Professional Documents
Culture Documents
For England and Wales the code relating to fire safety is Approved Document B
(ADB) of the Building Regulations. This document was last issued in two volumes in
2006; volume one for dwellings and volume two for other buildings. A minor update
was made in 2013 to include references to certain CEN standards not available in
2006. Wales published its own version of the document in 2015 to include its new
requirements for sprinklers in all residential buildings. ADB does not go into detail on
schools, shopping centres or healthcare facilities; these are covered by other
documents. Both volumes of ADB are on this web site.
Below is a summary of the requirements for fire sprinklers, taken in the order in
which they appear. In general the original text is lengthy and has been summarised.
Volume 1
Where this document calls for sprinklers it states that they should be designed to BS
9251, the British standard for residential and domestic sprinkler systems.
2.7 In four storey houses a sprinkler system can be fitted as an alternative to a
second, protected staircase.
2.20b Where a loft is converted into an additional storey and the ground floor is
open plan a sprinkler system may be fitted instead of extra fire doors.
9.15 Boundary distances between buildings may be halved if they are fitted with
a sprinkler system.
Volume 1 - Wales
B1 Section 2
2.2 Regulation 37A bring in a mandatory requirement for automatic fire
suppression systems in all new premises of Purpose Groups 1a, 1b, 1c, 2a and
2b constructed in Wales with the exception of hospitals, hotels, prisons, and
short stay hostels used for leisure purposes.
* Includes live/work units that meet the provisions of paragraph 3.52 of Volume 2.
Volume 2
1.25 Automatic sprinkler systems can also be used to operate a fire alarm system.
2.16 In a multi-storey flat without an entrance at ground level and with a floor
more than 4.5m above ground, sprinklers plus a protected stairway can
replace alternative exits on each floor or extra smoke detectors and a heat
detector in the kitchen plus a protected stairway.
3.52 In care homes sprinklers are an alternative to self-closing devices on
bedroom doors. Protected areas (fire compartments) may contain more than
ten beds if the care home is fitted with a sprinkler system.
4.29d Buildings with a floor above 30m and designed to be evacuated in
phases should be protected throughout with a sprinkler system.
5.58 Fully enclosed walk-in store rooms in shops (unless provided with an
automatic fire detection and alarm system or fitted with sprinklers) should be
separated from retail areas with fire-resisting construction (see Appendix A,
Table A1) if they are sited so as to prejudice the means of escape.
8.14 Blocks of flats with a floor more than 30m above ground level should be
fitted with a sprinkler system.
Table 12 Maximum dimensions of building or compartment
(non-residential buildings)
Purpose Group of Height of floor of top storey above Floor area of any one storey in the building or any
building or part ground level (m) one storey in a compartment (m2)
Industrial (2)
maximum
compartment maximum maximum
Height of floor of top storey above volume m3 floor area (m2) height (m)
ground level (m)
multi-storey
buildings single storey buildings
Notes:
1. 'Sprinklered' means that the building is fitted throughout with an automatic sprinkler system in accordance with paragraph 0.16.
2. There may be additional limitations on floor area and/or sprinkler provisions in certain industrial and storage uses under other legislation, for
example in respect of storage of LPG and certain chemical materials.
3. This reduced limit applies only to storeys that are more than 18m above ground level. Below this height the higher limit applies.
4. Compartment height is measured from finished floor level to underside of roof or ceiling.
In Table D1 of Appendix D, shop and commercial is defined as:
Shop or premises used for a retail trade or business (including the sale to members of
the public of food or drink for immediate consumption and retail by auction, self-
selection and over-the-counter wholesale trading, the business of lending books or
periodicals for gain and the business of a barber or hairdresser and the rental of
storage space to the public) and premises to which the public is invited to deliver or
collect goods in connection with their hire repair or other treatment, or (except in the
case or repair of motor vehicles) where they themselves carry out such repairs or other
treatments.
This means that long-term storage warehouses must have sprinklers if they are larger
than 2,000m2.
12.4 Portal Frames Note 1
The recommendations in the SCI publication to resist overturning need not
be followed if the building is fitted with a sprinkler system.
13.17 If a building is fitted throughout with a sprinkler system… the boundary
distance may be half that for an otherwise similar, but unsprinklered,
building, subject to there being a minimum distance of 1m. Alternatively the
amount of unprotected area may be doubled if the boundary distance is
maintained.
