Setting Calculations For HV Transformer Feeder
Setting Calculations For HV Transformer Feeder
110kV HV CT details
HV CT ratio : 500 /1A
HV CT primary : 500 A
HV CT secondary : 1A
LV1 CT details
LV1 CT ratio : 1000 /1A
LV1 CT primary : 1000 A
LV1 CT secondary : 1A
LV2 CT details
LV2 CT ratio : 2500 /1A
LV2 CT primary : 2500 A
LV2 CT secondary : 1A
Transformer details
HV Rated Power, Prated : 80 MVA
LV1 Rated Power, Prated : 40 MVA
LV2 Rated Power, Prated : 40 MVA
HV Rated Voltage, Vnom[1] : 110 kV
LV1 Rated Voltage, Vnom[1] : 25 kV
LV2 Rated Voltage, Vnom[1] : 11 kV
Frequency : 50 Hz
Fault current
Three phase fault current : 26769 A
Single phase fault current : 26200 A (As per the ETAP Short
circuit SLD, Refer
LV1 Three phase reflected fault current : 3692 A annexure-1)
LV2 Three phase reflected fault current : 2978 A
Protection Overview:
The following table lists the protective functions adopted for this feeder
Element
Relay Protection description
function
11.01.02 Setting calculations for Base current for differential voltage level
Since there are three Voltage levels are involved, it is understood that the maximum power among all objects
within the protected zone shall be taken as a base.
The maximum power corresponds to the following base currents on three different voltage levels connected to
the relays are,
b) At 25 kV Voltage Level,
Rated Load current on winding 2- Irated [2], = Prated / (√3*Vnom[2] )
= (40*1000)/(1.732*25)
Irated [2], = 923.79 A
CT secondary current = Irated [2] * CT ratio
= 0.92
c) At 11 kV Voltage Level,
Rated Load current on winding 3- Irated [3], = Prated / (√3*Vnom[3] )
= (40*1000)/(1.732*11)
Irated [3], = 2099.52 A
CT secondary current = Irated [3] * CT ratio
= 0.84
11.01.03 Setting calculations for minimum differential pickup current required for relay to
operate
During normal operation there is a "false" differential current measured by the protection due to the following:
Restrain characteristics
End Section 1 = 1.25 IBase
End Section 2 = 3 IBase
(As Per OEM Recommendation)
Slope Section 2 = 40 %
Slope Section 3 = 80 %
At +10% tap position, giving the transformer ratio is 122.25/25/11kV at 1.25 times the rated power
(End section 1) the 110 kV current is = (MVA*1.25 times / √3*HV Highest voltage)
= (80*1000)*1.25/(1.732*122.25)
= 472 A
= |1.125-1.25-1.25|
= 1.13 times of rated current
b) Stability of 80MVA transformer at full load and under operation at -15% Tap:
At -15% tap position, giving the transformer ratio is 94.75/25/11kV at 1.25 times the rated power
(End section 1) the 110 kV current is = (MVA*1.25 times / √3*LV Lowest voltage)
= (80*1000)*1.25/(1.732*94.75)
= 609 A
c) Stability of 80MVA transformer for through fault on 25kV and 11kV side at +10% Tap:
At +10% tap position, giving the transformer ratio for through fault on 25kV and 11kV at 1.25 times the rated
power
= (40/0.2734)
= 146.31
(End section 1) the 110 kV current is = (Fault MVA*1.25 times / √3*HV Highest voltage)
= (757.58*1000)*1.25/(1.732*122.25)
= 4472 A
25kV - LV1 side current = ((Fault MVA / ((√3*LV1 kV)*Ibase) / Irated [2]))
= (294.99*1000)/((1.732*25)*1.25)/923.79
= 9.22 times of rated current
11kV - LV2 side current = ((Fault MVA / ((√3*LV2 kV)*Ibase) / Irated [3]))
= (146.31*1000)/((1.732*11)*1.25)/2099.52
= 4.57 times of rated current
d) Stability of 80MVA transformer for through fault on 25kV and 11kV side at -15% Tap:
At -15% tap position, giving the transformer ratio for through fault on 25kV and 11kV at 1.25 times the rated
power
(End section 1) the 110 kV current is = (Fault MVA*1.25 times / √3*LV Lowest voltage)
= (757.58*1000)*1.25/(1.732*94.75)
= 5771 A
25kV - LV1 side current = ((Fault MVA / ((√3*LV1 kV)*Ibase) / Irated [2]))
= (294.99*1000)/((1.732*25)*1.25)/923.79
= 9.22 times of rated current
11kV - LV2 side current = ((Fault MVA / ((√3*LV2 kV)*Ibase) / Irated [3]))
= (146.31*1000)/((1.732*11)*1.25)/2099.52
= 4.57 times of rated current
11.01.04 Setting calculations for Low impedance restricted earth fault protection
IdMin Set is set to 20% of the full load current of transformer (LV1 side).
IdMin Set primary current (LV1) = (0.2*923.79)
= 185 A
IdMin Set secondary current (LV1) = Rated current of the transformer LV1 side/CT ratio
= (184.758*1)/(1000)
= 0.18 IBase
IdMin Set is set to 20% of the full load current of transformer (LV2 side).
IdMin Set primary current (LV2) = (0.2*2099.52)
= 420 A
IdMin Set secondary current (LV2) = Rated current of the transformer LV2 side/CT ratio
= (419.904*1)/(2500)
= 0.17 IBase
Relay operate angle for zero sequence directional feature if protected winding neutral point is grounded via
resistor increase ROA to 115 degrees
Discriminative time margin required = 0.20 sec (As per IEEE std.242-2001)
Hence, total operating time required = 0.70 sec
= (53.54/0.97)
I/Ip = 55.20 A
Since the three phase fault current is more than 20 times, hence the PSM choosen is 20.
11.01.06 Setting calculations for Residual Earth fault protection, four steps - 51N
= ((26200*1)/500)
= 52.40 A
= (52.4/0.4)
I/Ip = 131.00 A
Since the single phase fault current is more than 20 times, hence the PSM (I/Ip) choosen is 20.
11.01.09 Setting calculations for LV1 Standby Earth fault protection - 51Ns
Discriminative time margin required = 0.20 sec (As per IEEE std.242-2001)
Hence, total operating time required = 0.70 sec
Since the single phase fault current is more than 20 times, hence the PSM (I/Ip) choosen is 20.
11.01.10 Setting calculations for LV2 Standby Earth fault protection - 51Ns
Discriminative time margin required = 0.20 sec (As per IEEE std.242-2001)
Since the single phase fault current is more than 20 times, hence the PSM (I/Ip) choosen is 20.
Recommended
Parameter Setting Range
Settings
General Settings
CT sec1 1 - 10 A 1A
CT prim1 1 - 99999 A 500 A
CT sec2 1 - 10 A 1A
CT prim2 1 - 99999 A 500 A
CT sec3 1 - 10 A 1A
CT prim3 1 - 99999 A 500 A