PSS 3000/PSS 3100 Series
6400 Sonderborg
Denmark
Telephone 74 43 63 32
Yokohama 222-0033
Japan
Telephone (0 45) 4 71-22 81
USA
Telephone (2 48) 4 73-11 33
Telefax (2 48) 4 73-39 97
Installation Manual
Telefax
E-Mail:
74 43 63 42
pilz@pilz.dk
Telefax
E-Mail:
(0 45) 4 71-22 83
pilz@pilz.co.jp
E-Mail: info@pilzusa.com
Item No. 18 557
... In many countries we are represented by sales partners. Please refer to our
Homepage for further details or contact our headquarters.
www www.pilz.com
While every effort has been made to ensure that the information in this manual is accurate,
no responsibility can be accepted for errors or omissions contained within it.
We reserve the right to amend specifications without notice. We are grateful for any
feedback on the contents of this manual.
The names of products, goods and technologies used in this manual are trademarks of the
respective companies.
Introduction 1-1
Definition of symbols 1-2
Installation 4-1
Installing the PSS 3000 series 4-1
Installing the base module rack 4-1
Installing the modules for the PSS 3000 series 4-2
Expansion devices for the PSS 3000 series 4-3
Installing the module rack in a control cabinet 4-6
Interfaces 7-1
Appendix 9-1
Changes to the Installation Manual 9-1
This installation manual contains all the information you need to install a
PSS system from the PSS 3000 or PSS 3100 series.
If you are using the PSS SB 3000 or PSS SB 3100 you should also refer
to the “SafetyBUS p Installation Manual”.
Throughout this manual, the term “safety system” or simply “PSS” will be
used to refer to the programmable safety systems in the PSS 3000 and
PSS 3100 series.
Definition of symbols
DANGER!
This warning must be heeded! It warns of a hazardous situation which
poses an immediate threat of serious injury and death, and indicates
preventive measures which can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation which
could lead to serious injury and death, and indicates preventive
measures which can be taken.
CAUTION!
This refers to a hazard which can lead to a less serious or minor injury
plus material damage, and also provides information on preventive
measures which can be taken.
NOTICE
This describes a situation in which the unit(s) could be damaged and also
provides information on preventive measures which can be taken.
INFORMATION
This gives advice on applications and provides information on special
features, as well as highlighting areas within the text which are of
particular importance.
To ensure that the safety system functions correctly, please follow the
safety guidelines given below:
• CAUTION!
The tolerance on the supply voltage for the PSS PS power supply is
+10 % or -15 % maximum. On the PSS(1) PS 24 V, the maximum
tolerance is +20 % or -15 %.
Safe operation cannot be guaranteed outside this range.
• Overvoltage and spikes of interference can damage the PSS power
supply. If this occurs the unit will switch to a safe condition. Please refer
to the relevant EMC-measures described in Chapter 3.
PSS(1) PS 24 V
• The “PSS PS 24 V” and “PSS1 PS 24 V” power supplies require a
24 VDC supply. Check that the voltage supplied from the external power
supply corresponds.
• To achieve the lowest possible residual ripple (< ± 1.2 V), we
recommend that you install a three-phase bridge rectifier or regulated
supply.
• The external 24 V power supply must be capable of supplying a
minimum of 8 A for approximately 1 s.
• The fuse between the external and the PSS power supply protects the
cabling. The size of the fuse will depend on the cable cross section and
on local regulations.
• WARNING!
Safe electrical isolation must be ensured for the external 24 V supply.
Failure to do so could result in electric shock. Power supplies must
conform to DIN VDE 0551 / EN 60 742 and DIN VDE 0160.
• The external 24 V supply should be connected to the PSS power supply
as shown in the diagram below. The external supply should be earthed
in accordance with local regulations.
If the external supply is also being used to supply the input/output
modules, the 0 V output should be earthed as shown in the section
entitled “Supplying the input/output modules”.
+24 V PSS(1) PS 24 V
L1
~
24 V Functional
N = 0V
0V earth
module rack
PSS PS
L1 (115/230 V) L1
N N Functional
Only link
at 115 V earth
PE module rack
• Connect the external 24 V supply to the PSS power supply as shown in the
diagram below. The external supply should be earthed in accordance with
local regulations. If the external supply is also being used to supply the
input/output modules, earth the 0 V mains as described in the section
entitled “Supplying the input/output modules”.
+24 V
L1
~
= 0V 24 V
N 0V Earth
module rack
+24 V Module
L1
~
24 V Functional
N = 0V
0V earth
module rack
Installation
• CAUTION!
If the unit is operated at an ambient temperature of more than 45 0C,
surface temperatures on the housing may exceed 80 0C at full load. Do
not touch the metal parts on the housing: risk of burns!
• The safety system must be installed in such a way that buttons and
switches cannot be operated unintentionally.
