Professional Documents
Culture Documents
Variable Primary Flor - Chiller Operation Systems
Variable Primary Flor - Chiller Operation Systems
•Heat Exchangers
•Fan Laws
3 Way valve
3 Way valve
45f
50f
Temperature Differential on
the chilled water supply and
return
55f
▪Multiple chiller applications require the chillers to be in series for capacity reduction
▪Ease of control
▪Increased installation cost because of parallel piping required to allow for service
or isolation of one unit
2 Way modulating
CHW valve
Variable Flow
Secondary Chilled Check Valve in the Bridge or
Water Pump De-coupler Circuit
Variable Flow
Secondary Chilled Check Valve in the Bridge or
Water Pump De-coupler Circuit
ON
48F
ON
Constant Flow Example of 60% of
Primary Chilled Water load on each unit
Primary/Secondary Chilled Water Flow Design
(Variation)
ON
52F
OFF
Constant Flow Primary
Example of 120% flow
Chilled Water Pumps
CHWF in one chiller
Primary/Secondary Chilled Water Flow
Design
2 Way modulating
CHW valve
Variable Flow
Secondary Chilled Bridge or De-coupler Circuit
Water Pump
100% valve
position
52 deg f
42 deg f
0% flow
42 deg f
52 deg f
ON
60% of chilled
60% valve water flow
position 52 deg f
42 deg f
40% flow
42 deg f
48 deg f
ON
ON
Example of 60% system load
with 40% bypass
Primary/Secondary Chilled Water Flow Design
55% of chilled
55% valve water flow
position 53 deg f
43 deg f
5% flow
42 deg f
50% of chilled 53 deg f
water flow
ON
Off
Example of 55% system load
with 5% negative bypass
Accurate Control of the chillers in a
primary/secondary System requires:
-Measurement of the secondary supply temperature and water flow-
Problems:
▪Difficulty in matching the secondary chilled water flow rate to the primary
design
Original Variable Primary Chilled Water Flow
Design
2 Way modulating
CHW valve
2 Way modulating
CHW valve
2 Way modulating
CHW valve
2 Way modulating
CHW valve
100% open
42 deg f 52 deg f
0% Open
Minimum flow bypass
42 deg f 52 deg f
CHWP’s at
100% speed
ON
60% open
42 deg f 0% Open 52 deg f
42 deg f 52 deg f
CHWP’s at
60% speed
ON
20%
42 deg f flow 5% 52 deg f
42 deg f 52 deg f
CHWP at
25% speed
ON
2 Way modulating
CHW valve
CW to Chillers
61f
3f
825 tons Heat
Approach
Exchanger
Design
69.6f
61f
58f
825 tons
1100GPM
55f
each pump
Job site
1100GPM through each cooler example
137 tons each cooler or 25% load on each unit
Heat
Exchangers
Condensing
94.91 F 89.70 F 84.60 F 79.55 F 75.41 F 73.34 F 71.70 F 70.72 F
Temp
Cooler Wall
54.84 F 54.87 F 54.89 F 54.91 F 54.92 F 54.92 F 54.92 F 54.93 F
Temp
Suction
54.73 F 54.78 F 54.83 F 54.87 F 54.89 F 54.88 F 54.89 F 54.90 F
Temp Minimum Refrigerant temperature
differential is 15 deg f
Condenser
8.6 deg f X 433GPM/24= 155 Tons at 25% of cooler capacity
Cooler
3.0 deg t X 1100GPM/24= 137 tons
(1) (Cooler) HEAT GIVEN OFF BY THE FLUID TO THE REFRIGERANT AS IT PASSES
THRU THE TUBES
(2) (Condenser) THE OVERALL TRANSFER OF HEAT FROM THE REFRIGERANT IN THE
SHELL TO THE FLUID IN THE TUBES
Heat Out
Condenser
Compressor
Metering
Device Evaporator
Heat In
Heat In
IMPACT OF FLUID VELOCITY
FLUID FLOWING THRU A TUBE FORMS A STATIC FILM
OR BOUNDARY LAYER WHICH HAS A ZERO VELOCITY
AT THE TUBE WALL. THIS FILM ACTS AS AN INSULATOR
AND HINDERS THE FLOW OF HEAT FROM THE TUBE WALL.
THE LOWER THE VELOCITY, THE THICKER THE FILM, AND
THE HIGHER THE RESISTANCE TO HEAT FLOW.
Pumping Energy is
reduced by 90% with
a reduction in
Water pressure system head
differential is requirements
2.21ft or 0.9psi
Heat Heat
Exchangers Exchangers
Cooler Tube Cooler Tube
5.23 ft/s 3.23 ft/s
Vel Vel
1200.0 1200.0
Flow Rate Flow Rate
gpm gpm
Pressure 16.7 ft Pressure 10.1 ft
Drop wg Drop wg
Increasing reliability in a VPF System:
Heat Heat
Exchangers Exchangers
Cooler Tube Cooler Tube
5.23 ft/s 2.00 ft/s
Vel Vel
1200.0 458.0
Flow Rate Flow Rate
gpm gpm
Pressure 2.43 ft
Pressure 16.7 ft
Drop wg Drop wg
Increasing system reliability in a VPF System:
The use of three way valves will slightly increase the pumping
Cost, but it will remove control of the minimum flow from the
Building Automation System and increase the system reliability.
Increasing system reliability in a VPF System:
If the minimum flow Rate is 30% of the pump design, set the hertz
or minimum speed at 30% of the motor rating and measure the flow rate
With a flow meter or by using heat exchanger pressure differential. Identify
The frequency at which the minimum flow rate is produced and use that
For a minimum operating speed.
Increasing system reliability in a VPF System:
It is possible to reduce energy use by varying the flow on the evaporator, the
same logic does not always apply to condenser water flow rate reduction.
Condenser water flow should be constant unless head pressure control is
required.
Maintaining a constant ΔT through the condenser increases the amount of
energy used by the chiller at part load conditions.
Increasing system reliability in a VPF System:
CHW CHW
Return CHW Supply Return
Increasing system reliability in a VPF System: