You are on page 1of 23

AHC Co.

SECTION 16760

MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of contract, including general conditions, apply to


work of this section.

B. Basic electrical materials and methods, section 16050 applies to work of this section.

1.2 DESCRIPTION OF WORK

A. Work includes a complete fire alarm system in the building and providing all
materials, equipment, accessories, services and tests necessary to furnish and install an
analogue Addressable Fire Alarm Life Safety System of the non-coded, closed circuit
general alarm (Fire speaker with strobe light), electrically supervised type. Provide
supervised wiring, all operations, and hardware, as described herein and shown on
plans.

B. The system shall consist of, but not be limited to the following:

1. Main Fire Alarm indication and Control Panel (MFAP).

2. System PC and printer at the (MFAP) .

3. Analogue Addressable multi – sensor detectors.

4. Analogue Addressable manual fire alarm stations.

5. Analogue Addressable duct photoelectric smoke detector with remote indicator.

6. Fire Speaker with strobe light.

7. Control zone addressable modules.

8. Elevator recall control and relays.

9. Fire brigade interconnection.

11. Fire telephone system.

12. Voice evacuation system.

13. Fire pumps monitoring and alarm (Power failure, phase reversal, pump
running).

14. Battery and battery/inverter back-up operation.

15. Interface with B.M.S. system.

16. Conduit and wiring.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 1
AHC Co.
C. The fire alarm system is to be installed for addressable initiating and control circuits
with hard-wired signaling (Fire speaker/strobes) circuits utilizing conduit, tubing and
wire serving all peripheral devices such as manual stations, multi - sensor detectors,
and waterflow switches, etc.

D. Obtain and deliver a final certificate of approval to the Owner from the Fire
Department for all fire alarm and detection work under this contract through filing the
appropriate documents and including but not limited to the following:

1. Prepare as-built riser diagram showing all fire alarm related equipment, wire and
conduit sizes and counts and connections to elevator recall, and control
equipment, any sub-systems and must include a complete description of system
operation. Each drawing to have a standard Building Department note which
reads: "This plan is approved only for work indicated on the application
specification sheet. All other matters shown are not to be relied upon, or to be
considered as either being approved or in accordance with applicable codes."

E. It is the responsibility of this Contractor to produce all written requests to the Fire
Department for inspections of the fire alarm system and associated equipment.
Written requests to be produced in a fashion to ensure inspection when equipment is
fully operational in accordance with this specification. Contractor to gain final
approval in an expedient manner and not to delay the obtainment of a Certificate of
Occupancy for this location.

F. Contractor to be responsible for testing all the fire alarm equipment after completion
of work and prior to any inspection with written report given as proof of condition of
the system. All system devices and their circuits to be in first class operating
condition after completion of work.

G. Wiring

1. All wiring for the systems must be installed in true Class 'A' form with the
'return' portion of the circuit home run in separate conduits. Class 'A' return for
more than one circuit may be contained in a common conduit. Class 'A' return
conduits must be labeled as such with lettering, directional arrows or other
method to differentiate it from the other circuit conduits.

2. Wiring to be fire resistance cable run in PVC conduit for embedded installation
and in IMC for exposed installation. Addressable initiating and control circuits to
be twisted/shielded. Signaling (Fire speaker/strobe) circuits to be
twisted/non-shielded.

3. All raceways are to be run in concealed areas to minimize exposure in public


corridors and spaces. Where raceways are run in corridors, they must be
installed in upper corners at ceiling secured to protect against tampering where
possible.

H. All components of the Fire Alarm Life Safety system to be by one manufacturer.

I. After the completion of the installation of the Fire Alarm System, the Contractor shall
perform a complete demonstration test of all systems and devices to the satisfaction of
the Engineer.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 2
AHC Co.
1.3 QUALITY ASSURANCE

A. Manufacturers: firms regularly engaged in manufacture of fire alarm, life safety


equipment of types and capacities required, whose products have been in satisfactory
use in similar service for not less than 10 years. Provide fire alarm life safety system
equipment produced by a manufacturer listed as an Acceptable Manufacturer in this
section.

B. Standards Compliance: comply with requirements of all applicable local codes, BS.
Standards pertaining to Fire Alarm, Life Safety systems.

1.4 SUBMITTALS

A. List of all types of equipment and components provided including model numbers,
mounting accessories and quantities.

B. Description of operation of the system as described herein, to include all exceptions,


variances or substitutions listed at the time of bid.

C. Calculations to support size of standby batteries, manufacturer's printed product data,


catalogue cuts and description of any special installation procedures.

D. Proposed zone list with description of zones (alarm, monitor) as they would appear on
the MFAP (and FAP).

E. Provide shop drawings as follows:

1. 1:25 scale drawing of Fire Alarm Control Panel.

2. 1:50 scale floor plan showing equipment locations, drawings and raceway runs.

3. Fan shut-down, automatic and manual control wiring details. Coordinate with
HVAC section.

4. Complete riser diagram showing all equipment and size, type and number of all
conductors and conduits.

5. Peripheral device connection details showing all module and device wiring
details.

F. Provide samples of various items, when requested.

1.5 OPERATION

A. Activation of any manual pull station, or multi – sensor detector, to provide the
following automatic operations:

1. Sound a pulsing audible signal at the Fire Alarm Control Panel. Pressing the
alarm acknowledge key on the Fire Alarm Control Panel shall silence the audible
signal at MFAP (FAP) during the alarm condition.
Subsequent alarm conditions shall again sound the audible signal.

2. Flash the general alarm LED indicator on the Fire Alarm Control Panel. Pressing
the alarm acknowledge key on the fire alarm control panel shall continuously

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 3
AHC Co.
light the general alarm LED indicator during the alarm condition. Subsequent
alarm conditions shall again flash the general alarm LED indicator.

3. Display a general alarm indication and system status summary (numbers of


alarm, supervisory and/or trouble conditions) on the Fire Alarm Control Panel
Liquid Crystal Display (LCD). Pressing the alarm acknowledge key shall
display, for 30 seconds, the individual device display, to include the "alarm"
status and custom label (up to 40 characters and spaces) for the addressable
device reporting the alarm condition. At the end of the 30 second period, the
general alarm indication and system status summary shall again be displayed.
The individual device display may be recalled at any time by repressing the
alarm acknowledge key or until the alarm condition is reset to normal.

4. Enter the custom label for the device reporting the alarm condition with time and
date of occurrence into the fire alarm control panel historical alarm log for future
recall.

