Professional Documents
Culture Documents
BOQ - Electrical Work
BOQ - Electrical Work
1 Internal Electrical
a) Electrical Wiring Part
b) Distribution Boards
c) Rising Mains
d) Light Fixtures and Fans
e) Cable Trays
f) LT Cables & Terminations for buildings
g) UPS
h) Earthing & Lightning Protection
i) Building Panels
2 External Electrical
a) External Lighting
b) Transformers
c) DG System
d) Bus Ducts
e) HT Panels
f) LT Panels
g) External Cables & Terminations
QUANTITY DETAILS FOR ELECTRICAL WIRING ITEMS & DISTRIBUTION BOARDS AND RELATED ITEMS
Sl No. Area
Gr.C Primary point Gr.B Primary point 8.5 Mtr Long Primary point Gr.A Secondary point Gr.C Secondary point Gr.B Secondary point Group Controlled Group Controlled Group Controlled
Points from DB Points from DB Points from DB
(Gr. C @ 5 Mtr) (Gr. B @ 4 Mtr) (Gr. A @ 3 Mtr)
with Steel with Steel with Steel
Conduits Conduits Conduits
(Item No. 7a) (Item No. 7b) (Item No. 7c)
Steel PVC Steel PVC Steel PVC Steel PVC Steel PVC Steel PVC
(Item No. 6a) (Item No. 1a) (Item No. (Item No. 1b) (Item No. (Item No. 1c) (Item No. 3c) (Item No. (Item No. 3b)
6b) 6c) 3a)
BOQ ELECTRICAL WIRING & BOQ ELECTRICAL WIRING & BOQ ELECTRICAL WIRING & BOQ ELECTRICAL WIRING & BOQ ELECTRICAL WIRING & BOQ ELECTRICAL WIRING & BOQ ELECTRICAL WIRING & EARTHING
EARTHING EARTHING EARTHING EARTHING EARTHING EARTHING
A. Second Basement :
B. First Basement :
Stairs for both towers -- 12 Nos
Store Rooms for Both Towers 8 8
Staircase Lobbies north and south 24
Sides for both towers
Staircase Lobbies west and east 8
Sides for both towers
2.5 Mtr Wide Passages for both 112
towers
4.0 Mtr Wide Passages North & 28
South with service lobbies for
both towers
4.0 Mtr Wide Passages East & 20
West for both towers
3.5 Mtr Wide lobby for both 64
towers
Parking Lots 442
6 Mtr Driveway
Total 1st Basement 8.00 8.00 - - - - 8.00 442.00 248.00
C. Ground Floor:
Stairs for both towers -- 12 Nos
Store Rooms for Both Towers 4 4
Gents Toilet for both towers 12 40
Ladies Toilet for both towers 2 2 18
2.5 Mtr Wide Passages for both 112
towers
4.0 Mtr Wide Passages North & 28
South with service lobbies for
both towers
4.0 Mtr Wide Passages East & 20
West for both towers
3.5 Mtr Wide lobby for both 64
towers
Reception 8 32
Parking Lot 350
Driveways
Total Ground Floor 26.00 6.00 - - - 90.00 - 350.00 224.00
D. 1st Floor :
Stairs for both towers -- 12 Nos
Store Rooms for Both Towers 4 4
Gents Toilet for both towers 16 80
Ladies Toilet for both towers 14 68
2.5 Mtr Wide Passages for both 112
towers
4.0 Mtr Wide Passages North & 28
South with service lobbies for
both towers
QUANTITY DETAILS FOR ELECTRICAL WIRING ITEMS & DISTRIBUTION BOARDS AND RELATED ITEMS
Sl No. Area
Gr.C Primary point Gr.B Primary point 8.5 Mtr Long Primary point Gr.A Secondary point Gr.C Secondary point Gr.B Secondary point Group Controlled Group Controlled Group Controlled
Points from DB Points from DB Points from DB
(Gr. C @ 5 Mtr) (Gr. B @ 4 Mtr) (Gr. A @ 3 Mtr)
with Steel with Steel with Steel
Conduits Conduits Conduits
(Item No. 7a) (Item No. 7b) (Item No. 7c)
Steel PVC Steel PVC Steel PVC Steel PVC Steel PVC Steel PVC
(Item No. 6a) (Item No. 1a) (Item No. (Item No. 1b) (Item No. (Item No. 1c) (Item No. 3c) (Item No. (Item No. 3b)
6b) 6c) 3a)
TOTAL TOWER AREA 3,914.00 8,448.00 22.00 1,728.00 - - - - - - - 11,162.00 16.00 1,234.00 4,304.00
QUANTITY DETAILS FOR ELECTRICAL
QUANTITY DETAILS
WIRING FOR
ITEMS
ELECTRICAL
& DISTRIBUTION
WIRINGBOARDS
ITEMS &AND
DISTRIBUTION
RELATED ITEMS
BOARDS AND RELATED ITEMS
Group Controlled Twin Twin MCB Isolator with Switch Socket Switch Socket Switch Socket Switch Socket Submain / Circuit Main Submain / Circuit Main Submain / Circuit Main
Points from DB Controlled Controlled Enclosure , with 16- Combination Sets Combination Sets Combination Sets Combination Sets 3R X 2.5 Sqmm 3R X 4.0 Sqmm 3R X 6.0 Sqmm
(Long @ 8.5 Mtr) Light Points Light Points 32 Amp DP Isolator of (5-6 Amp Socket of (6/16 Amp of (2 Nos 6 Amp of (2 Nos 6/16 Amp
with Steel with PVC with Steel + 5-6 Amp Switch) Socket + 16 Amp Sockets + 2 Nos 6 Sockets + 2 Nos 16
Conduits Conduits Conduits Item Nos. 7.a & 10a (Item No. 10a) Switch) Amp Switches) Amp Switches)
(Item No. 7d) (Item No. 4) (Item No. 8) (Item No. 10b) (Item No. 10c) (Item No. 10d)
PVC Conduit Steel Conduit PVC Conduit Steel Conduit PVC Conduit Steel Conduit
(Item no. 5a) (Item No. 9a) (Item no. 5b) (Item No. 9b) (Item no. 5c) (Item No. 9c)
BOQ ELECTRICAL WIRING & EARTHING BOQ ELECTRICAL WIRING & BOQ For Distribution BOQ ELECTRICAL WIRING & EARTHING BOQ ELECTRICAL WIRING & EARTHING BOQ ELECTRICAL WIRING & EARTHING BOQ ELECTRICAL WIRING & EARTHING