Notes
Overview
Source of Interference
interference Coupling sink
Interference reaches the interference sink (e.g. the PSS 3000) in various
ways:
• DC coupling
This occurs if the source and sink of interference have common cable
connections. The common cable presents complex resistances, inducing
potential differences. Possible sources of interference are switches/
relays, running motors or varying potentials for other systems on the
same power supply.
NOTICE
Stronger HF transmitters should only be operated at a distance of more
than 0.6 m.
• Static discharge
Static discharge occurs where there are very high differences in potential
between two points. If the two points are brought closer together or if the
potential difference is increased, discharges can occur in the air gaps.
Possible sources of interference are people who are statically charged
from a synthetic carpet, for example.
The prescribed earth points are designed for your safety and to guarantee
compliance with noise resistance requirements.
Cabling
Equipotential bonding
Miscellaneous
Connecting the programming device
NOTICE
Fluorescent lamps should be avoided as they create interference fields.
However, if it is absolutely necessary to use fluorescent lamps, the
guidelines listed below should be followed:
• Place shield screening over the lamp.
• Used screened cable.
• Install a metal-sheathed switch.
• Use a mains filter or screened power supply cable.
Care must be taken to avoid interference when installing the unit within an
enclosure or wall-mounting:
• Shielding, earth conductor bars and the base module rack should be
attached to metal parts in order to divert any coupled interference on to
large metal areas. For wall-mounting we recommend that the overall
potential surfaces are made of steel.
• For varnished or anodised metal parts you should use special contact
plates or remove the protective coating.
• Install an earth bar for the cable screens.
• The earth bar can also be used as the ground conductor bar.
• Connect the earth bar to the mounting plate over a wide surface area
and with low impedance.
Use the following list to check that the safety system has been installed to
conform with EMC-regulations.
190,5 277,5
190,5 277,5 (7.5") (10.93")
(7.5") (10.93")
280
482,6 (11.02")
(19")
Dimensions of module rack PSS 3000 BM8 Dimensions of module rack PSS 3000 BM4
Dimensions stated in mm (") Dimensions stated in mm (")
INFORMATION
The modules require at least 65 mm free space for insertion (see diagram
below).
65
(2.56")
Back plate
(Pilz bus)
WARNING!
Before installing the modules, switch off all the power to the terminals and
power supply. You should also switch off all the power before inserting or
removing a connector. Serious, even fatal injuries could occur due to electric
shock if you touch conductive parts while power is applied.
• Tighten the two securing screws to prevent the module from coming loose
and to make the earth conductor connection.
• The module is secured correctly when the plastic sheath is embedded (see
diagram below).
Failsafe bus
Plastic
Pilz bus sheath
embedded
Securing screw
with plastic
sheath
INFORMATION
The first module slot is reserved for the power supply.
The second module slot is reserved for the CPU on the base module rack,
and for an expansion connection on expansion module racks.
INFORMATION
Failsafe modules cannot be used on the expansion rack!
Expansion connection
for base unit
Failsafe and
standard C 1 3 5 7
modules P
P
S U0 2 4 6
Expansion connection
for expansion rack
Standard
modules only 9 11 13 15
P
S 8 10 12 14
Standard
modules only 17 19 21 23
P
S 16 18 20 22
One power supply may be sufficient for two racks, depending on the
modules' power input requirements (see Chapter 8).
- The rack is addressed consecutively, starting with the base module rack.
- Maximum cable length: between base unit and expansion rack: 1200 mm,
between expansion units 320 mm.
NOTICE
Bus expansion cables must not be laid in the cable duct.
C 1 3 5 7 9 11 13 15
P P P
S U0 2 4 6 S 8 10 12 14
Standard
modules only
17 19 21 23
P
S 16 18 20 22
One power supply may be sufficient for two racks, depending on the
modules' power input requirements (see Chapter 8).
- The rack is addressed consecutively, starting with the base module rack.
- Maximum cable length: between base unit and expansion rack: 1200 mm,
between expansion units 320 mm.
NOTICE
Bus expansion cables should not be laid in the cable duct.
C 1 3 5 7 17 19 21 23
P P P
S U0 2 4 6 S 16 18 20 22
Standard
modules only
9 11 13 15
P
S 8 10 12 14
Standard
modules only
One power supply may be sufficient for two racks, depending on the
modules' power input requirements (see Chapter 8).
- The rack is addressed consecutively, starting with the base module rack.
- Maximum cable length: between base unit and expansion unit: 1200 mm.
NOTICE
Bus expansion cables should not be laid in the cable duct.
