You are on page 1of 15

NPFC Series LiFePO4 Battery Module for Telecom

Lithium Iron Phosphate Battery

NPFC Series
(LiFePO4 Battery Module for Telecom)

OPERATION MANUAL
Version V8.6

NARADA POWER SOURCE CO., LTD


Email: intl@narada.biz Website: en.naradapower.com
Contents

Notes Safety and Warning 03

One Product Introduction 04


Product Features 4
Main application 4
Appearance 5
Dimension & Layout 7
Working principle 10

Two Technical Characteristic 12


Electric Performance 12
Discharge performance 12
Charge performance 15

Three Operation 16
Parameter settings 16
Operation condition 17

Four Storage and Installation 17


Storage 17
Installation 18

Five Maintenance 21
General 21
Troubleshooting and Solutions 22

Annex1 23
Annex2 24
Annex3 25
Annex4 25

01 02
NPFC Series LiFePO4 Battery Module for Telecom

Safety and Warning Product Introduction


Chapter Notes Chapter One/01
The NPFC series LiFePO4 battery system installation, operation, maintenance should follow Product Features
important recommendations in this manual:
NPFC series battery system is 48V system for communications back-up type LiFePO4 (lithium iron
The equipment shall be installed by the professional trained staff.
phosphate) battery products, the system uses the advanced LiFePO4 battery technology with the
Battery maintenance should be carried out by the experienced professionals and aware of the benefit of long cycle life, small size, light weight, safety and environmental protection, and has a
preventive measures on the potential harm of the battery. strong environmental adaptability, it is idea for harsh outdoor environments.
Note: Be care of the risk of electric shock for large current in case of battery short circuit, pay
attention to the following points during operation The system also integrates a smart battery management and monitoring module, support for remote

■ Remove watches, rings or other metal objects


centralized monitoring and remote battery management and maintenance, to meet the requirements
■ Use tools with insulated handles of unattended. Therefore, the NPFC system can fully meet the backup power supply requirements of
■ Do not place tools or metal objects on the battery the access network equipment, mobile communications equipment, transmission equipment, micro

Do not direct access to the battery system to the mains grid power outlet. base stations and microwave communication equipment.

Do not put the battery system into fire, do not use or storage the battery near to the high
temperature source.
Main application
Do not use liquid or other objects placed into the battery system.

Do not open or cut the battery, not hit, throw or step on the battery. Network Telecommunication Facilities

OSP
Using special communication between battery module and power plant to charge battery
Terminal of FTTX
Be sure to subject to charge and discharge parameters setting in this manual.
Access network system
The output interface of the system is still voltage when grid power cut, avoid electric shock or
Indoor distribution system
short circuit when operation.
Telecom BTS
Please check if the box is damaged. If damaged, please immediately notify the supplier
Integrated outdoor power cabinet
If you find leaking liquid or white powder residue on product, prohibit operation.
UPS
Please take care of the following marks in using
Internet data center (IDC)

Solar energy

Electricity Protecting Watch With adults Common Bonding Network (CBN) and or Isolated Bonding Network (IBN)
Warning
danger your eyes Short-circuits custody

Do not put The product has


Read the Fire
Circle used batteries into passed the UL
manual forbidden
dustbin authentication

03 04
NPFC Series LiFePO4 Battery Module for Telecom

Appearance

Fig. 1-4 Appearance & Mechanical Drawing of 48NPFC80

Fig. 1-1 Appearance & Mechanical Drawing of 48NPFC10

Fig. 1-5 Appearance & Mechanical Drawing of 48NPFC100-19"

Fig. 1-2 Appearance & Mechanical Drawing of 48NPFC20

Fig. 1-6 Appearance & Mechanical Drawing of 48NPFC100-23"

Fig. 1-3 Appearance & Mechanical Drawing of 48NPFC50

05 06
NPFC Series LiFePO4 Battery Module for Telecom

Dimension & Layout

Fig. 1-9 Layout of Front Panel for NPFC Series Batteries

Fig. 1-7 Structural Drawing of NPFC Series Batteries (48NPFC10 as sample)

Table 3-3 Instruction for Layout of Front Panel

No. Marks Functions Detailed Information

There are four green LED lights in front panel indicating


Indicators for SOC. SOC is short for state of charge. Each SOC LED light
Fig. 1-8 Battery Output Terminal 1 SOC
capacity represents 25% of rated capacity. Detailed information is
shown in Annexed Table 1.1.