EARTHING Boards
A. Second Basement :
B. First Basement :
Stairs for both towers -- 12 Nos 24 144
Store Rooms for Both Towers 696 696
Staircase Lobbies north and south 4 120
Sides for both towers
Staircase Lobbies west and east 8 4 140
Sides for both towers
2.5 Mtr Wide Passages for both 12 720
towers
4.0 Mtr Wide Passages North & 4 220
South with service lobbies for
both towers
4.0 Mtr Wide Passages East & 4 220
West for both towers
3.5 Mtr Wide lobby for both 8 560
towers
Parking Lots 43 2365
6 Mtr Driveway 147 18 810
Total 1st Basement 179.00 - - 97.00 - 5,995.00 - 696.00 - -
C. Ground Floor:
Stairs for both towers -- 12 Nos 24 144
Store Rooms for Both Towers 696 696
Gents Toilet for both towers 210
Ladies Toilet for both towers 270
2.5 Mtr Wide Passages for both 12 780
towers
4.0 Mtr Wide Passages North & 4 240
South with service lobbies for
both towers
4.0 Mtr Wide Passages East & 4 240
West for both towers
3.5 Mtr Wide lobby for both 8 520
towers
Reception 50
Parking Lot 35 1225
Driveways 135 14 560
Total Ground Floor 159.00 - - 77.00 - 4,935.00 - 696.00 - -
D. 1st Floor :
Stairs for both towers -- 12 Nos 24
Store Rooms for Both Towers
Gents Toilet for both towers
Ladies Toilet for both towers
2.5 Mtr Wide Passages for both 12 144
towers
4.0 Mtr Wide Passages North & 4 260
South with service lobbies for
both towers
QUANTITY DETAILS FOR ELECTRICAL
QUANTITY DETAILS
WIRING FOR
ITEMS
ELECTRICAL
& DISTRIBUTION
WIRINGBOARDS
ITEMS &AND
DISTRIBUTION
RELATED ITEMS
BOARDS AND RELATED ITEMS
Group Controlled Twin Twin MCB Isolator with Switch Socket Switch Socket Switch Socket Switch Socket Submain / Circuit Main Submain / Circuit Main Submain / Circuit Main
Points from DB Controlled Controlled Enclosure , with 16- Combination Sets Combination Sets Combination Sets Combination Sets 3R X 2.5 Sqmm 3R X 4.0 Sqmm 3R X 6.0 Sqmm
(Long @ 8.5 Mtr) Light Points Light Points 32 Amp DP Isolator of (5-6 Amp Socket of (6/16 Amp of (2 Nos 6 Amp of (2 Nos 6/16 Amp
with Steel with PVC with Steel + 5-6 Amp Switch) Socket + 16 Amp Sockets + 2 Nos 6 Sockets + 2 Nos 16
Conduits Conduits Conduits Item Nos. 7.a & 10a (Item No. 10a) Switch) Amp Switches) Amp Switches)
(Item No. 7d) (Item No. 4) (Item No. 8) (Item No. 10b) (Item No. 10c) (Item No. 10d)
PVC Conduit Steel Conduit PVC Conduit Steel Conduit PVC Conduit Steel Conduit
(Item no. 5a) (Item No. 9a) (Item no. 5b) (Item No. 9b) (Item no. 5c) (Item No. 9c)
TOTAL TOWER AREA 901.00 - - 719.00 6,912.00 512.00 6,784.00 128.00 28,448.00 32,669.00 100,736.00 2,088.00 10,368.00 -
QUANTITY DETAILS FOR ELECTRICAL
QUANTITY
WIRING
DETAILS
ITEMSFOR
& DISTRIBUTION
ELECTRICAL WIRING
BOARDSITEMS
AND &
RELATED
DISTRIBUTION
ITEMS BOARDS AND RELATED ITEMS
g Sl No. Area
Submain / Circuit Main Submain / Circuit Main Submain / Circuit Main Submain / Circuit Main Submain / Circuit Main Distribution Boards Distribution Distribution Distribution Distribution
6R X 2.5 Sqmm 2R X 10 + 1R X 6 Sqmm 2R X 16 + 1R X 6 Sqmm 4R X 10 + 2R X 6 Sqmm 4R X 16 + 2R X 6 Sqmm (SPN 12 Way) Boards (SPN 16 Boards (HTPN 8 Boards Boards
Way) Way) (HTPN 12 (VTPN 12
Way) Way)
PVC Conduit Steel Conduit PVC Conduit Steel Conduit PVC Conduit Steel Conduit PVC Conduit Steel Conduit PVC Conduit Steel Conduit Item No. 1e Item No. 1g Item No. 2e Item No. 2f Item No. 3d
(Item no. 5d) (Item No. 9d) (Item No. 9e) (Item No. 9f) (Item No. 9i) (Item No. 9j)
BOQ ELECTRICAL WIRING & EARTHING BOQ ELECTRICAL WIRING & EARTHING BOQ ELECTRICAL WIRING & EARTHING BOQ ELECTRICAL WIRING & EARTHING BOQ ELECTRICAL WIRING & EARTHING BOQ FOR DISTRIBUTION BOARDS
A. Second Basement :
B. First Basement :
Stairs for both towers -- 12 Nos
Store Rooms for Both Towers
Staircase Lobbies north and south
Sides for both towers
Staircase Lobbies west and east
Sides for both towers
2.5 Mtr Wide Passages for both
towers
4.0 Mtr Wide Passages North &
South with service lobbies for
both towers
4.0 Mtr Wide Passages East &
West for both towers
3.5 Mtr Wide lobby for both
towers
Parking Lots
6 Mtr Driveway
Total 1st Basement - - 240.00 - 255.00 - 160.00 - 320.00 3.00 3.00 2.00 2.00 2.00
C. Ground Floor:
Stairs for both towers -- 12 Nos
Store Rooms for Both Towers
Gents Toilet for both towers
Ladies Toilet for both towers
2.5 Mtr Wide Passages for both
towers
4.0 Mtr Wide Passages North &
South with service lobbies for
both towers
4.0 Mtr Wide Passages East &
West for both towers
3.5 Mtr Wide lobby for both
towers
Reception
Parking Lot
Driveways
Total Ground Floor - - 240.00 - 255.00 - 160.00 - 320.00 3.00 3.00 2.00 2.00 2.00
D. 1st Floor :
