Products Catalogue

DN1C63H DN2C63H DN3C63H


C63 10000 C63 10000
DN4C63H
C63 10000 C63 10000
50/60Hz 3 50/60Hz 3
50/60Hz 3 3
IEC/EN 60898-1 IEC/EN 60898-1 1 3
IEC/EN 60898-1
1 3 5
50/60Hz 1 3 5 7
1 IEC/EN 60898-1
2 4 2 4 6
2 4 6 8
240 2
415V~ 415V~
415V~
415V~

Since 1886,
Westinghouse
Leading Has Brought
The Best
The Future of To Life.
Electrification Westinghouse remains a trusted name
globally in consumer and industrial
products. Built on a heritage of innovation
A Global Heritage Brand with and entrepreneurial spirit, Westinghouse
130 Years of Product Innovation products were the first to supply the
United States with AC electric power,
Perfect Products, Creative Services, transmit a commercial radio broadcast
and Competitive Price and capture man's first step on the moon.
Today, Westinghouse continues to grow
its diverse portfolio with a wide range of
product categories that include home
appliances, consumer electronics, lighting
and power generation.
DUAL POWER AUTOMATIC
TRANSFER SWITCH
Application
WRDQ3 S e r i e s d u a l power a u t o m a t i c transfer switch i s design a n d manufactured by
our company, is a special product developed as per to customers’ requirements. This

2 product has three functions of Auto Transfer with Auto Recovery, Auto Transfer without
Auto Recovery and Grid-Generator Mode, monitoring the three phase voltage of two power
sources at the same time, when any phase happened with over voltage, under voltage, phase
missing, it can automatically transfer from the fault power source to normal power source.
DUAL POWER (ATS)

For the product with Grid-Generator model, i t can also send Generator start signal. It is a
widely used dual power transfer switch with perfect performance, reliable and highly
automation. WRDQ3 Series Product including 4 series products of WRDQ3, WRDQ3NX,
WRDQ3CM, WRDQ3NM.
This series auto transfer switch confirms to IEC60947-6-1 Standard.

Model Meanings
WRD Q 3 □ □ □ □ - □ / □ □

① ② ③④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩

① Company code
② Auto transfer switch
③ Design code
④ Structure type: C: can with DZ47, CM1. N: Can with DZ47, C65, CM1
Circuit breaker spec.
⑤ X: Below 63A MCB
M: Above 100A MCCB (have A, B, C, D four type controllers for option )
Controller Model:
A: Basic type (only with auto change auto recovery integrated ATS)
⑥ B: Intelligent type (Numerical indicate the voltage, Generator start, Fire linkage)
C: Intelligent type (Same function as B type, but with LCD display )
D: Intelligent type ( S a m e f u n c t i o n s as B type, but with frequency indication and
remote communication)
⑦ Frame class
⑧ Rated current of circuit breaker
⑨ Poles: 2, 3, 4
⑩ R: Auto change auto recovery S : Auto change no recovery F: Power grid – Generator

Model Meanings
● Ambient Temperature: -5℃ +50℃ and 24h average not more than +50℃;
● Atmospheric conditions: humidity not more than 50% at max. +50℃ higher humidity is
allowed at lower temperature, at most wet month, the average max humidity is 90% at the
average min temperature +35℃ , and have considered the condensation on the product
surface due to temperature variation.
● Altitude: Not more than 2000m;
● Pollution class: ambient pollution class 3.

5
Application
WRDQ3-63 is CB type dual power transfer switch, mainly apply to the two power systems with
neutral line earthed and rated current below 63A, rated voltage 230V, 50/60Hz, transfer
between two power sources when one power source fault, to ensure the power supply reliable
and safety. 2

DUAL POWER (ATS)


Technical And Structure Features
WRDQ3-63 Series A TS usage category AC-33iB, electrical appliance grade CB class, its
structure comprised with two MCB and accessories, mechanical interlock transmission
mechanism, automatic controller, motor operation mechanism etc. Meanwhile the MCB
inside the ATS have its original overl o a d and short circuit protection function, can also used
as ON/OFF and protection of the main circuit.

Outline and Installation Dimensions

O
N R

N R

WRDQ 3 63 4P
Ue:230V 50/60Hz Uimp:6kV
AC-33iB

Terminal And Wiring Instruction

101~103 main power external indicator light 201~203 backup power external indicator light

Signal output (AC220V 0.5A) Signal output (AC220V 0.5A)

101- indicator light common null line 201- indicator light common null line

102- main power signal output 202- backup power signal output

103- main power ON signal output 203- backup power ON signal output

6
Application
The fully new designed WRDQ3NX-A/B/C/D series Auto transfer switch is based on deep
development on power transfer switch, make new design to product structure, controller,

2 executive unit, electromagnetic compatibility etc., completely overturned the traditional


dual power auto transfer switch design concept. It is a one of the smallest ATS, compact
construction, easy for installation; Modularized design, enhance the power supply
continuity, energy saving effect is better than other similar product.
DUAL POWER (ATS)

Working Conditions
● Ambient Temperature: -5℃ +50℃ , and 24h average not more than +50℃;
● Atmospheric conditions: humidity not more than 50% at max.+50 ℃ , higher humidity is
allowed at lower temperature, at most wet month, the average max humidity is 90% at the
average min temperature +35℃ , and have considered the condensation on the product
surface due to temperature variation.
● Altitude: Not more than 2000m;

● Pollution class : ambient pollution class 3.

Technical Features
The ATS according to the voltage status of the working power and the working model set by
user, decide whether transfer from one power source to another power source. The function
depends on the selected controller. The controller have A,B,C,D four types, the main
functions and features as followings:

Type
WRDQ3NX-A WRDQ3NX-B WRDQ3NX-C WRDQ3NX-D
Features
Operating power AC150-265V 50/60Hz
Installation mode Integrated
Two
Working position Two Position Three Position Three Position
Position
Auto and Auto and
Operation mode Auto and Manual Auto and Manual
Manual Manual
5A relay contact 5A relay contact
Generator control No No
point point
Passive contact Passive contact
input, With one input, With one
Fire linkage No No
no passive no passive
contact feedback contact feedback
contact contact
Auto change auto Auto change auto
recovery recovery
Auto Auto Auto change no
Transfer mode change auto Auto change no change auto auto recovery
recovery auto recovery recovery and Power Grid-
and Power Grid- Generator
Generator

7
Type
WRDQ3NX-A WRDQ3NX-B WRDQ3NX-C WRDQ3NX-D
Features
Transfer delay Fixed 0.2s 0~30s adjustable Fixed 0.2s 0~30s adjustable

Recovery delay Fixed 0.2s 0~30s adjustable Fixed 0.2s 0~30s adjustable

Monitored phase A, N phase monitoring A, B, C, N Phase monitoring 2


Under volt monitor Yes

DUAL POWER (ATS)


Phase missing monitor A, N A, B, C, N
Use category AC-33iB (CB Class)

Basic Structure
WRDQ3NX-A/B/C/D series A T S is comprised with two MCB and accessories, mechanical
interlock transmission mechanism, intelligent controller. It have A、B、C、D four type
controller, A type is basic type, B is intelligent type, C/D is improved type, based on A/B type
increased with three phase monitoring function, meanwhile the MCB inside the ATS have its
original over load and short circuit protection function.