5. Sound the alarm tone followed by the Pre-Recorded Voice Massage giving
details of Alarm Device and Area of Activation using massage-splicing
capability, in the Area of Origin and adjacent areas. The Voice Alarm Massage
may be silenced during the alarm condition by operation of the Fire Alarm
Control Panel alarm silence switch. Subsequent alarm conditions shall resound
the Pre-Recorded Massage.

6. Flash all alarm strobe lights throughout the building. The alarm strobe lights
may be turned off during the alarm condition by operation of the Fire Alarm
Control Panel alarm silence switch. Subsequent alarm conditions shall again turn
on the alarm strobe lights.

7. Automatically shut down all supply and return/exhaust fans of air recalculating
systems serving the building, floor(s) in alarm. Give visual status of fan(s) at
MFAP (FAP).

8. Recall all automatic elevators to the ground/entry level or alternate level if


designated by the local authorities.
9. Automatically silence all paging and/or sound system(s).

10. Send an alarm signal to a Central Station monitoring facility to dispatch the Fire
Department.

11. Sound an audible signal at the remote annunciator panel. The audible signal may
be silenced during the alarm condition.

12. Visually annunciate the individual addressable device reporting the alarm
condition or the software defined group of addressable devices, which includes
the addressable device reporting the alarm condition, at the remote annunciator
panel, via an individual or "group" alarm LED indicator. The visual indication
shall remain on until the alarm condition is reset to normal.

13. Generate emails to send to pre-assigned email address. Persons receiving emails
shall be able to access the MFAP or FAP using standard Internet Browser using
authorized user names and passwords. Using Internet Browser, it shall be
possible to Access all Cards, Device and points Information from the system.
System not supporting this capability will not be acceptable.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 4
AHC Co.
14. PC command center will indicate the location of fire on the building layout plans
(CAD drawing) and activate the remote printer to printout a hard copy record of
the alarm activation to include the time and date and custom label for the device
reporting the alarm condition.

B. System Supervisory Operation for Off/Normal Conditions

1. The following equipment or devices associated with the fire alarm system shall
be supervised for normal and off/normal conditions:

a. Fire pump power failure and phase reversal.


b. Supervisory sprinkler valve switch.

2. Activation of any items in B.1 above to automatically:

a. Sound an audible signal at the Fire Alarm Control Panel. Pressing the
supervisory acknowledge key on the Fire Alarm Control Panel shall silence
the audible signal during the off/normal condition. Subsequent off/normal
conditions shall resound the audible signal.

b. Flash the general supervisory service LED indicator on the Fire Alarm
Control Panel. Pressing the supervisory acknowledge key on the Fire Alarm
Control Panel shall continuously light the general supervisory service LED
indicator during the off/normal condition. Subsequent off/normal conditions
shall again flash the general supervisory LED indicator.

c. Display a general supervisory indication and system status summary (numbers


of alarm, supervisory and/or trouble conditions) on the Fire Alarm Control
Panel Liquid Crystal Display (LCD). Pressing the supervisory acknowledge
key shall display, for 30 seconds, the individual device display, to include the
"off/normal" status and custom label (up to 40 characters and spaces) for the
supervisory device reporting the off/normal condition.

d. At the end of the 30 second period, the general supervisory indication and
system status summary shall again be displayed. The individual device
display may be recalled at any time by repressing the supervisory
acknowledge key or until the off/normal condition is restored to normal.

e. Enter the custom label for the zone reporting the off/normal condition with
time and date of occurrence into the Fire Alarm Control Panel historical
trouble log for future recall.

f. Sound an audible signal at the Remote Annunciator Panels. The audible


signal may be silenced during the off/normal condition.

g. Visually indicate a general supervisory, off/normal condition at the Remote


Annunciator Panels, via one general supervisory, off/normal LED indicator.
The visual indication shall remain on until the off/normal condition is restored
to normal.

h. Generate emails to send to pre-assigned email address. Persons receiving


emails shall be able to access the MFAP or FAP using standard Internet
Browser using authorized user names and passwords. Using Internet Browser,
it shall be possible to Access all Cards, Device and points Information from
the system. System not supporting this capability will not be acceptable.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 5
AHC Co.
i. PC command center will indicate location of fire and activate the printer to
printout a hard copy record of the off/normal activation to include the time
and date and custom label for the device reporting the off/normal condition.

1.6 SYSTEM SUPERVISION

A. Fire Alarm Life Safety System to be electrically supervised to automatically detect


and report trouble conditions as follows:

1. The fire alarm system wiring (except control wiring between fans and their
control zone addressable module) shall be electrically supervised to
automatically detect and report trouble conditions to the Fire Alarm Control
Panel.

2. Any opens or grounds on Monitor Zone Addressable Module alarm initiating,


supervisory or status monitoring circuit wiring and any opens, grounds or shorts
across addressable data communications, alarm signal or alarm light wiring shall
initiate a system trouble condition.

3. System addressable devices shall be supervised for placement and normal


operation. Removal of an addressable device or the failure of its internal
electronic circuitry shall initiate a system trouble condition. System shall place
the addressable device in self-test mode every four seconds and devices not
reporting normal outputs shall be reported as Self Test Abnormal Trouble.

4. Each Fire Zone shall be provided with two speaker circuits where speakers are
wired alternatively from each circuit. Each speaker circuit shall have its own
amplifier having its own back-up amplifier (one-for-one backup). Failure of one
amplifier shall not disable or degrade the system operation. System shall report
the failure of the amplifier and shall continue to work normally.

5. Trouble conditions shall automatically:

a. Sound an audible signal at the Fire Alarm Control Panel. Pressing the trouble
acknowledge key on the Fire Alarm Control Panel shall silence the audible
signal during the trouble condition. Subsequent trouble conditions shall
resound the audible signal. The audible trouble signal shall also resound at
programmable time intervals to remind the system operator that the trouble
condition(s) still exists.

b. Flash the general system trouble LED indicator on the Fire Alarm Control
Panel. Pressing the trouble acknowledge key on the Fire Alarm Control Panel
shall continuously light the general trouble LED indicator during the trouble
condition.
The visual indication shall remain on until the trouble condition is restored to
normal. Subsequent trouble conditions shall again flash the general trouble
LED indicator.