Stairs for both towers -- 12 Nos
Store Rooms for Both Towers
Gents Toilet for both towers
Ladies Toilet for both towers
2.5 Mtr Wide Passages for both
towers
4.0 Mtr Wide Passages North &
South with service lobbies for
both towers
QUANTITY DETAILS FOR ELECTRICAL
QUANTITY
WIRING
DETAILS
ITEMSFOR
& DISTRIBUTION
ELECTRICAL WIRING
BOARDSITEMS
AND &
RELATED
DISTRIBUTION
ITEMS BOARDS AND RELATED ITEMS
g Sl No. Area
Submain / Circuit Main Submain / Circuit Main Submain / Circuit Main Submain / Circuit Main Submain / Circuit Main Distribution Boards Distribution Distribution Distribution Distribution
6R X 2.5 Sqmm 2R X 10 + 1R X 6 Sqmm 2R X 16 + 1R X 6 Sqmm 4R X 10 + 2R X 6 Sqmm 4R X 16 + 2R X 6 Sqmm (SPN 12 Way) Boards (SPN 16 Boards (HTPN 8 Boards Boards
Way) Way) (HTPN 12 (VTPN 12
Way) Way)
PVC Conduit Steel Conduit PVC Conduit Steel Conduit PVC Conduit Steel Conduit PVC Conduit Steel Conduit PVC Conduit Steel Conduit Item No. 1e Item No. 1g Item No. 2e Item No. 2f Item No. 3d
(Item no. 5d) (Item No. 9d) (Item No. 9e) (Item No. 9f) (Item No. 9i) (Item No. 9j)
TOTAL TOWER AREA - - - 7,952.00 - 7,997.00 - 14,944.00 - 22,656.00 137.00 137.00 134.00 134.00 134.00
INTERNAL ELECTRICAL _ ELECTRICAL WIRING & EARTHING
Electrical Wiring
1 SITC of Point Wiring with PVC Conduit & 3 X 1.5 Sqmm FRLS PVC Cu wires, Metal
Box, Modular plate , Switches etc as required complete as per specification.
-
3 SITC of Secondary Point Wiring , including cost of 3X1.5 Sqmm FRLS PVC Cu -
Wires, PVC conduit 20 mm ,
a) Group C Each -
b) Group B Each 11,162.00
c) Group A Each -
-
4 SITC of Twin Control Point with PVC conduit 20 mm , 3 X 1.5 Sqmm FRLS PVC Cu Each -
Wires , Metal Box, Modular plate , 2 way modular Switch etc as required complete
as per specification.
-
5 Sub Main and Circuit Main with PVC conduit of suitable size and accessories . -
a) 3X 2.5 Sqmm RMT 28,448.00
b) 3X 4.0 Sqmm RMT 100,736.00
c) 3X6.0 Sqmm RMT 10,368.00
d) 6X 2.5 Sqmm RMT -
e) 4X 4.0 Sqmm + 2 X 4.0 Sqmm RMT -
f) 4X 6.0 Sqmm + 2 X 6.0 Sqmm RMT -
g) 4X 16.0 Sqmm + 2 X 6.0 Sqmm RMT -
-
6 SITC of Point Wiring with Steel conduit & 3 X 1.5 Sqmm FRLS PVC Cu wires, Metal -
Box, Modular plate , Switches etc as required complete as per specification.
10 Supplying and fixing the following Modular Switch Socket combinations with
suitable size of Metal boxes and modular front plates etc.
a) Switch Socket Combination Sets of (5-6 Amp Socket + 5-6 Amp Switch) Sets 6,912.00
b) Switch Socket Combination Sets of (6/16 Amp Socket + 16 Amp Switch) Sets 512.00
c) Switch Socket Combination Sets of (2 Nos 6 Amp Sockets + 2 Nos 6 Amp Switches) Sets 6,784.00
d) Switch Socket Combination Sets of (2 Nos 6/16 Amp Sockets + 2 Nos 16 Amp Sets 128.00
Switches)
11 Supply and laying of following sizes PVC Conduits along with accessories.
12 Supply and laying of following sizes Steel Conduits along with accessories.
a) 20 mm dia 500
b) 25 mm dia 750
c) 32 mm dia 400
3 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including Sets 132
accessories, and providing masonry enclosure with cover plate having locking
arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt
as required.
4 Supply and laying GI Earth strips of following sizes in ground including excavation
and backfilling of the earth as required.
50 X 8 GI Strip Rmtr 1043
75 X 8 GI Strip Rmtr 760
50 X 6 GI Strip Rmtr 4752
5 Supply and laying GI Earth strips / wires of following sizes along with cablle
trays / on walls or ceilings including proper clipping with necessary hardwares as
required.
50 X 6 GI Strip Rmtr 310
25 X 6 GI Strip Rmtr 3495
25 X 3 GI Strip Rmtr 250
8 swg GI Wire Rmtr 10636
6 Supply and laying Cu Earth strips of following sizes in ground including excavation
and backfilling of the earth as required.
25 X 5 Cu Strip Rmtr 500
50 X 5 Cu Strip Rmtr 320
7 Supply and laying GI Earth strips / wires of following sizes along with cablle
trays / on walls or ceilings including proper clipping with necessary hardwares as
required.
25 X 5 Cu Strip Rmtr 350
50 X 5 Cu Strip Rmtr 320
8 Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, Sets 16
G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate
including holes etc. complete as required.
9 Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for Sets 1760
lightning conductor complete as required.(For horizontal run)
10 Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for Sets 1152
lightning conductor complete as required.(For verical run)
11 Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm Sets 16
long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as
required.
