Liebert NPS I
Ensuring Continuity of Power to Load
User Manual
for Installation & Operation
Liebert
Network Power Switch I
Models
16Amp 2 POLE
32Amp
1 POLE
63Amp
Hight in U :- 3U / 4U
Mounting type :- R - Rack
Liebert Nework Power Switch I
* Available in output voltage at 110Vac apart from standard 230Vac output voltage.
NPS - I 3.0
Emerson Network Power: The global leader in enabling
business-critical continuity.
Emerson Network Power (India) Private Ltd.(formerly Tata Liebert Limited) is a wholly owned
subsidiary of Emerson Electric USA. a $US 20.9 billion company that is ranked 94th on the Fortune 500
list of America's largest companies. Set up in September 1993. the Indian subsidiary has seen a
consistent growth rate of more than 30% p.a . over the last 16 years. After the company transitioned
itself to Emerson Network Power India in 2001. the company has made a conscious effort to align itself
with its global parent. From grid to chip for telecommunication networks, data center, health care and
industrial facilities. Emerson has moved from being a UPS and Precision AC manufacturer to a "Global
Leader in enabling Business Critical Continuity solutions:'
Emerson Network Power India's solutions cater to an array of large enterprises spanning across
Government, BFSls, BPOs, Industrial Process Control Rooms, Food Processing Industries, Broadcast
Facilities, Building Services Control Room, Surveillance and Monitoring Centers and Retail Malls.
Emerson Network Power has been amongst the pioneers to develop and introduce energy efficient product
concepts ln a break through move in 2008, Emerson Network Power India unveiled Energy
Logic concept for data centers that has virtually removed the three most critical constraints faced by
data center managers today: power cooling and space.
An ISO9001 certified company: Emerson Network power(lndia) Private Ltd . crossed a major milestone
in its quality journey when it was accorded Level II recognition by MAlT (Manufacturers Association for
Information Technology) in 1998. This is the highest ever recognition accorded by MAlT in India for a
company and the first in the manufacturing sector. In 1999 the Confederation of Indian Industries.(CII)
recognised the company for its strong commitment to Quality through a Certificate under the CII-Exim
Business Excellence Award.
Emerson also has a long list of awards to its credit. notable ones being:
• Frost & Sullivan "Voice of Customers Awards" for the Indian UPS Industry
Apart form this the company has won various product line & customer service leadership awards in
IT/lTES/Data Centers. Large Enterprises, Hospitals, Telecom and Customer service leadership award in
Banking/lnsurance/ Non-banking financial.
Emerson Network Power (India) Private Ltd. is headquartered in Thane. Maharashtra and is
supplemented by a strong national network of 31 branch offices. Emerson Network Power (India)
Private Ltd. today addresses the requirements of various markets through 60+ business partners,
network solution partners and resellers pan India.
Liebert Asco Power Technologies, and Emerson Energy Systems are divisions of Emerson and Emerson
Network Power. Through its Emerson Network Power companies. Emerson is serving network dependent
data. telecommunications and Internet-related businesses with a full spectrum of reliable power and
connectivity solutions.
More information on Emerson Network Power, its services and solutions is available at:
www.emersonnetworkpower.com
1 2
3 4
5
Modbus
1. Introduction 1
2. About Symbols 2
3. Safety 3
5. Installation 7
6. Parts Designation 8
7. System Description 9
9. Front View 12
9.1. Mimic 14
12. Specifications 19
15. Maintenance 24
You have made the right choice in buying our System, and become a customer
of Emerson Group. We presently have three modern manufacturing plants, and
after sales network operating from 50 destinations in India. We hope that you
will become our special customer & build permanent relation with us.
There are two important factors for the reliable functioning of Liebert Network
Power Switch I, its proper installation & proper operation. This manual gives
you in detail instructions on the installation operation and maintenance of the
Liebert Network Power Switch I.
Caution
We request you to read the entire manual prior to installation,
performing system operation or maintenance. Should you
require any assistance for operation or installation please call
on our nearest service center by giving information such as
Model, Sr. No., Date of Purchase and your observations.
Caution
Warning
Notice
This pictogram draws attention to important information about the product or part
of the operating instructions.
3.1. General
The interior of Liebert Network Power Switch I , when it is powered, has
hazardous AC voltage present inside. The control logic, which is supplied by
low voltage, has low power. Part of this type of equipment is powered by +/-
5 V, +/- 15 V & +30 V logic power supplies. These are referenced to
potentials other than earth zero. So high voltages with respect to earth exist
on some circuit boards in it.