Earth
connector
cross- FS Bus
section:
>2.5 mm2 277.4
(AWG#12) (10.92")
ST Bus
10 PS CPU DI DI DO
(0.39") pilz pilz pilz pilz pilz
min.65
W x H cable duct (2.56")
max. 100 mm (3.94") x 50 mm (1.97") max. 120
(4.72")
10
(0.39")
ST Bus
min. 50
PS DI DI DO
(1.97")
pilz pilz pilz pilz pilz
Distance from
control cabinet
min. 100 mm (3.94") min. 60 (2.36")
Power section
Drill 4 x M6 holes in the mounting plate of the control cabinet, as per the
installation dimensions for the base module rack. Screw the base module
rack on to the mounting plate in your control cabinet.
10 320,6 10
(0.39") (12.62") (0.39")
37,7
(1.48") M6
190,5
(7.5") 265,9
(10.47")
340,6
(13.41")
190,5
(7.5") 265,9
(10.47")
259,4
(10.21")
Dimensions of module rack PSS BMPS 3/1
Dimensions stated in mm (")
WARNING!
Before installing the modules, switch off all the power to the terminals and
power supply.
• Insert the module along the guide rail.
• Push the module firmly into the socket on the bus plate.
• Tighten the screws at the front to prevent the module coming loose and
to make the earth conductor connection.
WARNING!
Unused slots should always be covered with a blanking plate (order
reference: 303 200). If not, an electric shock could endanger life, or
foreign bodies could cause a short circuit and damage the unit.
The first module slot is reserved for the power supply and the second
module slot is reserved for the CPU (not on the PSS1 BMPS 3/1).
WARNING !
Before installing the modules, switch off all the power to the terminals and
power supply.
• Remove the two screws securing the module to the module rack (1).
• Use a screwdriver on the groove of the upper securing rail to lever the
module out (2).
It is essential that you keep to the minimum distance between the wall of
the control cabinet and the power section.
304.6
(12")
265.9
M4 earth (10.47")
connector
cross section
>2.5 mm2
(AWG#12)
Distance from Distance from
control cabinet control cabinet
min. 50 mm min. 60 mm min. 50 mm
(1.97") (2.36") (1.97")
Power section
It is essential that you keep to the minimum distance between the wall of
the control cabinet and the power section.
223.4
(8.76")
265.9
M4 earth (10.47")
connector
cross section
>2.5 mm2
(AWG#12)
Distance from Distance from
control cabinet control cabinet
min. 50 mm min. 60 mm min. 50 mm
(1.97") (2.36") (1.97")
Power section
Failsafe
I 13
7 I 14 7
8 I 15 8
9 0V 9
10 0V 10
__X__.3 __X__.3
1 I 16 1
2 I 17 2
3 I 18 3
4 I 19 4
5 I 20 5
6 X3
I 21 6
7 I 22 7
8 I 23 8
9 0V 9
10 0V 10
__X__.4 __X__.4
1 I 24
2 1
I 25 2
3 I 26 3
4 I 27 4
5 I 28
6
X4 5
I 29 6
7 I 30 7
8 I 31 8
9 9
10 0V
0V 10
PSS DI
Notes on wiring
The way in which this is done will depend on the degree of hazard within
the plant itself, the switching frequency of the input devices and the level
of safety of the input devices and actuators. These points must be
assessed in conjunction with the relevant standards or approvals body
(e.g. BG or TÜV).
With multi-channel pulsed input devices, short circuits and line breaks can
be detected via feasibility checks in the control program.
NOTICE
Please read the description for each application!
Failsafe
PSS(1) DI 2
Features:
• Input module with 32 inputs
• Response time: I00 ... I15: 1 ms, I16 ... I31: 3 ms
• Module code: 8003 8003
• Depending on the application area and its respective regulations, this
module may be used without test pulses for applications up to
category 3 in accordance with EN 954-1. The possibility of a short circuit
occurring in the external wiring between different inputs or against L+
must be eliminated through appropriate wiring.
• For category 4 applications, the module must always use test pulses.
• Only one 0 V output terminal needs to be connected
• Only input signals which operate in accordance with the zero signal
principle (on switching off) are permitted for safety-related applications
• Signals may be connected using unscreened cables.
CAUTION!
The connection shown overleaf is only approved for non-safety
applications. The connection of safe input devices for safety-relevant
applications is described later in the chapter.
__X__.1
I 00 Input X.0 (X: slot)
I 01
I 02
I 03 Input device is not failsafe
I 04
I 05
I 06
I 07
0V
0V
__X__.2
I 08 Input X.8
I 09
I 10
I 11
I 12
I 13
I 14
I 15
0V
0V
Failsafe
__X__.3
I 16 Input X.16
I 17
I 18
I 19
I 20
I 21
I 22
I 23
0V
0V
__X__.4
I 24 Input X.24
I 25
I 26
I 27
I 28
I 29
I 30
I 31
0V
0V
PSS DI 2
L+
24 V DC
L-
PSS(1) DI 2
Example: Single-channel, failsafe input device, without test pulses
Features:
• Depending on the application area and its respective regulations, this
connection diagram is suitable for pulsed and continuous input
devices up to category 2 in accordance with EN 954-1. The possibility
of a short circuit occurring in the external wiring between different inputs
or against L+ must be eliminated through appropriate wiring.