17.9 If the building is fitted throughout with an automatic sprinkler system…
sufficient firefighting shafts should be provided such that every part of every
storey, that is more than 18m above fire and rescue service vehicle access
level, is no more than 60m from a fire main outlet in a firefighting shaft,
measured on a route suitable for laying hose.
17.10 If the building is not fitted with sprinklers then every part of every storey
that is more than 18m above fire and rescue service vehicle access level,
should be no more than 45m from a fire main outlet contained in a protected
stairway and 60m from a fire main in a firefighting shaft, measured on a
route suitable for laying hose.
18.13 A system of mechanical extraction may be provided as an alternative to
natural venting to remove smoke and heat from basements, provided that the
basement storeys are fitted with a sprinkler system.
Table A2 Minimum periods of fire resistance
Purpose group of building Minimum periods (minutes) for elements of structure in a:
Basement storey ($) Ground or upper storey
including floor over
Depth (m) of a lowest Height (m) of top floor above ground, in
Basement a building or separated part of a building
More Not more Not more Not more Not more More
than 10 than 10 than 5 than 18 than 30 than 30
1. Residential:
a. Block of flats
- not sprinklered 90 60 30* 60**† 90** Not permitted
- sprinklered 90 60 30* 60**† 90** 120**
b. Institutional 90 60 30* 60 90 120#
2. Office
- not sprinklered 90 60 30* 60 90 Not permitted
- sprinklered (2) 60 60 30* 30* 60 120#
3. Shop and commercial: not
- not sprinklered 90 60 60 60 90 permitted
- sprinklered (2) 60 60 30* 60 60 120#
4. Assembly and recreation: not
- not sprinklered 90 60 60 60 90 permitted
- sprinklered (2) 60 60 30* 60 60 120#
5. Industrial: not
- not sprinklered 120 90 60 90 120 permitted
- sprinklered (2) 90 60 30* 60 90 120#
6. Storage & other non-residential:
a. any building or part not
described elsewhere:
- not sprinklered 120 90 60 90 120 Not permitted
- sprinklered (2) 90 60 30* 60 90 120#
b. car park for light vehicles:
i. open-sided car park (3) Not applicable Not applicable 15*+ 15*+(4) 15*+(4) 60
ii. any other car park 90 60 30* 60 90 120#
Single storey buildings are subject to the periods under the heading "not more than 5". If they have basements, the basement storeys are subject to the period
appropriate to their depth.
“6.94 With the exception of buildings over 30m in height, the guidance in this
document does not require the installation of sprinklers in patient care areas of
healthcare buildings. However, the design team is expected to consider the advantages
that might be gained by installing life-safety sprinklers throughout the building. Any
decision should be considered as an integral part of the fire safety strategy and should
clarify the decision to select low or ordinary hazard. However sprinklers or automatic
fire suppression should be installed in commercial enterprise areas in accordance with
Health Technical Memorandum 05-03: Part D – ‘Commercial enterprises on
healthcare premises’.”
Schools
Scotland requires sprinklers to be fitted in all new schools. In England and Wales the
government has issued guidance through Building Bulletin 100, which strongly
recommends sprinklers in all but a few low risk schools.
Care Homes
Scotland requires sprinklers in all new care homes. The full details of sprinkler
requirements in Scotland are on this web site. In England either sprinklers or self-
closing fire doors on every bedroom must be fitted (see 3.52 above).
BS 9999: Code of practice for fire safety in the design, management and use of
buildings
Aside from statutory guidance, there is a British standard for fire safety. Approved
Document B is prescriptive, statutory guidance. PD 7974 provides guidance for fire
safety engineered designs, while BS 9999 lies in between the two approaches. It is
written as clear guidance but its contents are based on fire safety engineering
analyses. While it does not have the same status as the statutory guidance in
Approved Document B, government representatives attended every meeting in
drafting this standard and did not raise any objections to it.
BS 9999 introduces risk profiles for the different types of occupant and potential fire
growth rates in buildings. If sprinklers are fitted the fire growth rate is assumed to be
one category slower, which allows longer travel distances and narrower escape routes.
BS 9991
To complement BS 9999, a code of practice was published for fire safety in
residential buildings. Like BS 9999, it contains many design freedoms for sprinklers.
The two most important are flexibility in the internal layout of flats, which may be
open-plan, and increased travel distances in corridors. In addition, reduced fire
brigade access is accepted.