Professional Documents
Culture Documents
Energy Efficiency in District Cooling System - 24
Energy Efficiency in District Cooling System - 24
System
CONTENTS
• Chilled water is generated at a single point to meet the requirements of entire site
Applicability
• Higher building density and high cooling demand
– Business districts
– Universities
• Diversity of cooling loads in different buildings
Benefits
• Reduction in system cooling capacity compared
to aggregate capacities of buildings
• Operating all equipment near to their optimum
conditions (Upon reaching to critical mass of
cooling demand)
Heat flow diagram
Building Side Central Chiller Plant
Air loop Chilled Plant CHW loop
Energy
Building Cooling Atmo-
A H Us Transfer Chillers
loads Tower sphere
Stations
Energy Efficiency
Distribution
in District
system
At 3 levels
Cooling System
Building side
Energy Efficiency practices –
Centralized chiller plant
Chilled
water
supply
temperature
– High
Chiller
selection &
operation
Chiller efficiency – C O P
9.6
9.5
9.3
9.2
8.7
10.0 8.2
8.2
7.7
6.7
8.0
5.1
COP
6.0
7.0
6.9
6.9
6.7
6.4
6.4
5.9
5.8
4.0
4.7
3.6
2.0
0.0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Loading
Source: Johnson chiller data
• Improvement in COP is in the range of 30 – 40 %
Effect of condenser water supply
temperature on chiller COP
Constant chilled water temperatures – 6 / 12
7.0
6.9
6.9
8.0
6.7
6.4
6.4
5.9
5.8
6.0
4.7
COP
3.6
5.1
5.1
5.0
5.0
4.0
4.2
4.0
3.7
3.2
2.0
2.8
2.8
0.0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Loading
Source: Johnson chiller data
9.6
9.5
9.3
9.2
• Hence, rise the chilled water 10.0
8.7
8.2
8.2
7.7
temperature as per the load 8.0
6.7
COP
7.0
5.1
6.9
6.9
6.0
6.7
6.4
6.4
5.9
5.8
4.0
4.7
3.6
2.0
0.0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Loading
VFD on
60 kW Fan
VFD on Condenser
VFD on Condenser 50 kW Pump
Pump
Situation 1
One chiller running at
full load
600 kW
Constant Primary
Pump
28 kW
Variable Secondary
Pump
Situation 2
Two chiller running at 50% part load
VFD on VFD on
Fan Fan
10.6 kW 10.6 kW
VFD on Condenser 8.8 kW VFD on Condenser 8.8 kW
Pump Pump
164 kW 164 kW
Variable Secondary
Pump
Performance Comparison
Situation 1
One chiller running
on full load
Situation 2
Two chiller running
on 50% part load
Installing VFDs for Centrifugal
Chillers
• VFD operation of compressor increases COP at part load
• VFD operation decreases energy consumption with same output , hence the higher COP
at part loads
Cooling Tower
7.0
6.9
6.9
6.7
6.4
6.4
rejection part of the chiller 7.0
5.9
5.8
6.0
4.7
• Condenser water supply temperature 5.0
COP
3.6
5.1
5.1
5.0
5.0
4.0
effects the COP of the chiller
4.2
4.0
3.7
3.0
3.2
2.8
2.8
• Lesser the condenser water supply 2.0
1.0
temperature, higher the COP of 0.0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
chiller
Loading
Effectiveness =
Hot Water Temperature (In)
Range / (Range + Approach)
Range
Cooling
wet bulb temperature of ambient air tower
Approach
• Approach depends on the effective Cold Water Temperature (Out)
Gliding CHW
temperature
at part loads
Approach of
cooling tower
should be low
Energy Efficiency practices -
Building side
Building side systems
Energy
Building Cooling
A H Us Transfer Chillers
Tower
Atmosphere
loads
Stations
50 % savings
60 %
60 %
Supply Air
29oC DB 43oC DB
Potential for Free Cooling in
Gandhinagar
• Provision to
bypass cooling
coil to
minimize fan Opening/closing of
energy dampers is automatic
through building
management system (BMS)
Incorporating Advanced
Technologies in District cooling
Click to edit
Master title style
130 C 5 0C
AHU
CHW loop
CHW loop
Central Chiller
plant @ 12 0C
Indo-Swiss Building Energy Efficiency Project 29
Chiller C O P - Improvement
9.6
9.5
9.3
9.2
8.7
10.0 8.2
8.2
7.7
6.7
8.0
5.1
COP
6.0
7.0
6.9
6.9
6.7
6.4
6.4
5.9
5.8
4.0
4.7
3.6
2.0
0.0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Loading
Source: Johnson chiller data
• Improvement in COP is in the range of 40 – 50 %
Indo-Swiss Building Energy Efficiency Project 30
Additional Benefits
to air systems
= 1 W / ft2
• Built in 2011
Indo-Swiss Building Energy Efficiency Project Source : Infosys_TechnicalPapaer_Guruprakash32sastry
CASE STUDY
Infosys - SDB 1 Building , Hyderabad
Building Energy Index for 2011 – 12
140
116.7
120
Conventional Radiant
100 85.9
80
kWh / Sq m
58.7
60
40 35.5 34.2
25.7
20 14.4 17.2
8.1 8.8
0
Lighting Misc. Power Computers HVAC Total
Utilty
• Radiant cooling system consumed 56 % less energy for HVAC than VAV
cooling system for 2011 – 12 FY
Source : Infosys_TechnicalPapaer_Guruprakash sastry
CASE STUDY
Infosys - SDB 1 Building , Hyderabad
Cost analysis for both the systems:
Conventional Radiant
No Utility
INR
1 Chiller 31 45 200 31 45 200
2 Cooling tower 13 06 400 13 06 400
7.0
COP
Off Peak load – night time
5.0
– day time
4.0
3.0
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Loading
• Chiller is being operated at lesser efficient load during both Peak load and
Off - peak load periods
Chiller with T E S - Operation
7.0
Discharging
-TES 6.0 Best efficient
COP
operation
5.0
Charging Charging
-TES -TES 4.0
3.0
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Loading