You are on page 1of 27

For Messrs.

NSCC

TECHNICAL PROPOSAL
of
VARIABLE FREQUENCY DRIVE (VFD)

TMEIC Asia Pte Ltd.


Motor & Drive Engineering Department
Tokyo, Japan

Please revise by each overseas affiliate.

(8) Date 2019/10/29


(7) Spec. No.
(6) Quote No. ADE90807-A
(5) Order No.
(4) Approved by Checked by Written by
(3)
(2)
(1)
Rev Date Remarks

SPEC-MVe2-E01 Rev.1
P-1

INDEX
Page

GENERAL CONDITIONS ............................................................................................................................... 2


1. SCOPE ....................................................................................................................................................................2
2. RULES AND STANDARDS...................................................................................................................................2
3. SCREW THREADS................................................................................................................................................2
4. UNITS ......................................................................................................................................................................3
5. LANGUAGE ............................................................................................................................................................3
6. DOCUMENTS TO BE SUBMITTED.....................................................................................................................3
7. COLOR TO BE PAINTED......................................................................................................................................3
8. SITE CONDITIONS ................................................................................................................................................4
9. DESIGN DETAIL ....................................................................................................................................................5
10. ELECTRICAL SOURCE ......................................................................................................................................5
11. TEST AND INSPECTION ....................................................................................................................................5
12. SPARE PARTS ....................................................................................................................................................5
13. PACKING ..............................................................................................................................................................5
14. WARRANTY .........................................................................................................................................................5
15. SCOPE OF SUPPLY ...........................................................................................................................................6
16. WORK EXCLUDED .............................................................................................................................................6
TECHNICAL SPECIFICATIONS .................................................................................................................... 7
1. VARIABLE FREQUENCY DRIVE ........................................................................................................................7
2. TOOL ....................................................................................................................................................................11
3. SPARE PARTS....................................................................................................................................................12
4. FACTORY WITNESS TEST : None specified ...................................................................................................13
5. SITE COMMISSIONING .....................................................................................................................................14
INTERFACE LIST........................................................................................................................................................15
THREE LINE DIAGRAM AND INTERFACE DIAGRAM..........................................................................................16
STRUCTURAL SPECIFICATION ..............................................................................................................................18
REFERENCE DRAWINGS ........................................................................................................................................21

SPEC-MVe2-E01 Rev.1
P-2

GENERAL CONDITIONS
1. SCOPE

This specification generally covers following scopes of electrical equipment which is supplied by TOSHIBA
MITSUBISHI-ELECTRIC INDUSTRIAL SYSTEMS CORPORATION (TMEIC).

1) Design
2) Manufacturing
3) Test
4) Inspection
5) Transportation

However, system design, such as power distribution system design, load study, relay coordination study etc. will be
out of our scope.

PLACE: Viet Nam


USER: NSCC

2. RULES AND STANDARDS

The following standards will be applied for all electrical equipment listed in this specification.

JIS: Japanese Industrial Standard


JEC: Standard of the Japanese Electrotechnical Committee
JEM: Standard of the Japan Electrical Manufacturers' Association
IEC: International Electrotechincal commission

VFD electrical performance: IEC61800-4, JEC


VFD test: IEC61800-4 routine test
Input transformer: IEC60076
Dimensions: IEC60072
Components and others: Manufacturer’s standard

3. SCREW THREADS

All bolts, nuts and screws will conform to the METRIC THREAD of ISO
(International Organization for Standardization).

SPEC-MVe2-E01 Rev.1
P-3
4. UNITS

SI system will be used for design and manufacturing of the equipment.

Length in: mm
Weight in: ton/kg
Temperature: Centigrade

5. LANGUAGE Please revise as needed


by each overseas affiliates.
English will be used.

6. DOCUMENTS TO BE SUBMITTED
PDF file (APPROVAL/FINAL)
* Technical specification 1/1
* Motor terminal drawings 1/1
* Outline and foundation drawing 1/1
* Schematic diagrams 1/1
* Spare parts list 1/1
* Accessories list 1/1
* Instruction manual for installation and maintenance 0/1
* Test record 0/1

* CAD data will not be submitted

7. COLOR TO BE PAINTED

Equipment RAL or Munsell notation

VFD Munsel 5Y7/1


Others Manufacturer's standard

Painting procedure will be manufacture’s standard.

SPEC-MVe2-E01 Rev.1
P-4
8. SITE CONDITIONS

The ratings of devices and equipment herein specified are based on the following site conditions.