Table 1-1 Mechanical Performance of NPFC Series


Indicator for There is one red LED light in front panel indicating alarms.
2 ALM
alarms Detailed information is shown in Annexed Table 1.2.
Rated Rated Dimensions(mm) Battery
Battery Capacity Weight
Voltage Output
Model① (Ah)③ (Kg)
(V)② Width Depth Height Terminal
There is one green LED light in front panel indicating
Indicator for
48NPFC10 48 10 442 245 44 1U 7.3 10mm/M4 3 RUN running status. Detailed information is shown in Annexed
running status
48NPFC20 48 20 442 245 88 2U 13.4 10mm/M4 Table 1.3.

48NPFC50 48 50 442 400 132.5 3U 29.5 13mm/M6


ADD is applicable to modules connected in parallel. ADD
48NPFC80 48 80 442 400 132.5 3U 39.0 13mm/M6 Address of consists of four binary bits, and maximum quantity of
4 ADD Dip communication
48NPFC100-19’’ 48 100 442 400 220 5U 46.5 13mm/M6 batteries connected in parallel is 16pcs (2^4). Detailed
switch
48NPFC100-23’’ 48 100 520 400 132.5 3U 46.0 13mm/M6 information is shown in Annex 2.

It is adopting RS-232 series port to upload data. Contents


of data transmit include BMS parameters, battery running
Up-link status, alarms, etc. Generally, speed rate of RS-232 is
5 RS232 communication 1200bps. RS232 up-link communication can be available
port for the battery module with a binary communication
address of 0000 (Master PACK). Protocol for RS232
communication is shown in Annexed Table 3.1

07 08
NPFC Series LiFePO4 Battery Module for Telecom

It is adopting RS485 series port communication pattern Working Principle


Cascading to upload data. Communication of modules connected

communication in parallel (Slave PACKs) is available through RS 485. The NPFC battery system mainly includes Fe lithium battery pack, battery protection, cell balancing
6 RS485
port Data of slave PACKs will be transmitted to Master PACK. unit, monitoring module and charge-discharge management module for optional. Its schematic
Protocol for RS232 communication is shown in Annexed
diagram shown in Figure 1.1
Table 3.2

Press RESET button when abnormity occurs to assure


7 RESET Reset button
stability of battery performance.

Failure Alarm: indicate BMS or battery fail including but


not limited to charge and discharge MOS fail, cell voltage
Dry Dry contact under 0.5V, NTC disconnect.
8
contact indicators Fault Alarm: Output short circuit, charge and discharge
over current, charge and discharge over temperature/low
temperature.

Power When turn-off, battery get into sleep mode, and cut-off
9 ON/OFF switch
switch output, the alarm output also will be stopped. Fig. 1-10 Schematic Diagram

Using terminals with four cores. Polarities are +, -, +, - LFP cells Chemical power, energy storage and power supply components.
Battery Terminals for
10 from left to right. The two ‘+’ and ‘-’ are equal relatively.
Output battery output
Detailed information is shown in Fig. 2.4. Protect LFP cells against overcharge, over discharge, over current, over
Battery protection
temperature, short circuit
LCD Display battery Cell balancing Equalization LFP cells for unbalanced cells
11 (optional) Detailed information is shown in Annexed Table 3.3
information
Charge-discharge Discharge circuit management, and charging current limit
management (optional according to customer requirements)
Connect earth by flexible cable above GREEN Sheathed,
UL94-V0, gauge of the grounding wire should be equal to Support centralized monitoring system (optional according to customer
Monitoring
12 GND Ground screw or greater than the gauge of the battery return wire, .no requirements)
less than 6AWG, connection through 2-hole 0.75in center
spacing, on right side of cabinet back.
NPFC battery working principle:

Vented
DC power input charge and discharge management unit after filter, DC divided two circuits, one
13 Cooling FAN Cooling system to disperse BMS heat circuit directly supply the load, another circuit to charge Fe lithium pack. When grid power on, the
holes
system supplies the loads and charging inside Fe lithium batteries; When grid power failure, Fe
lithium inside system supply DC power to the load, to ensure uninterrupted power supply as power
system.

