You are on page 1of 2

FIRE SERVICE FEATURES

507.3 Fire flow. Fire-flow requirements for buildings or por- not be deterred or hindered from gaining immediate access
tions of buildings and facilities shall be determined by an to fire protection equipment or fire hydrants.
approved method. 507.5.5 Clear space around hydrants. A 3-foot (91 4
507.4 Water supply test. The fire code official shall be noti- mm) clear space shall be maintained around the circumfer-
fied prior to the water supply test. Water supply tests shall be ence of fire hydrants, except as otherwise required or
witnessed by the fire code official or approved documenta- approved.
tion of the test shall be provided to the fire code official prior 507.5.6 Physical protection. Where fire hydrants are sub-
to final approval of the water supply system. ject to impact by a motor vehicle, guard posts or other
507.5 Fire hydrant systems. Fire hydrant systems shall com- approved means shall comply with Section 31 2.
ply with Sections 507.5.1 through 507.5.6.
507.5.1 Where required. Where a portion of the facility SECTION 508
or building hereafter constructed or moved into or within
the jurisdiction is more than 400 feet (1 22 m) from a
FIRE COMMAND CENTER
hydrant on a fire apparatus access road, as measured by an 508.1 General. Where required by other sections of this code
approved route around the exterior of the facility or build- and in all buildings classified as high-rise buildings by the
ing, on-site fire hydrants and mains shall be provided International Building Code, a fire command center for fire
where required by the fire code official. department operations shall be provided and shall comply
with Sections 508.1 .1 through 508.1 .6.
Exceptions:
1 . For Group R-3 and Group U occupancies, the
508.1.1 Location and access. The location and accessibil-
ity of the fire command center shall be approved by the
distance requirement shall be 600 feet (1 83 m).
fire code official.
2. For buildings equipped throughout with an
approved automatic sprinkler system installed in
508.1.2 Separation. The fire command center shall be
separated from the remainder of the building by not less
accordance with Section 903.3.1.1 or 903.3.1.2,
than a 1 -hour fire barrier constructed in accordance with
the distance requirement shall be 600 feet (1 83 m).
Section 707 of the International Building Code or horizon-
507.5.1.1 Hydrant for standpipe systems. Buildings tal assembly constructed in accordance with Section 71 1
equipped with a standpipe system installed in accor- of the International Building Code, or both.
dance with Section 905 shall have a fire hydrant within
1 00 feet (30 480 mm) of the fire department connec-
508.1.3 Size. The fire command center shall be not less
than 0.01 5 percent of the total building area of the facility
tions.
served or 200 square feet (1 9 m2) in area, whichever is
Exception: The distance shall be permitted to greater, with a minimum dimension of 0.7 times the
exceed 1 00 feet (30 480 mm) where approved by the square root of the room area or 1 0 feet (3048 mm), which-
fire code official. ever is greater.
507.5.2 Inspection, testing and maintenance. Fire 508.1.4 Layout approval. A layout of the fire command
hydrant systems shall be subject to periodic tests as center and all features required by this section to be con-
required by the fire code official. Fire hydrant systems tained therein shall be submitted for approval prior to
shall be maintained in an operative condition at all times installation.
and shall be repaired where defective. Additions, repairs,
alterations and servicing shall comply with approved stan-
508.1.5 Storage. Storage unrelated to operation of the fire
command center shall be prohibited.
dards. Records of tests and required maintenance shall be
maintained. 508.1.6 Required features. The fire command center
shall comply with NFPA 72 and shall contain the follow-
507.5.3 Private fire service mains and water tanks. Pri- ing features:
vate fire service mains and water tanks shall be periodi-
cally inspected, tested and maintained in accordance with 1. The emergency voice/alarm communication system
NFPA 25 at the following intervals: control unit.
1 . Private fire hydrants of all types: Inspection annu- 2. The fire department communications system.
ally and after each operation; flow test and mainte- 3. Fire detection and alarm system annunciator.
nance annually.
4. Annunciator unit visually indicating the location of
2. Fire service main piping: Inspection of exposed, the elevators and whether they are operational.
annually; flow test every 5 years.
5. Status indicators and controls for air distribution
3. Fire service main piping strainers: Inspection and systems.
maintenance after each use.
6. The fire fighter’ s control panel required by Section
Records of inspections, testing and maintenance shall 909.1 6 for smoke control systems installed in the
be maintained. building.
507.5.4 Obstruction. Unobstructed access to fire hydrants 7. Controls for unlocking interior exit stairway doors
shall be maintained at all times. The fire department shall simultaneously.