• The input device must be approved for failsafe applications.
• Please read the instructions provided with the input device.
• If you are using the PSS(1) DI module, the connection shown overleaf is
only approved for non-safety applications.
CAUTION!
It will not be possible to detect short circuits in the cable between the input
device and input with the L+ line or between adjacent inputs. Nor will a
short circuit between several input devices be detected. Depending on the
type of input device connected, this could create a risk to both personnel
and machinery (e.g. emergency stop). You should always ensure that the
unit is suitably wired to eliminate the risk of short circuits.
__X__.1
I 00
I 01
I 02
I 03
I 04
I 05
I 06
I 07 Single-channel, failsafe input
0V device
0V
__X__.2
I 08
I 09
I 10
I 11
I 12
I 13
I 14
I 15
0V
Failsafe
0V
__X__.3
I 16
I 17
I 18
I 19
I 20
I 21
I 22
I 23
0V
0V
__X__.4
I 24
I 25
I 26
I 27
I 28
I 29
I 30
I 31
0V
0V
PSS DI 2
L+
24 V DC
L-
PSS(1) DI 2
Example: Dual-channel input devices, without test pulses
Features:
• PSS(1) DI and PSS(1) DI 2: Depending on the application area and its
respective regulations, this connection diagram is suitable for pulsed
input devices up to category 4 in accordance with EN 954-1, provided
the functionality of both input device channels is monitored in the user
program via a feasibility check (see example in the Programming
Manual).
• PSS(1) DI2: Depending on the application area and its respective
regulations, this connection diagram is suitable for continuous input
devices up to category 3 in accordance with EN 954-1, provided the
functionality of both sensor channels is monitored in the user program
via a feasibility check (see example in the Programming Manual).
• The possibility of short circuits occurring between adjacent connector
terminals cannot be eliminated. For this reason, the two identical
(homogenous) channels on an input device must not be connected to
adjacent inputs.
• If you are using input devices with different (diverse) channels, adjacent
inputs may be used. Short circuits will be detected in the application
program via the feasibility check (see example in the Programming
Manual).
CAUTION!
It will not be possible to detect short circuits in the cable between the input
device and input with the L+ line, nor short circuits between several input
devices. Depending on the type of input device connected, this could
create a risk to both personnel and machinery (e.g. emergency stop). You
should always ensure that the unit is suitably wired to eliminate the risk of
short circuits.
Failsafe
__X__.3
I 16
I 17
I 18
I 19
I 20
I 21
I 22
I 23
0V
0V
__X__.4
I 24
I 25
I 26
I 27
I 28
I 29
I 30
I 31
0V
0V
PSS DI (2)
L+
24 V DC
L-
PSS(1) DI 2
Example: Single-channel, failsafe input device, with test pulses
Features:
• Depending on the application area and its respective regulations, this
connection diagram is suitable for applications up to category 2 in
accordance with EN 954-1.
• The input device must be approved for failsafe applications.
• Please read the instructions provided with the input device.
• The test pulse must be allocated to the input via the configurator on the
programming device (see Programming Manual).
• Testing will detect short circuits between lines L+ and L-, and also
between the pulsed outputs.
• Only input devices with N/C contacts can be approved.
• Cable runs: 1 ms inputs: 200 m;
With 1 kOhm resistance parallel to input:
Max. 800 m
3 ms inputs: 800 m
CAUTION!
Short circuits between the cable from the signal to the input device and the
cable from the input device to the input will not be detected.
Failsafe
__X__.3 Test pulse 0 __X__.3
O 16 I 16
O 17 I 17
O 18 I 18
O 19 I 19
O 20 I 20
O 21 I 21
O 22 I 22
O 23 I 23
24 V 0V
0V 0V
__X__.4 __X__.4
O 24 I 24
O 25 I 25
O 26 I 26
O 27 I 27
O 28 I 28
O 29 I 29
O 30 I 30
O 31 I 31
24 V 0V Additional
0V 0V input
PSS DIO T PSS DI (2)
devices
L+
24 V DC
L-
PSS(1) DI 2
Example: Dual-channel, failsafe input device, with test pulses
Features:
• Depending on the application area and its respective regulations, this
connection diagram is suitable for applications up to category 4 in
accordance with EN 954-1.
• This type of connection is mainly used for continuous signals.
• The operating system will detect all shorts between contacts and short
circuits to L+ and L-.
• Short circuits across the contact can be detected via the feasibility check
in the application program.
• The test pulse must be allocated to the input via the configurator on the
programming device (see Programming Manual).
• Only input devices with N/C contacts can be approved (in the case of
diverse channels, only the N/C contact).