DN1C63H DN2C63H DN3C63H


C63 10000 C63 10000
DN4C63H
C63 10000 C63 10000
50/60Hz 3 50/60Hz 3
50/60Hz 3 3
IEC/EN 60898-1 IEC/EN 60898-1 1 3
IEC/EN 60898-1
1 3 5
50/60Hz 1 3 5 7
1 IEC/EN 60898-1
2 4 2 4 6
2 4 6 8
240 2
415V~ 415V~
415V~
415V~

Product Features
Product with modularized design, executive unit, transmission mechanism, control circuit
completely independent, easy for replacement.
① : Mechanical transmission device adopt gear transmission, completely eliminate the
possibility of closing at same time;
② : Compact appearance, it is one of the smallest product on the market;
③ : The control circuit layout adopt working power and sampling power separate with single
chip control, to overcome the electromagnetic interference from the hardware
construction;
④ : Working power voltage range: AC200-400V;
⑤ : Less power consumption, max. peak power loss 4.8W, only 20% of other similar products;
⑥ : Product have complete functions, with generator start, fire linkage, ON delay functions etc.;
⑦ : Modularized design, good components interchange performance, easy installation;
⑧ : Can use various executive circuit breaker;

8
Control Panel Functions
① : Main power indicator light
When main power voltage normal, this indicator lighten

2 ② : Backup power indicator light


When backup power normal, this indicator lighten
③ : Main power ON indicator light
DUAL POWER (ATS)

When switch on the main power position, this indicator lighten; when during the switch recovery
delay status, this indicator flickering
④ : Backup power ON indicator light
When switch on the backup power position, this indicator lighten; when during the transfer delay
status, this indicator flickering.
⑤ : Auto/Manual transfer mode control switch
When switch on left side is Auto transfer mode, on the right side is manual transfer mode
⑥ : Transfer delay time setting potentiometer ( Main power to backup power transfer delay time )(A/C
type without, B/D type have)
When ATS is on main power ON position, if main power fault and backup power normal, controller
start the timing ( the time setting by transfer delay potentiometer), after the timing is over then
controller start transfer to the backup power supply; When setting longer time delay can avoid
switch transfer due to power grid instant voltage drop ( for example, there is a big size motor start
in the same power grid, will cause the voltage drop in a short time period)
⑦ : Recovery time delay setting potentiometer ( Backup power to main power transfer delay
time) (A/C type without, B/D type have)
When ATS is on backup power ON position, if main power recovery and normal,
controller start the timing ( the time setting by the recovery delay potentiometer), after the
timing is over then controller start transfer to the main power supply

9
Basic Structure
This controller is a simple controller developed as per to market demand, have the features
of simple operation, suitable functions and display intuitive etc.

Characteristic
2

DUAL POWER (ATS)


Modularized installation mode with main body.
A, C type controller all have under voltage and voltage missing monitor function.
A, C type controller all can arbitrary interchange with single phase and three phase circuit.
A, C type controller all have Auto/Manual two working mode.

Technical Data
● Working voltage range: AC150~265V ● Transfer delay: 0.2s
● Ambient Temperature: -20℃ ~+60℃ ● Recovery delay: 0.2s
● Power consumption: ≤5W

Basic Structure
This c o n t r o l l e r is a multi-function electric monitor device, it is a collection of monitor,
analysis, control, protection etc. many functions as a integration, widely used in highly
automation genset control system and electric power automatic control system.

Characteristic
Setting the controller working mode and transfer delay time through the pull switch.
Fire linkage control f u n c t i o n : B type controller with a set of passive fire-fighting signal input
terminal. The input signal using opto-coupler isolation, have strong anti-interference ability;
And also have a set of passive feedback signal output terminals, can send the switching
position back to fire-fighting control equipment.
Generator start/stop control function : Controller with a relay contact point to control the
generator start and stop.
D type based on B type single phase voltage monitoring change as three phase monitoring.

Technical Data
● Working voltage range: AC150~265V ● Transfer delay: 0s~30s adjustable
● Ambient Temperature: -20℃ ~+60℃ ● Recovery delay: 0s~30s adjustable
● Power consumption: ≤5W

10
Terminal Wiring Instruction
①: 101、102 three pole switch main power common null line ( can connect to any one )

②: 201、202 three pole switch backup power common null line ( can connect to any one )

2 ③ : 301~303 main power external indicator light signal output (AC220V 0.5A);

301-Indicator light common null line


DUAL POWER (ATS)

302-Main power signal output

303-Main power ON signal output

④: 401~403 backup power external indicator light signal output (AC220V 0.5A);

401-Indicator light common null line

402-backup power signal output

403-backup power ON signal output

⑤ : 501~503 Generator start control output terminals

When the backup power is Auto start generator, users can connecting the 501~503 terminals to the
generator controller to achieve the generator auto start function, inside 501~503 terminal, there is a set of
3A passive relay contact point, 503 is the relay common terminal, 501 is relay NC point, 502 is relay NO
point; When main power normal, 503 and 501 is closed、503 and 502 open, if main power failure and
backup power no electricity, 503 and 502 close, and meanwhile
503 and 501 open to send the generator start signal, after generator start successfully, it auto
transfer to the backup power supply, during the backup power supply normal and if main power
recovery, then after the recovery delay control, it transfers to main power supply, main power
circuit breaker ON, then after 3s delay 503 and 501 closed, 503 and 502 open to send generator
stop signal.

⑥ : 601~604 fire linkage control terminals; These terminals are used for remote control of the switch
off the power supply after the fire alarm.