* Ambient temperature 0 to 40 deg. C


Daily mean temperature 5 to 35 deg. C
Annual mean temperature 5 deg. C and 25 deg. C
* Altitude Less than 1000 m above sea level
* Relative humidity Between 5% and 85% (Non condensation)
* Relative humidity change Shall be 0.5% or less per hour
* Atmospheric pressure Within the range of 70kPa to 106kPa
* Vibration Frequency of 2Hz<f<9Hz: Amplitude 0.9mm or less
Frequency of 9Hz<f<100Hz: Acceleration 3m/s2 or less (0.3G)
* Area Non hazardous area
* Corrosive gas Sulfur dioxide (SO2): 0.1 mg/m3 or less
Hydrogen sulfide (H2S): 0.01 mg/m3 or less
Chloride gas (Cl2): 0.1 mg/m3 or less
Hydrochloric acid mist (HCl): 0.1 mg/m3 or less
Hydrogen fluoride (HF): 0.003 mg/m3 or less
Ammonia gas (NH3): 0.3 mg/m3 or less
Ozone (O3): 0.01 mg/m3 or less
Nitrogen oxide (NOx): 0.1 mg/m3 or less

Note: When cleaning the equipment room, please use a vacuum cleaner to prevent stirring up the dust.
Do not apply silicon wax to the floor in the equipment room. It may affect the electric contact.
After external cables (grounding wires, main circuit cables and control wires) are connected,
completely seal the cable lead-in holes with putty. If the cable lead-in holes are left unfilled, open air
will enter the equipment and may cause harm to the equipment.

SPEC-MVe2-E01 Rev.1
P-5
9. DESIGN DETAIL

Design covered by this specification is subject to minor modifications by us at the time of manufacture to meet the
latest practice and most efficient arrangement of apparatus.

10. ELECTRICAL SOURCE

The following power source shall be provided by others.

AC 6000V, 50Hz, 3-phase, three-wire for main circuit


AC 380V, 50Hz, 3-phase for control circuit & cooling fans
Voltage fluctuation : -10% to +10%
Frequency fluctuation : -5% to +5%

11. TEST AND INSPECTION

Test and inspection will be carried out at our works for each piece of machinery and equipment. Test records of
main equipment will be submitted. The performance test witnessed by the purchaser will be carried out at our works,
if requested. However, the necessary charges such as fare and accommodation, etc. shall be borne by the
purchaser.

12. SPARE PARTS

Only such spare parts as listed in this specification will be supplied.

13. PACKING

The equipment will be packed for exportation by ship. The special notation such as fragile, this side up, center of
gravity, weight, etc., where necessary, will be clearly described on each packing, together with tag number,
purchaser order number and brief description of the contents.

14. WARRANTY

(1) The Seller warrants that the Product shall be free from defects in design (other than a design made,
furnished or specified by the Buyer for which the Seller has disclaimed responsibility in writing), material and
workmanship for eighteen (18) months from the date of shipment or twelve (12) months from the date on
which the Product is put into operation, whichever period shall first expire, provided that the Buyer gives the
Seller written notice of any defect and satisfactory proof thereof promptly upon discovery of such defect but
in no case later that fifteen (15) days after expiration of the aforesaid warranty period.
(2) The Seller’s obligation under the aforesaid warranty shall be limited to, at the Seller’s option, (a) repairing,
(b) replacing or (c) supplying a replacement part for any part of the Product which, if properly installed, used
and maintained, proves defective owing solely to causes attributable to the Seller’s design, material or
workmanship.
(3) The Seller’s obligation under Paragraphs (1) and (2) hereof shall not apply to the Product or any part thereof
which is normally consumed in operation or has a normal life inherently shorter than the warranty period
stated herein.

SPEC-MVe2-E01 Rev.1
P-6

(4) The total liability of the Seller on any claim whether in contract, tort (including negligence) or otherwise,
arising out of, connected with or resulting from the performance or breach of any contract based upon the
Quotation shall not exceed the price of the Product or the value of any part thereof which gives rise to the
claim.
(5) In no event, whether as a result of breach of contract, warranty, alleged negligence or liability without fault, shall
the Seller be liable for special, indirect or consequential damages.
Please revise this item as needed
by each overseas affiliate.
15. SCOPE OF SUPPLY
1. VARIABLE FREQUENCY DRIVE 1 set
2. TOOL 1 set
3. SPARE PARTS 1 set
4. FACTORY WITHNESS TEST none specified
5.SITE COMMISSIONING 1 engineer (5 working days)
If Tool are not required, please delete this item.
16. WORK EXCLUDED

The following items are out of our scope, however TMEIC provide the technical assistance if necessary.