• On input devices with identical channels, each channel should be given
a separate signal, where possible. This will ensure that all short circuits
are detected, with the exception of short circuits which short out the
input device (cable from the signal to the input device and cable from the
input device to the input).
• If the input device has only one signal, a short circuit between the
cables from the input device to the inputs will not be detected. You
should always ensure that the unit is suitably wired to avoid the risk of
this type of short circuit.
• Cable runs: 1 ms inputs: 200 m;
With 1 kOhm resistance parallel to input:
Max. 800 m
3 ms inputs: 800 m
Failsafe
0V 0V channels
__X__.3 Test pulse 0 __X__.3
O 16 I 16
O 17 I 17
O 18 Test I 18 Dual-
O 19 pulse I 19 channel
O 20 1 I 20 input
O 21 I 21
O 22 I 22 device
O 23 I 23 with
24 V 0V diverse
0V 0V chan-
__X__.4 __X__.4 nels
O 24 I 24
O 25 I 25
O 26 I 26
O 27 I 27
O 28 I 28
O 29 I 29
O 30 I 30
O 31 I 31
24 V 0V More
0V 0V input
PSS DIO T PSS DI (2) devices
L+
24 V DC
L-
Please ensure safety regulations and EMC guidelines are observed!
PSS(1) DI2O T
Features:
• Test pulse output module with 16 inputs.
• Module code: 8001 8012
• The inputs correspond to the 1 ms inputs on the PSS(1) DI2.
• The outputs are push-pull outputs. Do not use the push-pull level to drive
a load to L+, otherwise the switch-off test will detect a connection to L+
and will register an error.
• In the configurator on the programming device, outputs can be
configured as test pulses or as single-pole 2 A outputs in groups of 8
(see Programming Manual). Configuration is carried out automatically,
depending on the number of test pulses used:
Number < 8: X.16 ... X.23 are test pulse outputs
X.24 ... X.31 are single-pole 2 A outputs
Number > 8: X.16 ... X.31 are test pulse outputs
Number = 0: X.16 ... X.31 are single-pole 2 A outputs
• If the number of pulses is less than 8, test pulse outputs up to and
including X.23 must remain unwired.
• DIF2 and DI2 inputs must not be connected to the same pulsed output.
• Adjacent inputs should not be operated with the same pulse.
NOTICE
When using single-pole outputs, always ensure that line or cable breaks
and short circuits between lines can always be detected, or ensure they
cannot occur by using appropriate wiring.
• Outputs configured as 2 A outputs have monitoring inputs available
under the same address. These can be used for feasibility checks.
• If cable runs are greater than 200 m with a cable cross section of
1.5 mm2, or cable runs are greater than 300 m with a cable cross section
of 2.5 mm2, the operating system will not detect a short circuit to earth.
• If cable runs are greater than 800 m, interference from switching
operations in 24 VDC signals may affect the pulsed outputs.
• Each output is protected against short circuit, overload and
overtemperature. Outputs are designed for resistive and inductive loads.
• For details of press applications please refer to the relevant application
description.
__X__.1
I 00
I 01
I 02
I 03
I 04
I 05
I 06
I 07
0V
0V
Inputs __X__.2
I 08
I 09
I 10
I 11
I 12
I 13
I 14
I 15
0V
0V
__X__.3
Failsafe
O 16
O 17 Test pulses for
O 18 input devices
O 19
O 20
O 21
O 22
O 23
24 V
Test pulse 0V
outputs or single- __X__.4
pole 2 A outputs O 24
O 25
O 26
O 27
O 28
O 29
O 30
O 31
24 V
0V
PSS DI2O T
L+
24 V DC
L-
PSS(1) DI2O Z
Features:
• Dual-pole switching output module with 16 inputs
• Module code: 8001 8011
• The inputs correspond to the 1 ms inputs on the PSS(1) DI.
• The outputs are dual-pole switching 2 A outputs.
• The operating system of the programmable safety system tests the
outputs during each cycle. Any short circuits or open circuits to the load
will be detected.
• To avoid overloading the contacts, the current at the connection
terminals should be 10 A maximum.
• The maximum continuous current over all the outputs is 10 A.
• During testing, the load is isolated from the supply for 100 ... 200 µs
in each cycle (depending on the load and the line length).
The load must not switch off during this time.
Outputs that are switched off are switched on for approximately 100 µs,
in order to test the monitoring inputs. The load must not switch on during
this time.
• Error messages can occur when testing outputs on which the contactors
are smaller than the recommended load. The error messages are
triggered by too high an inductance on the contactors. In this case it
helps to have a 1 kOhm resistor connected in parallel to the contactor
coil.
• Each output is protected against short circuit, overload and
overtemperature. Outputs are designed for resistive and inductive loads.
