PLACES OF ASSEMBLY
t
FDAS 1. All assembly occupancies shall be provided with fire alarm system with manual
initiation; provided however, that where occupants of the building exceed three
hundred (300) persons, the initiation shall be through an automatic detection
system.
2. The required fire alarm system shall activate an audible and visible alarm in a
constantly attended receiving station within the building when occupied for purposes
of initiating emergency action.
AFSS 1. The following assembly occupancies with occupant load of one hundred fifty (150)
persons or more shall be protected throughout by an approved, supervised
automatic sprinkler system:
a. bars with live entertainment;
b. dance halls;
c. discotheques; and
d. assembly occupancies with festival seating.
2. Buildings containing assembly occupancies with occupant load of more than three
hundred (300) persons shall be protected by an approved, supervised automatic
sprinkler system:
a. throughout the storey containing the assembly occupancy;
b. throughout all storeys below the storey containing the assembly occupancy;
c. in case of an assembly occupancy located below the level of exit discharge,
throughout all storeys intervening between that storey and the level of exit
discharge, including the level of exit discharge.
3. The provisions of paras 1 and 2 above shall not apply to assembly occupancy with all
sides open and places of worship at the level of exit discharge with sufficient means
of egress.
Wet Assembly occupancies with an occupant load exceeding one thousand (1,000)
standpipe
2. In building provided with automatic fire suppression system, the operation of the
system shall automatically actuate electrical school fire alarm system.
Requirements for Fire Alarm System for existing educational buildings shall conform to
those required for new educational buildings, in accordance with para “D” of Section
10.2.9.5 of this RIRR.
AFSS 1. Every portion of educational buildings below the floor of exit discharge, being
utilized as classroom or laboratory, shall be protected with approved, supervised
sprinkler system in accordance with Section 10.2.6.7 of this RIRR:
Cooking equipment shall be protected in accordance with Section 10.2.7.1 of this RIRR.
Wet four or more storeys in height
standpipe
2. A smoke detection system shall be installed in day care occupancies, other than
those housed in one (1) room having at least one (1) door opening directly to the
outside at grade plane or to an exterior exit access, and such system shall comply
with both of the following:
a. Detectors shall be installed on each storey in front of the doors to the stairways and
in the corridors of all floors occupied by the day care occupancy.
b. Detectors shall be installed in lounges, recreation areas, and sleeping rooms in the
day care occupancy.
AFSS 3. Buildings with unprotected openings, up to five (5) communicating floor levels not
considered as a high rise building, shall be protected throughout by an approved,
supervised automatic sprinkler system in accordance with Section 10.2.6.7 of this
RIRR.
4. Portable fire extinguishers shall also be provided pursuant to Section 10.2.6.9 of this
RIRR.
AFSS c. Approved, supervised sprinkler system shall be provided throughout all hospitals and
nursing homes, except for one (1) storey building with a bed capacity of not
exceeding five (5). Replenishment of water supplies shall be strictly considered in the
design. Quick-response sprinklers shall be required in smoke compartments
containing patient sleeping rooms.
d. Approved, supervised sprinkler system shall be in accordance with the requirements
of Section 10.2.6.7 of this RIRR.
e.In light hazard occupancies, required automatic fire suppression systems shall be
in accordance with Section 10.2.6.7 of this RIRR for systems and shall be electrically
interconnected with the fire alarm system. The main automatic fire suppression
control valve shall be electrically monitored so that at least a local alarm will sound
when the valve is closed.
f. If the fire suppression system is an automatic sprinkler, its piping serving no more
than six (6) sprinklers for any isolated hazardous area, may be connected directly
to a domestic water supply system having a capacity sufficient to provide six liters
per minute per square meter (6 L/min/m2) of floor area throughout the entire
enclosed area. As outside-screw-and-yoke shutoff valve shall be installed in an
accessible location between the sprinklers and the connection to the domestic water
supply.
g. Portable fire extinguishers shall be provided in all health care occupancies in
accordance with Section 10.2.6.9 of this RIRR.
Wet four or more storeys in height
standpipe
2. Facilities having sleeping accommodations for not more than sixteen (16) residents
shall comply with Section 10.2.14.2 of this RIRR.
FDAS a. An automatic detection and alarm system shall be required in all large residential
custodial care facilities in accordance with Section 10.2.6.6 of this RIRR.
d. Smoke alarms shall be installed inside every sleeping room, outside every sleeping
area in the immediate vicinity of the bedrooms, and all levels within a resident unit.
e. Corridors and spaces open to the corridors shall be provided with smoke detectors
arranged to initiate an alarm that is audible in all sleeping areas.
AFSS a. All buildings shall be protected throughout by an approved, automatic sprinkler
system, and quick-response or residential sprinklers, except for one (1) storey
building with a bed capacity of not exceeding five (5). Replenishment of water supply
shall be strictly considered in the design. Quick-response sprinklers shall be required
in smoke compartments containing patient sleeping rooms.
8. Smoke detectors shall not be required in Use Condition II open dormitories where
staff is present within the dormitory whenever the dormitory is occupied.
AFSS 1. All buildings classified as Use Condition II, Use Condition III, Use Condition IV, or
Use Condition V shall be protected throughout by an approved, supervised
automatic sprinkler system in accordance with Section 10.2.6.7 of this RIRR.