c. Display a general trouble indication and system status summary (numbers of


alarm, supervisory and/or trouble conditions) on the Fire Alarm Control Panel
Liquid Crystal Display (LCD). Pressing the trouble acknowledge key shall
display, for 30 seconds, the individual device or circuit display, to include the
"trouble" status and custom label (up to 40 characters and spaces) for the
addressable device or circuit reporting the trouble condition. At the end of the
30 second period, the general trouble indication and system status summary
shall again be displayed. The individual device/circuit display may be
MVP RIYADH HOTEL
MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 6
AHC Co.
recalled at any time by repressing the trouble acknowledge key or until the
trouble condition is restored to normal.

d. Enter the custom label for the device or circuit reporting the trouble condition
with time and date of occurrence into the fire alarm control panel historical
trouble log for future recall.

e. Sound an audible signal at the Remote Annunciator Panel. The audible signal
may be silenced during the trouble condition.

f. Visually indicate a general trouble condition at the remote annunciator panel,


via one general trouble LED indicator. The visual indication shall remain on
until the trouble condition is restored to normal.

g. Generate emails to send to pre-assigned email address. Persons receiving


emails shall be able to access the MFAP or FAP using standard Internet
Browser using authorized user names and passwords. Using Internet Browser,
it shall be possible to Access all Cards, Device and points Information from
the system. System not supporting this capability will not be acceptable.

h. Activate the remote printer to printout a hard copy record of the trouble
condition activation to include the time and date and custom label for the
device or circuit reporting the trouble condition.

1.7 SYSTEM WALK TEST

A. The Fire Alarm Control Panel shall permit one person system walk test. The walk test
mode shall be passcode protected, requiring the entry of a minimum four digit
passcode before the walk test mode is enabled. System shall give options of Silent
Walk-test, Voice Walk-test. Under Silent walk test options, system shall not activate
the Speakers but record the testing data in system history log. Under Voice Walk test
mode system shall announce the testing Device number using Speaker saying “testing
Device # … on channel #…”

B. Fire alarm system addressable devices may be divided into as many as eight groups
for testing purposes. Putting one group into the walk test mode shall not impair the
normal operation of the remaining seven groups.

C. When a group of addressable devices is put into walk test mode, the alarm verification
function, if provided, shall be disabled in order to expedite testing.

D. The walk test mode may be enabled for a programmable amount of time up to 8 hours.
If no devices in the system/an enabled group have been activated during the
programmed time, the Fire Alarm Control Panel shall automatically revert to normal
system operation.

E. When placed in the walk test mode by authorized personnel, activation of any alarm
initiating device shall:

1. Relay Device Testing Massage on Speakers giving exact details of device


number and channel number.

2. Log the alarm condition in the Fire Alarm Control Panel historical trouble log for
future review/recall.
3. The Fire Alarm Control Panel shall automatically reset itself after each alarm
test.
MVP RIYADH HOTEL
MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 7
AHC Co.

F. When placed in the walk test mode by authorized personnel, momentary


disconnection of addressable data communication, alarm initiating, supervisory or
alarm signalling circuit wiring shall:

1. Relay Device Testing Massage on Speakers giving exact details of device


number and channel number.

2. Log the trouble condition in the Fire Alarm Control Panel historical trouble log
for future review/recall.

3. The Fire Alarm Control Panel shall automatically reset itself after each circuit's
wiring is reconnected.

1.8 QUALIFICATIONS OF MANUFACTURER

A. Manufacturer and/or supplier of system specified shall have following qualifications


and submit documentary evidence of same:

1. Existence at time of bidding of local factory authorized office near project site,
with staff of factory trained engineers and technicians who are qualified to
provide instruction, routine and emergency maintenance and repairs on portions
of systems. Proof to include evidence of at least three similar installations
currently in satisfactory service. Installations by another distributor of proposed
manufacturer will not be accepted as proof.

2. Having 10 years or more of experience in successful application, installation and


operation of computerized systems, and sub-systems, as herein specified and
noted.

3. Provide written guarantee that local office will be maintained with qualified staff
of engineers and technicians for an agreed upon period.

1.9 TRAINING OF CONSOLE OPERATORS

A. Manufacturer to train not less than 5 operators of console, with personnel on job
instruction provided by competent engineer representing Manufacturer.

B. Manufacturer to provide each operator with complete, printed operating instructions


and brief sub-system description in manual or handbook form.

C. Manufacturer to provide two distinct training sessions, with minimum training time of
one day each. Sessions scheduled to suit requirements, may be scheduled at any time
from award of contract to end of guarantee period at owner's request.

D. Manufacturer to train operators in preventive maintenance of console printers and


other equipment, inclusive of replacing paper, tapes and bulbs.

E. Manufacturer to furnish letter stating that operators have completed training operation
of system.

1.10 COORDINATION

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 8
AHC Co.
A. Contractor to coordinate with Mechanical Contractor and Section 15000 for
installation of duct mounted smoke detectors and motor controls.
B. Contractor to coordinate with electrical contractor and section 16000 for interface with
electrical power supply.

C. Contractor to coordinate with Elevator Contractor for interface with terminal recall
relay.

D. Contractor to coordinate with Architect for final locations of devices and appearance.

1.11 ZONING OF DEVICES (FOR LED ANNUNCIATION AT FAP & MFAP

A. Manual Alarm Stations: Provide one alarm zone per floor.

B. Area Multi - Sensor Detectors: One detector zone per floor plus individual zone for
all electric rooms/closets per floor and mechanical rooms per floor.

C. Sprinkler Water Flow Switches: Individually zoned per switch for alarm.

D. Sprinkler Valve Tamper Switches: Provide one monitor zone for each switch or a
maximum of two switches per zone if serving the same sprinkler branch line.

PART 2 - PRODUCTS

2.1 RECOMMENDED MANUFACTURER

- Refer to list of recommended manufacturer.

2.2 MATERIAL

A. Wire and Conduit: Provide in accordance with system requirements as stated herein
and by the manufacturer in accordance with all applicable codes and authorities
having jurisdiction and installed in conduit throughout.

2.3 EQUIPMENT

A. Basic System Equipment, Addressing and Operating Capabilities

1. The addressable fire alarm system shall provide an individual multiplex data
address for each addressable manual fire alarm station, addressable area smoke
detector, addressable heat detector, Monitor Zone Addressable Module and
Control Zone Addressable Module.

2. The Fire Alarm Control Panel shall be UL listed and shall comply with Standard
NFPA 72, and provide addressable data communications circuits to provide
connection of and communication with the addressable devices, as required by
these specifications and/or as shown on the drawings. Each addressable
communications circuit shall provide the capability of communicating with up to
250 addressable devices without any restriction on number of Sensors or
modules. System having restriction on number of Sensors and/or modules on
addressable communication circuit shall not be acceptable. In order to permit
future additions, no more than 80% of the addresses available on any single
addressable data communications circuit shall be utilized.
3. Addressable data communications between the Fire Alarm Control Panel
Addressable Interface Circuit Modules and addressable devices shall be digital

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 9
AHC Co.
transmissions which shall consist of multiple 11 bit messages with start, data,
parity and stop bits.