__X__.1
I 00
I 01
I 02
I 03
I 04
I 05
I 06
I 07
0V
0V
__X__.2
I 08
I 09
I 10
I 11
I 12
I 13
I 14
I 15
0V
0V
__X__.3
O 16+ Output X.16 (X: slot)
Failsafe
O 16-
O 17+
O 17-
O 18+
O 18-
O 19+
O 19- Output X.19
24 V
24 V
__X__.4
O 20+ Output X.20
O 20-
O 21+
O 21-
O 22+
O 22-
O 23+
O 23-
Output X.23
0V
0V
PSS DI2O Z
L+
24 V DC
L-
PSS(1) DIF
Features:
• Input module with facility for process interrupts: maximum 16
• Module code: 9002 0000
• This module will trigger a CPU interrupt if the pulse edge at an input
changes.
• The inputs that trigger a process interrupt and the pulse edge that
causes the interrupt to be triggered are defined via the configurator in the
programming device (see Programming Manual).
• Only one 0 V output terminal needs to be connected.
• The 0 V terminals between the inputs prevent short circuits occurring
between the inputs.
• Only those process interrupts triggered by a pulse edge change from “1”
to “0” are safety-relevant.
• The input signals may require screened cables, depending on the signal
frequency and the ambient conditions. If screened cables are used, the
0 V terminal between the inputs may be used for the screen.
• Process interrupts which are safety-relevant must be tested to ensure
they function correctly. The inputs may be tested using test pulses or via
the feasibility check (see example “Process interrupt test”).
• If a cable run exceeds 50 m, a resistance of 1 kOhm must be connected
in parallel with the input. The maximum cable run will then be 400 m.
NOTICE
Do not replace a DIF 2 module with a DIF module!
If a DIF module is inserted instead of a DIF 2 module, alarms could be lost
because the two modules have a different filter time.
__X__.1
I 00
0V
I 01
0V
I 02
0V
I 03
0V
0V
0V
__X__.2
I 04
0V
I 05
0V
I 06
0V
I 07
0V
0V
0V
Failsafe
__X__.3
I 08
0V
I 09
0V
I 10
0V
I 11
0V
0V
0V
__X__.4
I 12
0V
I 13
0V
I 14
0V
I 15
0V
0V
0V
PSS DIF
L+
24 V DC
L-
PSS(1) DIF
Example: Process interrupt test
Features:
• The test pulse must be allocated to an input via the configurator in the
programming device (see Programming Manual).
• PSS(1) DIF inputs have a shorter filter time than PSS(1) DI inputs. The
test period automatically adjusts to the DIF.
• DIF and DI inputs must not be connected to the same pulsed output.
Failsafe
__X__.3 __X__.3
O 16 I 08
O 17 Test pulse 2 0V
O 18 I 09
O 19 0V
O 20 I 10
O 21 0V
O 22 I 11
O 23 0V
24 V 0V
0V 0V
__X__.4 __X__.4
O 24 I 12
O 25 0V
O 26 I 13
O 27 0V
O 28 I 14
O 29 0V
O 30 I 15
O 31 0V Additional
24 V 0V sensors with
0V 0V
PSS DIO T
process
PSS DIF
interrupt
L+
24 V DC
L-
PSS(1) DIF 2
Features:
• Input module with facility for process interrupts: maximum 16
• Module code: 9002 0000
• This module will trigger a CPU interrupt if the pulse edge at an input
changes.
• The inputs that trigger a process interrupt and the pulse edge that
causes the interrupt to be triggered are defined via the configurator in the
programming device (see Programming Manual).
• Only one 0 V output terminal needs to be connected.
• The 0 V terminals between the inputs prevent short circuits occurring
between the inputs.
• Only those process interrupts triggered by a pulse edge change from “1”
to “0” are safety-relevant.
• The input signals may require screened cables, depending on the signal
frequency and the ambient conditions. If screened cables are used, the
0 V terminal between the inputs may be used for the screen.
• If a cable run exceeds 50 m, a resistance of 1 kOhm must be connected
in parallel with the input. The maximum cable run will then be 400 m.
CAUTION!
The DIF 2 module cannot be tested via the test signal on the DIO T
module because of the greater response time of the input filters. The DIF 2
should only be used with pulsed input signals which can be monitored via
a feasibility check.
NOTICE
Do not replace a DIF 2 module with a DIF module!
If a DIF module is inserted instead of a DIF 2 module, alarms could be lost
because the two modules have a different filter time.
__X__.1
I 00
0V
I 01
0V
I 02
0V
I 03
0V
0V
0V
__X__.2
I 04
0V
I 05
0V
I 06
0V
I 07
0V
0V
0V
Failsafe
__X__.3
I 08
0V
I 09
0V
I 10
0V
I 11
0V
0V
0V
__X__.4
I 12
0V
I 13
0V
I 14
0V
I 15
0V
0V
0V
PSS DIF 2
L+
24 V DC
L-
PSS(1) DOR
Features:
• All relay outputs are volt-free.
