You are on page 1of 6

Name: Abegail B.

Catindig Subject/Time/Day: EE13/1:30p – 3:00p/TF


Section: CEIT-04-701A Instructor: Engr. Jaymer G. Punzalan

1. Which of the following wires is not suitable for both dry and wet locations?

a. THHW
b. RH
c. XHHW
d. TW
THWN is a code for thermoplastic heat and water resistant which is suitable for use in both dry and
wet locations with a maximum temperature rating of 75ºC (167ºF).
The RH wire refers to “red heating” which means that this is the connection you need in order
to power the heating system of your air conditioning unit. Yes, even your air conditioning unit
has a heating system to keep the temperature in balance.
XHHW is an alphabetism or initialism which stands for "XLPE (cross-linked polyethylene) High Heat-
resistant Water-resistant." XHHW is a designation for a specific insulation material, temperature
rating, and condition of use (suitable for wet locations) for electrical wire and cable.
Type TW insulated wires are used for normal power applications up to 600 volts. They can be used
for installation in conduit and ducts, at temperatures down to -10oC(+14oF). Type TW insulated wire
are designed to operate at conductor temperatures of 60oC (140oF) in wet and dry locations.
(THERMOPLASTIC, WATER-RESISTANT WIRE)

2. The equipment grounding conductor of a branch circuit shall be identified by a


continuous __________ color.

a. Green
b. Black
c. White
d. Yellow
Wire-type equipment grounding conductors shall be bare or have insulation or covering that
is green with one or more yellow stripes. (NEC 2014 Code Language)
Ground wires channel that unintentional current to the earth so people aren't shocked.
Name: Abegail B. Catindig Subject/Time/Day: EE13/1:30p – 3:00p/TF
Section: CEIT-04-701A Instructor: Engr. Jaymer G. Punzalan
Name: Abegail B. Catindig Subject/Time/Day: EE13/1:30p – 3:00p/TF
Section: CEIT-04-701A Instructor: Engr. Jaymer G. Punzalan

3. Which of the following colors of insulation or marking are permitted to identify “hot”
phase conductors in conduit wiring methods?

a. Black, red, and blue for 120/208- volt systems


b. Yellow, orange, and brown for 277/480 – volt systems
c. Any colors except white, gray, or green
d. All of the above.
The introduction of the NEC clearly states that it is not intended to be a design manual, and
therefore creating a colour code for ungrounded or "hot" conductors falls outside the scope
and purpose of the NEC. However, it is a common misconception that "hot" conductor colour-
coding is required by the Code.

In the United States, colour-coding of three-phase system conductors follows a de facto


standard, wherein black, red, and blue are used for three-phase 120/208-volt systems, and
brown, orange or violet, and yellow are used in 277/480-volt systems. (Violet avoids conflict
with the NEC's high-leg delta rule.) In buildings with multiple voltage systems, the grounded
conductors (neutrals) of both systems are required to be separately identified and made
distinguishable to avoid cross-system connections. Most often, 120/208-volt systems use
white insulation, while 277/480-volt systems use grey insulation, although this particular
colour code is not currently an explicit requirement of the NEC.

4. According to the Philippine Electrical Code at an ambient temperature of 30°C, 8.0 nim2
copper conductors with the following insulation have the following ampacities: TW
insulation - 30 A; THW insulation - 45 A; for THHN insulation - 50 A. If each of these
insulated wires carry the same 40 amperes which will generate heat the fastest?

a. TW insulated wire
b. THW insulated wires
c. Each will generate heat at the same rate
d. THHN insulated wire
TW wire– Indicates a single conductor having flame-retardant, moisture-resistant
thermoplastic insulation. The wire is rated 60°C wet or dry.TW cable and wires are used
generally in building wiring, feeder and branch circuits, and internal secondary industrial
distribution.

5. Temporary electrical installations for holiday displays must be permanently removed


after which of the following time periods:

a. 31 days after installation


b. 60 days after installation
c. 90 days after installation
d. 31 days after the end of the event
Name: Abegail B. Catindig Subject/Time/Day: EE13/1:30p – 3:00p/TF
Section: CEIT-04-701A Instructor: Engr. Jaymer G. Punzalan

Again, one of the biggest requirements we must adhere to is the 90-day time constraint rule, as the
equipment is not intended for long term use. The longer lights stay up; the more likely these lights will
become damaged, leading to fire and shock hazards.

6. Open conductors shall be supported on which of the following:

I. Glass or porcelain knobs


II. Racks or brackets
Ill. Strain insulators

a. l or lll
b. l or ll
c. ll or lll
d. Any of the above
e. 2.25.1.12 Open-Conductor Supports.
f. Open conductors shall be supported on glass or porcelain knobs, racks, brackets, or strain
insulators.

Article 2.25 - Outside Branch Circuits And Feeders

7. Equipment for installation in hazardous locations must be tested and approved for use
according to the classification of the hazards involved. These are divided into __
groups.

a. 4
b. 3
c. 7
d. 6
Name: Abegail B. Catindig Subject/Time/Day: EE13/1:30p – 3:00p/TF
Section: CEIT-04-701A Instructor: Engr. Jaymer G. Punzalan

8. The earthing transformer is used

a. to avoid the harmonics in the transformers


b. to provide artificial neutral earthing where the neutral points of the three phase
system are not accessible
c. to improve the current capacity of the neutral wire
d. to decrease the rating of the relay
The earthing transformer provides an earth for the connections and transformers windings
at the generator voltage when the generator voltage circuit-breaker is open. This protection
is time delayed to grade with the generator stator earth fault protection which trips only the
generator voltage circuit-breaker.

9. In transformer, the purpose of breather is to

a. extracts moisture of the air.


b. To take insulating oil from conservator.
c. To provide cooling to the winding.
d. To provide insulation to the winding.

Transformer Breather Helps to Prevent Atmospheric Moisture and Reduce Maintenance Costs.
During the breathing cycle of a transformer, it is crucial to prevent atmospheric moisture from
entering the transformer, which can contaminate the oil.
Name: Abegail B. Catindig Subject/Time/Day: EE13/1:30p – 3:00p/TF
Section: CEIT-04-701A Instructor: Engr. Jaymer G. Punzalan

10. What is the main use of a zigzag transformer?

a. To step down voltage


b. To provide path to zero sequence currents
c. To stabilize .transformer sequence currents
d. To step down current

Zero-sequence (earth fault) current exists between the transformer's neutral to


the faulting phase. The purpose of a zigzag transformer in this application is to
provide a return path for earth faults on delta-connected systems.

Reference:
 Multivector- PEC Review Material - https://electricianphilippines.com/free-rme-reviewer-files/

You might also like