12 Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in Mtr 320
ground as required.
Total
1 SITC of Point Wiring with PVC Conduit & 3 X
1.5 Sqmm FRLS PVC Cu wires, Metal Box,
Modular plate , Switches etc as required
complete as per specification.
Group C Nos 48.00
Group B Nos 63.00
-
2 SITC of Secondary Point Wiring , including Nos 220.00
cost of 3X1.5 Sqmm FRLS PVC Cu Wires, PVC
conduit 20 mm ,---Group B
-
3 Circuit Main Wiring with PVC Conduit -
a) 3X 2.5 Sqmm Mtr 2,060.00
b) 3X 4.0 Sqmm Mtr 1,125.00
c) 3X6.0 Sqmm Mtr 90.00
-
4 Supplying and fixing the following Modular -
Switch Socket combinations with suitable size
of Metal boxes and modular front plates etc.
b) 40 Amps , 30 mA Each
c) 63 Amps , 30 mA Each
d) 100 Amps , 30 mA Each
e) 25 Amps , 100 mA Each
f) 40 Amps , 100 mA Each
g) 63 Amps , 100 mA Each
h) 100 Amps , 100 mA Each
i) 25 Amps , 300 mA Each
j) 40 Amps , 300 mA Each
k) 63 Amps , 300 mA Each
l) 100 Amps , 300 mA Each
1 BEE 5 star rated, ceiling fans of the following sizes with Brush Less Direct Current -
(BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos.
canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9,
Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350
RPM (tolerance as per IS : 374-2019), THD less than 10%, Provision of remote or
electronic regulator unit for speed control and all remaining accessories including
safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation
resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC
Supply, earthing etc. complete as required.
-
2 300 mm dia heavy duty metallic exhaust fans with finz and birds screen Sets 576.00
QUANTITIES OF LIGHT FIXTURES & FANS
Drawing Title Name of Location Quantities of Light Fixtures Quantities of Fans
Wall Mounted Wall Mounted Spot Light Ceiling Mounted Recess Mounted Down Fully diffused recessed 1200 mm Wall Mirror Light 600 mm Wall 1200 mm Sweep 900 mm Exhaust Fans
Tube Light Tube Light Tube Light Light mounted 1'X4' LED Light Bracket Light Ceiling Fans Sweep
(Normal) (Emergency) Fixture @ Ceiling Level luminaire with high Ceiling Fans
transmitive diffuser--43W
Total 2307 70 2884 56 12428 3584 596 512 1024 2304 576
CABLE TRAY
1 Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm Rmt 1408
thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates &
hardware in approved manner.
2 Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm Rmt 896
thick) GI sheet of 200 mm width & 75 mm height complete with necessary coupler plates &
hardware in approved manner.
3 Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm Rmt 288
thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates &
hardware in approved manner.
4 Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm Rmt 160
thick) GI sheet of 400 mm width & 75 mm height complete with necessary coupler plates &
hardware in approved manner.
5 Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm Rmt 64
thick) GI sheet of 500 mm width & 75 mm height complete with necessary coupler plates &
hardware in approved manner.
6 Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm Rmt 64
thick) GI sheet of 600 mm width & 75 mm height complete with necessary coupler plates &
hardware in approved manner..
7 Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm Rmt 64
thick) GI sheet of 750 mm width & 75 mm height complete with necessary coupler plates &
hardware in approved manner..
8 Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm Rmt 192
thick) GI sheet of 1000 mm width & 75 mm height complete with necessary coupler plates
& hardware in approved manner..
9 Hot deeped Galvanised cover suitable for perforated type Cable tray manufactured from Rmt 12
16 swg (1.6 mm thick) GI sheet of 150 mm width & 15 mm height complete with necessary
hardware in approved manner.
10 Hot deeped Galvanised cover suitable for perforated type Cable tray manufactured from Rmt 12
16 swg (1.6 mm thick) GI sheet of 200 mm width & 15 mm height complete with necessary
hardware in approved manner.
11 Hot deeped Galvanised cover suitable for perforated type Cable tray manufactured from Rmt 12
16 swg (1.6 mm thick) GI sheet of 300 mm width & 15 mm height complete with necessary
hardware in approved manner.
12 Hot deeped Galvanised cover suitable for perforated type Cable tray manufactured from Rmt 24
16 swg (1.6 mm thick) GI sheet of 400 mm width & 15 mm height complete with necessary
hardwere in approved manner.
13 Hot deeped Galvanised cover suitable for perforated type Cable tray manufactured from Rmt 24
16 swg (1.6 mm thick) GI sheet of 500 mm width & 15 mm height complete with necessary
hardware in approved manner
14 Hot deeped Galvanised Ladder Type Cable Tray manufactured from 16 swg (1.6 mm Rmt 48
thick) GI sheet of 600 mm width & 100 mm height comprising all required standard
Acessories..
15 Hot deeped Galvanised Ladder Type Cable Tray manufactured from 16 swg (1.6 mm Rmt 50
thick) GI sheet of 750 mm width & 100 mm height comprising all required standard
acessories..
16 Hot deeped Galvanised Ladder Type Cable Tray manufactured from 16 swg (1.6 mm Rmt 75
thick) GI sheet of 1000 mm width & 100 mm height comprising all required standard
acessories..
DETAIL OF UPS
Item No Discription of Items Unit Qty As per
Consultant's BOQ
1
2
DG SET
Discription of Items
Providing, Installing, Testing and Commissioning of ‘Silent Type’ Diesel Generating set alongwith having
Prime Power Rating of following KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for
50 Hz, 3 phase system & for 0.85 Load Factor and consisting of the followings:Diesel Engine Diesel engine 4
stroke water cooled, selectric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 40
Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10%
over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all
the required accessories.Engine mounted Instrument Panel fitted with and having digital display for
following:(i) Start-stop switch with key(ii) Water temperature indication(iii) Lubrication oil pressure
indication(iv) Lubrication oil temperature indication(v) Battery charging indication(vi) RPM
indication(vii) Over speed indication(viii) Low lub. Oil trip indication(ix) Engine Hours
indicationAlternator Synchronous alternator rated at following KVA, 415 volts at 1500 RPM, 3 phase 50 Hz,
AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall
be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR
conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class- F/H insulation ( Class-H
insulation and temp. rise limited to class-F)
Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of
MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation
and vibration isolation arrangement as per recommendations of manufacturer.