601~602—Fire linkage control signal input terminal, this terminal external only connect to a set
of NO passive contact point (if the signal from fire-fighting equipment is an active signal, must first

pass through a small relay, then connect the relay NO point to controller, otherwise will burn the
controller), when the external contact point closed, the controller immediately control the switch
transfer to OFF position to switch off the load power supply, at same time through 603 and 604
terminal to send the signal back to fire-fighting control center;

603~604—inside is a set of NO relay contact point, used for sending the fire-fighting movement
signal back; When it is normal, the contact is NO status, when there is fire-fighting signal input to
the controller, and the switch transfer to OFF position, the 603 and 604 closed.

Notes: when the fire linkage function is active, the ATS will stop working, if want the ATS to
working again, must first clear up the fire-fighting signal and then switching the Auto/Manual
control switch one time, the ATS will recovery normal working.

11
Outline and Installation Dimensions(mm)

DUAL POWER (ATS)


Notes: the size in brackets is for 3 pole switch size; A,B,C,D type size same.

Terminal Wiring

12
Application

2
WRDQ3CMA series intelligent dual power auto transfer switch (brief as ATS) suitable for
emergency power supply system with rated AC voltage 400V, 50/60Hz. When one power source
fault, can auto interchange from main power to backup power, no need manual operation, to
protect the power supply stability. Mainly a p p l y to the important place which not allow power
DUAL POWER (ATS)

cutoff such as Hospital, shopping mall, bank, chemical industry, metallurgy, high building,
military facilities and firefighting etc.

Structure Introduction
WRDQ3CMA Dual power auto transfer switch use category is AC-33iB, electrical appliance
grade is CB class.

WRDQ3CMA ATS comprised with two 3P or 4P MCCB and its accessories (Aux. contact、
Alarm contact), Mechanical interlocking transmission mechanism, intelligent controller etc.
With integral structure which the controller and executive unit installed at a same base;

The features:

● There is a reliable mechanical interlock device and electric interlock protection between
two MCCB, completely avoid the possibility of two MCCB power ON at same time;

● Have short circuit, overl o a d protection functions;

Outline and Installation Dimensions(mm)

A B B D
Type - Size Ref. No H
3P 4P 3P 4P 3P 4P 3P 4P
WRDQ3CMA-63 W605150 355 380 24 322 347 220 150
WRDQ3CMA-100 W605151 390 420 24 357 387 220 150
WRDQ3CMA-225 W605152 435 470 24 402 437 220 150
WRDQ3CMA-400 W605153 565 615 33 505 555 300 200
WRDQ3CMA-630 W605154 682 740 33 622 680 300 200
WRDQ3CMA-800 W605155 720 790 35 665 735 320 200

13
Summary
This controller is a simple controller we developed as per to market demand, have the
features of simple operation, suitable functions and display intuitive etc., this controller have
advantages of stable quality, reliable performance, high anti electromagnetic interference
ability etc., widely used in various kind of severe environment with strong electromagnetic
radiation and interference.
2

DUAL POWER (ATS)


Technical Data
Working Power AC150-260V 50/60Hz
≤20W
-20℃ ~+60℃

Structure Features

Terminals And Wiring Instruction


① : 1~4 Main power external indicator signal ( active AC220V/0.3A)
1-Main power indicator live line
2-Main power indicator null line
.JBO 1PXFS *OEJDBUJPO

3-Main power ON indicator live line


.BJO QPXFS PO JOEJDBUF
#BDLVQ 1PXFS *OEJDBUJPO
4-Main power ON indicator null line
#BDLVQ QPXFS PO JOEJDBUF
② : 5~8 Backup power external indicator signal (active AC 220V/0.3A)
5-Backup power indicator live line
6-Backup power indicator null line
7-Backup power ON indicator live line
8-Backup power ON indicator null line

14
Application
WRDQ3NM Dual Power ATS is a fully new product of our company, by organizes top
engineers in two years research and development, grand launch at the end of 2014,

2 completely subvert the traditional dual power ATS design style, leading in the international
industrial design concept in the design process, from the product structure, appearance,
ergonomic, and control circuit etc., comprehensive improvement of the traditional ATS, so as
to make it has the quality of international firs-class products and with high competitive price.
DUAL POWER (ATS)

WRDQ3NM series intelligent dual power auto transfer switch (brief as ATS) suitable for
emergency power supply system with rated AC voltage 400V, 50/60Hz. When one power
source fault, can auto interchange from main power to backup power, no need manual
operation, to protect the power supply stability. Mainly apply to the important place which not
allow power cutoff such as Hospital, shopping mall, bank, chemical industry, metallurgy, high
building, military facilities and firefighting etc. Product accord with standard of
IEC60947-6-1: 《Auto transfer switch》, 《Civil high building fire-fighting standard》, 《High
building fire-fighting standard》, 《Civil building electric design standard》 etc.

Working Conditions
● Ambient temperature: -20℃ ~ +50℃ ; 24hours average not more than +50℃ ;

● Atmospheric conditions: humidity not more than 50% at max. +50℃ , higher humidity is
allowed at lower temperature, at most wet month, the average max humidity is 90% at the
average min temperature +35℃ , and have considered the condensation on the product
surface due to temperature variation.

● Altitude: Not more than 2000m;

● Pollution Class: The installation site environment pollution Class 3.

Basic Structure
WRDQ3NM series intelligent ATS comprised with two 3P or 4P MCCB and its accessories
(Aux、contact、Alarm contact), Mechanical interlocking transmission mechanism,
intelligent controller etc. Have integral and split type two structures. Integral type is
controller and executive unit installed at a same base; Split type is controller installed on the
panel and the executive unit installed on the base inside the panel box, a 2m length signal cable
connecting the controller with the executive unit.

The features:

● There is a reliable mechanical interlock device and electric interlock protection between
two MCCB, completely avoid the possibility of two MCCB closed at same time;

● Intelligentized controller adopt the single chip microcomputer (SCM) as the control core,
simple hardware, strong functions, easy extension, high reliability;

● Intelligent controller circuit layout design adopts power sampling separate with SCM
control, from the hardware to overcome the electromagnetic interference;

15
● With short circuit, overload protection functions, over-volt & under-volt phase missing auto
transfer function and intelligent alarm function;

● Auto transfer data by external setting freely, with operation motor protect function;

● Signal connecting cable have passed FLUKE instrument channel test, anti near crosstalk、
2
attenuation crosstalk and back wave loss, can meet the test criteria for permanent link;

DUAL POWER (ATS)


● The ATS controller installation method provide customer with highly autonomy, split
installation only needs simply connect the attached RJ45 signal cable to the corresponding
terminal port;

● The controller part based on the previous similar product, have made enhancement
process of the electronic components makes it more matching with the product operation.