2. The automatic sprinkler system required by the preceding paragraph shall be fully
supervised and electrically connected to the fire alarm system.
3. Portable fire extinguishers shall be provided in accordance with para “C” of
Section
FDAS a. An automatic fire detection and alarm system, in accordance with Section 10.2.6.6
of this RIRR, shall be provided for any hotel or dormitory having accommodations
for fifteen (15) or more guests. For less than fifteen (15) guests, a manual fire alarm
system shall be installed.
b. Every sounding device shall be of such character and so located as to arouse all
occupants of the building or section thereof endangered by fire.
c. An alarm-sending station and manual fire alarm box shall be provided at the hotel
desk or other convenient central control point under continuous supervision of
responsible employees.
d. Suitable facilities shall be provided for immediate notification of the BFP.
e. Positive fire alarm sequence may be permitted.
f. Hotels and dormitories including its guest rooms and guest suites shall be required
to be equipped with both audible and visible notification appliance.
g. In hotels and dormitories not equipped with automatic fire detection and alarm
system, guest rooms, living area and sleeping rooms within a guest suite shall be
installed with single-station smoke detectors.
AFSS a. All hotels and dormitories with four (4) storeys or more in height shall be protected
throughout by approved, supervised sprinkler system.
1) Hotels and dormitories with four (4) storeys and below shall be installed with
sprinkler system in accordance with NFPA 13R.
2) Hotels and dormitories with five (5) storeys and above shall be installed with
sprinkler system in accordance with NFPA 13.
b. Portable fire extinguishers shall be installed in accordance with Section 10.2.6.9 of
this RIRR.
c. Apartment Buildings. Buildings containing three (3) or more living units with
independent cooking and bathroom facilities, whether designated as condominium,
row house, apartment house, tenement, garden apartment, or by any other name.
FDAS a. Every apartment building of four (4) storeys or more in height, or more than twelve
(12) apartment units, except row houses shall have automatic fire detection and alarm
system in accordance with Section 10.2.6.6 of this RIRR.
b. Apartment buildings of not more than three (3) storeys in height shall be provided with
manual fire alarm system, provided that dwelling units shall be installed with single-
station or multi-station smoke detectors.
AFSS a. All apartments, except row houses with four (4) storeys in height, shall be protected
throughout by approved, supervised sprinkler system.
b. For four (4) storeys and below it shall be installed with sprinkler system in
accordance with NFPA 13R.
c. For five (5) storeys and above, it shall be installed with sprinkler system in
accordance with NFPA 13.
d. Portable fire extinguishers shall be installed in accordance with Section 10.2.6.9 of
this RIRR.
C. Lodging or Rooming Houses. Building in which separate sleeping rooms are rented
providing sleeping accommodations for a total of fifteen (15) or less persons, on either
a transient or permanent basis; with or without meals, but without separate cooking
facilities for individual occupants.
FDAS A manual fire alarm system shall be provided in accordance with Section 10.2.6.6 of
this RIRR. Likewise, each sleeping room shall be installed with single station-
smoke or heat detector.
D. Single and Two -Family Dwellings. Detached dwellings in which each living unit is
occupied by members of a single family.
FDAS Each living unit or sleeping room shall be installed with single-station smoke or heat
detectors.
AFSS Each single and two -family dwelling shall be provided with portable fire
extinguishers in accordance with Section 10.2.6.9 of this RIRR.
Wet four or more storeys in height,
standpipe
DIVISION 15. MERCANTILE OCCUPANCIES
FDAS Class A and Class B stores shall be provided with an automatic fire alarm system in
accordance with Section 10.2.6.6 of this RIRR.
Cooking equipment shall be protected in accordance with Section 10.2.7.1 of this RIRR.
AFSS All business occupancy buildings fifteen meters (15 m) or more in height shall be provided
throughout with approved, supervised sprinkler system, fully electrically supervised
designed in accordance with NFPA 13.
AFSS 1. Every high-hazard occupancy shall be provided with automatic fire suppression
system appropriate to the particular hazard in accordance with NFPA or other
internationally accepted standards.
2. Portable fire extinguishers shall be installed in accordance with Section 10.2.6.9 of
this RIRR.
3. Standpipe systems shall be installed in accordance with Section 10.2.6.8 of this
RIRR.
Wet having a floor area exceeding one thousand eight hundred sixty square meters (1,860 m²)
standpipe per floor.
approved by the C/MFM having jurisdiction. The Fire Command Center shall be accessible
directly from the exterior of the building at the floor of exit discharge with a sign on the
door stating “Fire Command Center”.
A. The Fire Command Center shall be separated by not less than two (2) hours fire
resistive
construction.
B. The Fire Command Center shall be not less than ten square meters (10 m2) with no
dimensions less than one and a half meters (1.5 m) with minimum ceiling height of not
less than two and four tenths meters (2.4 m).
D. Shut off valves and water flow devices at the riser connection must be provided on
each floor. Combined sprinkler/standpipe systems must have an individual control valve
and check valve at each sprinkler connection.
High rise buildings shall be protected with approved, supervised sprinkler systems
designed and installed in accordance with NFPA 13. The approved, supervised sprinkler
systems must protect all floor spaces including every closet and concealed
spaces/plenums of certain configuration and construction – particularly where
combustible materials are located such as exposed electrical wiring, combustible duct
work, and combustible sound/thermal insulation. The system shall be interconnected to
the Fire Command Center of the building.