ETABS 17.0.

1 License #

ETABS Concrete Frame Design


ACI 318-08 Column Section Design

Column Element Details (Summary)

Level Element Unique Name Section ID Combo ID Station Loc Length (m) LLRF Type
PISO 2 C27 199 LCOL 15 X 25 Comb17 2.1 2.35 0.646 Sway Intermediate

Section Properties

b (m) h (m) dc (m) Cover (Torsion) (m)


0.15 0.25 0.05748 0.0273

Material Properties

E c (tonf/m²) f' c (tonf/m²) Lt.Wt Factor (Unitless) f y (tonf/m²) f ys (tonf/m²)


1208370.8 979.4 1 42184.18 42184.18

Design Code Parameters

ΦT Φ CTied Φ CSpiral Φ Vns Φ Vs Φ Vjoint


0.9 0.65 0.75 0.75 0.6 0.85

Axial Force and Biaxial Moment Design For P u , M u2 , M u3

Design P u Design M u2 Design M u3 Minimum M2 Minimum M3 Rebar Area Rebar %


tonf tonf-m tonf-m tonf-m tonf-m cm² %
20.5179 0.9154 -0.7784 0.405 0.4666 41.712457(O/S #2) 11.12(O/S #2)

Axial Force and Biaxial Moment Factors

C m Factor δ ns Factor δ s Factor K Factor Effective Length


Unitless Unitless Unitless Unitless m
Major Bend(M3) 0.364464 1 1 1 2.1
Minor Bend(M2) 0.253539 1 1 1 2.1

ESE DUITAMA.EDB Page 1 of 2 18/09/2023


ETABS 17.0.1 License #

Shear Design for V u2 , V u3

Shear V u Shear ΦV c Shear ΦV s Shear ΦV p Rebar Av /s


tonf tonf tonf tonf cm²/cm
Major, V u2 1.7416 1.6168 0.7614 1.7416 0.0125
Minor, V u3 0.9392 1.2949 0 0 0

Joint Shear Check/Design

Joint Shear Shear Shear Shear Joint Shear


Force V u,Top V u,Tot ΦV c Area Ratio
tonf tonf tonf tonf m² Unitless
Major Shear, V u2 N/A N/A N/A N/A N/A N/A
Minor Shear, V u3 N/A N/A N/A N/A N/A N/A

(6/5) Beam/Column Capacity Ratio

Major Ratio Minor Ratio


N/A N/A

O/S #2 Reinforcing required exceeds maximum allowed