 1500

Cond 501 Less than 3000

Temp./c 28.2 Less than 35

D.O2 ppm 1.6 Large than 5

Turbidity FTU 117 50 FTU (max.)

Oil ppm 248.2 Less than 10

NO3 ppm Less than 50

SO-24 Less than 400

Sal% Less than 4

Chloride CL ppm Less than 600

S.S ppm Less than 60

COD ppm 160 Less than 100

BOD ppm 81 Less than 40