• Module code: 8014 0000
• The module meets the guidelines for the safe separation of relays
separated by a free connection (e.g. O 01 and O 02).
• Maximum switching voltage: 250 VAC/250 VDC, switching current: AC:
0.1 - 4 A, DC: maximum 4 A at 24 V, maximum 0.1 A at 250 V.
• Switching capability in accordance with EN 60 947-5-1:
- AC15/C300: 120 V/1.5 A; 240 V/0.75 A
- DC13/Q300: 125 V/0.55 A; 250 V/0.27 A
• Switching frequency at maximum load: 15/minute
• Each relay has a monitoring input available via positive-guided contacts.
Relay outputs and monitoring outputs have the same address.
• The application program must carry out function tests, if necessary.
• The supply voltage must be at least 21.6 V. Select a suitable power
supply and connect it to the module using individual supply cables. If the
supply falls below 21.6 V an error may be registered, with error message
“F06 n60” (n = channel A, B or C).
• Suppression will be required if inductive loads are being switched. Use
flywheel diodes, varistors or RC modules.
CAUTION!
Voltage must only be applied to the terminals on the PSS1 DOR module
when the module is inserted in the PSS 3100 module rack. Serious, even
fatal injuries could occur due to electric shock if you touch conductive parts
while power is applied.
CAUTION!
Switch off all the power before inserting or removing a connector. Serious,
even fatal injuries could occur due to electric shock if you touch conductive
parts while power is applied.
__X__.1
O 00 13 L1
O 00 14 N
O 01 13
O 01 14
*
O 02 13 L1
O 02 14 M N
* __X__.2 1~
O 03 13 L1 Standard
connection
O 03 14
O 04 13
for safe
N actuators
O 04 14
*
N
O 05 13
O 05 14
*
Failsafe
__X__.3
O 06 13
O 06 14
O 07 13
O 07 14
O 08 13
O 08 14
*
24 V
* __X__.4
O 09 13
O 09 14
O 10 13
O 10 14
O 11 13 Fuse max. 10 A
O 11 14
*
0V
PSS DOR
L+
24 V DC
L- * Safe separation
PSS(1) DOS
Features:
• Output module with 32 single-pole 1.5 A outputs
• Module code: 8015 0000
• Shorts between contacts are detected via test pulses when switching on
and off. These are generated by the operating system.
• If a short circuit occurs between the lead from the output to the load and
the 24 VDC supply lead, it will no longer be possible to switch off the
load. The following remedies are possible:
- Eliminate the possibility of an error by using separate multicore cable
for the 24 VDC
- Use dual actuators for safety
- Use an additional shutdown device such as a main contactor.
• The module has a second shutdown route and can therefore be used for
single-channel operation in applications conforming to EN 954-1 (11/94)
up to safety category 3 (depending on the application area and its
respective regulations). Please note that the second shutdown route is
only tested when the system switches from “STOP” to “RUN”.
To achieve category 4, dual actuators must be connected to adjacent
blocks of 8 outputs.
• A separate fuse should be connected in series with each block of 8
outputs.
__X__.1
O 00
O 01
O 02
O 03
O 04
O 05
O 06
O 07
24 V
0V
__X__.2
O 08
O 09
O 10
O 11
O 12
O 13
O 14
O 15
24 V
0V
__X__.3
O 16
Failsafe
O 17
O 18
O 19
O 20
O 21
O 22
O 23
24 V
0V
__X__.4
O 24
O 25
O 26
O 27
O 28
O 29
O 30
O 31
24 V
0V F1 F2 F3 F4
PSS DOS
24 V DC
0V
Notes
The following connection diagrams show the wiring for standard modules.
The PSS 3000 uses modules from the P10-range as standard modules,
while the PSS 3100 uses modules from the P9-range.
NOTICE
Standard modules are not approved for safety applications.
Module code:
P9/P10 DO: 4120
P9/P10 DIO: 2120
P9/P10 DI: 0020
P9/P10 AIO: A023
P9/P10 DOR: 4420
P9/P10 PMAO: E0A6
P9/P10 PMIA: E1A6
P9/P10 MMC3: E2A7
P9/P10 MMC6: E3A7
24 V, range 20 ... 30 V
incl. 5 % residual ripple
3~
0V
24 V, range 20 ... 30 V
incl. 5 % residual ripple
3~
0V
10 V K Screened
1 push-pull
H COM
cables should
20 mA output
1
be used on
_X _.2 _X__.2 analogue inputs
Range mA 1) T1 and outputs.
C C T2
Input 3
10 V
H COM H K
e.g.
20 mA 2
2 Counter
Range mA 1) C T1 1) Bridge when
C 10 V H T2 installed as
Input 4
K
H COM 3 current input.
