Professional Documents
Culture Documents
Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct
A R T I C LE I N FO A B S T R A C T
Keywords: The behavior of slender ultra-high performance concrete (UHPC) columns under eccentric loading was in-
High-strength concrete vestigated in this study. Eight slender UHPC columns were tested, with the major experimental variables being
Slender columns the amounts of confinement steel and steel fibers. The behavior of the columns was evaluated using various
Strengthening performance measures, including the failure pattern, load–deflection relationship, ductility, steel reinforcement
Steel fibers
strain, and axial load–moment interaction diagram. Results showed that the inclusion of steel fibers with a
volume fraction of 0.75% or more effectively restrained spalling and crushing of the slender UHPC columns. In
particular, the inclusion of a 1.5% volume fraction of steel fibers was able to compensate a 70% reduction in the
confinement steel while still promoting the ductility of the slender columns under eccentric loading.
Furthermore, analytical studies were conducted to estimate the crushing strain of the UHPC material in the
outermost fiber of the column section under a combined flexural and axial action. The applicability of an
analytical procedure and the current design codes for evaluating the total moment demand of the slender UHPC
columns under the influence of the P-Delta effect were also evaluated.
1. Introduction strength at early ages. Yang et al. [4] studied the bending behavior of
UHPC structural beams. The study showed that the steel fiber-re-
Ultra-high performance concrete (UHPC) is an emerging cement- inforced UHPC beams exhibited ductile behavior with a ductility index
based composite that has an ultra-high compressive strength [1–4]. The ranging between 1.60 and 3.75. Liu et al. [13,14] investigated the re-
ultra-high strength of UHPC is derived from a tailored mixing design, sponses of UHPC subjected to impacts and blasts. It was found that the
which has a high cementitious material content and an optimized UHPC column preserved more than 70% of its loading capacity after
gradation of granular materials with no or minimal coarse aggregate. 35 kg TNT detonation, while the high strength concrete column only
When UHPC is reinforced with short, discontinuous fibers, it gains a maintained 40% loading capacity after 8 kg TNT detonation.
strain-hardening behavior under uniaxial tension, and features a da- Yoo et al. [16] studied the flexural behavior of UHPC beams re-
mage pattern of closely spaced narrow cracks [5] due to the bridging inforced with glass fiber-reinforced polymer (GFRP) rebar and hybrid
effect of the fibers. The inclusion of fibers also provides a confining reinforcements. It was found that both AFGC/SETRA [26] and JSCE
effect that enables UHPC to exhibit a substantially higher compression [27] recommendations were appropriate for predicting the mo-
ductility and strength retention when compared to conventional high- ment–curvature response of UHPC beams with GFRP rebar and hybrid
strength concrete materials. Due to the appealing properties, the reinforcements. Hung and Chueh [17] studied the cyclic flexural per-
number of studies on UHPC has been increasing exponentially in recent formance of UHPC structural beams reinforced with high-strength steel
years. The primary research areas of UHPC can be generally categorized rebar. Their results showed that the addition of steel fibers substantially
into material design and properties [5–9], structural behavior enhanced the damage tolerance ability of the high-strength beams, even
[4,10–16], development of innovative composites [17–20], and struc- when the fibers were used only in the top and bottom sections of the
tural retrofitting and strengthening [21–25]. beam. Hung et al. [18] experimentally investigated the seismic beha-
Abdulkareem et al. [6] developed a new mixture of UHPC with vior of squat UHPC shear walls. It was found that the brittle shear-
improved sustainability. The early age properties of the developed critical behavior of the squat UHPC wall was transformed into ductile
UHPC were studied. It was found that the use of chemical activator of flexural-dominant behavior via the inclusion of steel fibers with a vo-
potassium hydroxide in UHPC with a high content of blast furnace slag lume fraction of 1.5%. The proposed advanced concrete members not
caused slag’s dissolution and reaction, which increased the compressive only took advantage of the ultra-high mechanical properties of high-
⁎
Corresponding author.
E-mail address: cchung@mail.ncku.edu.tw (C.-C. Hung).
https://doi.org/10.1016/j.engstruct.2018.07.088
Received 16 March 2018; Received in revised form 26 July 2018; Accepted 29 July 2018
0141-0296/ © 2018 Elsevier Ltd. All rights reserved.