3.2 Safety Warning
Ensure somebody is available to isolate the electricity supply if necessary.
Stand on an approved rubber insulating mat when working on the
equipment.
WARNING ! : Some rubber mats contain a carbon base pigment and are
not suitable!
q Remove watches, rings, earrings and other metal jeweleries and any loose
material like pens, tools or metal objects from pocket before working on the
equipment.
q Do not touch printed circuit boards. High voltages exist, there is an electric
shock hazard.
q Turn off power before working on electric or electronic circuit, except when
absolutely necessary. Consider all wire and terminals to be live until proven
otherwise by a safe test method.
q Turn off power to equipment before checking or replacing fuses. Locate and
correct the cause of a blown fuse or tripped circuit breaker before replacing
the fuse or resetting the breaker.
q Always check the electrical rating of equipment you use, and be sure you
use that equipment within its ratings.
q Turn the Liebert Network Power Switch I off and isolate the Liebert
Network Power Switch I before cleaning. Use only a soft cloth, never use
liquid or aerosol cleaners. Keep the front and rear vents free of dust
accumulation that could restrict airflow, required for cooling. This
equipment contains several circuit that are energized with high voltage.
Only test equipment designated for troubleshooting should be used. This is
particularly applicable for oscilloscopes.
• Immediate action is essential. Severe electric shock may affect heart action
and breathing.
Transport the Liebert Network Power Switch I on the pallet in the original
packaging, using a suitable lifting truck, to the storage or installation site
4.2 Unloading
After receipt of the Liebert Network Power Switch I, before unloading, compare
contents of Delivery Challan with the Invoice.
Ensure proper unloading facility exists with transporter / local subcontractor.
Ensure that the equipment is kept upright as per the arrow marked indicated
on its packing.
During unloading, ensure that the unit is not tilted beyond 45 degree angle
with the ground surface, to prevent internal damages.
4.3 Storage
4.3.1 Liebert Network Power Switch I Storage
If the Liebert Network Power Switch I system is not going to get installed
immediately, we recommend keeping it in proper storage.
4.4 Floor Loading
The route / passage up to the installation site and the actual foundation
location must be capable of supporting the weight of the Network Power
Switch.
6
Liebert Network Power Switch I
Instruction Manual/Liebert NPS I /Ver3.0/ OCT 2013 05
4.5 Access to the Area
1. Plan the route such a way that the Liebert Network Power Switch I will
pass through
all elevations, corners and doorways, smoothly.
2. Ensure adequate service maintenance space min 1000 mm is
provided from front & back side, and 600 mm from both sides of the
equipment.
4.6 Ventilation
All ventilation apertures must be kept free and clean. These systems can work
in a continuous environmental within 0 to 40°C temperature range, although,
ideally the ambient temperature should be below 25 °C.
The heat can be removed from the equipment room by a forced cooling
ventilation system or, alternatively, an air conditioning system.
The required air changes per hour will depend on the system rating, the heat
loss and the cooling air temperature.
4.7 Installation Altitude
The maximum altitude without de-rating of the Liebert Network Power Switch I
should be 1000 meter above sea level. Consult factory for the de-rating factor
above 1000 meter altitude.
2 Keep box on the plain surface such that THE ARROW ON BOX
SHOULD POINT VERTICALLY UPWARDS.
3 If the unit is packed in wooden container, remove buttons from all sides,
EXCEPT from BOTTOM SIDE. Remove these bolts to remove the
wooden base.
Caution
Improper installation of the system may cause injury to
personnel or damage the equipment. The system must be
installed & grounded in accordance with the Local as well
as National Electrical codes
Part Designation
C Capacitor
F Fuse
HS Heat Sink
KA Relay
R Resistor
S Switch, Isolator
TA Current Transformer
VD Diode
X Connector
VTT1
F1
MANUAL
VTT3 BYPASS
TA
SWITCH
VTT2
8. SINGLE LINE DIAGRAM
F2
SOURCE 2 A3
A2 OUTPUT
PHASE
NEUTRAL
A1
VTT4
SOURCE 2
NEUTRAL
EARTH
10
8
8.1 SINGLE LINE DIAGRAM
1 Pole
OUTPUT
NEUTRAL
PHASE
OUTPUT
SW2
A1
A3
A2
TA
VTT2
VTT1
F1
F2
SOURCE 1
SOURCE 1
SOURCE 2
NEUTRAL
SOURCE 2
NEUTRAL
PHASE
PHASE
EARTH
Modbus
Alram
Sources
Feeding
Healthy
Priority
1
1 Source 1 Healthy
2 Source 2 Healthy
3 Source 1 Priority
4 Source 2 Priority
5 Source 1 Feeding
6 Source 2 Feeding
B) Alarms indications
1 No Sync
2 Over Load
C) Switch Indication
SR. N0.