Address, parity, overrun, framing and check sum tests must be passed for any
message to be considered valid. Addressable data communications circuits
between the Fire Alarm Control Panel and addressable devices shall operate at
4800 baud. Each NFPA 72, Style 6 (Class A, four-wire) addressable data
communications circuit shall be capable of communicating with an addressable
device up to 375 wiring meters distant and with a total up to 1,500 meters of
wiring in all branches.

4. Monitor Zone Addressable Modules shall be provided to connect to and provide


individually addressed alarm initiating, supervisory or status monitoring circuits
for non-addressable devices such as sprinkler waterflow alarm switches, remote
building(s) alarm and trouble, sprinkler valve tamper switches, fans and/or
dampers. Each Monitor Zone Addressable Module shall provide one NFPA 72,
Style D (Class A, four wire) supervised circuit. Assignment of individual
MZAM circuits for alarm, supervisory or status monitor operation shall be
accomplished during the programming of the Master Controller Module Central
Processing Unit (CPU) software.

5. Control Zone Addressable Modules shall be provided to connect to and provide


Fire Alarm System Control of remote equipment such as air handling systems
and stairwell smoke hatches.

Each Control Zone Addressable Module shall provide one individually


addressable control relay with Double-Pole, Double-Throw (DPDT) contacts
fused. Assignment of individual CZAM relays for control operation shall be
accomplished during the programming of the Master Controller Module Central
Processing Unit (CPU) software. Each of the following types of equipment shall
be provided with a CZAM control relay typically as follows:

a. Fans: Provide one release contact for each fan as required by the Mechanical
Specifications and Local Codes and authorities.

6. Each of the following types of remote equipment associated with the fire alarm
system shall be furnished with a manual control switch at the Fire Alarm Control
Panel, as required by the functional requirements of these specifications, but
shall be typically as follows:

a. Provide a switch with LED status for lock-out of elevator recall operations for
use during testing of system.

b. Provide a switch with LED status for disconnection of Central Station


signaling.

c. Provide a switch with LED status for each supply and return/exhaust fans.

B. Fire Alarm indication and Control Panel(s): The Fire Alarm System Control Panel(s)
shall incorporate all control, alarm, relay and necessary modules and components in
surface mounted cabinets. The operating controls and zone/supervisory indicators
shall be located behind locked, steel door/Plexiglas window assemblies, with keys
made available only to Fire Department and other authorized operating personnel. All
control modules shall be labeled, all zone locations shall be identified, and the panel
shall be provided with a set of permanently mounted operating instructions.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 10
AHC Co.
The panel, door and frame assembly shall be steel, with red finish. The panel shall
contain system power supplies, data bus conductors, battery charger and all necessary
function modules and components, including but not necessarily limited to the
following:

1. Master Controller Module: A panel shall be provided to act as a central


processing, indicating and control location for the fire alarm system and shall
include:

a. Solid state, microprocessor based, Central Processing Unit (CPU) to process


all system data and generate all system automatic alarm functions. Any
addressable device or conventional hard-wired alarm initiating, supervisory or
status monitoring circuit may be software programmed to activate any system
control relay or signalling circuit. All control-by-event programming, custom
LCD display labels and alarm codes shall be stored in non-volatile solid state
memory, which shall be on-site programmable. CPU shall have a Back-Up
Solid state memory to store a Secondary Operating System. System not
having Secondary Operating RAM shall provide a Redundant CPU Card to
provide the secondary operating software.

b. Four levels of access to system control and software functions. Level 1 shall
be the lowest level of access and shall not require a passcode. Levels 2, 3 and
4 shall require a passcode of up to ten digits, with Level 4 being the highest
(most restricted) level of access. System software shall permit up to 20
individual passcodes to be programmed into the system.

c. Solid state memory for alarm and trouble historical logs. Each log, alarm or
trouble, shall be capable of storing up to 1200 events with the time and date of
occurrence. System shall have separate Alarm and Separate Trouble History
log. System having single history log for both alarm and trouble shall not be
considered equal.

d. A module placement supervisory circuit through the module data conductors.

e. 80 character, alphanumeric, backlit, Liquid Crystal Display (LCD).

f. System alarm LED indicator with alarm condition acknowledge button.

g. System supervisory condition LED indicator with supervisory condition


acknowledge button.

h. System trouble condition LED indicator with trouble condition acknowledge


button.

i. System power LED indicator.

j. System alarm silence button.


k. System reset button.

l. Central station alarm disconnect switch with "activated" LED indicator.

m. Four programmable control switches with "activated" LED indicators.


n. An alarm/trouble audible signal.

o. Display action and data entry/control keypads.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 11
AHC Co.
p. Two NFPA 72, Style 7 (Class A, four-wire) alarm signalling circuits.

q. Two alarm operated Single-Pole, Double-Throw (SPDT) relays.

r. One trouble operated Single-Pole, Double-Throw (SPDT).

2. System Meter Module: The system meter module shall provide visual indication
of system voltage and supervisory current. The meter module shall contain a
voltmeter with a range of from 0 to 50 VDC for indicating system voltage. The
module shall be readily disconnected for ease of servicing and placement
supervised via its connection to the Master Controller Module.

3. Addressable Interface Module: The addressable interface module(s) shall


provide one addressable data communications circuit to enable the Fire Alarm
Control Panel to communicate with the addressable devices. A single open or
ground fault shall not impair a circuit's operation. Addressable data
communications circuit wiring shall be supervised for opens in the circuit, shorts
across the pair and ground faults. An addressable data communications circuit
fault shall initiate a system trouble display and audible trouble signal at the Fire
Alarm Control Panel.

Faults on one addressable data communication circuit shall not impede operation
of other circuits. The module shall be readily disconnected for ease of servicing
and shall be placement supervised by the Master Controller Module.

Provide available spare space in the FAP & MFAP for a minimum of two future
addressable interface modules.

4. Indicating Appliance Signal Circuit Modules: The indicating appliance signal


circuit module(s) shall provide two or six independently controllable alarm signal
circuits. Each alarm signal/speaker circuit shall be configured for NFPA 72,
(Class A, four-wire) supervised operation monitoring for opens, shorts or ground
faults. When wired in the Class A, four-wire configuration, a single open or
ground fault shall not prevent the activation of the alarm signal devices.