● Product appearance lead in international design concept, more elegant and practical.

● Mechanism innovation made following improvements:

The push handle adopt adjustable slider structure design,


have more wide circuit breakers ON/ OFF travelling
distance, make the production process more simple.

Optimized cam transmission mechanism design ensures


the reliability of mechanical interlock and at same time
makes the mechanical life more than 10000 times.

Adopt mechanical positioning detect structure, make the


ATS switching more accuracy and reliable during fire
linkage.

16
Working Mode
● WRDQ3NM series intelligent dual power ATS have two working mode: Auto mode and
Manual mode.

2 ● Auto Mode: WRDQ3NM series ATS according to the controller functions have three modes:
Auto change Auto recovery (R) Auto change no auto recovery (S) and Power Grid-
Generator (F), the first two mode used in power grid-power grid system, the latter mode is
DUAL POWER (ATS)

used in power grid-generator system.

● Manual mode: manual mode has three working mode, main power, backup power and
breaker trip modes. Under manual working mode, there will be no auto transfer function.

○ Main power mode: Forced disconnecting backup power, and turn ON the main power;

○ Backup power mode: Forced disconnecting the main power and turn ON the backup power;

○ Breaker trip mode: To disconnecting two power sources, also can switch on the fault
tripped circuit breaker.

Outline and Installation Dimensions(mm)

Size A B C
Ref. No D H
Type 3P 4P 3P 4P

WRDQ3NMB-63 W605156 355 380 240 322 348 220 145

WRDQ3NMB-100 W605157 390 420 240 358 388 220 145

WRDQ3NMB-225 W605158 435 470 240 402 438 220 145

WRDQ3NMB-400 W605159 565 615 330 505 555 300 200

WRDQ3NMB-630 W605160 682 740 330 622 680 300 200

WRDQ3NMB-800 W605161 720 790 350 665 735 320 200

WRDQ3NMB-1250 W605162 730 800 390 685 755 367 252

17
Terminal Wiring

5P GJSF GJHIUJOH DPOUSPM SPPN

5P HFOFSBUPS SFNPUF DPOUSPM UFSNJOBM


.BJO QPXFS
.BJO QPXFS 0/
.BJO QPXFS 0''
2

DUAL POWER (ATS)


#BDLVQ QPXFS
34 34 #BDLVQ QPXFS 0/
#BDLVQ QPXFS 0''

7
34 34

Controller Features and Functions


● This product adopts B type controller;
● Can set the controller working mode and transfer data by the control button;
● Through the display can directly read the measuring and control data, including the
voltage and delay time etc.
● Fire linkage control function: controller with a set of passive fire-fighting signal input
terminal. The input signal using opto-coupler isolation, have strong anti-interference ability;
And also have a set of passive feedback signal output terminals, can send the switching
position back to fire-fighting control equipment.
● Generator start/stop control function: Controller with a relay contact point to control the
generator start and stop, and also can manually setting the generator start/stop delay time
(need connect a aux. power with DC15-30V);
● Can remove the display panel and install on the switchgear panel, users can observe the
ATS status without open the switchgear doors.

Split Controller Outline and Mounting Size(mm)

18
Terminal Wiring Instruction
● 101~104 Main power external indicator signal (Active AC220V/0.5A)

2
101-Indicator common null line 102-Main power indicator signal output

103-Main power ON signal output 104-Main power trip signal output

● 201~204 Backup power external indicator signal (Active AC220V/0.5A)


DUAL POWER (ATS)

.JBO 1P XFS *OEJDB UJPO


'JSF -JOLBHF $POUSPM

201-Indicator common null line 202-Backup power indicator signal output

203-Backup power ON signal output 204-Backup power trip signal output


#BDLVQ 1PXFS
(FOFSB UPS

*OEJDB UJPO
$POUSP M

● 301~302 Controller DC aux. power input (DC15V~30V/0.5A)


$PNNVOJDBUJPO

The main purpose to put an aux. power is to control the generator start delay time under
$POUSPM

"VYJMJBSZ
1PXFS

the Power Grid-Generator mode, if without aux. power, the generator start delay time is
0s, if the generator starts delay function not needed, then no need to connect the aux.
power.

● 401~404 Fire linkage control terminal; Used to remote control cutoff the ATS power supply
after the fire alarm.

401, 402 Fire linkage control signal input terminal, this terminal external only connect to a set
of NO passive contact point(if the signal from fire-fighting equipment is an active signal,
must first pass through a small relay, then connect the relay NO point to controller,
otherwise will burn the controller), when the external contact point closed, the controller
immediately control the switch transfer to OFF position to switch off the load power
supply, at same time through 403 and 404 terminal to send the signal back to fire-fighting
control center;

403, 404 Inside is a set of NO relay contact point, used for sending the fire-fighting
movement signal back; when it is normal, the contact is NO status , when there is fire-
fighting signal input to the controller, and the switch transfer to OFF position, the 403 and
404 closed. (Notes: when the fire linkage function is active, the ATS will stop working, if
want the ATS to working again, must first clear up the fire-fighting signal and then switching
the Auto/Manual control switch one time, the ATS will recovery normal working)

● 501~503 Generator start control output terminals

When the backup power is Auto start generator, users can connecting the 501~503 terminals to
the generator controller to achieve the generator auto start function, inside 501~503
terminal, there is a 3A passive relay contact point, 502 is the relay common terminal, 503 is
relay NC point, 501 is relay NO point; Under Power grid-Generator mode and controller is auto
mode, when main power normal, 502 and 501 is closed, 502 and 503 open, if main power failure
and backup power no electricity, 502 and 503 closed after generator start delay time, and
meanwhile 502 and 501 open to send the generator start signal, after generator start
successfully, it auto transfer to the backup power supply, during the backup power supply
normally and if main power recovery, then after the recovery delay time control, it transfer to
main power supply, main power circuit breaker ON, then after generator stop delay time 502 and
501 closed, 502 and 503 open to send generator stop signal.

