Voltage/Frequency Display
3. Settings c) Undervoltage Function
Trip History LED Data LED Description
a) Setting Display Undervoltage pickup occurs when any line to line or
1 trip voltage Undervoltage trip
1 U<< Undervoltage %
line to neutral voltage is less than [nominal voltage -
When the relay is not under tripping condition, U<< %], relay trips when delay time is elapsed. 3 trip voltage Overvoltage trip
pressing "RESET/MODE" can scroll through various 2 t << Undervoltage time delay 5 Ub Unbalance trip
settings. Function LED shows number or alphabet to d) Overvoltage
indicate which setting is being view as shown in 5 PL Phase loss trip
3 U>> Overvoltage %
Figure 4. Table 1 gives description of each setting. Overvoltage pickup occurs when any line to line or line 5 PS Phase sequence trip
4 t >> Overvoltage time delay to neutral voltage is more than [nominal voltage + U>>
t EST Test
Tip: To quickly jump back to voltage display during %], relay trips when delay time is elapsed.
setting display, press and hold “RESET/MODE” for 5 Unbalance % Table 3: Trip display
more than 1.5 seconds. e) Unbalance
6 t Unbalance time delay b) Trip Reset
Unbalance is calculated as: During tripping condition, press "RESET/MODE" to
b) Programming Setting 7 Phase Loss
reset the relay, the relay will reset if lower than
(Vmax-Vmin)/Vmin X 100% threshold. Manual reset threshold for U>> / U<<
Step 1: Press “RESET/MODE” until the Function LED 8 Phase Sequence
shows the required setting. and Unbalance is: Setting % - 1%.
A tstart Start time delay
Where Vmax is the maximum voltage among the 3
voltages. Vmin is the minimum voltage among the 3 Auto/Manual reset setting applies to U<<, U>>,
Step 2: Press “UP” and “DOWN” simultaneously to voltages.
enter programming mode. b Phase Unbalance tripping. Phase Sequence and Phase
Unbalance pickup occurs when unbalance is more loss is always auto reset.
The Function LED blinks to indicate that the relay is in c Nominal voltage than setting %, relay trips when delay time is elapsed.
programming mode. c) Auto reset level
d Relay R1 function Phase Sequence trip occurs when the phase
Step 3: Press “UP” or “DOWN” to select the desired sequence in any 2 or all of the lines are reversed. This sets the U<< and U>> auto reset level. Unba-
value. lance auto reset is fix to 2%.
E Relay R2 function
Phase Loss trip occurs when any voltage is less than
Step 4: To save the selected value, press “UP” and F Relay R2 type 70% of nominal. Eg1. if U>> is set to 10% and Auto reset level is set
“DOWN” simultaneously again. It will exit the to 2%, U>> trips when voltage >110%, U>> reset
programming mode with the Data LED displaying the when voltage <108%
g Auto/Manual reset f) Starting Delay
newly set value.
h Auto reset level Starting delay is the delay time for R1 to energized Eg2. if U<< is set to 20% and Auto reset level is set
To exit programming mode without saving the selected to 5%, U<< trips when voltage <80%, U<< reset
during power up under normal condition.
setting, press “RESET/MODE” once. Figure 4: Display mode when pressing when voltage >85%
Reset/Mode g) Relay Function Selection
If Auto reset % is equal or larger than U<< / U>> %,
Setting Function Setting Range Description During tripping, output contact relay R1 or R2 will be it will be automatically set to U<< / U>> % - 1%.
1 U<< Undervoltage off, 1-25 % Undervoltage % from nominal voltage de-energized/energized if the related tripping element
2 t<< Undervoltage delay 0.1-30 s Time delay for undervoltage is activated.
The setting is shown below: d) Trip Test
3 U>> Overvoltage off, 1-20 % Overvoltage % from nominal voltage
4 t>> Overvoltage delay 0.1-30 s Time delay for overvoltage
Trip test is used to simulate a tripping condition.
Code Phase OV UV Code : Displays on Data LED Press "TEST" button and hold for 1.5s, trip LED
5 Unbalance off, 3-20% Unbalance % 0 0 0 0 Phase: Unbalance, Phase Loss blinks. After 3.5 seconds, "tESt" will blink, R1 de-
6 t Unbalance delay 0.5-30 s Unbalance time delay 1 0 0 1 and Phase Sequence energized and R2 will operate dependent on relay
7 Phase loss off, on Phase loss disable/enable 2 0 1 0
OV : Overvoltage R2 type. Press "RESET/MODE" to reset.
Phase sequence disable/enable
UV : Undervoltage
8 Phase sequence off, on 3 0 1 1 e) Trip History Display
A t start Starting delay 0-999 s On time delay of R1 during power up 4 1 0 0
During Voltage and frequency display, Press
b Phase L-L, L-N L-L: Display and uses Line to Line voltage 5 1 0 1
“RESET/MODE” button to jump to Trip History
L-N: Display and uses Line to Neutral voltage 6 1 1 0 Display. Display shows the previous trip status with
0= De-activated
c Nominal Voltage 415V: 380,400,415V or Nominal voltage. Value depends on model and L-L or 7 1 1 1 a 'dot' blinking at Function LED. To clear trip history,
220,230,240V 1= Activated
220V: 220,230,240V or L-N setting press "UP" and "DOWN" simultaneously.
Table 2: Relay function selection
127,133,139V
110V: 100,110,120V or f) Trip Bypass Mode
58,64,69V 4. Trip To disable tripping due to incorrect setting, press
d Relay R1 function 0-7 *Refer to Table 2
a) Trip Display “RESET/MODE” and “TEST” simultaneously during
E Relay R2 function 0-7 *Refer to Table 2 power up. The Trip LED slow blink to indicate Trip
F Relay R2 type 0-1 0: Normally de-energized During pickup, Trip/Pickup LED blinks. During tripping Bypass Mode. Go into programming mode to correct
1: Normally energized condition, Trip/Pickup LED on. Function LED and Data the setting. Power off and on to reset the relay. The
g Auto/Manual reset 0=auto, 1=manual auto: auto reset when trip condition clear LED blinks with trip source as shown: relay will return to normal if no button is pressed for
manual: press "RESET/MODE" to reset longer than 2 minutes.
h Auto resert level 1-10 % Auto reset level for U<< and U>>