When a circuit fault is detected, the module shall light the general trouble LED
on the Master Controller Module and initiate a system general trouble condition.
Each signal circuit shall be protected by an individual fuse on the module. The
module shall be readily disconnected for ease of servicing and placement
supervised by the Master Controller Module.

5. Audio Control and Massage Center Module: The module shall provide eight
channel digital audio capability with capacity up to 32 minutes of pre-recorded
massages. It shall be possible to record the massages on the field and download
directly to this module. This module shall also have built-in voice tone
generators and each component of this module is supervised be the CPU. This
module shall support one local Microphone and one remote microphone.
Addition of optional auxiliary Input module shall provide the ability to connect
multiple remote Microphones and other music sources if required. System shall
have the Fire Fighters Intercom Module to facilitate two-way voice
communication between Master station and Remote Phones.
6. Amplifier Module: Amplifier Module shall provide the decoding and
amplification of digital voice massages coming from Audio Control and Massage
Center and transmit these massages as well as live voice from microphones to
selected speaker circuits. Speaker circuits shall be built-in with the amplifiers for
extra reliability. Each amplifier shall be provided with back-up amplifier and
MVP RIYADH HOTEL
MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 12
AHC Co.
shall be housed in the FAP. System requiring separate cabinets specifically for
amplifiers shall not be considered as integrated systems and hence shall not be
acceptable.

7. Remote Annunciator Interface Module: Two type of Annouciator Interface


Module shall be provided with system. 1. Internet Interface Module : Capable of
Generating e-mails for system events and transmit these emails to
preprogrammed email address and shall provide the Web Browser based Access
to FAP and MFAP. 2. RS-232 Interface Module: The RS-232 annunciator
interface module shall provide one digital, serial communication circuit to enable
the Fire Alarm Control Panel to communicate with remote serial annunciators.
The serial communication circuit wiring shall be supervised for opens in the
circuit, shorts across the pair and ground faults.

A serial communication circuit fault shall initiate a trouble display, audible


trouble signal and printout, if a system printer has been provided. The module
shall be readily disconnected for ease of servicing and shall be placement
supervised by the Master Controller Module.

8. Battery Pack: The fire alarm system shall be provided with battery backup
capability. The battery shall be sealded lead acid battery maintenance free, float
voltage is internally adjustable, life time 5 years at 0-30°C ambient temperature,
protection by thermal magnetic circuit breaker and charger should be trikle type
the batteries shall provide 24-hours of normal standby operation and 15 minutes
of normal alarm operation at the end of the 24-hour standby period. The batteries
shall be placement and high/low voltage supervised by the Master Controller
Module.

9. Network Interface Module: Network Interface Module shall provide the


networking capability of FAP and MFAP. All Panels shall be networked in a
peer-to-peer network where each panel works independently. Network shall
support 99 FAP’s (nodes) in one loop and shall be capable of handling 396
Nodes in multiple-loop network.

C. Peripheral Devices: The following material to be supplied and installed as indicated


on the drawings:

1. System PC Display and Keyboard (located at the MFAP): The PC display shall
have coloured, non-glare, 20 inch diagonally measured screen. The detachable
keyboard shall be of the enhanced, 101 key type and shall permit data
communication with the system Central Processing Unit (CPU) to permit the
operator to acknowledge system alarms and request status reports. The following
feature shall be available

- Graphical Annunciation and Control.


- Up to 25,000 Custom Graphic Screens, Field Generated/Edited Via Auto
CAD DXF File Format Drawing Tools.
- Custom Alarm and Trouble Messages Guide Operator Dispatch Response.
- Seven Access Levels for 256 Users.
- Includes Network Interface for Wired or Fiber Optic Communications.
- 20" High Resolution Monitor.
- Desk Top Enclosures.
- Touch-screen and Mouse Operation.
- Extensive Historical Logging:
Up to 500,000 Events.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 13
AHC Co.
- Compatible with Spread Sheet and Data Base Programs for Report
Customization.
- Operator Notations can be Added.
- Graphical Diagnostic Tools Identify Exact Status of Network Nodes and
Wiring.
- Dial-Up Service Modem for Remote Access.
- RS232 Ports for Connection to Printers, Paging Systems, or Third Party
Systems.

2. System Printer: Desk-top lazzer type and shall provide the following operational
capabilities:

a. A permanent hard-copy record of all pertinent details of system activity.


Included on this record shall be all unscheduled status change events, all
operator acknowledgments of these events and all operator control commands
into the system and the time and date of all occurrences.

b. The system printer shall record all alarm, supervisory and trouble conditions
by address number and custom label.

The custom label, of up to 40 characters and spaces, and time and date of
alarm, supervisory or trouble condition activation shall be printed out in a
language text so that the source of the condition is clearly understood without
referring to a code directory. Printout by address or code number only shall
not be as considered functionally equivalent.

c. The custom label (location message), of up to 40 characters and spaces, for a


specific device or circuit shall correspond to that displayed on the Fire Alarm
Control Panel Liquid Crystal Display.

3. Fire alarm repeater panel (FARP): The fire alarm repeater panel shall receive its
data from the Fire Alarm Control Panel via a supervised serial communications
circuit. There shall be 8 LED indications per component module. One LED shall
be provided for each indication and each indication label. Custom labels of up to
three lines of nine characters and spaces shall be typed as required for each
indication. The custom labels shall be protected by clear plastic windows. The
LED indicators shall be located behind locked, door/window assembly, with
keys made available only to Fire Department and other authorized operating
personnel. The panel, door and frame assembly shall be steel with medium beige
finish. Annunciator shall include LED test capability a system general trouble
LED indicator, a system general off/normal LED indicator, an alarm/trouble
buzzer and silence switch.
Provide required number of alarm LED indications herein above described. The
(FARP) shall be provided for semi-flush mounting or surface mounting with
matching back-box, where shown on the drawings.

4. Addressable Manual Fire Alarm Stations: Manual Station Shall be UL listed and
shall be Double Action (Break Glass and pull alarm lever), non-coded type
manual station, of cast metal construction, with normally open, Single-Pole,
Single-Throw general alarm contacts. The manual station shall include an
addressable module which shall consist of printed circuit board with discrete
circuitry for monitoring the station alarm contacts. Device addressing shall be
done using Dip-Switch. No soft-addressing methods will be acceptable.
Changing the in-out wiring terminals at the device during installation as well as
during maintenance shall not cause any problem to the system operation. When
operated, the alarm lever shall remain in its "down" position to indicate its
MVP RIYADH HOTEL
MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 14
AHC Co.
operation, with alarm contacts closed until the station is reset. The station shall
be reset by opening the front, resetting the lever and closing the station front.
The station shall be tested by opening the station front and then returning same to
normal. It shall be necessary to open the station to replace the break rod. A
spare break rod shall be furnished with each station.