1) Electrical room heating, ventilation and air conditioning


2) Panel installation and internal connection between panels
3) Consumables required for installation and start-up
4) MV switchgear
5) LV switchgear, motor control center and distribution panel
6) Power and control wire, cable and wiring work external to the inverter
7) Operator control devices
8) Witness test
9) Combination test for each equipments
10) Erection
11) Cable selection and cable list
12) Cable From/To list
13) Any other equipment and system not listed in this specification

SPEC-MVe2-E01 Rev.1
P-7

TECHNICAL SPECIFICATIONS
1. VARIABLE FREQUENCY DRIVE

Quantity 1 set
Application Fan
Motor rating 6P - 1450kW -6000V - 50Hz - A
Load torque characteristic square-law load torque

Load GD2 TBD


Inverter type TMdrive-MVG2
Ratings
Transformer 1720kVA
Inverter
Capacity 2000kVA at 6000V
Output current 193A
Overload 125% for 1 min.
Voltage class Input :6000V, Output : 6000V
Output frequency 25 to 50Hz
Main circuit 3-phase 6000V - 50Hz
Control circuit 3-phase 380V - 50Hz (1kVA) (Internally provide)
Cooling fan circuit 3-phase 380V -50Hz
Input Transformer Dedicated for TMdrive-MVG2 use, Insulation class H with 3 taps, without
electrostatic shield
Control specifications
Converter Diode converter
Control method Multi-level Sinusoidal PWM control, V/f control (Open loop)
Frequency precision ±0.5% of max output frequency with analog input reference
Acc./Dec. time 0.1 to 3270 sec. (depend on GD2 of load and motor)
Main Protective Functions Current limit, Over-current, Over-voltage, Overload, Under-voltage,
CPU error, Cooling fan abnormal, Speed reference loss,
Cell inverter fault
Speed Reference By analog reference DC4 - 20 mA (Isolated)
Main Operation Functions Restart after instantaneous power interruption
(<2s as standard)
Operation under power loss (0-300ms, non-torque control)
Resonant frequency skip
Multiple acceleration / deceleration rates
Auto speed reduction for overload (Square torque load)
Speed reference loss: Trip, Deceleration trip, Speed lock
Serial Interface Profibus

SPEC-MVe2-E01 Rev.1
P-8

SPEC-MVe2-E01 Rev.1
P-9

Operation Board
Display LCD display (40 figures - 8 lines)
Key board Navigation Key Board, Controls Key board
3 LEDs (READY, RUN, FAULT/ALARM, DC BUS DISCHARGED )
Push buttons Interlock, Fault reset
PC Interface Ethernet LCD display (240x64 dots)
Main data displays
(Current, Frequency, etc. )
Navigation Keyboard

Mode display LED


READY
RUN
FAULT / ALARM Control Keyboard

Fault reset

Ethernet connector Interlock switch


Analog output signal pins

SPEC-MVe2-E01 Rev.1
P-10

VFD PAINTING SPEC

SPEC-MVe2-E01 Rev.1
P-11

2. TOOL

Quantity 1 set

Spare parts ( Tool ) are not quoted.

Please recommended these spare parts.


If these spare parts not required, delete this item.

SPEC-MVe2-E01 Rev.1
P-12

3. SPARE PARTS

Quantity 1 set

Spare parts are not quoted.

TMEIC recommend spare parts.


Without spare parts, it will take much time to repair damaged parts
and may cause system shut down for a long time, which is
not responsibility of TMEIC.
If there is no by-pass circuit, spare parts are essential.

SPEC-MVe2-E01 Rev.1
P-13

4. FACTORY WITNESS TEST : None specified

Period One day


(Only one unit)
Place Fuchu factory in Tokyo, Japan

VFD TEST ITEMS


1. GENERAL PROVISION
THIS INSPECTION PROCEDURE PRESCRIBE FOR TEST OF GENERAL EQUIPMENT
2. APPLIED STANDARD
1. JAPANESE INDUSTRIAL STANDARD・・・・・・・・・・・・・・・・・・JIS
2. STANDARDS OF JAPANESE ELECTRO TECHNICAL COMMITTEE ・・・・JEC
3. JAPAN ELECTRICAL MANUFACTURES STANDARDS ・・・・・・・・・・JEM
4. INTERNATIONAL ELECTRO TECHNICAL COMMISSION ・・・・・・・・・IEC
3. TEST ITEM
Factory Witness Test
No. TEST ITEM AND CONTENTS
test test record