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
strength steel and UHPC materials, but also resolved the concern of the 2.2. Column design
potential premature failure for high-strength reinforcement and con-
crete. Ferrier et al. [19,20] studied the behavior of UHPC elements The major design variables of the column members included (1) the
reinforced with FRP bars. This new type of UHPC elements was de- amount of steel fibers and (2) the transverse reinforcement. The spacing
signed to be lightweight and to be able to sustain large force demands. of the transverse reinforcement was s = h/4 or h/2 (i.e., 50 mm or
Palacios et al. [10] studied the cyclic behavior of a steel-reinforced 100 mm), where h is the minimum cross-sectional dimension of the
column with the plastic hinge region fabricated using UHPC. Their column (200 mm). Two transverse reinforcement configurations were
experimental results showed that the use of UHPC completely changed used in the columns. The first configuration was a D10(#3) perimeter
the typical failure mode of the concrete columns as it improved con- hoop without any crossties. The other configuration was a D10(#3)
finement and prevented concrete crushing. Hor et al. [22] experimen- perimeter hoop with a D10(#3) crosstie having 135-degree seismic
tally studied the behavior of reinforced concrete slabs strengthened hooks each way, which allowed every longitudinal steel bar around the
with UHPC. It was found that the UHPC overlay delayed the develop- perimeter of the column core to be laterally supported by either the
ment of shear cracking. Ricker et al. [24] investigated the punching corner of a hoop or a seismic hook, as required by ACI 318 [28] for fc′
strength of flat plates reinforced with UHPC and double-headed studs. larger than 68 MPa. The notations and reinforcement details of the
The test results showed that the slabs including a UHPC element had column members are summarized in Table 3. The numbers following
significantly higher strength capacity compared to the counterparts “H” and “T” are the spacings of the perimeter hoops and crossties, re-
without UHPC. Lampropoulos et al. [25] studied the efficiency of using spectively, except where a “0” is used to represent none. The number
UHPC to strengthen existing reinforced concrete beams. It was de- following “F” denotes the volume fraction of the steel fibers. For ex-
monstrated that the beams strengthened with three UHPC side jackets ample, “H5T0-F150” denotes a column having 5 mm-spaced perimeter
exhibited satisfactory structural performance. hoops, without crossties, and having steel fibers with a 1.5% volume
While benefits in terms of design and performance can be foreseen fraction. The H5T5-F0 column, which was designed to conform to ACI
when using UHPC to replace conventional concrete materials in steel- 318 [28], was the control specimen in this study.
reinforced structural members, the behavior of steel-reinforced UHPC
members has yet to be fully understood. For example, although it 3. Test instrumentation and load protocol
permits a considerable reduction in the cross-sectional dimensions of
concrete columns, the increased slenderness effect could adversely in- 3.1. Tensile and compressive tests for UHPC
fluence the behavior of the columns. The non-negligible slender effect
will magnify the deflection and moment demand of the slender UHPC The compressive strength, fc′, of the UHPC materials was obtained
columns due to its interaction with the axial load, i.e., the P-Delta ef- using compressive tests on 75 mm × 150 mm cylinder specimens. The
fect, which may cause the slender UHPC columns to have a reduced compressive tests were conducted according to ASTM C39. The tensile
load-resistant capacity. behavior of the UHPC materials was identified by performing direct
In response, the present study investigated the behavior of steel- tensile tests on dog-bone specimens, the configuration, dimensions, and
reinforced slender UHPC columns under eccentric loading. The influ- test setup of which are presented in Fig. 2. During the tensile test, the
ence of various design variables on the performance of the columns was magnitude of the applied force was measured using a load cell directly
examined, including the (1) stirrup spacing, (2) crossties, and (3) connected to the actuator. The elongation of the specimen within a
amount of short discontinuous fibers. In addition to the experimental gauge length of 160 mm was monitored using two linear variable dis-
study, the applicability of current design practices and an analytical placement transducers (LVDTs) mounted on either side of the specimen.