20 mA
3
_X_ .3 _X__.3
Range mA 1) T1
2) On analogue
C C T2 outputs, the
Input 5
10 V
H COM H K voltage and
20 mA 4
4 current output
Range mA 1) C T1 can be used
C 10 V H T2 simultaneously.
Input 6
K
H COM 5
5 20 mA
_X_.4 _X__.4
Output 1 Output 2
C 10 V
H COM
6 20 mA
2) 10 V 3) Integration
C
H 20 mA time for all
7 COM analogue
+15 V 3) inputs with
0V bridge is:
24 V
-15 V
0V 16.6 ms
AIO PMI (mains: 60 Hz)
+15-V-
voltage
supply
24 V, range 20 ... 30 V 3~
incl. 5 % residual ripple 0V
Connection to earth bar (EN 60 204 Part 1)
or earth fault monitoring
24 V, range 20 ... 30 V
incl. 5 % residual ripple
3~
0V
Input 1
T2
K
Voltage
24 V
supply for
0V
input device
T1
Input 2
T2
K
24 V Voltage
0V supply for
_X _.2 input device
T1
Input 3
T2
K
Voltage
24 V
supply for
0V
input device
T1
Input 4
T2
K
24 V Voltage
0V supply for
_X_ .3 input device
Output 3 Output 2 Output 1
10 V
COM
20 mA
10 V
COM
20 mA
10 V
COM
20 mA
_X__.4
Output 4
10 V
COM
20 mA
Supply
24 V
0V
PMAO
24 V, range 20 ... 30 V
incl. 5 % residual ripple
3~
0V
5V
supply to
i/p device
Power
+5 V
+24 V
0V 24 V, range 20 ... 30 V
3 ~ incl. 5 % residual ripple
PMIA
P9/P10 MMC3
READY
P9/P10 MMC6 INPUT
D A
Inputs:
MMC3: Input A .... C
MMC6: Input A ... F
1 1: K1 9: Free
9 2: -K1 10: K2
2
E 10 3: Free 11: -K2
B 3
11 4: K0 12: Cam
4 5: -K0 13: Start
12
5 6: 24 V 14: Stop
13
6 7: 5 V 15: Registration
14
7 8: 0 V
15
8
K and -K: 5 V differential signal
F C
Screen
Outputs:
3 outputs per connector
MMC3: Output 1, outputs A ... C
1 MMC6: Output 1 and 2, outputs A ... F
9
2 1: Root (base) A (D) 9: Analogue o/p A (D)
OUTPUT 10
3 2: N/C contact A (D) 10: GND
2 1 11 3: N/O contact A (D) 11: Root (base) B (E)
4
12 4: Analogue o/p B (E) 12: N/C contact B (E)
5
13 5: GND 13: N/O contact B (E)
6
14 6: Root (base) C (F) 14: N/O contact C (F)
7
15 7: N/C contact C (F) 15: GND
8
8: N/O contact C (F)
Screen
5V
supply to
+5 V
Power
i/p device
+24 V
0V 24 V, range 20 ... 30 V
incl. 5 % residual ripple
3~
PG programming interface
1 N. C.
N. C. 6
2 N. C
A 7
3 B
N. C. 8
4 N. C.
N. C. 9
5 N. C. N.C. = no connection
1 N. C.
DSR 6
2 RXD
RTS 7
3 TXD
CTS 8
4 DTR
N. C. 9
5 GND N.C. = no connection
1 N. C.
N. C. 6
2 CAN_L brown
green CAN_H 7
3 CAN_GND white
N. C. 8
4 N. C.
N. C. 9
5 CAN_SHLD N.C. = no connection
PSS(1) CPU 2
PG programming interface
1 RXD
TXD 6
2 N.C.
A 7
3 B
N. C. 8
4 N. C.
N. C. 9
N.C. = no connection
5 GND
Fig. 7-4: Configuration of the programming interface PSS CPU2 and PSS1 CPU2
1 A
DSR 6
2 RXD
RTS 7
3 TXD
CTS 8
4 DTR
B 9
5 GND
Fig. 7-5: Configuration of the user interface PSS CPU2 and PSS1 CPU2
When an expansion rack is used on the PSS 3000, the number of power
supplies required will depend on the total power required by the modules:
C 1 3 5 7
P P A
S U 0 2 4 6
Power supply
cable
9 11 13 15
B
8 10 12 14
CAUTION!
The power supply cable must not be laid in the I/O or expansion cable duct!
C 1 3 5 7
P P A
S U 0 2 4 6
9 11 13 15
B
P
S 8 10 12 14
The following tables list the power requirements for the individual modules.
This will enable you to calculate the total power requirement for the module
racks.
Installation Manual: PSS 3000/PSS 3100 Series 8-1
Optimising the Power Supplies
Notes
The Installation Manual was completely revised and is now also valid for
the PSS SF 3000, PSS SF 3100, PSS SB 3000 and PSS SB 3100.
Notes