Battery Management System (BMS)


Smart BMS technology is adopted for battery modules of NPFC series to assure smart automatic
management for batteries. Features of BMS are shown as below:

09 10
NPFC Series LiFePO4 Battery Module for Telecom

There is a centralized monitoring unit in BMS. Functions such as remote measurement, remote
communication, remote controlling are available. Battery modules can be controlled remotely
Technical Characteristic
by staffs in control center. NPFC series are in line with the requirements of the development of
modern communications technology.
Chapter Two/02
It is combined by technologies of power source and computer. Parameters and status of rectifiers Electric Performance
and AC/DC distributions can be detected and controlled.
Rated Rated Voltage Charge Charge Current (A) Max.
Battery Capacity③ Rage
Voltage② Voltage Discharge
Excellent electromagnetic compatibility. BMS used for battery modules of NPFC series can Model① (Ah) (V)
(V) (V) Recomm Max. Current (A)
comply with the outdoor power plants during operation, no interfere with each other.
48NPFC10 48 10 40.5 to 54.5 54.0 2 10 10

BMS can provide protections against overcharge, over-discharge, over-temperature, overcurrent, 48NPFC20 48 20 40.5 to 54.5 54.0 4 20 20

short circuit, etc., to assure reliable safety and operation life. 48NPFC50 48 50 40.5 to 54.5 54.0 10 50 50

48NPFC80 48 80 40.5 to 54.5 54.0 15 80 80


With patented cell balancing technology, BMS provide high efficiency for cell balancing and
48NPFC100-19’’ 48 100 40.5 to 54.5 54.0 20 100 100
prolong system operate life.
48NPFC100-23’’ 48 100 40.5 to 54.5 54.0 20 100 100

Configuration flexibility, support parallel connection expansion


Note:
①Battery Model Battery models listed in the datasheet are standard products. Narada can also supply
customized design in cell, BMS and dimensions for various application scenarios.
②Rated Voltage 48V = 3.20Vpc * 15pcs (Rated voltage of each LFP cell is 3.20Vpc)
③Rated Capacity Five-hour rate capacity (0.2C to 40.5V at 25°C)

Discharge performance

Fig. 2-1 Constant Current Discharge Curve of NPFC Series

11 12
NPFC Series LiFePO4 Battery Module for Telecom

Constant current and constant power data sheet


Table 3.1 – Constant Current Discharge Datasheet of NPFC Series Table 3.2 – Constant Power Discharge Datasheet of NPFC Series
Battery Model 48NPFC10 Battery Model 48NPFC10
Curren 0.1C 0.15C 0.2C 0.25C 0.3C 0.4C 0.5C 0.6C 0.8C 1C Curren 45W 90W 135W 180W 225W 270W 315W 360W 405W
End Volt. h min End Volt. h min

46.5V 9.61 6.36 4.74 3.80 3.14 2.21 1.68 1.31 1.02 41.3 46.5V 10.89 5.34 3.50 2.55 1.96 1.57 1.29 1.07 /
45.0V 9.79 6.49 4.85 3.89 3.23 2.39 1.88 1.53 1.17 52.6 45.0V 11.09 5.45 3.59 2.65 2.07 1.70 1.44 1.24 30.0
43.5V 9.91 6.59 4.93 3.98 3.27 2.45 1.94 1.60 1.21 55.7 43.5V 11.22 5.52 3.63 2.68 2.12 1.73 1.47 1.27 33.1
42.0V 10.00 6.65 4.97 3.97 3.30 2.48 1.97 1.63 1.23 57.0 42.0V 11.30 5.56 3.66 2.71 2.13 1.76 1.49 1.30 43.2
40.5V 10.05 6.69 5.00 4.00 3.33 2.50 1.99 1.65 1.24 57.9 40.5V 11.35 5.59 3.68 2.73 2.15 1.78 1.50 1.30 46.5
Battery Model 48NPFC20 Battery Model 48NPFC20
Curren 0.1C 0.15C 0.2C 0.25C 0.3C 0.4C 0.5C 0.6C 0.8C 1C Curren 90W 180W 270W 360W 450W 540W 630W 720W 810W
End Volt. h min End Volt. h min