Fuel Tank: Daily service fuel tank of 990 liters capacity fabricated out of 3 mm thick M.S. sheet complete
with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of
suitable dia. Complete with valves, level indications & accessories as required as per specifications.
Exhaust System: Dry exhaust mainfold with hospital exhaust silencer and catalytic convertor.
Starting System:12V/24V DC starting system comprising of starter motors: voltage regulator and
arrangement for initial excitation complete with suitable nos. of batteries (25 plates, 180 Amp. Hour
capacity lead acid type) as required as per specifications.
Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine &
alternator, extraction, discharging hot air in to the atmosphere as per specifications.Fabricating, Installing,
Testing & Commissioning of automatic mains failure control including auto by-pass panel, suitable for
following KVA silent type DG set complete with relays, timers, set of CTs for metering & protection and
energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH &
provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF
panel to diesel engine and elsewhere if required, all complete and inter locking including the
following:Auto/Manual/Test/Off selector switchEmergency push buttons Suitable CTs Energy analyser
unit to indicate current voltage frequency power factor and KWH Indicating lamps for load on mains and
load on set Fuse for instruments Battery charger, complete with transformer/ rectifier, D.C. voltmeter and
ammeter, selector switch for trickle, off and boost and current adjustment.Main supply failure monitor
Supply failure timer Restoration timer Control unit with three impulse automatic engine start/stop and
failure to start lockout. Impulse counter with locking and reset facility.ON/OFF/Control circuit switch with
indicatorAudio/Video annunciation for(i) High water temperature(ii) Low lubricating oil pressure(iii)
Engine over speed(iv) Engine fails to start(v) Full load/maximum load warning
1010 KVA
Supplying and fixing exhaust gas piping of suitable dia. welded black MS, B Class pipe
conforming to IS:3589 cut to required lengths and installed with necessary bends, supports and
clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/Rockwool,50
mm thick wiremesh & aluminum cladding etc., as required as per specifications.
Unit Qty
Sets 3
Lot 3
BOQ FOR RISING MAINS & BUS DUCTS
1 Following capacity Sandwich Type Rising Mains / Bus Trunking for use on 3 phase 4 wire 415 volts,
50Hz A.C. supply with metal clad enclosure having IP-65 (for outdoor) and IP-54 (for indoor) rating
after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in
convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at,
nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each
floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous
earthing with 2 Nos aluminium strip of size 50X6mm (one on each side) including, G.I. clamping
brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required
(Isc - 50 KA/Sec)
a) 3200A, 4P, 415V Sandwich Aluminium Bustrunking with 2 Runs Of 50x6mm Aluminium earthing Mtr 16
Straight Length – Indoor ( IP 55 )
b) 3200A, 4P, 415V Sandwich Aluminium Bustrunking with 2 Runs Of 50x6mm Aluminium earthing Mtr
Straight Length – Outdoor ( IP 65 with canopy )
c) 2500A, 4P, 415V Sandwich Aluminium Bustrunking with 2 Runs Of 50x6mm Aluminium earthing Mtr 24
Straight Length – Indoor ( IP 55 )
d) 2000A, 4P, 415V Sandwich Aluminium Bustrunking with 2 Runs Of 50x6mm Aluminium earthing Mtr 304
Straight Length – Indoor ( IP 55 )
e) 1600A, 4P, 415V Sandwich Aluminium Bustrunking with 2 Runs Of 50x6mm Aluminium earthing Mtr 24
Straight Length – Indoor ( IP 55 )
f) 1250A, 4P, 415V Sandwich Aluminium Bustrunking with 2 Runs Of 50x6mm Aluminium earthing Mtr 24
Straight Length – Indoor ( IP 55 )
g) 1000A, 4P, 415V Sandwich Aluminium Bustrunking with 2 Runs Of 50x6mm Aluminium earthing Mtr 144
Straight Length – Indoor ( IP 55 )
h) 400A, 4P, 415V Sandwich Aluminium Bustrunking with 2 Runs Of 50x6mm Aluminium earthing Mtr 24
Straight Length – Indoor ( IP 55 )
2 3200 A , 415 V End feed Unit suitable for above rising main and 3200 A 4P ACB , but without ACB Sets 4
2000 A , 415 V End feed Unit suitable for above rising main and 3200 A 4P ACB , but without ACB Sets 4
3 Distribution tap off box made of 1.6mm thick sheet steel enclosure duly painted with
powder coating on existing rising mains complete as required, suitable for mounting 4P MCCB-s (TM
Release ), but without MCCB-s
a) 250 A Sets 136
1 SITC of DG Synchronisation cum Main LT Panel , with modular construction IP42(Indoor) and -
IP55(Outdoor), factory built, modular, sectionalised, compartmentalized, extendable type LT cubicle panel
of suitable size suitable for operation on 433/415 volts, 50 Hz AC 3 phase 4 wire supply system fabricated
from CRCA sheet steel of 2mm thick for frame work and covers, 3mm thick for gland plates with stiffeners
wherever required, having vibration free structure chemically treated with seven tank process or better
before painting for surface treatment and powder coated in approved shade, with suitable electrolytic
grade high conductivity bus bars extensible, DMC/ SMC (whichever is superior) bus bar supports, with
short circuit withstand capacity as mentioned ,bottom base channel of section not less than 100mmX
50mmX 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common
earth bar of required size at the rear with 2 Nos. earth stud, connections and interconnection with solid
conductor wires / copper strips, neutral links, control wiring with 1.5 sqmm. & 2.5sqmm. PVC insulated
FRLS copper conductor S/C cable for voltage & current respectively, including providing and fixing
following switch gears and as per specification
Incomer for Transformers : 3200 Amp EDO 4P ACB , 415 Volt , MP Release with ATS--- 3 Nos Sets 1.00
Incomer for DG-s : 1600 Amp EDO 4P ACB , 415 Volt , MP Release --- 3 Nos
Incomer for Solars : 800 A MCCB , 415Volt , MP release--- 2 Nos
ATS : 2500 A 4P --3 Nos , 800 A 4P -- 1 Nos
Busbar : 3 Ph, 4 Wire ,7500 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC
FRLS Sleeves
Outgoing Feeders : * 1600 Amp 4P ACB EDO -- 3 Nos (APFC Panels)
* 1250 Amps 4P ACB EDO -- 3+4 Nos (Common Area Building Panels & 4 for stack
parking panels)
* 3200 Amps 4P ACB EDO --- 4 Nos ( For Rising Main)
* 1250 Amps 4P ACB EDO --- 2 Nos ( For UPS Input Panel)
* 800 Amps 4P MCCB , MP Release ----- 2 Nos ( For Fire Fighting Panel
& Ventilation Panel)
Meters : Digital MF Meters for all Incomers and O/G Feeders with suitable rating Metering & Protection
CT-s
Under Voltage, REF, Master Trip, Trip Circuit Supervision to be provided
-
2 SITC of LT Capacitor Panels of following capacities with required APFC relays, capacitors, detuned Sets 3.00
reactors and other accessories as per specifications.