method for estimating the total moment demand of slender UHPC Although such an LVDT setup, which has been widely adopted by other
columns with non-negligible P-Delta effects were evaluated. studies due to its efficiency, generally captures the elongation of spe-
cimens with reasonable accuracy, it should be noted that the accuracy
of the measurement can be further enhanced by using two additional
2. Column specimens
LVDTs on the other two faces of the specimen. This is because the use of
four LVDTs addresses the deformation state of the entire cross section,
Eight slender UHPC column members were fabricated and tested in
including the behavior of out-of-plane bending. Both the compressive
this study. The geometries of the members were identical, as shown in
and tensile tests were performed using a displacement control proce-
Fig. 1. Each column member had a test region with dimensions of
dure with a loading rate of 0.01 mm/s to simulate the quasi-static
200 mm × 200 mm × 1200 mm, as well as enlarged cross-sections at
loading condition. For each batch of UHPC material used for casting the
the two ends to limit the damage to the test region during the test.
column members, three compressive specimens and three tensile spe-
cimens were fabricated and tested. The material tests were performed
2.1. Materials within 24 h before or after testing the corresponding column member.
The average of the three test results was employed as the representative
The mix proportions of the UHPC material are summarized in material property.
Table 1. The components included Type I ordinary Portland cement,
silica fume, silica sand (with particle sizes ranging between 0.1 mm and 3.2. Eccentric loading tests
0.3 mm), quartz powder, water, polycarboxylate-based superplasticizer,
and high-strength hooked steel fibers. The UHPC material contained The columns were tested under eccentric axial loading. The test
either a 0%, 0.75%, or 1.5% volume fraction (Vf ) of steel fibers. The setup is shown in Fig. 1(b). The two ends of each column member were
employed steel fibers had a length of 30 mm, a diameter of 0.38 mm, an pin-linked to steel connecters fixed to a strong floor and a hydraulic
elastic modulus of 201 GPa, and a nominal yield strength of 3070 MPa. actuator, respectively. The pin connections allowed free rotation in the
The UHPC materials had a designed 28-day compressive strength of test plane of the column while constraining the degrees of freedom
120 MPa. As such, due to the capacity limit of the hydraulic actuator for associated with translations. The erected column member, which had a
kℓ
eccentric loading, the columns were tested on the 21st day. slender ratio of r u = 40 , was categorized as a slender column according
The columns were reinforced with D10 and D16 steel bars that had a to ACI 318 [28]. Moreover, the experimental test was designed for the
nominal yield strength of 420 MPa. The actual tensile properties of the columns to show a tensile-controlled failure pattern under a combined
steel reinforcements, which were obtained using direct tensile tests, are axial and bending action. This was achieved by applying an axial force
summarized in Table 2. with an eccentricity of 260 mm, which was larger than the eccentricity
702
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
Table 1 Table 3
Mix proportions of UHPC (proportion by weight except for fibers). Reinforcement details of the slender UHPC columns.
Type I Silica Silica sand Quartz Water and Fiber (by Column Steel reinforcement Vf (%)
Portland fume powder superplasticizer volume)
cement Longitudinal Transverse
1 0.22 0.5 0.39 0.28 0%, 0.75% Rebar ρl (%) Hoop Crosstie ρt (%)
or 1.5%
H5T0-F0 8-D16 4.0 D10@50 mm None 1.8 0
H5T0-F150 D10@50 mm None 1.8 1.5
H5T5-F0 D10@50 mm D10@50 mm 2.7 0
Table 2
H5T5-F75 D10@50 mm D10@50 mm 2.7 0.75
Tensile properties of steel bars.
H10T0-F0 D10@ None 0.9 0
Size/ Yield strain Yield strength Ultimate Elongation (%) 100 mm
diameter (MPa) strength (MPa) H10T0-F150 D10@ None 0.9 1.5
100 mm
D10 (#3) 0.0025 459 612 11.0 H10T10-F0 D10@ D10@ 1.3 0
D16 (#5) 0.0022 439 630 13.6 100 mm 100 mm
H10T10- D10@ D10@ 1.3 1.5
F150 100 mm 100 mm
703
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
The failure patterns of the tested columns are shown in Fig. 5, while
the relationship concerning axial load versus lateral displacement for
each column, together with the result for the control specimen, are
presented in Fig. 6. The columns without fibers had a similar damage
pattern before their peak strength was reached, namely, minor concrete
spalling, multiple fine horizontal cracks, and an obvious localized
horizontal crack. Although the difference in the transverse reinforce-
ment layout had only a minor influence in the behavior of the slender
UHPC columns before the peak strength was reached, its impact on the
post-peak behavior was notable. For the H5T0-F0 and H10T0-F0 spe-
cimens with no crossties, as soon as their peak strength was reached, a
large region of concrete crushed and spalled in the compressive side of
Fig. 3. Locations of the installed Optotrak markers. the column under the combined flexural and axial action, causing their
strength to drop dramatically (as can be seen in Fig. 6(a) and (b)). It is
worth noting that the spalling of the concrete cover caused the axial
summarized in Table 4. Meanwhile, Fig. 4 shows the representative
stiffness center of the column to shift away from the loading center.
