Professional Documents
Culture Documents
Data:
I ). Relay type = 7UT6121-5EB22-1AA0
II ). Transformer Rating = 40 MVA
III ). Voltage at maximum tap Umax = 151.80 kV
IV ). Voltage at minimum tap Umin = 112.20 kV
V ). Transformation Ratio = 132 /12
VI ). Tap changing Range = + 15 % to - 15 %
Calculations:
A ). Rated Current
B ). Differential Initial Setting I - Diff >
C ). Differential Bias Slope Setting SLOPE 1
D ). Differential Bias Slope Limit SLOPE 2
E ). Differential Highest Setting I - Diff >>
F ). Magnetising Inrush Restraint Level
A Load Current:
where Umax, Umin are the voltages at the limits of the regulated range.
The voltage set on 132 kV side UHV = 2 x [(151.8 x 112.2) ÷ (151.8 +112.2)]
= 129.03 kV
HV SIDE :
Transformer Rated Current
HV regulated side = 40000 ÷ (√3 x 129.0) = 178.9817
SIEMENS Page 6 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
LV SIDE :
Transformer Rated Current
LV unregulated side = 40000 ÷ (√3 × 12.0) = 1924.501
Corresponding maximum full load current
on secondary side of CT I N2 = 1924.5009 ÷ 2500 / 5 A = 3.849
= 3.849 @ INObj
Differential current in max. tap position I Diff = IN1(+15%) − INObj (Refer 7UT manual page 34)
= I NObj 0.850 -1
= -0.150 I NObj
Differential current in min. tap position I Diff = IN1(-15%) − INObj = 1.15 *I NObj - I NObj
Differential current in min. tap position I Diff = 1.15 *I NObj - I NObj (Refer 7UT manual page 34)
= I NObj 1.150 -1
= 0.150 I NObj
SIEMENS Page 7 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
CT magnetizing errors and mismatching of Cts has been considered as= 0.015 %
○ Base Point 1
Considering the differential and restraining currents are equal at normal loading, therefore,
by straight line equation; m = (y2 - y1) ÷ (x2 -x1)
m= 1 - 0 ÷ 1 - 0 = 1
\
-1
tan = (m) = 45°
Since in the beginning, errors in Cts are unaccountable and differential / stabilizing
currents are balance, therefore, base point of slope 1 is to be selected as,
BASE POINT 1 = 0.00
(Available settings: 0.00 … 2.00 I/I no)
○ SLOPE 1
SIEMENS Page 8 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
e.g.
○ tap changer's regulation range of power transformer and
○ CT transformation manufacturing limitations.
These errors increases with increase in load, to find the suitable slope consider I diff = 20 %
Therefore at full load, current I 1 = 1 and due to 20% errors I2= 0.8
Then according to stabilising current equation,
I stab, x = I1 + I2 = 1 + 0.8 = 1.8
(Refer 7UT manual page 258)
Therefore, from the above calculations we found that slope 0.150 is better
compensated for errors.
But as per client's recommendation the slope setting is set 0.3 at full load.
\ I stab
x, = I1 + I2 = 1 + 0.8 = 1.8
I diff, y = m.X+b ( slope equation )
= 0.30 x 1.8
I diff = 0.540
SIEMENS Page 9 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
○ Base Point 2
This produces higher stabilization in the range of high currents which may lead to
current transformer saturation.
To consider base point for slope 2;
For higher load currents 25% overloading is considered, therefore,
○ SLOPE 2
● Address 1243 A Slope 2 provides stabilization in differential scheme in case of higher
through fault currents resulted current transformer saturation. The stability of the protec-
tion can be influenced by these settings.
To find the suitable slope consider the stabilization current, I stab y = m.X+b
For through fault current under heavy load, following satisfies
Now we set slope at 0.4 and check the suitability and veryfying the relation by;
I diff(act) < I diff(set)
I diff(set), y = m.X+b at m = 0.4 X = 9.469 b = -1
= 0.40 x 9.469 - 1
I diff(set) = 2.788
SIEMENS Page 10 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
Transformer
It is set to be as
(Available settings: 0.5 … 35 I/I no) I - Diff >> = 7.5 I/Ino
SIEMENS Page 11 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
In special cases it may be advantageous to delay the trip signal of the protection.