76 201 8 INTERNATIONAL FIRE CODE ®


FIRE SERVICE FEATURES

8. Sprinkler valve and water-flow detector display tanks, location of emergency generator and
panels. location of natural gas service;
9. Emergency and standby power status indicators. 1 3.6. Fire protection system information that
10. A telephone for fire department use with controlled includes: location of standpipes, location of
access to the public telephone system. fire pump room, location of fire department
connections, floors protected by automatic
11 . Fire pump status indicators. sprinklers and location of different types of
12. Schematic building plans indicating the typical floor automatic sprinkler systems installed
plan and detailing the building core, means of including but not limited to dry, wet and
egress , fire protection systems, fire-fighter air- pre-action;
replenishment systems, fire-fighting equipment and 1 3.7. Hazardous material information that
fire department access, and the location of fire walls , includes: location and quantity of hazard-
fire barriers , fire partitions, smoke barriers and ous material.
smoke partitions.
1 4. Work table.
13. An approved Building Information Card that
1 5. Generator supervision devices, manual start and
includes, but is not limited to, all of the following
transfer features.
information:
1 6. Public address system, where specifically required
1 3.1 . General building information that includes:
by other sections of this code.
property name, address, the number of
floors in the building above and below 1 7. Elevator fire recall switch in accordance with
grade, use and occupancy classification ASME A1 7.1/CSA B44.
(for mixed uses, identify the different types 1 8. Elevator emergency or standby power selector
of occupancies on each floor) and the esti- switch(es), where emergency or standby power is
mated building population during the day, provided.
night and weekend;
1 3.2. Building emergency contact information
that includes: a list of the building’ s emer- SECTION 509
gency contacts including but not limited to FIRE PROTECTION AND UTILITY
building manager, building engineer and EQUIPMENT IDENTIFICATION AND ACCESS
their respective work phone number, cell 509.1 Identification. Fire protection equipment shall be
phone number and e-mail address; identified in an approved manner. Rooms containing controls
1 3.3. Building construction information that for air-conditioning systems, sprinkler risers and valves, or
includes: the type of building construction other fire detection, suppression or control elements shall be
including but not limited to floors, walls, identified for the use of the fire department. Approved signs
columns and roof assembly; required to identify fire protection equipment and equipment
location shall be constructed of durable materials, perma-
1 3.4. Exit access stairway and exit stairway nently installed and readily visible.
information that includes: number of exit
access stairways and exit stairways in 509.1.1 Utility identification. Where required by the fire
building; each exit access stairway and exit code official, gas shutoff valves, electric meters, service
stairway designation and floors served; switches and other utility equipment shall be clearly and
location where each exit access stairway legibly marked to identify the unit or space that it serves.
and exit stairway discharges, interior exit Identification shall be made in an approved manner, read-
stairways that are pressurized; exit stair- ily visible and shall be maintained.
ways provided with emergency lighting; 509.2 Equipment access. Approved access shall be provided
each exit stairway that allows reentry; exit and maintained for all fire protection equipment to permit
stairways providing roof access; elevator immediate safe operation and maintenance of such equip-
information that includes: number of eleva- ment. Storage, trash and other materials or objects shall not
tor banks, elevator bank designation, eleva- be placed or kept in such a manner that would prevent such
tor car numbers and respective floors that equipment from being readily accessible.
they serve; location of elevator machine
rooms, control rooms and control spaces;
location of sky lobby; and location of SECTION 51 0
freight elevator banks; EMERGENCY RESPONDER RADIO COVERAGE
1 3.5. Building services and system information 510.1 Emergency responder radio coverage in new build-
that includes: location of mechanical ings. New buildings shall have approved radio coverage for
rooms, location of building management emergency responders within the building based on the exist-
system, location and capacity of all fuel oil ing coverage levels of the public safety communication sys-

® 77

You might also like