uniaxial tensile stress-strain curves of the UHPC materials with varying
This consequently magnified the 2nd-order bending-moment demand of
amounts of steel fibers. It can be seen that the inclusion of steel fibers
the column, and thus caused the columns to fail. Notably, the H10T0-F0
enabled the UHPC material to exhibit tensile strain-hardening behavior,
specimen, which had a stirrup spacing twice as wide as that of the
followed by gradual softening. This tensile strain-hardening behavior
H5T0-F0 sample, failed immediately after the peak strength was
provides evidence of the potent bridging effect provided by the fibers
reached. In contrast, the brittle post-peak behavior was greatly im-
that enabled the internal force to be transferred across the cracks to
proved by the crossties, even for the case of the H10T10-F0 specimen
704
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
Table 4
Tensile and compressive properties of the UHPC materials.
Column type fc′ (MPa) ftc (MPa) εtc (%) ftp (MPa) εtp (%) ftu (MPa) εtu (%)
Note: ftc is the tensile cracking strength, εtc is the tensile cracking strain, ftp is the peak tensile strength, εtp is the peak tensile strain, ftu is the ultimate tensile strength,
and εtu is the ultimate tensile strain.
(Fig. 6(c)), which had the large stirrup spacing of h/2. This outcome is
likely because the enhanced confinement due to the crossties resulted in
greater restraint in the dilatation of the concrete core under axial
loading, thereby postponing major concrete spalling. Accordingly, the
close stirrup spacing of h/4 and the presence of crossties enabled the
control specimen H5T5-F0 to have a strength plateau sustaining the
peak strength until significant concrete crushing and spalling occurred.
In comparison with the control specimen H5T5-F0, incorporation of
the steel fibers in the H5T5-F75 specimen (Vf = 0.75%) provided robust
bridging effects that reduced the width of the flexural cracks. It also
greatly reduced the spalling area of the column, as can be seen in
Fig. 5(e), due to the additional confinement for both the concrete core
Fig. 4. Tensile stress-strain curves of the UHPC materials. and cover provided by the fibers. For comparison purposes, the spalling
area of each column was estimated and normalized with that of the
control specimen H5T5-F0. The total spalling area of the column was
estimated by summing the spalling area of each grid that was drawn on
the surface of the column before the test. In particular, three levels, i.e.,
0% for no spalling, 50% for partial spalling, and 100% for total spalling,
were used to quantify the spalling area of each grid. The calculated
results illustrated in Fig. 7 imply that the inclusion of even a small
amount of steel fibers, e.g. the H5T5-F75 (Vf = 0.75%) sample, could
reduce the spalling area by as much as 74% when compared with the
control specimen H5T5-F0. This enabled the H5T5-F75 sample to have
a more ductile post-peak behavior than the control specimen H5T5-F0,
as can be seen in Fig. 6(g). Nevertheless, the strength of H5T5-F75 still
dropped suddenly by about 20% at the peak strength due to the con-
crete failure in the compressive side of the combined flexural and axial
action at the critical section of the column, as can be seen in Fig. 6(g).
At the end of the test, fiber fracture and pullout could be observed
within the major horizontal flexural crack in the H5T5-F75 specimen.
Fig. 6(d)–(f) shows that the load-displacement curves for the col-
umns with Vf = 1.5% exhibited ductile post-peak behavior and a gra-
dually softening strength. In addition, with a fiber content of
Vf = 1.5%, concrete spalling and crushing throughout the test was ef-
fectively restrained, even in the case of the H10T0-F150 specimen with
no crossties and a transverse reinforcement ratio a mere one third that
of the control specimen. The sudden loss in strength observed for the
columns with Vf = 0 and 0.75% was successfully prevented for those
with Vf = 1.5%. Moreover, the addition of crossties appeared to have
little influence on the post-peak behavior for the columns with fibers,
whereas it enhanced the strength-retention ability for those without
fibers. It is also worth noting that although the H5T0-F150 specimen
had no crossties, the inclusion of fibers (Vf = 1.5%) enabled it to have a
2nd peak strength greater than the 1st peak strength.
