Professional Documents
Culture Documents
2021
The Basics
In the design process, these typical fire-protection system goals are on the table for consideration:
Saving lives.
Saving property.
Preserving business continuity.
It all depends on how a building is used and occupied. A warehouse or storage facility, for example, will
have different fire-protection requirements than a multi-tenant office building.
While no standard fire-protection design blueprint exists for any two buildings, the systems found in any
building typically include these basic components:
Detection.
Alarms and notification.
Suppression.
All components of modern fire-protection systems need to work together to effectively detect, contain, control, and/or
extinguish a fire in its early stages - and to survive during the fire. To achieve the most beneficial symbiosis between these
components, it’s best to involve an experienced system designer, such as a fire-protection engineer, in the early stages of the
planning and design process.
* OBJECTIVE:
The function of the Fire Detection and Protection System is to ensure reliable and efficient Fire Detection and
Protection facilities in the occupancy.
In order to mitigate the occurrence and spread of fire.
Providing protection and safety for operating personnel and dumped materials
Early detection and warning of fire, so as to minimize the damage and consequential losses resulting from the fire.
The above requirements will be met by optimum selections of Fire Protection System devices and by adequate Fire
Detection and early warning measures. The system is designed in compliance with the recommendation guidelines of
Tariff Advisory Committee (TAC) and the relevant norms of IS Standard the objective of this report is as follows:
Identify the risk / hazardous areas and determine the type of Fire Protection and Detection System for various
areas.
Determine and recommend basic system features and equipment parameters
Describe the system features and operation. 5
Indicating the requirements of fire water pumps and storage tank for the proposed occupancy
* CONTENTS
1.0 SCOPE
2.0 STANDARDS AND CODES
3.0 TYPES OF SYSTEM PROPOSED
4.0 FIRE HYDRANT SYSTEM
5.0 AUTOMATIC SPRINKLER SYSTEM
6.0 ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM
7.0 TWO WAY PUBLIC ADDRESS SYSTEMS
8.0 PORTABLE FIRE EXTINGUISHERS
9.0 FIRE SIGNAGES
10.0 FIRE SAFETY PLAN
11.0 EMERGENCY ASSEMBLY POINT
1.0 SCOPE
The Scope of works shall comprise of supply, installation, testing & commissioning of External & Internal Hydrant
system & Hose reel Sprinkler System with Alarm Valve System Pipes with all fittings & flanges, valves, hangers,
supports, Isolation valves Portable Fire Extinguishers Fire Pumps & Accessories of Parala plant. The scope includes
all the related things like testing at manufacturers’ works, packaging, transportation, shipping, unloading at port,
transportation to site, unloading, storage, insurance, transportation from stores to erection site etc. The design of Fire
Fighting System in respect of fire safety as the functional usage requires office building of large number of people at
a single location and any emergency must be ensure minimum disruption in operations.
The objective of this report is to design a Fire Fighting system that shall provide:
Life safety of occupants.
Property protection.
Compliance with all relevant statutory requirements.
Minimum disruption during emergency to the operations.
2.0 CODES AND STANDARDS
The design and planning of Fire Protection, Detection & PA system shall be done keeping in view the following
codes and standards:
Hazard Classification
As per IS 15105 , Food & beverages & Breweries plants are comes under Ordinary hazard occupancies, So design of the
Fire water system is as per Ordinary hazard occupancies requirements mentioned in IS 15105 std.
3.0 TYPES OF SYSTEM PROPOSED
1 1 No Electrically driven main pump for Hydrant & 90 mtr @ 3250 LPM Combined Fire Pump Room
Sprinkler system
Combined Fire Pump Room
2 1 No Diesel Engine driven standby pump for Hydrant
& sprinkler system 90 mtr @ 3250 LPM
2 No of Common compartmentalized Control panel located at pump house controls all pumps and further the
status of pumps shall be extended to IBMS system for monitoring through the Fire alarm panel.
4.0 FIRE HYDRANT SYSTEM
Hydrant system with ring main runs at basement ceiling level with isolation valves. The yard hydrant points shall be
extended from the same mains and also the wet risers shall be connected from the mains with isolation valves.
Hydrant mains shall be M.S heavy grade pipe with suitable type of fittings made of by same material. Under ground pipe shall
be protected by means of suitable wrapping coating matrial
System consisting of internal hydrants for all floor levels near staircase or corridor, External hydrants at suitable locations
and Fire brigade inlet connection for emergency pumping to the system and for the fire tank.
External Hydrants
Hydrants are proposed at every 45m of periphery of the Building to protect the building from outside with all
accessories isolation valves.
System consisting with Sprinkler mains pipes from pump room, piping network inside the floor area with properly designed pipe
supports, Sprinkler control valve located outside the building and isolation valves. Sprinklers shall be standard response
pendant type, 68 deg. C temperature rating and shall design to cover 9 to 12 sq. m.