46.5V 9.61 6.36 4.74 3.80 3.14 2.21 1.68 1.31 1.02 41.3 46.5V 10.89 5.34 3.50 2.55 1.96 1.57 1.29 1.07 /
45.0V 9.79 6.49 4.85 3.89 3.23 2.39 1.88 1.53 1.17 52.6 45.0V 11.09 5.45 3.59 2.65 2.07 1.70 1.44 1.24 30.0
43.5V 9.91 6.59 4.93 3.98 3.27 2.45 1.94 1.60 1.21 55.7 43.5V 11.22 5.52 3.63 2.68 2.12 1.73 1.47 1.27 33.1
42.0V 10.00 6.65 4.97 3.97 3.30 2.48 1.97 1.63 1.23 57.0 42.0V 11.30 5.56 3.66 2.71 2.13 1.76 1.49 1.30 43.2
40.5V 10.05 6.69 5.00 4.00 3.33 2.50 1.99 1.65 1.24 57.9 40.5V 11.35 5.59 3.68 2.73 2.15 1.78 1.50 1.30 46.5
Battery Model 48NPFC50 Battery Model 48NPFC50
Curren 0.1C 0.15C 0.2C 0.25C 0.3C 0.4C 0.5C 0.6C 0.8C Curren 225W 450W 675W 900W 1125W 1350W 1575W
End Volt. h End Volt. h

46.5V 9.56 6.35 4.75 3.78 3.12 2.29 1.79 1.45 1.02 46.5V 10.35 5.11 3.36 2.46 1.92 1.53 1.27
45.0V 9.76 6.49 4.85 3.87 3.21 2.39 1.89 1.57 1.15 45.0V 10.55 5.22 3.45 2.55 2.02 1.66 1.40
43.5V 9.89 6.58 4.92 3.92 3.25 2.42 1.93 1.60 1.19 43.5V 10.66 5.28 3.49 2.58 2.06 1.69 1.43
42.0V 9.98 6.64 4.96 3.96 3.29 2.45 1.94 1.61 1.21 42.0V 10.75 5.32 3.52 2.61 2.07 1.70 1.45
40.5V 10.04 6.68 5.00 3.99 3.31 2.46 1.96 1.63 1.22 40.5V 10.79 5.35 3.54 2.62 2.09 1.72 1.46
Battery Model 48NPFC80 Battery Model 48NPFC80
Curren 0.1C 0.15C 0.2C 0.25C 0.3C 0.4C 0.5C 0.6C 0.8C Curren 358W 715W 1080W 1430W 1800W 2145W 2500W
End Volt. h End Volt. h

46.5V 9.59 6.34 4.71 3.70 3.02 2.21 1.70 1.34 1.02 46.5V 10.46 5.06 3.21 2.34 1.76 1.40 1.13
45.0V 9.78 6.49 4.85 3.87 3.20 2.39 1.89 1.55 1.13 45.0V 10.65 5.21 3.39 2.52 1.97 1.62 1.35
43.5V 9.91 6.57 4.92 3.92 3.26 2.44 1.95 1.61 1.19 43.5V 10.77 5.28 3.45 2.57 2.03 1.68 1.43
42.0V 9.99 6.64 4.97 3.96 3.29 2.47 1.97 1.64 1.22 42.0V 10.85 5.32 3.48 2.60 2.05 1.71 1.45
40.5V 10.05 6.68 5.00 3.99 3.32 2.49 1.98 1.66 1.24 40.5V 10.90 5.35 3.50 2.61 2.07 1.71 1.46
Battery Model 48NPFC100 Battery Model 48NPFC100
Curren 0.1C 0.15C 0.2C 0.25C 0.3C 0.4C 0.5C 0.6C 0.8C Curren 450W 900W 1350W 1800W 2250W 2700W 3150W
End Volt. h End Volt. h

