CMV-R Series
ALL DC Inverter Heat Recovery A/C
OWNER'S
MANUAL
In the case of extremely strong wind, please prevent the air from
flowing backwards into the outdoor unit.
1. IMPORTANT SAFETY INFORMATION Snow canopy is necessary in snowfall places on the outdoor
unit. Please consult the local dealer for details.
! CAUTION Do not use the air conditioner until a service person confirms that the
portion where the refrigerant leaks is repaired.
Failure to observe a caution may result in injury or damage
to the equipment. This appliance is intended to be used by expert or trained users
in shops, in light industry and on farms, or for commercial use
by lay persons.
Owner's manual
1
If the supply cord is damaged, it must be replaced by the Noise can be amplified by anything blocking the air outlet of
manufacturer, its service agent or a similarly qualified person outdoor unit.
in order to avoid a hazard.
Choose a proper places that the noise and hot or cold wind
An all-pole disconnection switch having a contact separation blown out of the outdoor unit will not bring inconvenience to
of at least 3mm in all poles should be connected in fixed your neighbors and not affect the growth or animal or plant.
wiring.
Do not allow a child to mount on the outdoor unit or avoid
Disconnect the power supply before cleaning and placing any object on it.
maintenance. Falling or tumbling may result in injury.
The appliance shall not be installed in the laundry. Do not operate the air conditioner when using a room
fumigation-type insecticide.
The A-weighted sound pressure level is below 70 dB.
Failure to observe could cause the chemicals to become deposited
in the unit, which could endanger the health of those who are
Correct Disposal of this product hypersensitive to chemicals.
This marking indicates that this product should not be disposed with Do not place appliances which produce open fire in places
exposed to the air flow from the unit or under the indoor unit.
other household wastes throughout the EU. To prevent possible harm
It may cause incomplete combustion or deformation of the unit due
to the environment or human health from uncontrolled waste disposal,
to the heat.
recycle it responsibly to promote the sustainable reuse of material
resources. To return your used device, please use the return and Do not install the air conditioner at any place where flammable
collection systems or contact the retailer where the product was gas may leak out.
purchased. They can take this product for environmental safe If the gas leaks out and stays around the air conditioner, a fire may
recycling. break out.
Before cleaning, be sure to stop the operation, turn the breaker All the picture in this manual are for explanation purpose only, there
off or pull out the supply cord. may be slightly different from the air conditioner you purchased
Otherwise, an electric shock and injury may result. (depend on model). The actual shape shall prevail.
In order to avoid electric shock or fire, make sure that an earth To avoid danger, never put sticks or other objects into it.
leak detector is installed.
Please preheat the air conditioner for at least 12 hours before
Be sure the air conditioner is grounded.
operation. Do not switch off the power if you need to stop the unit
In order to avoid electric shock, make sure that the unit is grounded
for 24h or shorter time. (This is to heat the crank case heater to
and that the earth wire is not connected to gas or water pipe,
avoid the compulsive start of compressor.)
lightning conductor or telephone earth wire.
In order to avoid injury, do not remove the fan guard of the Make sure the air inlet and outlet are not blocked, or it may degrade
outdoor unit. the performance of air conditioner or start up protector which will
stop the unit from running.
Do not operate the air conditioner with a wet hand.
An electric shock may happen.
2 3 4
Owner's manual
2
Table.2-1 Operation conditions
51
Air inlet(Both in left and right sides, as well as in rear side)
For proper performance, run the air conditioner under the following
52 Refrigerant pipe connective opening or wires outlet temperature conditions:
53 Refrigerant pipe connective opening or wires outlet
Table.3-1
54 Fixed foot Temperature
Air outlet (heat air to be blows out in the cooling operation, vice Outdoor temperature Indoor temperature Room relative Humidity
5 Mode
versawhile the heating)
Cooling mode -5℃~48℃ 16℃~32℃ Below 80%
Owner's manual
3
4. TROUBLES AND CAUSES
! CAUTION
In case the following malfunctions, lease switch off the power and
contact the local dealer. Incorrect ON/OFF operation.
Troubles Causes
Owner's manual
4
5. MALFUNCTION
Malfunction display of outdoor unit's DSP1 and DSP2
Tab.5-1
No Error code Error or protection type Note
2 E1 Phase error
20 minutes after first power on or indoor and outdoor communication
3 E2 Communication error with indoor unit break off over 2 minutes after first power on 20 minutes
4 E3 Reserve
6 E5 Reserve
7 E6 Indoor temp. Sensor error T3 pipe temp error. (Left pipe temp.)
15 xH4 3 times of P6 protection in 60 minutes Must restart electricity, otherwise cannot recover
17 H6 3 times of P4 protection in 100 minutes Must restart electricity, otherwise cannot recover
Qty. of outdoor unit decreases Indoor units lost for over 3 minutes, not recoverable until the
18 H7 unit qty. recover
19 H8 Pressure sensor error Must restart electricity, otherwise cannot recover
25 xP4 Discharge temp. Protection After 3 times P6 protection in 100 minutes will report H6
27 xP6 Inverter module protection After 3 times P6 protection in 30 minutes will report H4
34 xL3 Reserve
37 xL6 Reserve
39 xL8 Protection of the speed change between a moment before and after is>15Hz
40 xL9 Protection of the speed change between the setting speed and the actual speed >15Hz
Owner's manual
5
6. CONSTRAINT COOLING AND QUERY
MAIN BOARD
Constraint Cooling
(OUTDOOR UNIT)
Once pressing the forced cooling button (see the chart on the right),
all the indoor unit will be on forced cooling mode and the wind
speed is HIGH. Forced cooling button
Cool
Table.6-1
No Display content Note
Number of indoor units Displays when system standby
Inverter compressor frequency Displays when system is running
1 Outdoor unit address 0,1,2,3
2 Outdoor unit itself capacity 8,10,12,14,16
3 Modular outdoor unit qty. Available for main unit
4 Total capacity of outdoor unit Capacity requirement
5 Cooling capacity Auxiliary unit only display capacity of main mode
Owner's manual
6
The display contents as followings:
Normal display:
When standby, the high position displays the address of the outdoor
unit,and the low position displays the Qty. of indoor units
that can communicate with outdoor unit.When it is operating,it will display
the rotation frequency of the compressor.
Fan speed:
0-stop; 1~15 speed increase sequentially, 15 is the max. fan speed.
7. AFTER-SALES SERVICE
If the air conditioner was operate abnormally, please plug off the
power supply firstly, and contact with After-sales Center or Special
Distributor. For detail please refer to the attached accessory
Consumer Service Instruction.