5. Discussion
Fig. 5. Failure patterns of the columns. The eccentrically loaded behavior of the slender UHPC columns was
further investigated using various performance measures, including the
deflection, steel reinforcement strain, UHPC crushing strain, ductility,
axial load–moment interaction diagram, and the total moment demand.
705
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
706
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
Table 5
Summary of experimental results of the slender columns.
Column Ppeak (kN) Mpeak (kN-m) δpeak (mm) δult (mm) Ductility ratio epeak (mm) ′
εcrush εcrush εcrush
′ Manalytic MACI
εcrush Mpeak Mpeak
Note: Ppeak and Mpeak are the peak axial strength and moment, respectively; δpeak is the peak lateral displacement corresponding to Ppeak ; δult is the ultimate lateral
′ are the crushing strains of the UHPC material at the outermost fiber of the column
displacement; epeak is the eccentricity measured at the peak strength; εcrush and εcrush
section estimated based on the NDI data and the measured longitudinal reinforcement strains, respectively; and, MACI and Manalytic are the predicted total moment
demands at the peak strength according to ACI 318 [12] and the analytical approach, respectively.
707
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
Fig. 9. Relationships between axial load and compressive strain demand in the longitudinal reinforcement.
the control specimen, i.e., H5T5-F0, showed the highest ductility value,
which was 41%, 122%, and 3% greater than those of the H5T0-F0,
H10T0-F0, and H10T10-F0 specimens, respectively. It is found that the
inclusion of crossties had a major impact on the ductility performance
of the slender UHPC columns without fibers. In particular, although the
H10T10-F0 sample had a stirrup spacing twice as wide as that of the
control specimen H5T5-F0, it had a similar ductility value.
The inclusion of steel fibers in the slender UHPC columns sig-
nificantly enhanced the ductility of the column by more than twofold,
as evidenced by the effective restraint on concrete spalling and
crushing. Notably, even the addition of only a small amount of fibers,
i.e., Vf = 0.75%, in the column also greatly enhanced the ductility ratio
by 2.2 times. The enhancement on the ductility due to the increasing
transverse reinforcement ratio and addition of crossties could also be
observed for the columns with fibers. It is worth mentioning that al-
though the H10T0-F150 specimen (s = h/2 and ρt = 0.89) had a stirrup Fig. 11. Comparison of the ductility ratios.
spacing twice as wide as that of the control specimen H5T5-F0 (s = h/4
and ρt = 2.67) and its crossties were removed, it nevertheless exhibited setup can be found in Section 3.2. For comparison purposes, the ideal
a ductility value 235% greater than the control specimen H5T5-F0. loading path corresponding to a constant eccentricity of e = 260 mm
Overall, the test results in this study imply that the inclusion of fibers was also plotted in the figure. It can be seen that the actual loading
with a Vf greater than 0.75% was able to replace up to 70% of the code- paths for all columns were initially linear, closely matching the ideal
required confinement steel for slender UHPC columns without com- path with e = 260 mm. As the axial load demand for the columns
promising the structural performance of the column under the com- continued to increase, the actual loading paths gradually “softened”
bined axial and flexural action. due to the progressively magnified P-Delta effect. For the columns
without fibers, column failure occurred when the actual loading path
just reached or was still some distance away from the failure envelope,
5.5. Axial load–moment interaction diagrams of the columns
except for the control specimen H5T5-F0. This implies that the close
stirrups and the inclusion of crossties in the control specimen H5T5-F0,
In Fig. 12, the axial load–moment interaction diagrams (commonly
as stipulated by ACI 318, was able to ensure the stability of the column,
termed P-M diagrams) show the actual loading paths of the tested
preventing premature failure due to the combined factors of extreme
slender columns in conjunction with the failure envelopes calculated
brittleness at the material level and the P-Delta effect at the structural
according to ACI 318 [28]. The moment demands of the columns during
level. It is worth noting that the H5T0-F0 specimen in Fig. 12(a), which
the tests were calculated as Mexp = (einitial + δult ) × Pmeasure , where
einitial = 260mm is the initial eccentricity, δult is the measured deflection, had reinforcement details conforming to the versions of ACI 318 earlier
and Pmeasure is the measured axial force. Details of the measurement than 2014, showed a premature failure pattern before its loading path
Fig. 10. Relationships between axial load and tensile strain demand in the longitudinal reinforcement.