1-1 GENERAL CONSTRUCTION CHECK ○ ― ○

1-2 PHYSICAL DIMENSION CHECK ○ ― ○

1-3 WIRING CHECK ○ ― ○

PARTS RATING, NAME PLATE & MARK OF


1-4 ○ ― ○
TERMINAL BLOCK CHECK

2-1 INSULATION RESISTANCE MEASUREMENT ○ ― ○

2-2 DIELECTRIC TEST ○ ― ○

3 CONTROL POWER-SUPPLY VOLTAGE SETTING ○ ― ○

4 SEQUENCE TEST ○ ― ○

RATING OUTPUT VOLTAGE TEST


5 ○ ― ○
RATING CURRENT TEST ※1

6 SIMULATION TEST ※2 ○ ― ○

7 ACCESSORIES & SPARE PARTS CHECK ○ ― ―

※1 Rating current test will be applied for each cell inverter, not for inverter system.
※2 A factory test motor will be used for simulation test. The motor will be driven without load.,

SPEC-MVe2-E01 Rev.1
P-14

5. SITE COMMISSIONING

Quantity 1 engineer (5 working days)


Work Pre-meeting with customer.
No-load test with motor uncoupled
Actual load test

Notes External cables and interface should be checked by customer beforehand.


Some technical helpers should be available at site.
De-coupling and re-coupling should be done by customer.
The final cost of dispatching SV should be adjusted by actual days.

Please revise this item as needed


by each overseas affiliate.

SPEC-MVe2-E01 Rev.1
P-15

INTERFACE LIST

Input Start/Stop signal Close at Run, Dry type contact DC24V-12mA


signals Open at Stop
Emergency Stop Open at Dry type contact DC24V-12mA
Signal (Motor coast down stop) Emergency Stop
Status of customer’s Close at CB close Dry type contact DC24V-12mA
Incoming CB
Status of customer's Close at CB close Dry type contact DC24V-12mA
Output CB
Status of customer's Close at CB close Dry type contact DC24V-12mA
Bypass CB
Speed reference - 4 - 20mA Input impedance
signal or = 10 ohm
0 - 10V Input impedance
= 1 Mohm
Output Inverter Ready Close at Dry type contact Note1), Note2)
signals signal Inverter ready
Run signal Close at Run Dry type contact Note1), Note2)
Open at Stop
Alam signal Close at Inverter Dry type contact Note1), Note2)
Alarm
Fault signal Close at Inverter Dry type contact Note1), Note2)
heavy fault
Trip signal for Close to trip Dry type contact Note1), Note2)
Incoming CB Incoming CB

Output CB ON signal Close at ON Dry type contact Note1), Note2)


Open at OFF
Output current - 4 - 20mA Load impedance
< 500 ohm
Output frequency - 4 - 20mA Load impedance
< 500 ohm

Note1) Contact Rating: max.AC220V-0.8A, max. DC110V-0.2A, or max.DC24V-1.5A


Note2) Contact of Ready signal and Run signal opens during power failure
Note3) This data is typical. As for details, we will discuss later.

SPEC-MVe2-E01 Rev.1
P-16

THREE LINE DIAGRAM AND INTERFACE DIAGRAM


If a letter is hard to look,
Please download the files of Single-line diagram from Replied Quotation List of IQS.

SPEC-MVe2-E01 Rev.1
P-17
Remarks:

1) Please provide an analog speed reference signal from the customer control system for inverter operation.
Since detail motor and load characteristics are not available, the inverter capacity is selected for this quotation
according to the motor capacity and current value specified. If detail studies of the applications results in
inverter capacity changes, appropriate price will be provided. It is assumed that the load is a standard
square-torque load.
2) It is assumed that motor acceleration will be performed under inverter rated capacity. If the load is a critical part
of customer process and require continuous running, it is recommended to install commercial power bypass
circuit in order to operate motor with commercial power in case of inverter failure.
3) 3/3.3/6/6.6kV output types are a front maintenance type construction, and 10/11kV output types are
front / rear maintenance. Therefore the maintenance spaces are required on the front and rear side
of the panels.
4) Shipping split of this MV inverter is between the transformer panel and the inverter panel.
5) External interface will be TMEIC standard shown in this specification.
6) External analog signals shall be isolated.
7) Display on the front door is TMEIC standard.
8) Cable entry shall be From bottom
9) Exhaust air duct provision is not provided.
10) Control source (3ph-380V-50Hz) shall be externally supplied.
11) External cabling shall follow TMEIC’s recommendation (See attached drawings).
Otherwise we are not responsible for any problem or technical issue.
12) By-pass circuit is recommended just in case of inverter failure.
13) If ride-through control and/or automatic restart are applied, all MV circuit breakers shall be of latched type.

