Recommended Connection Wires between equipmnets

Item Connection Equipment Model Number Distance limitation

The distance limitation is 25 meters. If exceed 25 meters,


CAT 5e
we suggest to add power line RVV2*0.5.
1 From Indoor monitor --> Isolator module
The distance limitation is 40 meters. If exceed 40 meters,
SYV75-3+RVV7*0.3
we suggest to add power line RVV2*0.5.

RVV2*0.3 The distance limitation is 70~100 meters.


2 From Alarm sensor--> Indoor monitor
RVV4*0.5 (When sensor need power from
The distance limitation is 60~80 meters.
indoor monitor)

From Outdoor Station --> The last Isolator Module CAT 5e + RVV2*1.0 or RVV3*0.5+SYV75- For high building above 20 floor, we suggest use
3
(Signal bus) 5+RVV2*1.0 RVV3*0.5+SYV75-5+RVV2*1.0

Isolator module Power supply UPS-P--> isolator


4 RVV2*1.0 The distance limitation is 50 meters.
module

5 Outside network Bus RVVP3*0.75+SYV75-5 The distance limitation is 500 meters.

Outdoor Station Power supply UPS-DP-P -->


6 RVV3*1.0 The distance limitation is 50 meters.
Outdoor station

Outdoor Station Power supply UPS-DP-P --> First


7 RVV2*1.0 The distance limitation is 25 meters.
Isolator Moduel

8 Outdoor Station Power supply UPS-DP-P --> Lock RVV2*1.0 The distance limitation is 25 meters.

Remark:
1. If the distance is within 600 meters, SYV75-5 wire is adapt to the outside network bus line. When it is above 600 meters,
then use SYV75-7 wire instead.

2. When the building is above 15 floors, we suggest use "Section Connection" Method:
a. each 10~12 floors regard as one section.
b. Add 1pc Outdoor station isolator,Model: VA-2/4 (depends on how many sections in total).
c. Connect the first isolator module of each section to Outdoor isolator module.
d. Wires will be: CAT 5e .