46.5V 9.59 6.34 4.71 3.70 3.02 2.21 1.70 1.34 1.02 46.5V 10.35 5.11 3.36 2.46 1.92 1.53 1.27
45.0V 9.78 6.49 4.85 3.87 3.20 2.39 1.89 1.55 1.13 45.0V 10.55 5.22 3.45 2.55 2.02 1.66 1.40
43.5V 9.91 6.57 4.92 3.92 3.26 2.44 1.95 1.61 1.19 43.5V 10.66 5.28 3.49 2.58 2.06 1.69 1.43
42.0V 9.99 6.64 4.97 3.96 3.29 2.47 1.97 1.64 1.22 42.0V 10.75 5.32 3.52 2.61 2.07 1.70 1.45
40.5V 10.05 6.68 5.00 3.99 3.32 2.49 1.98 1.66 1.24 40.5V 10.79 5.35 3.54 2.62 2.09 1.72 1.46

13 14
NPFC Series LiFePO4 Battery Module for Telecom

Charge Performance Operation


Chapter Three/03
Parameter settings
Lead-acid batteries can be replaced by lithium battery of NPFC series if power is matched. Table 3-2
is new parameter settings of power plant for lithium battery.

Table 3-1 Parameter Settings of Power Plant for NPFC Series Batteries

No. Parameters Units Defaults

1 Float charge voltage V 54.0

2 Equalization charge voltage V NA or 54.1

3 Standard charge current A 0.2C

4 Charge current limitation A 0.5C ~ 1.0C


Fig. 2-2 Charge Characteristic with Various Current Limitation of NPFC Series 5 Equalization charge interval day NA

6 Equalization charge duration H NA

7 Condition to equalization charge A NA

8 Condition to float charge A 0.05C

9 LVLD (Low voltage load disconnection) V > 43.2

10 LVBD (Low voltage battery disconnection) V > 40.5

11 Restore voltage for LVBD V /

12 Temperature compensation for float charge -mV/°C NA

13 Temperature compensation for equalization charge -mV/°C NA

Note:
1.Equalization charge is requested to switch off for NPFC series batteries.
2.Rectifer parameter shall be set according to specific site requirement based on battery units used.
3.System instantaneous discharge and charge current shall be less than 250A for each module.

15 16
NPFC Series LiFePO4 Battery Module for Telecom

Operation Condition Installation


Table 3-2 Requirements for Operation Environment
Unboxing & Inspection
Discharge -20 ~ +60 ■ Please study this manual before installation.
Temperature Charge 0 ~ +60
Range (°C) ■ Please inspect the package before unboxing, if any destroy with appearance, contact with the
Storage 0 ~ +40 supplier as soon as possible.
Discharge +15 ~ + 35 ■ This device shall be installed and operated by professionals.
Recommended
Charge +15 ~ + 35
Temperature(°C)
Storage +15 ~ + 30 Preparation for Installation
Humidity 5% ~ 95% ■ Batteries shall not be placed in direct sunshine or close to heat source.
■ Batteries shall be installed in place with good ventilation to assure enough heat dissipation.
■ Batteries shall be placed in are with clean ambient and low humidity.
■ Heavy weight shall not be placed on any cable.
■ Following are the tools possibly but not limited be use for installation:

Items Tool Items Remarks for Use

1 Insulation gloves Insulation protection for body

Storage and Installation 2

3
Insulation taps

Screw drivers
Insulation protection for tools

Fix the cables of the batteries & power plant

Chapter Four/04 4 Multi meter Measure the module voltage in commission

5 Current meter Measure the module current in commission

6 USB to RS485 cable For communication between the batteries and laptop
Storage
7 Laptop Operate the software
■ Storage temperature range: 0°C to 45°C.
■ Storage battery should be at 60%-80%SOC.
Installation of Battery Modules
■ Recharge charge before using to recover capacity loss of self-discharge during storage and
1.Installation and fixation
transport.
Battery modules of NPFC series are applicable to installation in 19-inch cabinets and wall-hanging.
■ Recharge battery during long-term storage for self-discharge. Recharge program as follow table:
■ 19 inch cabinet installation
Storage temperature Recharge interval Single Module Recharge Procedure Insert battery module into 19-inch cabinet, and fix two handles of battery module with cabinet rack
using 4pcs M6 screws.
10°C-30°C Every 6 months 1) Charge with 0.2C to 100%SOC
■ Wall-hanging installation
2) Discharge with 0.2C to 0%SOC
0°C-10°C Wall-hanging installation also can be adopted, fix two handles of battery module with triangle rack
Every 3 months 3) Charge with 0.2C per module for 4 hours
30°C-45°C on the wall using 4pcs M6 screws.