5. Multi – sensor Detector: shall be UL listed Early fire detection will be achieved
by combining the performance of photoelectric smoke sensor with a fast –
acting and accurate thermal sensor to provide both features in a single sensor
assembly.

Analogue information from each sensor will be digitally communicated to the


fire alarm control panel.

- Photoelectric Sensing;-

Photoelectric sensor use a stable, pulsed infrared LED light source and a
silicon photodiode receiver to provide consistent and accurate low power
smoke sensing. Seven levels of sensitivity must be available for each
individual sensor, ranging from 0.2% to 3.7% per foot of smoke obscuration.
Sensitivity is selected and monitored at the fire alarm control panel.
Sensor Head: must provides 360° smoke entry for optimum smoke response.

- Heat Sensing:

heat sensors monitor a fast reacting thermistor providing operation that is self-
restoring and rate compensated. Due to its small thermal mass, the sensor
accurately and quickly measures the local temperature for analysis at the fire
alarm control panel.
The control panel allows alarm selection to be per sensor as fixed temperature,
or rate – of rise temperature, or the combination of both.
Temperature Detection: rate – of – rise temperature detection is selection at
the control panel for either 15° F (8.3° C) or 20° F (11.1° C) per minute. Fixed
remperature sensing is independent of rate – of – rise sensing and selectable to
operate at 135° F (57.2° C) or 155° F (68° C). In a slow developing fire, the
temperature may not increase rapidly enough to operate the rate – of – rise
feature. However, an alarm will be initiated when the temperature reaches its
selected fixed temperature settings.
Utility Temperature Monitoring: heat sensors can be programmed as a utility
device to monitor for temperature extremes in the range from 32° F to 122° F
(0° C to 50° C). This feature can provide freeze warnings or alert to HVAC
system problems.

All Sensor Addressing mechanism and electronics shall be in the base to


avoid programming of address while replacing the sensors Head and also
during maintenance staff wrong Head placement mistakes. Device addressing
shall be done using Dip-Switch. No soft-addressing methods will be
acceptable. Changing the in-out wiring terminals at the device during
installation as well as during maintenance shall not cause any problem to the
system operation.

6. Photoelectric Projected Beam Type Smoke Detector.

Projected photoelectric beam smoke detection is used to protect large areas,


where spot type smoke detection is impractical.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 15
AHC Co.
The microprocessors based long-range beam smoke detector consisting of a
separate transmitter and matching receiver providing accurate and repeatable
monitoring of smoke passing through the light beam.

The transmitter produces a crystal controlled, infrared beam which is monitored by


the receiver to determine smoke obscuration. When the receiver measures beam
intensity below a preset, selectablthreshold, an alarm output is generated .
Standard alarm delay is 30 seconds.

Complete beam blockage and dust accumulation that reduces signal level to 50%
will initial a trouble output. Intermittent beam blockage, such as cleaning, is
ignored. Tamper switches monitor the access covers and cause a circuit trouble if
activated.

Although external light sources must be considered when locating the beam
detector pair, the transmitter beam has a format signature that allows the receiver to
minimize interference from such sources.

7. Heat Sensors

Thermal Sensor: Combination fixed-temperature and rate-of-rise unit with plug-


in base and alarm indication lamp; 135-deg F fixed-temperature setting except as
indicated.

Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be


thermistor-based, rate-compensated, self-restoring and shall not be affected by
thermal lag.

Sensor fixed temperature sensing shall be independent of rate-of-rise sensing and


programmable to operate at 135-deg F or 155-deg F. Sensor rate-of-rise
temperature detection shall be selectable at the FACP for either 15-deg F or 20-
deg F per minute.

Sensor shall have the capability to be programmed as a utility monitoring device


to monitor for temperature extremes in the range from 32-deg F to 155-deg F.

8. Air Aspirating Smoke Detector

The Compact Air Aspirating Smoke Detectors (ASD) shall be UL Listed and
shall be provided in computer and communication equipment areas. ASD shall
be analogue addressable type Laser Sensor and shall sit on the addressable
devices loop along with other devices. Just relay contact interface with ASD
shall not be acceptable. It shall be possible to change ASD sensitivity from the
FAP. ASD shall be specifically designed to provide all the benefits of aspirating
smoke detection, including very early warning, in single environment small areas
and where space is a premium. This shall be achieved through the combination
of approved Laser Based detection technology, dual-stage air filtration
technology and a aspirator design incorporated into a smaller enclosure with a
simplified display .

Air shall be continually drawn through a simple pipe network to a central


detector by a high efficiency aspirator. Air entering the unit shall pass a flow
sensor before a sample is passed through a dual-stage dust filter (the majority of
air is exhausted from the detector and where required back vented to the
protected area. The first stage removes dust and dirt from the air sample before it
enters the chamber for smoke detection. The second ultra fine stage provides a
MVP RIYADH HOTEL
MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 16
AHC Co.
clean air supply to be used inside the detection chamber to form clean air
barriers, which protect the optical surfaces from contamination.

9. Monitor Zone Addressable Modules: Shall be individually addressable alarm


initiating/supervisory circuit board(s) and shall consist of printed circuit board
with discrete circuitry for monitoring normally open, dry contacts using NFPA
72, (Class A, four-wire) circuit supervision. The monitor shall respond to polling
signals from the Fire Alarm Control Panel and shall report alarm
initiating/supervisory circuit status changes to it. The monitor shall include a
field programming capability for the assignment of its individual address number
and clamp-type terminals for making wiring connections.

The monitor shall draw its power from the Fire Alarm Control Panel via a
separate power circuit. The monitor shall be furnished for flush mounting or
surface mounting, where shown on the drawings.

10. Control Zone Addressable Modules: Shall be individually addressable control


relay and shall consist of printed circuit board with discrete circuitry for
controlling one individually addressable control relay with Double-Pole,
Double-Throw contacts. The control shall respond to control signals from the
Fire Alarm Control Panel.

The control shall include a field programming capability for the assignment of its
individual address number and clamp-type terminals for making wiring
connections. The control shall draw its power from the Fire Alarm Control Panel
via a separate power circuit.