19
Controller Panel Functions
Ŀ ŀ Ł 1.Auto mode indication;

2
2.Manual mode indication;

"VUP .BOVBM 'BVMU


ł 3. Fault indication: When ATS is fault or load short circuit causes the circuit breaker trip, this
0/ 7
Ń /
0''
4
)[
Ň indicator will lighten;
ń 4FUUJOH "#$ ň

DUAL POWER (ATS)


Ņ 3
0/ 7
4 4.Main power voltage data indication zone: under working status, it displays the main power
0''
)[
'JSF -JOLBHF TUBSU (FOFSBUPS TUBSU voltage and time delay, under setting status, it displays the item code;
ņ
5.Main power circuit breaker ON/OFF indicate;
*ORVJSZ
4FUUJOH
.BOVBM

7.Backup Power circuit breaker ON/OFF indicate;

8.Fire linkage function start indicate;

9.Main power voltage, time and frequency unit;

10.A, B, C phase indicate;

11.Backup power voltage, time and frequency unit;

12.Backup power voltage data indication zone:

under working status, it displays the backup power voltage and time delay, under setting
status, it displays the item code;
13.Generator start signal indicate;

14.Auto/Manual mode select button:

under working status, it used to select the Auto and Manual mode, under the setting status it
used as save and escape function;

15.Main power transfer button:

under manual control mode and main power good, push this button will forced to transfer to
main power; Under setting status, it used for up page button;

16.Backup power transfer button:

under manual control mode and backup power good, push this button will forced to transfer
to backup power; Under setting status, it used for down page button;

17.Trip button:

under manual control mode if any one of the two power is good, push this button will change
to OFF position; under setting status it is used for data reduce button;

18.Fault inquiry button:

if the fault indicator is lighten on the display, through this button can check the fault code;
under setting status, it is used for data increase button;

19.Setting button:

push this button will enter the controller setting menu.

20
DUAL POWER AUTOMATIC
TRANSFER SWITCH
Application

2
WRDS2 Series Auto transfer switch mainly used for electric distribution network or motor
network with rated voltage 380V, 50Hz, DC rated voltage 220V, rated current 16A to 3200A,
change over between main power and backup power system, power grid and genset.
Meanwhile can be used as isolation of unfrequency making and breaking circuit.
DUAL POWER (ATS)

It is widely used in the transmission and distribution system and automation system of the
important place which not allow power cutoff such as firefighting, Hospital, Bank, high building
etc.
WRDS2 Series ATS accord to the following standard:
International:
IEC60947-1(2001) 《Low voltage switchgear and controlgear, part one: General Rules》
IEC60947-3(2005) 《Low voltage switchgear and controlgear, switch, isolator and combined
fuse switch etc.》
IEC60947-6-1 (2005) 《Low voltage switchgear and controlgear multi-function switch: auto
transfer switch etc. 》

Model Meanings
WR DS 2 - □ / □

① ② ③ ④ ⑤

① Company code
② Dual power ATS
③ Design code
④ Rated Current
⑤ Poles (3, 4)

Working Conditions
Ambient temperature: -20℃ ~+50℃; 24hours average not more than +50℃ ;

Atmospheric conditions: humidity not more than 50% at max.+50℃, higher humidity is allowed
at lower temperature, at most wet month, the average max humidity is 90% at the average
min temperature +35℃ , and have considered the condensation on the product surface due
to temperature variation;

Altitude: Not more than 2000m;

Pollution Class: The installation site environment pollution Class 3.

23
Main Technical Parameters
WRDS2-100-3200A series Auto transfer switch electric properties and mechanical properties

Rated Thermal
Current Ith
100A 250A 630A 1000A 1600A 2000A 2500A 3200A
2
3Pole Ref.No W605272 W605273 W605274 W605275 W605276 W605277 W605278 W605279 W605280 W605281 W605282 W605283 W605284 W605285 W605286 W605287 W605288 W605289 W605290

DUAL POWER (ATS)


4Pole Ref.No W605291 W605292 W605293 W605294 W605295 W605296 W605297 W605298 W605299 W605300 W605301 W605302 W605303 W605304 W605305 W605306 W605307 W605308 W605309

Rated Current In(A) 16 20 40 63 80 100 125 160 200 250 400 630 800 1000 1250 1600 2000 2500 3200
Rated insulation
voltage Ui(V) 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 1000 1000 1000
Dielectric strength
5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 10000 10000 10000 10000 10000 10000 10000
(V)

Rated impulse
withstand voltage
Uimp KV 8 8 8 8 8 8 8 8 8 8 12 12 12 12 12 12 12 12 12
(installation
category)
Rated
Working AC-
16 20 40 63 80 100 125 160 200 250 400 630 800 1000 1250 1600 2000 2500 3200
current 33iB
Ie(A)
Rated short time
withstand
9/5 9/5 9/5 9/5 9/5 9/5 12/25 12/25 12/25 12/25 40/20 50/25 90/50 90/50 90/50 90/50 50 50 55
current Icw (kA
Rms)0.1S/1S
Rated Breaking
capacity (A Rms) 128 160 320 500 640 800 1000 1280 1600 2000 3200 5000 6400 8000 10000 12800 16000 20000 25600
AC-33iB 380V
Rated Making
capacity (A Rms) 160 200 400 630 800 1000 1250 1600 2000 2500 4000 6300 8000 10000 12500 16000 20000 25000 32000
AC-33iB 380V
I-0-II
0.5 0.5 0.5 0.5 0.5 0.5 1 1 1.1 1.1 1.2 1.2 1.2 1.2 1.2 1.2 2.4 2.4 2.4
Transfer I -0-II (S)
Time I-0
0.3 0.3 0.3 0.3 0.3 0.3 0.6 0.6 0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.8 1.6 1.6 1.6
II-0(S)

3Poles 4.15 4.15 4.25 4.35 4.45 4.45 8.2 8.2 10.4 10.4 17.8 19 28 31 31 34 - - -
Weight
(kg)
4Poles 4.2 4.2 4.3 4.4 4.5 4.5 8.7 8.7 11.3 11.3 20.2 22 32 36 36 40 95 98 135

Use category AC-33iB(PC)

24
Performance And Characteristic
● It adopted double complex contact/ horizontal pulling mechanism/micro motor energy pre storage and micro-computer
control technology, basically come to Zero arc (no arcing chamber);

2 ● Adopted reliable mechanical interlock and electric interlock, executive unit adopt independent load disconnect switch, it
makes more reliable and safety;
● Adopt “Zero Position” technology, it can force to set to Zero Position under emergency situation (cut off two way power
supply, meet the fire linkage requirements;
DUAL POWER (ATS)