SPEC-MVe2-E01 Rev.1
P-18

STRUCTURAL SPECIFICATION

Item TM-MVG2 Standard Remarks / Optional Specification


Protective construction IP30(except for fan opening)
Cooling Forced air cooling with fans on top
Panel structure Metal semi-closed, self-standing structure
Front door Handle position Right handle and left hinge Double door for panel wider than
1200mm
Hinge With hinge and locking bar
Door fixture Door of medium voltage panel is screwed Turn off the main power
on top and bottom two points.
The handle is auto-lock.
Structure

Door stopper Three-point locking bar(rod latch) Slide type


Handle DIRAK swing handle(padlockable)
Model number : 207-9006
Color : Black
KEY number : No.200
Thickness Front door 2.3mm
JEM-1459(1998) Ceiling plate 2.3mm
Bottom plate 2.3mm or more
Sideplate 2.3mm Steel screw
Back plate 2.3mm
Interior plate 1.6mm or more
Color Outside panel 5Y7/1
JEM-1135(1996) Inside panel 5Y7/1
Inter panel Galvanized, bare metal, no paint
Unit, implement Standard color of Maker
Painting

Measuring gauge N1.5


frame
Handle N1.5
Coating Outside panel LEATHER TONE
Inside panel LEATHER TONE
Inter panel Galvanized, bare metal, no paint
Lineup title Material Acrylic print
Color Black character on white base
Size Lineup title:31.5mm x 250mm
Customer ID:31.5mm x 63mm
Font Round Gothic type
Mounting Adhesive SUS screw as option
Location Front of control output panel
Position TMEIC standard
Name plate etc.

Application label On front panel Acrylic print


(for lamp, SW) Adhesive
Internal Plastic laminated paper, adhesive backed
parts(such as
MCCB etc)
Device No Plastic laminated paper, adhesive backed
Other Manufacturing Plastic laminated paper, adhesive backed
label
Rating label Plastic laminated paper, adhesive backed
PL label Plastic laminated paper, adhesive
backed(Language:English)
Company logo Resin plate(TEMIC) (size:255x60)

SPEC-MVe2-E01 Rev.1
P-19

Item TM-MVG2 Standard Remarks / Optional


Specification
Internal wiring

Wire color Control wire Power circuit : brack


(IEC Control circuit DC : blue
standard) Control circuit AC : red
Earth wire yellow-green spiral or stripe
gum electric Black Special wire, wire in cell
wire unit and
Shield wire Gray electric circuit are
excluded.
Wire type Control UL wire
wire(type)
Control 0.75mm2 Connector, printed
wire(size) wiring board and
unit are excluded.
Power cable KIP (EP rubber) wire
BUS Copper (no plating)
Crimp Non-insulated ring terminal
terminal
Wire marking Read from hookup-side
Tube marking

Terminal AC(3 phase) none specified


Phase DC No DC external cable connection
(IEC
standard)
External cable

BUS Type Heat shrink two or four hole connector Crimp terminal also
connection (comply to JIS-C2804) available
Position Bottom (lengthwise and breadthwise) Receptacle and
telephone jack are
excluded
External TMEIC Standard
terminal block
Cable entry Main From bottom
circuit(input)
Main From bottom
circuit(output)
Control circuit From bottom
Earth From bottom
Incoming cover Main circuit : steel 2.3mm
Others : steel 2.3mm

SPEC-MVe2-E01 Rev.1
P-20

Item TM-MVG2 Standard Remarks / Optional Specification


Interior

Cable support Support Provided


Bracket Not provided
Space heater Not provided
Lighting Not provided Only control panel
Outlet socket Not provided Only control panel
MCCB cover Provided
y
Accessar

Channel base Shape C-channel


Shipment With panels
Fixtures Anchor bolt (not supplied)

SPEC-MVe2-E01 Rev.1
P-21

REFERENCE DRAWINGS
1. If drawing is not clear, please download.
2. This outline drawing is for the equipment made by Fuchu. In case of overseas manufacturing, the outline drawing
is different, so please contact each manufacturing base.

SPEC-MVe2-E01 Rev.1
P-22

SPEC-MVe2-E01 Rev.1
P-23

SPEC-MVe2-E01 Rev.1
P-24

SPEC-MVe2-E01 Rev.1
P-25

SPEC-MVe2-E01 Rev.1
P-26

SPEC-MVe2-E01 Rev.1