800 KVAr
3 SITC of Common Area Building Panels with following details ; Sets 2.00
Incomer : 415 Volt , 1250 Amps ACB , EDO , Micro Processor Release --- 2 Nos with 1 nos 1250 Amps ATS .
Multifunction Meters for both incomers with CT-s of suitable ratings.
Bus Bar : 1600 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
Outgoing feeders : * 125 Amps 4P MCCB with TM Release -- 18 Nos ( Floor Panels)
* 630 Amps 4P MCCB with MP Release -- 2 Nos (Elevators)
* 160 Amps 4P MCCB with TM Release ---- 3 Nos (Basement Lighting &
Power)
* 630 Amps 4P MCCB with MP Release ---- 1 Nos (Plumbing Panels)
*
-
4 SITC of Fire Pump Panels with following details ; Sets 1.00
Incomer : 415 Volt , 800 Amps MCCB , Micro Processor Release --- 1 Nos
Multifunction Meters for incomer with CT-s of suitable ratings.
Bus Bar : 1000 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
Outgoing feeders : * 250 Amps 4P MCCB with TM Release and Star Delta Starter -- 5 Nos
* 100 Amps 4P MCCB with TM Release and Star Delta Starter ---- 1 Nos
* 63 Amps 4P MCCB with TM Release and Star Delta Starter ---- 5 Nos
-
5 SITC of UPS Input Panel as per following details : Sets 1.00
Incomers : 415 Volt , 1250 Amps ACB EDO , MP Release --- 2 Nos
Multifunction Meters for incomer with CT-s of suitable ratings.
Bus Bar : 2000 Amps Hi Grade Electrolytic Akuminium Conductor with heat shrinkable PVC FRLS Sleeves
-
6 SITC of UPS Output Panel as per following details : Sets 1.00
Bus Bar : 2000 Amps Hi Grade Electrolytic Akuminium Conductor with heat shrinkable PVC FRLS Sleeves
Outgoing feeders : 2000 Amps 4P ACB, EDO with MP Release --2 Nos
-
Sl No. Description of Items UOM Quantity
Incomer : 415 Volt , 400 Amps MCCB , Micro Processor Release --- 1 Nos
Multifunction Meters for incomer with CT-s of suitable ratings.
Bus Bar : 1000 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
-
8 SITC of Elevator Individual Panels as per following details : Sets 16.00
Incomer : 415 Volt , 100 Amps MCCB , Micro Processor Release --- 1 Nos
Digital Ammeter , Voltmeter and indication lamps
Current transformers of suitable capacities.
Bus Bar : 150 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
-
9 SITC of Floor LT Panels for Lighting as per following details : 3.00
Incomer : 415 Volt , 100 Amps MCCB , Micro Processor Release --- 1 Nos
Digital Ammeter , Voltmeter and indication lamps
Current transformers of suitable capacities.
Bus Bar : 150 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
10 SITC of Floor LT Panels for Lighting & Power as per following details : 41.00
Incomer : 415 Volt , 320 Amps MCCB , Micro Processor Release --- 2 Nos
415 V, 320A ATS ---2 Nos
Digital Ammeter , Voltmeter and indication lamps
Current transformers of suitable capacities.
Bus Bar : 300 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
Incomer : 415 Volt , 320 Amps MCCB , Micro Processor Release --- 2 Nos
415 V, 320A ATS ---1 Nos
Digital Ammeter , Voltmeter and indication lamps
Current transformers of suitable capacities.
Bus Bar : 300 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
Incomer : 415 Volt , 800 Amps MCCB , Micro Processor Release --- 2 Nos with 800 A ATS
Digital Ammeter , Voltmeter and indication lamps
Current transformers of suitable capacities.
Bus Bar : 1000 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
-
13 SITC of Plumbing with following details ; 1.00
Incomer : 415 Volt , 630 Amps MCCB , Micro Processor Release --- 1 Nos
Multifunction Meters for incomer with CT-s of suitable ratings.
Bus Bar : 800 Amps Hi Grade Electrolytic Aluminium conductor with heat shrinkable PVC FRLS Sleeves
Note : No Updated SLD covering the full scope was available , BOQ was prepared based on DBR & Pre-Bid Replies.
BOQ OF HT PANELS
Sl No.
2
3
BOQ OF HT PANELS
Description of Items
Note : HT Panels shall be internal arc tested for 1 sec at rated fault current value 33kV HT Panel- (Single VCB Board Near H
Meter )
Incoming : Surge arrester (1 No.) 30kV,10kA, metal oxide varistor type surge arrestor suitable for both lightning and switc
surges,complete with its bushings and earthing terminations etc. as required.
Line PT (1 No.) 2 core line mounted, fixed type,3 phase, cast resin, potential transformer with rated turn/voltage ratio of
33000/(1.732):110/(1.732) ,rated burden of 50 VA, 33kV rated inbuilt primary side fuse,110V rated secondary and tertiary si
fuses complete with isolating plugs as required. Core 1 : CL 0.5, star connected with neutral grounded for metering and
indications. Core 2 : CL 3P, star connected with neutral grounded for protections.