● Load disconnect switch change over adopt singleness motor drive, switch over smooth and reliable, no noise, little impact;
● The driving motor have instant current across only under the load disconnect switch change over, stable working status
no need to provide the working current, outstanding energy saving;
● Executive load disconnect switch have mechanical interlock, make sure the Normal power and Reserve Power working
reliable and no interference;
● Distinct ON and OFF position indicator, padlock function etc., make reliable and safe isolation between power supply and loading.
● High security, high automatization, high reliability, working life more than 8000 times;
● Electromechanical integration design, accuracy change over, flexible, smoothly, adopt international advanced logical
control technology, high anti-interference ability, no interference outward.
● Have main power ON, backup power OFF; main power OFF, backup power ON; main and backup power OFF; three working
mode (I-o-II);
● Easy installation, control circuit adopt plug type terminal connection;
● Four operating functions: Emergency manual, motor remote control, emergency OFF under auto control status, auto
control operation.

Basic Type Switch Control Characteristic


● Suitable for two way main and backup power system, auto change auto recovery;
● Can expand functions by outer connection;
● Auto, Remote, Manual control functions;
● Delay 0.5s signal detect, avoid miss actuation;
● Under Auto control status have “O” position remote control;
● Key switch select the operating mode;
● Can with RS-485 communication port ( optional), according to customer required.

ATS Working Flow

25
WRDS2-100 - 1600A Auto Transfer Switch
● WRDS2-16A~630A outline and mounting size

DUAL POWER (ATS)


Outline and mounting size (mm)
In A A1 B B1 C E G J K L N P R S T U W ФX Y Y1
100A 330 244 115 107 182 125 174 228 85 6.5 83 30 12 18 (2.5)5 99 125 5.2 42 92
250A 436 436 178 134 240 198 174 344 108 7 99 50 24 30 (3.5)7 148 173 11 72 157
630A 502 433 260 222 282 244 174 416 176 9 101 65 40 50 (5)10 222 185 12 83 193

● WDS2 -800A-1600A outline and mounting size

Outline and mounting size (mm)


In A A1 B B1 C E G J K L N P R S T U W ФX Y Y1
800A/3 871.5 524 340 250 387 319.5 448 499 212 11 88 120 60 69 8 250 198.5 12.5 84 252
800A/4 975.5 637.5 340 250 387 319.5 448 612.5 212 13 88 120 60 69 8 250 207 12.5 107 252
1000A/3 871.5 524 340 250 387 319.5 448 499 212 13 88 120 60 69 8 250 198.5 12.5 107 252
1000A/4 975.5 637.5 340 250 387 319.5 448 612.5 212 13 88 120 60 69 8 250 207 12.5 107 252
1250A/3 871.5 524 369 250 387 319.5 448 499 212 13 88 120 60 69 8 250 198.5 13 107 252
1250A/4 975.5 637.5 369 250 387 319.5 448 612.5 212 13 88 120 60 69 8 250 207 13 107 252
1600A/3 871.5 524 376 250 387 319.5 448 499 212 13 88 120 60 69 10 250 198.5 13 109 253.5
1600A/4 975.5 637.5 376 250 387 319.5 448 612.5 212 13 88 120 60 69 10 250 207 13 109 253.5

26
WRDS2-2000-3200A Outline and Installation Size
● WRDS2-2000-3200A outline and installation size

2
DUAL POWER (ATS)

Size Switch Installation Terminal

Spec A A1 B C E G H J K L N O P R S T U V Y Y1 Y3

2000A 1007 633 455 562 495 470 53 467 220 11 84.5 524 120 80 80 10 250 33 147 84 147

2500A 1007 633 455 562 495 470 28 467 220 11 84.5 524 120 80 100 10 250 13 152 79 152

3200A 1007 633 505 562 495 470 28 467 220 11 84.5 524 120 100 100 14 250 13 152 79 152

Wiring Instruction

WRDS2-100~630 WRDS2-1000~3200

27
WRDS2-100-630A Auto Transfer Switch Control And Operation
(Suitable For Rated Current 16A~630A)

DUAL POWER (ATS)


101~103 : main power external indicator signal ( Active AC230V/0.5A)
101- Indicator common null line 102- Main power indicator signal output 103- Main power ON signal output
201~203 : Backup power external indicator signal (Active AC230V/0.5A)
201- Indicator common null line 202- Backup power indicator signal output 203- Backup power ON signal output
301~302 : DC 24V aux. power input for generator start
301- DC24V positive input 302-DC24V negative input
401,404 : Fire linkage control signal input and feedback signal output
401,402 : Fire linkage control signal passive input, if the signal from fire-fighting equipment is an active signal, must first
connect to a small relay, then connect the relay NO point to 401,402, after NO contact closed ATS transfer to OFF position.
403,404 : Feedback signal for ATS transfer to OFF position cutoff the load power supply
Notes: when the fire linkage function is active, the ATS will stop working, if want the ATS to working again, must first clear up
the fire-fighting signal and then switching the Auto/Manual control switch one time, the ATS will recovery normal working
501~503 : Generator start control signal output
When the backup power is Auto start generator, users can connecting the 501~503 terminals to the generator controller to
achieve the generator auto start function, inside 501~503 terminal, is a set of passive relay contact point, 502 is the relay
common terminal, 503 is relay NC point, 501 is relay NO point; when main power normal, 501 and 502 is closed,503 and
501 open, if main power failure 501 and 502 open, meanwhile 503 and 502 closed, to send generator start signal.

28
WRDS2-1000-1600A Auto Transfer Switch Control And Operation
(Suitable For Rated Current 800A ~1600A)

2
● Basic type terminals
DUAL POWER (ATS)

29
Automatic Wiring Method (Suitable For Rated Current 800~3200A)

DUAL POWER (ATS)


● HL1 Main power good indication;

● HL2 Backup power good indication;

● HD1 Main Power ON indication;

● HD2 Backup power ON indication;

● FU1/U2 is 2A fuse.

● 101-106, 201-206, 301-306 is WRDS2 switch terminal.

● 401-406, 501-506 optional switch terminal for up 630A rating.

Auto+Forced Change "0" Position ( For Rated Current 800~3200A )


( Fire-Fighting Dual Power Source Off) Wiring Drawing

● HL1 Main power good indication;

● HL2 Backup power good indication;

● HD1 Main Power ON indication;

● HD2 Backup power ON indication;

● FU1/U2 is 2A fuse.