At each sprinkler distribution header shall tapped off from sprinkler riser with isolation valves and flow switches on each
distribution header and flow switch shall be connected to fire alarm panel to monitor in case of water flow in the event of fire
The Fire detection and alarm system shall be consisting with the following,
Interfaces
Fire Alarm System Interface with third party Systems at Fire alarm Control Panel (FACP), and programmed from
Network Control Station in Fire Control Room located at ground floor.
a. Fire Pump Status: Each fire pump shall have status indication for power failure, pump running and phase
reversal. An audible trouble signal shall sound until acknowledged and automatically restored. The running
condition of pump shall be permitted to be alarm condition whereas all other status of pumps shall be permitted
to be supervisory condition.
b. The operation of Sprinkler Water flow switch, Valve supervisory switch and Pressure Switches shall cause an
alarm / supervisory condition at Fire Alarm Control Panel.
c. Elevator Recall for Fire fighter services; Primary main floor recall shall be activated on alarm by an elevator lobby
or elevator machine room detector. Alternate floor recall shall be activated by detector in the main floor elevator
lobby.
d. Stair Pressurization: With-in a given zone, an automatic sprinkler system water flow switch, an open area smoke
detector outside a pressurized stairwell shall activate the stair pressurization systems for that zone.
e. AHU Tripping: Within a given zone, an automatic sprinkler system water flow switch, an open area smoke
detector, shall switch off the Air Handling units of affected area and simultaneously the respective fire damper.
f. External Dampers: Within a given zone, an automatic sprinkler system water flow switch, an open area smoke
detector, shall switch off associated damper of duct crossing through fire resistant wall.
g. Smoke Control System: Within a given zone, an automatic sprinkler system water flow switch, an open area
smoke detector or the manual fan control at Fire Control Room shall switch OFF/ON the smoke control fan of
associated Zone.
h. Building Management System (BMS): Shall interface with building management system for monitoring of fire net by
BMS.
Types of Extinguishers
Now that you have a basic understanding of the various types of fire and why different extinguishers are
necessary, 6 main types of fire extinguishers and their uses will be discussed:
An ABC powder fire extinguisher has numerous advantages as it is a multi-purpose extinguisher and is therefore one of
the most common extinguishers to have on hand.
A powder extinguisher sprays a very fine chemical powder composed most commonly of monoammonium phosphate.
This acts to blanket the fire and suffocate it.
Powder extinguishers are effective for class A, B and C fires, since it is not an electrical conductor and since it can
effectively break the chain reaction in a liquid or gas fire, something a water extinguisher cannot do.
A carbon dioxide fire extinguisher (CO2) is one of the cleanest types of extinguishers to use as it leaves no residue and
requires no cleanup.
The CO2 extinguisher does exactly that – extinguishes CO2. By doing so, it removes oxygen from the fire, effectively
suffocating it of oxygen. It is perfect for use on class B fires that involve flammable liquids and on electrical fires.
These extinguishers contain a solution composed of potassium that effectively launches a two-pronged assault on fires.
First, the liquid mist it sprays acts to cool the fire. Second, due to the chemical reaction of the solution with the cooking
medium, a thick soap-like substance forms, sealing the surface of the liquid to prevent re-ignition.
The wet chemical extinguisher, then, is ideal for a kitchen setting and class K fires. However, it can also be effective for
class A fires where a material such as wood or paper has caught fire.
The most versatile of the set, the water mist extinguisher, uses a newer technology that works across most classes of
fire.
This type of extinguisher releases microscopic water molecules that fight the fire on a variety of levels. First, because
so much water is dispersed in such a microscopic fog-like form, the level of oxygen in the air is decreased, which helps
to suffocate the fire.
Second, the water particles are drawn to the fire and, as water always does, acts to cool it, reducing the temperature.
Finally, and perhaps what is most unique about the water mist extinguishers, is that the water has been de-ionized (the
minerals have been removed). As a result, it can actually be used on electrical fires, as the de-ionized water will not act
as a conductor, as well as on burning liquids/gases that a standard water extinguisher could not be applied to.
Thus, a water mist extinguisher is safe and effective for use on classes A, B, C and K fires.
5. FOAM FIRE EXTINGUISHER
Foam fire extinguishers are suitable for class A and the flammable liquids of class B, though not effective for gaseous
fires.
They spray a type of foam that expands when it hits the air and blankets the fire. This blanket prevents the vapors from
rising off the liquid to feed the fire, thus starving it of fuel. Also, because the foam is mixed with water, it has a cooling
effect as well.
Foam extinguishers are some of the best for liquid fires, such as gasoline fires, but can also be used on Class A fires
involving solid combustibles like wood.
A clean agent fire extinguisher is a type of gaseous fire suppression. Stored in its liquid form, when it is sprayed and hits
the air, it converts to its gas form which is non-conductive, safe for use while humans are present, leaves no residue,
and has a very short atmospheric lifetime, making it eco-friendly.
The gas, often composed of Halon, extinguishes fire by reducing the oxygen levels and impeding the chain reaction.
Because it is non-conductive and so clean, it is ideal for rooms or businesses filled with electrical and computer
equipment. They are most commonly used for class B and C fires.
The portable fire extinguishers shall be provided as per NFPA 10, standards for portable fire extinguishers. However,
additional fire extinguishers shall be provided as per requirement of local Fire Services.
SL. TYPE OF FIRE EXTINGUISHER PROPOSED LOCATION
NO
1. carbon-di-oxide fire extinguishers (22.5 kg) trolley mounted – 6 NOS.
3. 9 lt. Aqueous film forming foam (AFFF) stored pressure type fire Type of Fire Extinguisher are shown at
extinguisher – 8 NOS. proposed location on plot plan & mention the
4. mechanical foam type fire extinguishers 50 kg – 7 NOS. type.
1. Signage with printed “IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.5cm
height letters in red with white back ground. The size of the board shall be 25cm x 30 cm and shall be fixed at
the height of 2mts. from finished floor near Manual call points.
2. Floor identification signage (i.e., GROUND FLOOR …etc.) at each stair enclosure on every floor, indicating the
floor number in words, lettering size shall be 7.5 cm with contrasting colour from back ground. Size shall be
15cm x 60cm.
3. Plant rooms and equipment’s room signage’s need to be considered for identifications.
10.0 FIRE SAFETY PLAN
A Fire safety plan for preventing and extinguishing any accidental fire in the building and action to be taken by the
occupants in case of such fire has been provided at strategic points, this shall be provided near each staircase area.
$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$$