■ Storage battery over 45°C or under 0°C will reduce battery life,
■ Storage battery in dry and low temperature, well ventilated place
■ Battery performance degradation after long-term storage, please shorten shelf time as possible
as you can.

17 18
NPFC Series LiFePO4 Battery Module for Telecom

Preferred Alternate

Fig. 4-1 Layout of paralleling connection for NPFC Series Batteries

4.Power on for battery module


■ When installation is accomplished, battery module is in dormant state. Once power on for the
Forbidden (Except for 48NPFC10, 48NPFC20, 48NPFC100-19) power plant and battery module, battery will go into normal running status, and discharge/charge
can be available.
■ Parameter settings for lithium battery modules in power plant are shown in Table 4.2.
2.Ground connection
GND screw on the 2-holes side panel of battery is connected with ground through a flexible cable 5.RS232/RS485 connection
equal to or greater than the gauge of the battery return wire, no less than 6AWG. In instances where ■ If there is only one battery module in operation, communication between battery module and
the battery module is deployed in a central office environment, please assure that a method has been computer can available through both RS232 and RS485.
implemented at the battery modules demarcation point, or within the adjacent power distribution ■ If there are more than one battery modules in operation, parallel communication can be available
network, that assures the supply return is referenced to ground. using RS485.
■ Communication protocols for RS232 and RS485 are shown in Annex 3.
3.Battery output connection
■ Connect ‘+’ of battery output with positive female copper bar of power plant, and ‘-’ with 6.Discharge with dummy load
negative female copper bar or breaker (optional). ■ Dummy load cannot be larger maximum discharge current of each battery model in
■ If multi battery modules will be connected in parallel, connect ‘+’ of battery output of each battery Table 2.1, and LVBD is larger than 40.5V.
module with positive female copper bar of power plant, and ‘-’ with negative female copper bar of ■ Voltage drop on cable between battery module and power plant shall be less than 0.5V.
power plant or breaker (optional) separately, see Fig4.3. Method of calculation for cross sectional area of cable is shown as below.
■ Length of cable between battery module and power plant shall be less than 2.0m. To make sure
similar voltage drop of cable for each battery, length of all positive and negative cables should be A=ΣI×L/(K×△U)
the same. In the above formula, A is across sectional area of wire (mm2), ΣI is the total current (A), L is length
■ Color for cable between ‘+’ and positive bar is suggested as BLACK, and cable between of cable, △U is the permit voltage drop on cable (V), and K is electrical conductivity of wire. For
‘-’ and negative or breaker as BLUE. example, for copper, K = 57.

19 20
NPFC Series LiFePO4 Battery Module for Telecom

Maintenance Troubleshooting and Solutions


Chapter Five/05 Table 5-1 Troubleshooting and Solutions

Troubles Troubleshooting Solutions

General Protection against under-voltage Charge battery

Proper maintenance will prolong the life of a battery and will aid in assuring that it is capable of Protection against over-temperature or under- Regulate cell temperature in

satisfying its design requirements. A good battery maintenance program will serve as a valuable aid temperature (cell temperature is lower than -25°C the range of -20°C to 60°C for

in determining the need for battery replacement. The users must consider their particular application or higher than 75°C) discharge

and reliability needs if maintenance procedures, other than those recommended in this document, Battery cannot Relieve short circuit and charge
Battery output is short circuit
are used. Battery maintenance should be performed by personnel knowledgeable of batteries and discharge battery
the safety precautions involved.
Remove some unimportant load
Protection against over current
■ The battery shall be recharged every three months if in long time storage and charge battery