11. Duct Smoke Detectors : photoelectric type, incorporating sampling tubes and
housing designed for this application. Duct mounted smoke detectors hidden
from view to be supplied with remote indicating pilot lights for wall/ceiling
mounting near the location of the hidden detector. The detector to be of the same
manufacturer as the control equipment and incorporate a built-in test station.

12. Speaker And Strobes:- audio / visible notification appliance with speaker and
high intensity xenon strobe.

Audible notification appliance (speaker):-

a. High quality voice and tone reproduction with taps for ¼, ½, or 2 W at 70


VRMS.
b. Capacitor input for connection to supervised notification appliance circuits.
c. UL listed to Standard 1480.
d. Speakers are wired separately from addressable module.

Visible notification appliance (strobe):

a. Xenon strobe with the following candela output:-

15 cd : For maximum room size 6.1 × 6.1 mt.


78 cd : For maximum room size 13.7 × 13.7 mt.
110 cd : For maximum room size 16.5 × 16.5 mt.

b. UL listed to standard 1971.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 17
AHC Co.
c. Supervision of each individual strobe’s wiring and connections with
activation at a synchronized 1 Hz flash rate.

13. Electromagnetic Door Holder:

a. Door holders are normally energized to provide door holding with a


minimum force of 25 Ibs. In the event of a fire emergency, the fire alarm
control panel will release the magnet allowing the door to close to prevent
the spread of smoke. Doors may be manually closed or opened when the
door holder is energized.

b. Electromagnetic door holders with models available for:

- Flush wall mount.


Or
- Floor mount, single or double door.

Low current, multi – voltage design reduces power supply and battery
demands:

- Operates with 24 VDC.

Internal full wave rectifier allows DC operation and provides switching


transient suppression.
Low residual magnetism allows easy door release for compatibility with low
pressure door closers.

c. Holding force in 25 Ibs minimum UL listed to standard 228.

14. Power Amplifiers:

a. One amplifier of at least 120 watt RMS rating is to be supplied per speaker
zone. Maximum initial loading 75% of output rating of amplifier.
b. Technical Performance

1) Power rating: 120W RMS continues duty measured with sine wave
signal.
2) Frequency response: 3 dB 50 Hz to 18 kHz fully loaded.
3) No load to full load differentiation less then 3 dB.
4) Noise 85 dB below rated output.
5) Distortion less then 0.3%.
6) Quiescent power consumption 42 ma.
7) Full load power consumption 6.0 mp.
8) Output voltage to be 25 volt constant voltage distribution
configuration.

15. a. Interface units (control and monitor module) shall be provided as indicated on
the drawings.

b. Each interface unit shall be provided with the following :

1. Facility to connect and fully monitor/control detection (min 10 No.


devices) and 2 No. alarm Bell circuits without the need for additional
control equipment.

16. Analogue Monitor Module (AMM)


MVP RIYADH HOTEL
MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 18
AHC Co.
a. AMMs shall provide an accurate, multi-featured interface for connecting
analog sensors (GAS Sensors, Temperature Sensors) to addressable fire
detection panels. The panel shall monitor the sensor and annunciates
whenever a selected threshold level or trouble condition is observed. Typical
applications include: GAS Detection, air quality for demand control
ventilation, air and liquid temperature, humidity, and air velocity.

b. The Analogue values shall be monitored using Industry Standard 4-20 milli-
Amp Format. The 4-to-20 mA loop is an established analog format that is
highly reliable and inherently supervised for loop integrity. For additional
monitoring, AMM shall also have the capability to monitor sensors “dry”
trouble contacts. Three level of threshold shall be programmable from the
FAP and at each level programmed action can be taken.

17. Visual Display Unit : Desk-top type, providing as the fire alarm system (CRT)
annunciator display with eighty (80) characters per line by twenty-four (24) lines
on a 30 cm diagonal screen. The VDU also to be equipped with keyboard and
battery standby power to enable it to operate, during alarm conditions, for ten
minutes at the end of a 24 hour period.

D. Warden Fire Telephone Communication (Two – Way) From The Fire Command
Center

1. General

i) Lifting a telephone handset from its cradle to automatically:-

a. Sound an audible signal at the fire command station.


b. Flash the individual telephone "call/select" LED indicator for the calling –
in circuit at the fire command center.

ii) Connecting the call, by operating the appropriate telephone line "call-
connect" switch, at the fire command center shall automatically:

a. Light the "call-connect"switch’s built-in "operated" indicator lamp.


b. Silence the audible call-in signal.
c. Connect the appropriate fire-fighter telephone circuit to the fire command
center master telephone for talking.

iii) Operating additional fire-fighter telephone line select switches, at the fire
command center shall automatically:

a. Permit fire-fighter telephone to talk to other fire-fighter telephone


locations via a patch in the telephone network, controlled at fire
command center. Up to five fire – fighter telephone may be operated
simultaneously.

iv) Fire – fighter telephone stations to be capable of making announcements


over alarm speaker circuits via a "patch" circuit and speaker circuit control
switches, controlled at the fire command center.

2. Fire – Fighter’ s Telephone Stations

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 19
AHC Co.
a. Fire – fighter’s telephone stations: provide a flush, mounted enclosure,
painted red, with telephone handset permanently mounted in a break glass
type enclosure.

PART 3 - EXECUTION

3.1 INSPECTION

A. Examine areas and conditions under which fire alarm system is to be installed. Notify
Engineer in writing of conditions detrimental to proper completion of the work. Do not
proceed with work until unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install fire alarm devices, wiring and main equipment as indicated, in accordance with
manufacturer's written instructions, requirements of applicable Standards, and in
accordance with recognized industry practices to ensure that installation complies with
requirements and serves intended function.

B. Coordinate as necessary to interface installation of fire alarm system with other work.

C. Protect all equipment from dirt, moisture and construction debris, subsequent and
during installation until project is accepted by Engineer.

D. Fire stop penetrations of floor slabs or fire walls in accordance with all local codes.

E. Contractor to furnish all conduit, wiring, outlet boxes, junction boxes, cabinets and
similar devices necessary for a complete installation. All wiring types as recommended
by the manufacturer installed in conduit throughout or as approved by the local Fire
Department. Junction boxes to be painted fire department red for identification.

F. All wiring shall be color coded throughout, to local or National Electrical Code
Standards. All wiring shall be of the type recommended by the manufacturer, type
Flame retardant, and shall be installed in dedicated, rigid, threaded, steel, galvanized
conduit throughout. Provide flex conduits at waterflow, tamper and smoke vent
connections.