VCB (1 No.) 33kV, 50Hz, 1250A, 3P, 31.5kA for 3 sec rated SCADA compatible, drawout type, roll on floor design VCB brea
panel with suitable breaker trolleys, 110 volts DC closing and tripping coils, 110 Volts DC spring charging motor, locking m
inbuilt antipumping relay, potential free NO & NC contacts required in addition to 4 spare NO and 4 spare NC contacts, do
interlocking, racking interlocking and any other controls or interlocks as described in specifications or SLD, solenoids, TNC
, earth truck complete as required.
Indication lamps 1 Sets of LED type phase indication lamps suitable for 110V,50Hz AC (red, yellow, blue)
1 Sets of LED type Indication lamps for breaker, suitable for 110V DC supply (on, off, trip, test, service, spring charge,TCH,
truck on)
1 Sets of LED type Indication lamps for DC fail suitable for 230V AC supply Numeric relay (1 No.) Numeric relay module w
LCD dislpay having following inbuilt
protection functions : under voltage, over voltage, frequency , trip circuit supervision, phase sequence,instantaneous
overcurrent,instantaneous earth fault,overcurrent and earth fault, suitable to record and store at least 100 events with date
time stamping with last five fault records stored in nonvolatile memory and with self supervision function, 4 spare digital b
2inputs
number
and334 KV 1250A
spare VCB
digital Incomer
output within
contacts 1 Numbers ofthose
addition to Outgoing VCBas1250A
required per andtheRMU.
scheme, SCADA compatible, along wi
Necessary
3No. 33kV Relays , Protective
,100/1A, device current
10VA, CL-5P10 and indicating lamps complete
transformers, to be included
as required.
Electro-mechanical relay Hinged armature type electromechanical master trip (lockout) relay complete with assembly- 1 N
Hinged armature type dc fail relay complete with assembly- 1 No.
PT fuse failure relay - 1 No EM-6400 equivalent multifunction meter with inbuilt selector switch and RS-485 port etc. comp
per specifications, compatibility to SCADA along with 3No. 33kV ,100/1A, 10VA, CL-0.5 current transformer as required. -
0-33000 volts analog type voltmeter with selector switch for Vr, Vy, Vb - 1 Nos.
Emergency trip button on front door at an accessible height -1 Nos. Selector type auto / manual switch -1 Nos. 230 volt, 50H
operated Hooter with noise level of 80db at every 3 metres with acknowledge and reset push button-1 Nos. 16-window
microprocessor based annunciation panel with visual LED indicator suitable for 230V AC complete as required. - 1 Nos.
110V DC Power Pack Busbar : Busbar (1 Set - 3P + E) Busbar made up of electrolytic grade high conductivity copper in requ
cross section and suitable for handling 33 KV, TP 50 Hz, 1250 A, 31.5 kA for 3 sec of required length and cross sectional area
Note : Concerning vendor needs to furnish the busbar calculations (for both phase and earth bus) at the time of GA approva
busbar size has to be as per the approved GA drawing.
33kV HT Panel- ESS- (1 I/C + 4 O/G)
Incoming : Surge arrester (12No.) 30kV,10kA, metal oxide varistor type surge arrestor suitable for both lightning and switc
surges,complete with its bushings and earthing terminations etc. as required.
Line PT (2 No.) 2 core line mounted, fixed type,3 phase, cast resin, potential transformer with rated turn/voltage ratio of
33000/(1.732):110/(1.732) ,rated burden of 50 VA, 33kV rated inbuilt primary side fuse,110V rated secondary and tertiary si
fuses complete with isolating plugs as required. Core 1 : CL 0.5, star connected with neutral grounded for metering and
indications.Core 2 : CL 3P, star connected with neutral grounded for protections.
VCB (2No.) 33kV, 50Hz, 1250A, 3P, 31.5kA for 3 sec rated SCADA compatible, drawout type, roll on floor design VCB brea
panel with suitable breaker trolleys, 110 volts DC closing and tripping coils, 110 Volts DC spring charging motor, locking m
inbuilt antipumping relay, potential free NO & NC contacts required in addition to 4 spare NO and 4 spare NC contacts, do
interlocking, racking interlocking and any other controls or interlocks as described in specifications or SLD, solenoids, TNC
, earth truck complete as required.
Indication lamps 1 Sets of LED type phase indication lamps suitable for 110V,50Hz AC (red, yellow, blue)1 Sets of LED ty
Indication lamps for breaker, suitable for 110V DC supply (on, off, trip, test, service, spring charge,TCH, earth truck on)1 Se
LED type Indication lamps for DC fail suitable for 230V AC supply Numeric relay (1 No.) Numeric relay module with LCD
dislpay having following inbuilt protection functions :under voltage, over voltage, frequency , trip circuit supervision, phas
sequence,instantaneous overcurrent,instantaneous earth fault,overcurrent and earth fault, suitable to record and store at lea
events with date and time stamping with last five fault records stored in nonvolatile memory and with self supervision
function, 4 spare digital binary inputs and 4 spare digital output contacts in addition to those required as per the scheme, SC
compatible, along with 3No. 33kV ,100/1A, 10VA, CL-5P10 current transformers, complete as required.
Electro-mechanical relay Hinged armature type electromechanical master trip (lockout) relay complete with assembly- 1
No.Hinged armature type dc fail relay complete with assembly- 1 No.PT fuse failure relay - 1 No.Metering EM-6400 equiva
multifunction meter with inbuilt selector switch and RS-485 port etc. complete as per specifications, compatibility to SCAD
along with 3No. 33kV ,100/1A, 10VA, CL-0.5 current transformer as required. -
1 Nos.0-33000 volts analog type voltmeter with selector switch for Vr, Vy, Vb - 1 Nos.Emergency trip button on front door a
accessible height -1 Nos.Selector type auto / manual switch -1 Nos.230 volt, 50Hz,AC operated Hooter with noise leve
80db at every 3 metres with acknowledge and reset push button-1 Nos. 16-window microprocessor based annunciation pan
with visual LED indicator suitable for 230V AC complete as required. -
1 Nos. 110V DC Power Pack
Busbar : Busbar (1 Set - 3P + E)Busbar made up of electrolytic grade high conductivity copper in required cross section an
suitable for handling 33 KV, TP 50 Hz, 1650 A, 31.5 kA for 3 sec of required length and cross sectional area.