■ Please clean the dust by the dust collector when dust is accumulated on vent Shutdown system and call
■ Please use clean and dry cloth/fabric to clean up the cabinet, if need further cleaning, please use System failure
maintenance service
neutral cleanser. Alcohol or ammonia synthesis is forbidden.
■ Carrying shall be handled gently, prevent from severe compact Battery is fully charged. Normal charge
Do not need to solve
■ Prevent battery from splashing liquid management
■ Suggest inspect the tighten of output screw every two years Protection against over voltage Do not need to solve

Battery cannot Protection against over-temperature or under- Regulate cell temperature in the

charge temperature (cell temperature is lower than -10°C range of 0°C to 55°C for charge
or higher than 65°C)

Shutdown system and call


System failure
maintenance service

All LED indicators Shutdown system


System failure
on Call for maintenance service

Fault of communication cable Inspect communication cable

Halt of SCM Press RESET button


Communication
failure Shutdown system
System failure
Call for maintenance service

Different flash status of LED indicators represents corresponding running status or alarms. Detailed
information is shown Annex 1.

21 22
NPFC Series LiFePO4 Battery Module for Telecom

Annex 1-Instructions for LED Flash Annex 2-Instructions for Dialing of ADD
ADD is applicable to modules connected in parallel. ADD consists of four binary bits, and maximum
Annex Table 1.1 – SOC LED Indicators Description
quantity of batteries connected in parallel is 16pcs (2^4).

SOC
Annexed Table 2.1 – Instruction for Addresses of Communication
☼ ☼ ☼ ☼ 75% ~ 100%

☼ ☼ ☼ ○ 50% ~ 75% Instructions for ADD Dialing Module Binary

1 2 3 4 No. Code
☼ ☼ ○ ○ 25% ~ 50%

☼ ○ ○ ○ 0% ~ 25% OFF OFF OFF OFF PACK 1 0000


ON OFF OFF OFF PACK 2 0001
Note: ☼ mean light on, ○ mean light off
OFF ON OFF OFF PACK 3 0010
ON ON OFF OFF PACK 4 0011
Annex Table 1.2 – RUN Indicators Description
OFF ON OFF OFF PACK 5 0100
ON OFF ON OFF PACK 6 0101
Flash Status Running Status of Battery
OFF ON ON OFF PACK 7 0110
Flash 1 Activation state, but neither charge nor discharge
ON ON ON OFF PACK 8 0111
Flash 2 Charging state
OFF OFF OFF ON PACK 9 1000
Continue light Discharging state
ON OFF OFF ON PACK 10 1001
Extinguish Dormant state
OFF ON OFF ON PACK 11 1010
ON ON OFF ON PACK 12 1011
OFF OFF ON ON PACK 13 1100
Annex Table 1.3 – ALM Indicators Description
ON OFF ON ON PACK 14 1101

Flash Status Alarm Information of Battery OFF ON ON ON PACK 15 1110

Extinguish Minor Alarm(Various Alarm Status) ON ON ON ON PACK 16 1111

Flash 2 Fail(Various fail)

Flash 3 Major Alarm(Various protection status)


Annexed Table 2-2 Instruction of ADD for Parallel Communication
Extinguish Normal, no alarm
Default PACK 1 PACK 2 PACK 3 PACK 4 PACK 5 PACK 6 PACK 7
0000 0001 0010 0011 0100 0101 0110 0111

Annex Table 1.4 – Flash Instruction of LED Indicators

ON OFF PACK 8 PACK 9 PACK 10 PACK 11 PACK 12 PACK 13 PACK 14 PACK 15


1000 1001 1010 1011 1100 1101 1110 1111
Flash 1 0.25s 3.75s

Flash 2 0.5s 0.5s

Flash 3 0.5s 1.5s


Note: Counting of ADD shall begin from 0000, without interruption, or parallel communication cannot be available