● 101-106, 201-206, 301-306 is WRDS2 switch terminal.

● 401-406, 501-506 optional switch terminal for up 630A rating.

30
Application

2
WRDS3 Series PC class dual power Auto transfer switch, mainly used in two way power supply
system with rated voltage below 400V, AC 50/60Hz, rated current up to 630A, when one power
supply abnormal, then it transfer between two power supply system, to ensure the power
supply reliablity and safety.
DUAL POWER (ATS)

The ATS have " Main Power", "Backup Power" and "Two way OFF" positions, with higher
breaking and making capacity, it not only can meet normal load transfer, but also can meet
high inductive impedance or big motor load transfer, meanwhile due to have high short time
withstand current capacity, no need special SPCD, doesn't affect the selective of inside
circuit, meanwhile it also can meet the application at big capacity power supply side.
《Low voltage switch equipment and control equipment Part 6-1: multi-funtional transfer
switch equipment》 Standard.

Model Meanings
WR DS 3 - 125 C 4P

① ② ③ ④ ⑤ ⑥

① Company code

② PC class auto transfer switch equipment

③ Design code

④ Rated working current

Controller type A: Basic type Single phase monitor


B: Standard type three phase monitor+fire-fighting ,generator control

⑤ C: Intelligent type three phase monitor+fire-fighting,generator


control+LCD display
D: Intelligent type three phase monitor+fire-fighting, generator
control+split LCD display

⑥ Poles (3P,4P)

Working Conditions
● Ambient temperature: -20℃ ~+50℃ ; 24hours average not more than +50℃ ;

● Atmospheric conditions: humidity not more than 50% at max. +50 ℃ , higher humidity is
allowed at lower temperature, at most wet month, the average max humidity is 90% at the
average min temperature +35℃ , and have considered the condensation on the product
surface due to temperature variation;

● Altitude: Not more than 2000m;

● Pollution Class: The installation site environment pollution Class 3.

31
Technical Data
Type WRDS3-125 WRDS3-250 WRDS3-630
3 Pole Ref.No W605310 W605311 W605312
4 Pole Ref.No
Poles
Rated Working current (A) Ie
W605313
3/4
16-125
W605314
3/4
140-250
W605315
3/4
315-630
2
Rated working voltage (V) Ue 400 400 400

DUAL POWER (ATS)


Rated insulation voltage (V)Ui 800 800 800
Rated impulse withstand voltage (KV) Uimp 8 8 8
Use categeory AC-33B AC-33B AC-33B
Rated short time withstand current(KA, rms)Icw 10kA(200mS) 10kA(200mS) 25kA(200mS)
Rated short circuit Making capacity (KA peak)Icm 20kA 30kA 50kA
Rated limit short circuit current (KA)Iq 120kA 120kA 120kA
Rated control power supply voltage (V) Us 230V/50Hz 230V/50Hz 230V/50Hz
Contact transfer time (s) 1.5 1.8 2
no electricify 8500 7000 3000
Operation
with electricify 1500 1000 1000
cycles
Total 10000 8000 4000
Outline size (mm) WxDxH 245×130×122 295×175×175 430×272×228
Weight (kg) 5 10 20

ATS Functions List


Type A type controller B type controller C type controller D type controller
Control
power voltage AC 230V/50Hz
Auto transfer Auto transfer and auto recovery Auto transfer auto recovery, auto transfer no auto recovery, power grid-generator
Manual transfer Manual main power, manual backup power, manual OFF
Isolation lock Off position have isolation function, also can padlock locked
Generator control - Generator start and stop
with passive fire linkage signal to switch OFF the device, with one
Fire linkage - set passive NO feedback contact
Mechanical indication: device ON/OFF status,
Mechanical indication: device ON/OFF status, operating operating mode
Display mode mode LED: device ON/OFF status, power status
LED: device ON/OFF status, power status LCD: device ON/OFF status, power status,
data setting
Key-press operation, Chinese/English display
Setting mode - interface, can set the working mode, low-voltage
value, over-voltage value, delay time, auto transfer
mode etc.
ABC three phase
over-voltage 265V ABC three phase over-voltage (240-290V
adjustable)
A phase voltage missing ABC three phase
Power monitoring low-voltage 187V ABC three phase low-voltage (150-200V
monitor adjustable)
ABC three phase
voltage missing ABC three phase voltage missing monitor
monitor
Transfer delay (0-300s adjustable)
Delay time - Recovery delay (0-300s adjustable)
Generator start, stop delay (0-300s adjustable)
Mounting mode Integrated mounting Split mounting

Note: B type controller if need auto transfer no recovery mode, please specify when ordering.

32
Product Structure

2
DUAL POWER (ATS)

33
Product Features
● High short time withstand capacity, high short circuit making capacity
Adopt high density silver alloy contact, can withstand thousands operating cycles and no burning loss, no pit or no

2
melting. No need daily contact maintenance, 100% rated current continues load. Contact system adopt bridge type double
break rotating insert structure, reach high short time withstand capacity and high short circuit making capacity, no need
special SCPO, no affect the selective of circuit, meanwhile also can meet the application in the big capacity power supply
system.
● 10Ie making and breaking capacity, match the AC-33B use category

DUAL POWER (ATS)


Optimized magnetic blow-out arc extinguish system, easily reach 10Ie making and breaking capacity, match AC-33B use
category and also match the load property of AC typical application , have wide application range.
● Stacking structure, small volume
Main, backup power switch part adopt modularize design, stacking arrangement, make the product volume more smaller
than other similar products.
● Three position with isolation lock
With “Main power position”, “OFF position”, “Backup power position” three working position, can used for fire linkage and
high inductive impedance load; OFF position with isolation lock function, can meet the isolation requirement during th load
side maintenance.
● Display controller can integrated installation, also can split installation
Display controller and transfer controller split set up, display controller can install on the switch body panel ( Integrated
type), also can install separately on the door panel of switchgear box (split type), convenient for user to check and control of
the ATS status.
● Multi-functions, different modes
Controller have under-voltage, over-voltage, phase missing automatic transfer function and motor-driven forced transfer
function, Auto mode have auto transfer with auto recovery and auto transfer without recovery two modes, to fit with
different location; Have fire linkage function, to cutoff the load power under emergency situation.

