Professional Documents
Culture Documents
Record drawings shall consist of current updated and shop drawings reflecting the
actual installation of all system equipment, components, and wiring
Total coverage shall include all rooms, halls, storage areas, basements, spaces above
suspended ceilings, and other subdivisions and accessible spaces, as well as the inside
of all closets, elevator shafts, enclosed stairways etc.
17.5.3.1.1.An inaccessible compartment that contain combustible material shall be fitted
with detectors. Same compartment to be made accessible.
Although 17.5.3.1 mentions elevator hoist ways as one of the areas where detection
must be installed where total coverage is specified, smoke detectors installed in
hoistways might require continuous maintenance and could be a common source of
false or nuisance alarms. If total coverage is the fi re protection design goal, then the
hoistway could be protected by a heat detector(s) to meet that goal or smoke detectors
that are specifically listed for the environment
Exception: For lobby ceiling configurations exceeding 15 ft (4.6 m) in height or that are
other than flat and smooth, detector locations shall be determined in accordance with
Chapter 17.
21.3.7 When sprinklers are installed in elevator pits, automatic fire detection shall be
installed to initiate elevator recall in accordance with 2.27.3.2.1(c) of ANSI/ASME
A.17.1/CSA B44, Safety Code for Elevators and Escalators
10.10.5. Supervisory signals shall be distinctive in sound from other signals, and their
sound shall not be used for an y other purpose
10.10.6 Trouble signals required to indicate at the protected premises shall be indicated
by distinctive audible signals, which shall be distinctive from alarm signals
Power related(Chapter 10)
A.10.6.7.3 The secondary power supply is not required to supply power to the fire alarm
system through parallel distribution paths. Automatic transfer switches are commonly
used to allow secondary power to be supplied over the same distribution system as the
primary power. The generator does not need to be dedicated to the fire alarm system
23.8.5.9.1 Where fire pumps are required to be monitored and a building fire alarm
system is installed, a pump running signal shall be permitted to be a supervisory or
alarm signal.
23.8.5.9.2 Where fire pumps are required to be monitored and a building fire alarm
system is installed, signals other than pump running shall be supervisory signals
A.17.12.2 The waterflow device should be field adjusted so that an alarm is initiated no
more than 90 seconds after a sustained flow of at least 10 gpm (40 L/min)
A.17.13 Alarm initiation can be accomplished by devices that detect the following:
(1) Flow of water in foam systems
(2) Pump activation
(3) Differential pressure
(4) Pressure (e.g., clean agent systems, carbon dioxide systems, and wet/dry chemical
systems)
(5) Mechanical operation of a release mechanism
Heat Detectors:
17.6.3.4.1.1 Ceiling Slope Less Than 30 Degrees. For a ceiling slope of less than 30
degrees, all detectors shall be spaced using the height at the peak
17.6.3.4.1.2 Ceiling Slopes of 30 Degrees or Greater. All detectors, other than those
located in the peak, shall be spaced using the average slope height or the height of the
peak
17.6.3.4.2.1 A row of detectors shall first be located at or within 36 in. (910 mm) of the
peak of the ceiling