23 24
NPFC Series LiFePO4 Battery Module for Telecom

Annex 3 – Communication Protocol for RS232 and RS485 The “Battery Parameters” subdirectory
■ Voltage: xxxx V
There is one RS232 port in front panel for up-link communication between batter module and ■ Current: xxxx A (charge:+, discharge:-)
upper computer, and one RS485 port in front panel for cascade communication for battery modules
connected in parallel. The “Battery Temperature” Subdirectory The ‘Battery Status’ Subdirectory
■ Temperature01:xx°C ■ Status: IDLE/CHARGE/DISCHARGE
■ Temperature02:xx°C ■ “Alarm status” Subdirectory
Annex Table 3.1 – RJ11 Pins Assignment (RS232) ■ Temperature03:xx°C ■ Overvoltage alarm YES/NO
RJ11 Pins Definition Sketch ■ Temperature04:xx°C ■ Under voltage alarm YES/NO
■ PCB Temperature: xx°C ■ Over temperature YES/NO
1 GND ■ Environment Temperature: xx°C ■ Under voltage alarm YES/NO
■ The “Cell Voltages” Subdirectory ■ Under capacity alarm YES/NO
Pack receipt, ■ Cell01: xxxx mV ■ Difference voltage YES/NO
2
computer delivery ■ Cell02: xxxx mV ■ Overcurrent YES/NO
■ Cell03: xxxx mV ■ Charger Reverse alarm YES/NO
Pack delivery, ■ Cell04: xxxx mV ■ “Protection status” Subdirectory
3
computer receipt ■ Cell05: xxxx mV ■ Overvoltage protect YES/NO
2 RXD Receive data - From battery to computer
3 TXD Deliver data - From computer to battery ■ Cell06: xxxx mV ■ Under voltage protect YES/NO
4 No connection ■ Cell07: xxxx mV ■ Over temperature protect YES/NO
5 GND – Signal ground
■ Cell08: xxxx mV ■ Under temperature protect YES/NO
■ Cell09: xxxx mV ■ Over current protect YES/NO

Annex Table 3.2 – RJ45 Pins Assignment (RS485) ■ Cell10: xxxx mV ■ Short current protect YES/NO
■ Cell11: xxxx mV ■ “Fail alarm” Subdirectory
RJ45 Pins Definition Sketch ■ Cell12: xxxx mV ■ Sampling line: OK/ERROR
■ Cell13: xxxx mV ■ Charge MOSFET: OK/ERROR
1 GND ■ Cell14: xxxx mV ■ Discharge MOSFET: OK/ERROR
■ Cell15: xxxx mV ■ Sampling chip: OK/ERROR
■ Cell16: xxxx mV ■ Short current times: xxxx
2 RS485_A
■ SOC: xxxx% ■ Temperature protect times: xxxx
■ Nominal Capacity: xxxx Ah ■ Over protect times: xxxx
3 RS485_B
■ Over current times: xxxx
■ Under voltage times: xxxx
4,5,6,7,8 No connection

The “Battery parameter settings” Subdirectory Non-manufacturers cannot enter


10 NPFC series LiFePO4 Battery System for Telecommunication Operation manual V1.0
Annex 4 – LCD Menu Instruction The “Version Information” Subdirectory

Press “MENU” to enter the following interface ■ “BMS version” Subdirectory


Welcome ■ BMS software version
Battery manage system ■ BMS hardware version
■ The “LCD version” Subdirectory
Press “MENU” next
■ LCD software version:
Press “MENU” to enter the following interface
■ LCD hardware version:
Battery parameters query
Battery status
Battery parameter settings LCD Instructions BMS under sleep mode please press“MENU”wake the BMS and LCD With in one minute
Version Information without operating LCD into turn off: Please press “MENU” wake the BMS and LCD

25 26
After-sale Services
Narada Power Source Co., Ltd.
Building A, No.822 Wen'er West Road, Hangzhou, Zhejiang, China
Tel: +86-571-56975980 Fax: +86-571-56975955
Website: en.naradapower.com E -mail: intl@narada.biz

Narada Asia Pacific Pte. Ltd.


Block 9 Khaki Bukit Road 1 #02-10 Eunos Technolink, Singapore 415938
Tel: +65-6848 1191 Fax: +65-6749 3498
Website: www.narada-ap.com Email: sales@narada-ap.com

Narada Europe (UK) Limited


Spectrum House, Dunstable Road, Redbourn, St. Albans, Herts Al3 7PR
Tel: +44 (0)845 612 2031 Fax: +44 (0)845 612 2031
E-mail: sales@naradaeurope.com

19

You might also like