708
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
reached the failure envelope. This result highlights the necessity for all Cm
δ= ⩾ 1.0
longitudinal reinforcements to be laterally supported by seismic hooks 1−P /0.75Pc (2)
or perimeter hoops for high-strength concrete columns with
fc′ > 68 MPa, as per the latest version of ACI 318 [28]. For the columns M1
Cm = 0.6−0.4
with fibers, failure occurred after the loading path was beyond the M2 (3)
failure envelope. Their damage control ability due to the inclusion of
fibers endowed them with enhanced stability at both the material and π (EI )eff
Pc =
structural levels, thus effectively preventing premature failure. (k ℓu)2 (4)
709
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
assumption that the deflection curve of the column is in the shape of a softening strength. In particular, even though the H10T0-F150
half sinusoid. Details of the derivation can be found in [29]. specimen (ρt = 0.89%) had no crossties and a stirrup spacing twice
The applicability of the moment magnifier method (Eq. (1)) and the as wide as the control specimen H5T5-F0 (ρt = 2.67%), the inclu-
analytical method (Eq. (5)) for evaluating the total moment demand of sion of steel fibers with Vf = 1.5% enabled the H10T0-F150 sample
the tested slender UHPC columns at their peak strength was in- to have a ductility ratio that was two times greater.
vestigated in this study. The accuracy of the predicted solutions was (2) While the variation in the transverse reinforcement configuration
quantified using the ratio of the predicted solution to the experimental had an insignificant effect, the inclusion of fibers in the slender
M
result, i.e., MACI and analytic ; where MACI and Manalytic are the total mo- UHPC columns led to a considerably greater peak lateral displace-
Mpeak Mpeak
ment demands calculated using Eqs. (1) and (5), respectively; while ment. Despite only a small amount of fibers with Vf = 0.75% being
Mpeak is the total moment demand obtained by the test, which was added in the H5T5-F75 specimen, the peak displacement was in-
calculated as Mpeak = epeak × Ppeak , with epeak and Ppeak being the mea- creased by 14%, as compared with its counterpart specimen
sured eccentricity and axial force at the peak axial strength of the without fibers. Moreover, the ultimate lateral displacements of the
column, respectively. The computed results are presented in Table 5. fiber-reinforced slender UHPC columns were greater than that of
The results indicate that the ratios obtained based on the moment the control specimen H5T5-F0 by 47%–97%.
magnifier approach and the analytical approach were between 0.94 and (3) The inclusion of steel fibers with Vf = 0.75% and 1.5% in the
1.04. While both approaches generated reasonable solutions for the slender UHPC columns substantially increased the average crushing
total moment demands of the slender UHPC columns under the influ- strain from 0.0025 to 0.0034 and 0.0036, respectively. Accordingly,
ence of the P-Delta effect, the moment magnifier method yielded a the fibers not only effectively improved the brittle nature of the
moment demand about 2% greater than that of the analytical method. UHPC at the material level, but also led to a more ductile flexural
Nonetheless, it is worth mentioning that the moment magnifier ap- performance of the slender UHPC column at the structural level.
proach is applicable for general RC columns whereas the analytical (4) Both the analytical method and ACI-318 magnified approach gen-
approach is only applicable for simply supported columns with M1/ erated acceptable estimations for the total moment demand of the
M2 = −1. It is also interesting to note that the average moment ratio tested slender UHPC columns. The accuracy ratios for the two ap-
decreased from a value above 1 for the columns without fibers, to equal proaches were similar, with both being between 0.94 and 1.04.
or slightly less than 1 for the columns with fibers. The slight over- While the actual total moment demand was slightly overestimated
estimation for the total moment demand of the slender UHPC columns for the columns without fibers, it was mostly slightly under-
without fibers can be attributed to their extreme brittleness, which estimated for the columns with fibers.
rendered the column vulnerable to premature spalling. As a result, the (5) Under the condition that the stirrup spacing was less than h/2 and
slender UHPC columns without fibers had a smaller peak lateral dis- the transverse reinforcement ratio was greater than = 0.89%, the
placement and associated second-order moment. On the other hand, the test results suggest that the code-required confinement steel for
inclusion of fibers in the slender UHPC columns effectively enhanced slender UHPC columns could be partially reduced via inclusion of
the deflection ductility of the column (particularly for the columns with steel hooked fibers with Vf = 1.5%, without compromising the
closer stirrups and Vf = 1.5%), leading to a greater second-order mo- performance of the column under the combined axial and flexural
ment demand. The computed moment ratios were found to be the action.