Note : Concerning vendor needs to furnish the busbar calculations (for both phase and earth bus) at the time of GA approva
busbar size has to be as per the approved GA drawing.
Outgoing : VCB (4 Nos.) 33kV, 50Hz, 1250A, 3P, 31.5kA for 3 sec rated SCADA compatible, drawout type, roll on floor desig
VCB breaker panel with suitable breaker trolleys, 110 volts DC closing and tripping coils, 110 Volts DC spring charging mot
locking magnet, inbuilt antipumping relay, potential free NO & NC contacts required in addition to 4 spare NO and 4 spar
contacts, door interlocking, racking interlocking and any other controls or interlocks as described in specifications or SLD,
solenoids, TNC switch , earth truck complete as required.
110V DC / 110V AC operated earth truck suitable for 33kV cable -
1 No.Indication lamps 5 Sets of LED type Indication lamps for breaker, suitable for 110V DC supply (on, off, trip, test, servi
spring charge,TCH, earth truck on)
5 Sets of LED type Indication lamps for DC fail suitable for 230V AC supply
Numeric relay Numeric relay module with LCD dislpay having following inbuilt protection functions & suitable to reco
and store at least 100 events with date and time with last five fault records stored in nonvolatile memory and with self
supervision function,
4 spare digital binary inputs and 4 spare digital output contacts in addition to those required as per the scheme, SCAD
compatible, breaker control (on/off) complete as required.
Note : Numeric relays shall have a provision of by-passing the second harmonic current during transformer switching oper
so that feed breaker does not trip during transformer switching.
under voltage, over voltage, frequency , trip circuit supervision phase sequence,instantaneous overcurrent,instantaneous ea
fault,overcurrent and earth fault along with 3No. 33kV ,50/1A, 10VA, CL-5P10 current transformers, complete as required.
Nos.Numeric relay module (for safe tripping of transformer's 33kV feed breaker) with LCD dislpay having following inbu
protection functions :High winding temperature with 3No. 33kV ,50/1A, 10VA, CL-5P10 current transformers, complete as
required. -
2 Nos.Numerical Relay module for REF protection of Transformer - 2 Nos.Electro-mechanical relay Hinged armature type
electromechanical master trip (lockout) relay complete with assembly- 2 Nos.Hinged armature type dc fail relay complete w
assembly- 2 Nos.Metering EM-6400 equivalent multifunction meter with inbuilt selector switch and RS-485 port etc. comple
per specifications, compatibility to SCADA along with 3No. 33kV ,50/1A, 10VA, CL-0.5 current transformer as required. - 2
Nos.0-33000 volts analog type voltmeter with selector switch for Vr, Vy, Vb - 2 Nos.Emergency trip button on front door at
accessible height -2 Nos.Selector type auto / manual switch -2 Nos.230 volt, 50Hz,AC operated Hooter with noise level of 8
every 3 metres with acknowledge and reset push button- 2 Nos.16-window microprocessor based annunciation panel w
visual LED indicator complete as per specifications and schedule as required.- 2 Nos.
UOM Qty
job 1.000
job 1.000
job 1.000
EXTERNAL LIGHTING
Item No Discription of Items
1 Supply of 7 Mtr high hot dip galvanised octagonal poles with 130 mm bottom
A/F & 70 mm top A/F made up of 3mm thk. HT sheet alongwith base plate
of size (220X220X12) mm thk, and foundation bolts of suitable sizes and
quantities (Single Arm)
2 100W LED Street Light Fixture (BRP409 LED115 CW SLC FG PSU GR V2) with
dimmable driver
3 LED Bollard 7W ( Philips BCP400 LED09 D CW PSU GR S1)
4 LED Post Top Light Fixtures with 1 Mtr Decorative Poles (Philips BGP300
LED28 757 PSU PC IN S1)
5 LED Bush/Ground Light (Philips BBP211 LED90/WW 2W 12V 30D)
6 LED Step Lights (Philips BWG150 LED50/WW PSU 220-240V IP67 7043)
7 16M high mast shaft in two sections suitable for 55m/sec wind speed, with
raising lowering system comprising, head frame, luminaries carriage suitable
to install 08 nos luminaries in symmetrical arrangement, drum winch, 5mm
diameter SS wire rope, trailing cable,connector, integral power tool motor,
manual handle, junction box, lightening finial including Supply & fixing of
foundation bolts manufactured from special steel along with nuts, washers,
anchor plate and common template.
8 200W LED Flood Light Fixture for High Mast (Philips BVP184 LED196 CW
FG WB 200W PSU)
9 Feeder Pillar for High Mast
10 Supply of Following Size armoured cables (1.1 KV Grade, XLPE, AL
Conductor)
a) 4C X 16 Sqmm
b) 3.5C X 35 Sqmm
c) 4C X 10 Sqmm
11 Laying of one number PVC insulated and PVC sheathed / XLPE power
cable of 1.1 KV grade of following size direct in ground including
excavation, sand cushioning,
protective covering and refilling the trench etc as required.
Upto 35 sq. Mm
12 Laying of one number additional PVC insulated and PVC sheathed /
XLPE power cable of 1.1 kV grade of following size direct in ground in
the same trench in one tier horizontal formation including excavation,
sand cushioning, protective covering and refilling the trench etc. as
required.
Upto 35 sq. Mm
13 Laying of one number PVC insulated and PVC sheathed / XLPE power cable
of 1.1 kV grade of following size on cable tray / trough ducts / through Hume
Pipe etc.
Sets 39
Sets 39
Sets 82
Sets 49
Sets 100
Sets 27
Sets 1
Sets 8
Sets 1
Mtr 2785
Mtr 173
Mtr 1383
Mtr 633
Mtr 2253
Mtr 213
Sets 22
TENTATIVE POWER CABLE SCHEDULE
TOTAL
HT AND LT CABLE TERMINATIONS BOQ