G. All wires shall test free from earth or crosses between conductors.

H. Circuit wiring from the Fire Alarm Control Panel to the system
peripheral equipment shall be a minimum of as follows:

1. Each addressable data communications circuit: Two cables, each composed of


two 1.0 mm2 conductors, twisted and shielded.

2. Each alarm initiating, supervisory or status monitoring circuit originating from a


Monitor Zone Addressable Module: Four 1.5mm2 conductors.

3. Alarm speakers and light strobes originating from the Fire Alarm Control Panel:
Four 2.5mm2 conductors.

4. Each control circuit originating from a Control Zone Addressable Module: Four
2.5mm2 conductors.

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 20
AHC Co.
5. Zone addressable module power circuit/feed: Four 2.5mm2 conductors.

I. Fire alarm system terminal and junction locations shall be identified in accordance with
NFPA Standard 70, Section 760-3. Terminal and junction boxes shall be painted red
and stenciled in white letters "FIRE ALARM," preventing unintentional interference
with the fire alarm system wiring during testing, servicing and additional modifications
to the system.

J. The system shall be arranged to receive power from three-wire, 220/380 volt, 50 Hertz
alternating current supply through fused cut-out. All low voltage operation shall be
provided from the Fire Alarm Control Panel(s).

K. All final connections between system equipment and the wiring shall be made under
the supervision of a trained manufacturer's technical representative.

L. Wiring within component enclosures and terminal cabinets: All wiring shall be
installed in a neat and workmanlike manner and shall be trained parallel with or at right
angles to the sides and back if any enclosure or cabinet. All circuit conductors broken,
spliced, or connected in any enclosure, cabinet, mounting or junction box shall be
connected to terminal blocks with each terminal spade lugs or with approved pressure
type terminal blocks. A terminal cabinet shall be installed where any circuit tap is
made and must be painted fire department red. All wiring within the enclosure shall be
readily accessible without removing any component parts.

M. System Field Wiring: Field wiring shall be copper sized as required. Wiring
connecting the power supply shall be minimum 4mm2 size conductors.
All conductors shall be installed in metal conduit run surface or concealed and as
required by applicable codes. Each conductor used for the same specific function shall
be distinctively color coded. Wiring for the fire systems shall be installed as herein
described and separate from any other wiring systems.

3.3 CLEAN UP

A. Upon completion of the installation, all debris created by the installation shall be
removed from the premises or disposed of as directed by the Engineer.

3.4 FIELD QUALITY CONTROL

A. Upon completion of installation of Fire and Life Safety System and after system has
been energized, test equipment to demonstrate compliance with requirements. Field
correct or replace defective equipment, and retest.

B. A factory trained technician to supervise the final connections, tests and adjustments of
all equipment upon completion. Each device be tested by the manufacturer's
representative, in the presence of the Engineer a test report completed in triplicate, and
signed by the Engineer to indicate that he witnessed the testing of the system. A copy
of the test report shall be posted adjacent to the Fire Alarm Control equipment and
enclosed in a glass directory stainless steel frame.

C. Upon completion and prior to all acceptance, perform complete system tests as follows:

1. Actuate all manual and automatic alarm and monitor initiating devices one at a
time and verify proper operation.

2. Verify:

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 21
AHC Co.

a. Operation of all signaling and indication systems as specified including


proper zone identification and labeling at the Fire Alarm Control Panel and
Remote Annunciator.

b. Fan shut-down.

c. Transmission of alarm to security office.

d. Manual control of items as specified.

e. Class and type of wiring.


f. Automatic operations of specified items.

3. Power:

a. Verify operation of standby power sources as follows:

1) Remove primary power and check for battery operation as specified.

2) Remove primary power and check for automatic switch-over to secondary


source.

4. Check for proper sequence and priorities.

D. Submit 5 copies of test data and results, signed by test personnel.

E. Correct or adjust items not found acceptable by authorized representative.

F. Repeat tests to indicate corrected items.

3.5 GUARANTEE

A. All components, parts and assemblies supplied by the manufacturer to be guaranteed


against defects in materials and workmanship for a period of 12 months from Owner
and fire department acceptance.

B. Equipment manufacturer to have a local branch office staffed with trained, full-time
employees who are capable of performing testing, inspection, repair and maintenance
services for the life of the System.

C. Contractor to guarantee all wiring to be free from inherent mechanical and electrical
defects for one year. The manufacturer to furnish a one-year maintenance contract,
free of charge to the owner, effective from the date of installation for maintenance and
inspections of the manufacturer's equipment; with a minimum of two inspections
during the contract year. A local manufacturer service department which stocks
standard parts to be available to the owner. If required, maintenance is to be performed
during normal working hours, at no cost to the owner, for a period of twelve months
from the completion date of the installation, unless damage is caused by misuse, abuse
or accident.

3.6 SERVICE AND MAINTENANCE

A. The equipment manufacturer shall make available a fully equipped service


organization, capable of guaranteeing an on-site service response time within 8 hours

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 22
AHC Co.
to a service request call. Site service shall be available 24 hours per day and seven
days per week.

B. As part of this Contract, the Contractor shall receive from the equipment manufacturer
and turn over to the Owner the following system spare parts:

1. 50% spare of each type of fuse.

2. 30% spare of each type of lamp.

3. 10% spare of each type of alarm initiating device.

4. 5% spare of each type of detector and station

C. The equipment manufacturer shall make available, to the Owner, a price quotation for a
one year maintenance and testing agreement, to take effect on the date of final
acceptance.

3.7 INTER CONNECTION WITH OTHER SYSTEMS

The system supplier is responsible to provide all required switches, auxiliary contacts, relays,
wiring, terminal blocks transducers to provide signaling and metering information for the
building & energy management system (BEMS) and to accept START/STOP, open/close, set
point from it.

Relevant signals are listed under controls, (BEMS) and motor control panels drawings and
data schedules.

All signals to the BMS system should be potential free to actuate devices of less than 20 VA.
@ 220 volt.

If any device will need more than 20 VA. at any operating condition the supplier should add
interposing relays.

All analog measures coming or going to the (BEMS) should be coordinated with the (BEMS)
supplier (either 4-20 MA or 1-5 volt or -10 volt) or directly connected to the (BEMS)
communication bus .

END OF SECTION 16760

MVP RIYADH HOTEL


MULTIPLEXED/ADDRESSABLE FIRE ALARM LIFE SAFETY SYSTEM
Date: MAR., 2008. Rev. : 1 16760 - 23

You might also like