smallest in the case of the H5T0-F150 specimen, with values of 0.96 and
0.94 for the magnifier approach and analytical approach, respectively. Acknowledgements
This can be attributed to the strength-hardening behavior of the H5T0-
F150 specimen, which led to a 2nd peak strength higher than the 1st This study was sponsored in part by the Ministry of Science and
peak strength. Technology, Taiwan, under Grant No. 104-2628-E-006-002-MY3. The
opinions, findings, and conclusions expressed in this paper are those of
6. Conclusions the authors, and do not necessarily reflect those of the sponsors.
710
C.-C. Hung et al. Engineering Structures 174 (2018) 701–711
[12] Hung CC, Hu FY. Behavior of high-strength concrete slender columns strengthened encased shear connectors in steel-concrete composite joints with UHPC grout.
with steel fibers under concentric axial loading. Constr Build Mater Constr Build Mater 2018;173:638–49.
2018;175:422–33. [22] Hor Y, Teo W, Kazutaka S. Experimental investigation on the behaviour of re-
[13] Liu J, Wu C, Su Y, Li J, Shao R, Chen G, et al. Experimental and numerical studies of inforced concrete slabs strengthened with ultra-high performance concrete. Constr
ultra-high performance concrete targets against high-velocity projectile impacts. Build Mater 2017;155:463–74.
Eng Struct 2018;173:166–79. [23] Tanarslan HM, Alver N, Jahangiri R, Yalçınkaya Ç. Flexural strengthening of RC
[14] Li J, Wu C, Hao H, Liu Z. Post-blast capacity of ultra-high performance concrete beams using UHPFRC laminates: Bonding techniques and rebar addition. Constr
columns. Eng Struct 2017;134:289–302. Build Mater 2017;155:45–55.
[15] Mészöly T, Randl N. Shear behavior of fiber-reinforced ultra-high performance [24] Ricker M, Häusler F, Randl N. Punching strength of flat plates reinforced with UHPC
concrete beams. Eng Struct 2018;168:119–27. and double-headed studs. Eng Struct 2017;136:345–54.
[16] Yoo DY, Banthia N, Yoon YS. Flexural behavior of ultra-high-performance fiber- [25] Lampropoulos AP, Paschalis SA, Tsioulou OT, Dritsos SE. Strengthening of re-
reinforced concrete beams reinforced with GFRP and steel rebars. Eng Struct inforced concrete beams using ultra high performance fibre reinforced concrete
2016;111:246–62. (UHPFRC). Eng Struct 2016;106:370–84.
[17] Hung C-C, Chueh C-Y. Cyclic behavior of UHPFRC flexural members reinforced with [26] AFGC/SETRA. Ultra high performance fibre-reinforced concretes. Interim
high-strength steel rebar. Eng Struct 2016;122:108–20. Recommendations. Bagneux, France: AFGC Publication; 2000.
[18] Hung C-C, Li H, Chen HC. High-strength steel reinforced squat UHPFRC shear walls: [27] JSCE. Recommendations for design and construction of ultra-high strength fiber
Cyclic behavior and design implications. Eng Struct 2017;141:59–74. reinforced concrete structures (Draft). Tokyo, Japan: Japan Society of Civil
[19] Ferrier E, Agbossou A, Michel L. Mechanical behaviour of ultra-high-performance Engineers; 2000.
fibrous-concrete wood panels reinforced by FRP bars. Compos B Eng [28] ACI (American Concrete Institute) Committee 318. ACI 318 Building code re-
2014;60:663–72. quirements for structural concrete (318-14). ACI-318, Farmington Hills, Michigan
[20] Ferrier E, Confrere A, Michel L, Chanvillard G, Bernardi S. Shear behaviour of new 2014.
beams made of UHPC concrete and FRP rebar. Compos B Eng 2016;90:1–13. [29] Wight JK. Reinforced concrete: Mechanics and design. 7th ed. Pearson; 2015.
[21] He S, Mosallam AS, Fang Z, Zou C, Feng W, Su J. Experimental study on CFSC
711