TO 300/860-ATS-3A
D-860-4.01-44958-750
F1
POWER
300-MCC-3A-MBKR 300-CC-103A
ST 1200A POWER LOGIC
300-CS-144
METER
RS485 CONSTRUCTION NOTES:
1200/5A (300-SCP-2)
3 PM620 1. SITE CONTRACTOR TO RE-CONNECT CABLES AT NEW
(300-MCC-3C) DISCONNECT SWITCH CLOSED COUPLED ONTO NEW ACTUATOR.
PLC
300-CS-706 2. EXISTING CABLES SHALL BE TESTED PRIOR TO RECONNECTING PER
480-120V 2. EXISTING RECONNECTED CABLE SHALL BE TESTED PER
2A ENBRIDGE STANDARD FCS-010, SECTION 16.5.5.2.1.
47 PLC ENBRIDGE FCS-010 SPEC, SECTION 16.5.5.2.1.
3 2
300-MCC-3A 3. SITE CONTRACTOR TO INSTALL FREE ISSUED NEW UNIT WRAPPERS IN
3. CONTRACTOR
SECTION F6. TO PURCHASE AND INSTALL NEW MCC BUCKET.
F2 F3 F4 F5 SEE HOLD NOTE 2.
480V, 1200A CONTINUED
BELOW LEFT 12.A
NEUTRAL HOLD NOTES:
PAD 250A 250A 250A 250A 3A 3A 3A 3A 15A 15A 15A 15A
300A ST 30A ST 30A ST (300-TX-31-FBKR) 70A 1. MOV
MOVFLA
FLAAND
TO DISCONNECT SWITCH
BE CONFIRMED ONCE RATING
FINALTO BE CONFIRMED
VENDOR DRAWINGONCE
IS
PART OF MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP MCP CERTIFIED
AVAILABLE.VENDOR DATA IS AVAILABLE.
70A
300-CP-712
2. MCP
MCCAND FUSIBLE
BUCKET DISCONNECT
RATING SWITCH SIZES
TO BE CONFIRMED TO BEFINAL
ONCE CONFIRMED ONCE
VENDOR
4 4 4 4 1 1 1 1 1 1 1 1 CERTIFIED VENDOR DATA IS AVAILABLE.
(300-CP-104)
DRAWING IS AVAILABLE.
TO 300-MCC-3C,R5
D-300-4.01-45765-750
851-CP-011
300-CP-110
851-CP-010
203-CP-150
300-CP-120
300-CP-106
203-CP-149
300-CP-116
300-CP-108
203-CP-148
300-CP-118
300-CP-112
300-CP-114
PLC
203-CP-184
300-CC-104
49
300-TX-31
45KVA
480-120/208V
54
15 15 CCT
60 60 60 60 0.5 0.5 0.5 0.5 3.2 7.5 3.2 7.5
KW KW
PLC
AC DISTRIBUTION
CENTRE FEEDER
FOAM BUILDING
FOAM BUILDING
300-TK-5 MIXER
300-TK-6 MIXER
300-TK-7 MIXER
300-TK-8 MIXER
DILUENT VALVE
OUTLET VALVE
OUTLET VALVE
UNIT HEATER
UNIT HEATER
INLET VALVE
INLET VALVE
INLET VALVE
INLET VALVE
INLET VALVE
300-APU-X33
300-MCC-2A
300-TK-7 TO
300-TK-6 TO
300-TK-5 TO
203-V-1313
203-V-1314
203-V-1315
203-BP-3/4
203-BP-3/4
203-BP-3/4
203-V-1316
300-MX-51
300-MX-61
300-MX-71
300-MX-81
300-ACP-3
300-V-511
300-V-531
300-V-611
300-V-631
851-UH-1
851-UH-2
300-TK-5
300-TK-5
300-TK-6
300-TK-6
A/C UNIT
SPARE
FLUOR'S DESIGN RESPONSIBILITY IS
SOLELY LIMITED TO THE CONTENT
INSIDE THE REVISION CLOUD.
PLC
REFERENCE DRAWINGS
300-CP-126
300-CP-128
300-CP-137E
300-CP-136F
299-CP-001
203-CP-25
300-CP-122
300-CP-124
203-CP-152
203-CP-153
203-CP-154
203-CP-155
300-CP-142
300-CP-143
299-CP-002
300-CP-136
203-CP-830
300-CP-137
11 AS BUILT AS PER PSI FIELD VERIFICATION 2017-06-23 PSI/JD/SM PSI/JD/SM
(08 JUN 2017) TSS
10 AS BUILT AFE 1041911B90 (LBB) 2014-05-26 STANTEC STANTEC
STANTEC
9 REVISED AS-BUILT AS PER 2012-10-09 JPF JPF
FIELD VERIFICATION PROJECT JACOBS
30A 30A AS BUILT AFE 0641991C01 (KAV) 2007-06-25
8 DAF DAF
STANTEC
7 AS BUILT AFE 0541911C01 (JDH) AND 2006-06-13 DF DF
0441911C01 (JCN) STANTEC
15 15 REV REVISION DATE
CHK APPR
3.2 7.5 0.05 0.25 0.5 0.25 0.25 0.25 20 150 150 NO DESCRIPTION BY
KW KW
4.2KW 1.6KW 1.0KW 3.4KW 3.1KW COPYRIGHT © THIS DRAWING IS THE PROPERTY OF ENBRIDGE AND SHALL NOT BE REPRODUCED
4.6 12 0.18 1.5 2 FLA 1.2 FLA 1.2 FLA 1.2 FLA 22.25 165 FLA 165 FLA EITHER IN WHOLE OR IN PART WITHOUT PRIOR WRITTEN CONSENT OF ENBRIDGE.
FLA FLA FLA FLA FLA
CONST. D-300-4.03-40185-750
NOTE 1 & 2
DIESEL LOADING
DIESEL LOADING
ATHABASCA (AB) TERMINAL
OUTLET VALVE
OUTLET VALVE
OUTLET VALVE
OUTLET VALVE
UNIT HEATER
UNIT HEATER
INLET VALVE
INLET VALVE
INLET VALVE
INLET VALVE
SUMP PUMP
300-ESB-2
203-BSV-31
203-BSV-41
203-V-3210
203-V-4210
300-ESB-2
300-UH-11
300-ESB-2
300-UH-12
LIGHTING
300-V-711
300-V-731
300-V-811
300-V-831
203-BP-3
203-BP-3
203-BP-4
203-BP-4
203-SP-1
299-BP-2
299-BP-1
300-MCC-3A (FRONT), (480V)
300-TK-7
300-TK-7
300-TK-8
300-TK-8
FLOOD
PUMP
PUMP
AREA
D-300-4.01-40173-750 12.A