You are on page 1of 1

SANJEN (UPPER) HYDROELECTRIC PROJECT

POWER CABLE SELECTION AND VOLTAGE DROP


10.00%
Hoisting Factor of FLA of selected
Motor Total Selection based upon Voltage Voltage Voltage Voltage Final
S.N Gate Name Qty. Hoisting Yype Capacity KW FLA safety Cable X Derating Final Selection
(HP) Distance Ampacity Drop Drop Drop Drop Impedance
(MT) X2.5 factor
1 undersluice gate 1 rope drum 12 2.238 3 121 5.05 13.00 1.5 Sqmm , 4 Core 21.147 3.75 0.49 2.5 Sqmm, 4 core 1.13
2 intake gate 1 rope drum 12 2.238 3 88 5.05 13.00 1.5 Sqmm , 4 Core 21.147 2.73 0.49 2.5 Sqmm, 4 core 0.82

3 screw spendal 5 1.492 2


gravel flushing gate 1 55 3.36 9.00 1.5 Sqmm , 4 Core 21.147 1.14 2.5 Sqmm, 4 core 0.51
4 desander inlet gate 2 screw spendal 5 1.492 2 27.5 6.73 17.00 1.5 Sqmm , 4 Core 21.147 1.14 2.5 Sqmm, 4 core 0.26
desander outlet
5 screw spendal 5 1.492 2
gate 4 143 13.46 34.00 4 Sqmm, 4 Core 36.252 4.52 3.03 2.14 6 Sqmm, 4 core 0.55
6 sand flushing gate 2 screw spendal 5 1.492 2 143 6.73 17.00 1.5 Sqmm , 4 Core 21.147 5.91 3.63 2.26 4 Sqmm, 4 core 0.83

7 screw spendal 5 1.492 2


reservoir inlet gate 1 165 3.36 9.00 1.5 Sqmm , 4 Core 21.147 3.41 2.09 2.5 Sqmm, 4 core 1.53
reservoir outlet
8 rope drum 14 2.238 3
gate 1 297 5.05 13.00 1.5 Sqmm , 4 Core 21.147 9.21 5.65 3.52 2.36 6 Sqmm, 4 core 1.15
reservoir flushing
9 screw spendal 5 1.492 2
gate 1 308 3.36 9.00 1.5 Sqmm , 4 Core 21.147 6.37 3.91 2.44 4 Sqmm, 4 core 1.78
10 tunnel inlet gate 1 rope drum 24 4.103 5.5 297 9.25 24.00 2.5 Sqmm, 4 core 27.189 10.36 6.46 4.33 2.59 10 Sqmm, 4 core 0.68