PLATE
16Amp
32Amp 2 POLE
63Amp XM3 XM2
63Amp 1 POLE
XM1
XM1
N L
OUTPUT SOURCE1
L N
EARTH
L
SOURCE2
N
XM2, Xm3 are the Additional Output Sockets
S1
ALARM ABNORMAL
S2
ABNORMAL
INSTA SWITCH
N L E N L N L
Output Source 2 Source 1
PFC
N L
OUTPUT SOURCE1
L N
EARTH
L
SOURCE2
N
In 4U Cabinet there are no connections at the back side
S1
ALARM ABNORMAL
S2
ABNORMAL
3. Apply input supply through MCB of suitable rating to both input sources.
Ü No Sync Ü Alarm
Ü Load on STSW
3.No Output Both the source failed. Check source condition at input side.
available Fuse blown in the priority Replace the faulty fuse. Find out the
source. cause of fuse failure / Probable
cause
Output overload.
4.No Voltage fuse blown. Replace the faulty fuse. Try to find
at Output out the cause of fuse failure.
Refer CI. No.1.2 of fault No 3
Regularly check, the arrangements made for the same are good & are in
working condition.
CHECKLIST
A. Quarterly
Particular attention was paid to reducing the volume, mass and variety of
metals and plastics used. Environmental compatibility was an important
criterion in to the selection of parts obtained from vendors.
ASIC components and SMD elements are used on the flat component groups.
The device can be stripped down into recyclable mechanical components with
screw and snap connections. Within the area of the EU, disposal should be
carried out by a certified disposal company .In other countries local
regulations must be observed.
Date of Purchase : / /
Date of Commissioning : / /
CUSTOMER COPY
WARRANTY
We guarantee our equipment for satisfactory working within the
limitations of the specifications offered, under normal conditions of
use for a period of twelve months from the date of commissioning or
eighteen months from date of despatch from the factory, whichever is
earlier. In the event of a defect, during the warranty, enough to cause
malfunction in the working as a result of faulty workmanship or
defective material of a major component, we promise to repair or
replace the part, free of charges. But we will be sole judges to
determine the real cause of the defect and if the same is found to have
developed due to abnormal use, high surges due to lightning,
accident, unapproved modifications, ignorance of operators, or a
willful act, the Risk will be entirely the Owner’s. Further, the
defective part as may be the case, shall have to be sent to the factory,
freight paid both ways and also Octroi if payable shall be to the
Owner’s account. Such defective parts, if replaced by new ones, will
be the property of Emerson. Any indirect or consequential damage or
loss is entirely excluded from the obligations of this warranty.
DATE OF DESPATCH
Date of Purchase : / /
Date of Commissioning : / /
MANUFACTURER COPY
WARRANTY
We guarantee our equipment for satisfactory working within the
limitations of the specifications offered, under normal conditions
of use for a period of twelve months from the date of
commissioning or eighteen months from date of despatch from
the factory, whichever is earlier. In the event of a defect, during the
warranty, enough to cause malfunction in the working as a result
of faulty workmanship or defective material of a major
component, we promise to repair or replace the part, free of
charges. But we will be sole judges to determine the real cause of
the defect and if the same is found to have developed due to
abnormal use, high surges due to lightning, accident, unapproved
modifications, ignorance of operators, or a willful act, the Risk
will be entirely the Owner’s. Further, the defective part as may
be the case, shall have to be sent to the factory, freight paid both
ways and also Octroi if payable shall be to the Owner’s account.
Such defective parts, if replaced by new ones, will be the property
of Emerson. Any indirect or consequential damage or loss is
entirely excluded from the obligations of this warranty.
DATE OF DESPATCH
Network Power
Emerson Network Power (India) Private Limited
Plot No. C - 20, Road No. 19
Wagle Industrial Estste
Thane - 400 604
Maharashtra, India
***WEST ZONE***
Mumbai Emerson Network Power (India) Pvt. Ltd.
Address Dheeraj Kawal, Next to Vikroli Station, L.B.S Marg, Vikroli (W)
Mumbai - 400079.
Tel 91- 22 - 40780303
Fax 91- 22 - 40110183
Ahmedabad Emerson Network Power (India) Pvt. Ltd.
Address 205, Sukhsagar Complex, Beside Fortune Landmark Hotel, Usmanpura,
Ashram Road, Ahmedabad - 380013.
Tel 079 - 27560230
Fax 079 - 27560240
Baroda Emerson Network Power (India) Pvt. Ltd.
Address 39/2, Arunodaya Society, Alkapuri,
Baroda - 390005.
Tel 0265 - 3929500
Fax 0265 - 2330383
Pune Emerson Network Power (India) Pvt. Ltd.
Address 4th floor, C wing, VEGA Center, Shankar-Sheth Road,
Swargate, Pune 411037. (India)
Tel 020 - 6626 2004
***NORTH ZONE***
Gurgoan Emerson Network Power (India) Pvt. Ltd.
Address Plot No. 2, Udyog Vihar,
Gurgoan - 122016 (Haryana)
Tel 0124 - 3315500
Fax 0124 - 3315480
Chandigarh Emerson Network Power (India) Pvt. Ltd.
Address SCO 58, 2nd Flr Sector 47C,
Chandigarh - 160047
Tel 0172 - 3931893
Fax 0172 - 3931894
Lucknow Emerson Network Power (India) Pvt. Ltd.
Address No. 5, 3rd Floor Block B1, Raja Ram Kumar Plaza,
75 Hazratganj, Lucknow - 226001
Tel 0522 - 33154000
Fax 0522 - 4103933
Jaipur Emerson Network Power (India) Pvt. Ltd.
Address 209 Shalimar Complex 1st Floor, Church Road MI Road,
Jaipur - 302001
Tel 0141 - 4024774
Fax --
***EAST ZONE***
Kolkata Emerson Network Power (India) Pvt. Ltd.
Address Advantage Tower, EN - 27, 7th Floor,
Sector-V, Salt Lake,
Kolkata - 700 091
Tel 91 - 33 - 33154000
Fax 91 - 33 - 33154001
Guwahati Emerson Network Power (India) Pvt. Ltd.
Address Institution of Enginners Building (3rd floor)
Near Lakhtakia Overbridge, Panbazar
Guwahati - 781 0071
Tel 91-361-2734485
Fax 91-361-2734486
Bhubaneshwar Emerson Network Power (India) Pvt. Ltd.
Address Plot No. 267, AN Plaza, Rasulgarh, Bhubaneshwar
Bhubaneshwar - 751 0101
Tel 0674 2586003 / 6743353
Fax 0674- 6742580058
Jamshedpur Emerson Network Power (India) Pvt. Ltd.
Address Ground Floor, Contractor's Area,
Kashi Kunj, Road No. 2, Bistupur,
Jamshedpur - 831 001.
Tel 0657-6546636
Fax –
***SOUTH 1 ZONE***
Bangalore Emerson Network Power (India) Pvt. Ltd.
Address 3rd Floor, Jindal Centre,
412, IV Block, Koramangala,
Bangalore - 560 034
Tel 080-33154000
Fax 080-33154000
Mangalore Emerson Network Power (India) Pvt. Ltd.
Address Raj Business Centre, 3rd Floor, Raj Towers,
Balamatta Road, Mangalore - 575 001
Tel -
Fax -
Cochin Emerson Network Power (India) Pvt. Ltd.
Address No.40/9338 (New No. 59/4517)
4th Floor, Chakos Towers, Padma Pullepady Road,
Cochin - 682 035
Tel 0484 - 3325405
Fax 0484 - 2381986
Thiruvananthapuram Emerson Network Power (India) Pvt. Ltd.
Address No.T.C.2/8(8), 1st Floor, 'Chandragiri'
Ulloor, Medical College P.O
Thiruvananthapuram - 695 011
Tel 0484 - 3325405
Fax 0484 - 2381986
Chennai Emerson Network Power (India) Pvt. Ltd.
Address "OMS Court"
1, Nathamuni Street,T. Nagar,
Chennai - 600 017
Tel 044 - 33154000
Fax 044 - 33154035
Chennai Emerson Network Power (India) Pvt. Ltd.
Address 343, SVP Complex, D-1st Floor, Sidhapudur,
Avarampalyam Road,
Coimbatore - 641 044
Tel 0422 - 3325400
Fax 0422 - 4389625
www.emersonnetworkpower.co.in
While every precaution has been taken to ensure accuracy and completeness in this manual, Emerson
Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this
information or for any errors or omissions.