Controller Functions
● Under-voltage detection
Controller makes under-voltage detection for main power and backup power, when the under-voltage is detected with the
power supply, it will start the auto transfer function to transfer to another power supply. When the power supply voltage is
detected recovered to acceptable range (Recovery value), controller will decide whether make transfer according to the
settled transfer mode and can set transfer delay time.
● Over-voltage detection
Controller makes over-voltage detection for main power and backup power, when the over-voltage is detected with the power
supply, it will start the auto transfer function to transfer to another power supply. When the power supply voltage is detected
recovered to acceptable range (Recovery value), controller will decide whether make transfer according to the setted
transfer mode and also can set transfer delay time.
● Transfer delay
When the main power is confirmed abnormal and backup normal, transfer delay start delay counting, after time delay is over
then transfer from the main power to backup power. This time delay can wait to confirm whether the main power is short time
abnormal, also can avoid switch frequently transfer.
● Recovery delay
Recovery delay is after backup power supply, and main power is confirmed available, then start delay counting, when delay
time is over then transfer from the backup power to main power. This delay time can wait the main power supply output stable
before it supply to the load.
● Generator start delay
Generator start delay can avoid starting genset due to short time power off. When main power fault then start delay counting,
and after the delay time is over then send generator start signal.
(Note: when the main power suddenly cutoff and genset didn’t start, under this situation it can’t delay due to no power supply to
the controller, if need to use this function have to connect a DC24V aux. power supply to the controller to achieve the time
delay function)
● Generator stop delay
Generator stop delay can remain the generator in hot backup status after it stop power supply to the load, avoid the genset
restarting due to main power in short time recovery. When transfer from the backup power to main power supply then start
the delay counting, after delay time counting is over then controller send genset stop signal.

34
● Transfer mode
Controller provides different transfer mode function according to the power supply property
1 : Power grid - Power grid:
At the application of power grid - power grid, ATS can provide auto transfer with auto recovery and auto transfer no auto

2 recovery two transfer mode.

Power grid - power grid auto transfer with auto recovery mode
DUAL POWER (ATS)

Power grid - power grid auto transfer no auto recovery mode

2 : Power grid - generator mode


Transfer between power grid - generator

35
Display Panel

DUAL POWER (ATS)


Ua
Ub
Uc
Ua
Ub
Uc

1: Auto、Manual working mode indicate;


2: Setting status indication;

3: Generator start signal indicate;

4: Fire linkage function status indicate;

5: Main power status data indication zone: during working status display main power voltage data and transfer delay time,
during setting status display setting item code;

6: Backup power status data indication zone: during working status display backup power voltage data and recovery delay
time, during setting status display setting item code;

7: Setting button: press this button will enter into controller setting menu;

8: Auto/Manual transfer mode selection button: under working status it used to select the Auto and Manual transfer mode,
under the setting status it used as save and escape function;

9: Trip button: under manual control mode if any one of the two power is good, push this button will change to OFF
position; under setting status it is used for data decrease button;

10: Main power transfer button: under manual control mode and main power good, push this button will forced to transfer
to main power; Under setting status , it used for up page button;

11: Backup power transfer button: under manual control mode and backup power good, push this button will forced to
transfer to backup power; Under setting status , it used for down page button;

12: + Button: under setting status this button is used as data increase button;

36
Outline And Mounting Size (mm)
● WRDS3-125 (3P,4P outline and mounting size same)

2
DUAL POWER (ATS)

● WRDS3-250 (3P,4P outline and mounting size same)

37
Outline and Mounting Size (mm)
● WRDS3-630 (3P,4P outline and mounting size same)

DUAL POWER (ATS)


● Display controller outline and split mounting hole size

38
Controller Terminal and Wiring Instruction

2
DUAL POWER (ATS)

● 101~103 main power external indicator signal (Active AC230V/0.5A)

101- Indicator common null line 102- Main power indicator signal output 103- Main power ON signal output

● 201~203 Backup power external indicator signal (Active AC230V/0.5A)


201- Indicator common null line 202- Backup power indicator signal output 203- Backup power ON signal output

● 301~302 aux. power input (DC15V- 24V/0.5A)

The purpose to put an aux. power is to control the generator start delay time under the Power grid-Generator mode, if without
aux. power, the generator start delay time is 0s, if the generator start delay function not needed, then no need to connect
the aux. power .

● 401~404 Fire linkage control terminals

401,402 Fire linkage control signal input, this terminal external only can connect to a set of NO passive contact (if the signal
from fire-fighting equipment is an active signal, must first connect through a small relay, then connect the relay NO point to
controller) after NO contact closed ATS immediately transfer to OFF position and cutoff the power supply.

403,404 Inside is a set of NO relay contact point, used for sending the fire-fighting movement signal back; when it is
normal, the contact is NO status, when there is fire-fighting signal input to the controller, and the switch transfer to OFF
position, the 403 and 404 closed. (Notes: when the fire linkage function is active, the ATS will stop working, if want the ATS
to working again, must first clear up the fire-fighting signal and then switching the Auto/Manual control switch one time, the
ATS will recovery normal working)

● 501~503: Generator start control signal output


When the backup power is Auto start generator, users can connecting the 501~503 terminals to the generator controller to
achieve the generator auto start function, inside 501~503 terminal, is a set of passive relay contact point, 502 is the relay
common terminal, 503 is relay NC point, 501 is relay NO point;

Under power grid- generator mode and auto transfer mode, when main power normal, 502 and 501 is closed,502 and
503 open, if main power failure and backup power no power, 502 and 503 closed after generator start delay time, meanwhile
502 and 501 open to send generator start signal, after generator start successfully ATS auto transfer to backup power supply,
if main power recovery good, then controller after recovery delay time to control the switch transfer to main power supply, after
main power ON, 502 and 501 closed after generator stop delay time, 502 and 503 open to send generator stop signal.

39
3P Product Wiring

DUAL POWER (ATS)


4P Product Wiring

40
USA: Westinghouse
20 Stanwix Street | Pittsburgh | PA | 15222

Poland : Westinghouse LV MV Product sp. z o.o.


Warsaw, Rondo ONZ 1, 12 floor, 00-124 Warsaw, Poland

Malaysia : Westinghouse Lv Mv Product Sdn. Bhd.


Seberang Perai Selatan 14110 Simpang Ampat
Pulau Penang, Malaysia

WWW.westinghouselvmv.com
Email: info@westinghouselvmv.com

™ & © 2021 Westinghouse Electric Corporation. All Rights Reserved.