But for this case we will not use this delay time, and relay will give tripping command
as soon as it senses differential condition above threshold.
Therefore Time delay is set zero.
SIEMENS Page 12 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
F 2nd HARMONIC
The Inrush current can amount to a multiple of the rated current and is characterized
by a considerable 2nd harmonic content which is practically absent in the case of short-
circuit. Stabilization during inrush condition via 2nd harmonic content in differential current
is also detected by relay which just initiates blocking of the tripping.
\ Selected value = 15 %
( It is recommended by manufacturer which is sufficient in 90 % cases)
(Available settings: 10 … 80%)
This cross-block can be limited to a selectable duration and can be set from 0 to
1000 AC period. Normally this function is set ineffective, however, in abnormal inrush
condition this can be set to block in a defined ac period.
According to the inrush current report of the transformer we suggest the setting of
H nth Harmonic
Steady-state over excitation of transformer is characterized by odd harmonic
content. The 3rd or 5th Harmonic is suitable to detect over excitation as the
third harmonic is offered eleminated in the transformer windings (e.g. In a delta
connected winding group), The fifth harmonic is usually used to avoid trip during
over excitation, since the trafo is being used as distribution transformer, therefore,
nth Harmonic function is set
(Available settings: 10 … 80 % = 30%
SIEMENS Page 13 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
As per 7UT612 manual section 2.1.2, If a transformer winding is regulated, then the
actual rated voltage of the winding is not used as UN for the stabilized side,but the
voltage corresponding to the average current of the regulated range. The following
applies:
UN = 2 x [(Umax x Umin) ÷ (Umax + Umin)] (Refer 7UT manual page 21)
where Umax, Umin are the voltages at the limits of the regulated range.
The voltage set on 132 kV side UHV = 2x [(151.8 x 112.2) ÷ (151.8 +112.2)]
= 129.03 kV
\ the rated primary voltage = 129.0 kV
The rated voltage of transformer side 2 in kV (phase to phase) is set under this address.
\ the rated primary voltage = 12.0 kV
The primary rated apparent power of transformer is set under this address. The power
must always be entered as a primary value, even if the device is generally configured
in secondary values.
The apparent of transformer is = 40.00 MVA
(Available settings: 0.20 to 5000.00 MVA)
○ Starpoint of transformer
SIEMENS Page 14 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
In order to ensure the correct polarity for the differential currents, the CT starpoint
in direction of protected object is set under this address.
Selected setting = (Towards object)
(Furhter to be confirmed at site)
In order to ensure the correct polarity for the differential currents, the CT starpoint
in direction of protected object is set under this address.
Selected setting = (Towards object)
(Furhter to be confirmed at site)
SIEMENS Page 15 +
Energy Sector Projects/Engineering EM-TS PROJECTS /A5175/Relay Settings
SIEMENS
Setting Parameters
General Data:
Address Function Value
0270 Rated Frequency 50 Hz
0271 Rated Sequence L1,L2,L3
0312 Rated Apparent Power of Trafo side.1 40MVA
0322 Rated Apparent Power of Trafo side.2 40MVA
0311 Rated Primary Voltage side.1 129kV
0321 Rated Primary Voltage side.2 12kV
0313 Starpoint of side.1 Solid Grounded
0323 Starpoint of side.2 Resistor Grounded
0314 Trafo Winding Connection Side.1 Y(Wye)
0324 Trafo Winding Connection Side.2 Y(Wye)
0325 Vector Group Numeral of Side.2 0
Towards Object
0511 CT Starpoint in direction of object side.1
(Further to be confirmed at site)
Towards Object
0521 CT Starpoint in direction of object side.2
(Further to be confirmed at site)
Differential Protection
SIEMENS Page 16 +