Phase resistance @ 20 °C - Star series 0,46
Overloads 10% for 1 hour every 12 hours
3-phase short circuit sustained current ≥ 300 % (3 In) with VARICOMP device
Voltage regulation accuracy ± 0,5 % In steady state condition
Radio interference EN 55011 - Class B Group 1
Wave form THF < 5%
Total harmonic content < 5% - At no load
STANDARDS
IEC 60034-1; CEI 2-3; BS 4999-5000; VDE 0530; NF 51-100,111; OVE M-10, NEMA MG 1.22.
pf 1
Efficiency [%]
pf 0,8
380 V 96
94
0% 25% 50% 75% 100% 125%
Load [%]
98
pf 1
Efficiency [%]
pf 0,8
400 V 96
94
0% 25% 50% 75% 100% 125%
Load [%]
98
pf 1
Efficiency [%]
pf 0,8
415 V 96
94
0% 25% 50% 75% 100% 125%
Load [%]
SIN.DT.037.4 Data and Technical Specification are subject to change in order to update or improve the products, without prior notice
THREE PHASE SYNCRONOUS GENERATOR
pf 1
Efficiency [%]
96 pf 0,8
416 V
94
92
0% 25% 50% 75% 100% 125%
Load [%]
98
pf 1
Efficiency [%]
96 pf 0,8
440 V
94
92
0% 25% 50% 75% 100% 125%
Load [%]
98
pf 1
Efficiency [%]
pf 0,8
460 V 96
94
0% 25% 50% 75% 100% 125%
Load [%]
98
pf 1
Efficiency [%]
pf 0,8
480 V 96
94
0% 25% 50% 75% 100% 125%
Load [%]
50 Hz - 1500 rpm
380 V 400 V 415 V
50
45
40
35
Voltage Dip [%]
30
25
20
15
10
5
0
0 1000 2000 3000 4000 5000 6000 7000
60 Hz - 1800 rpm
416 V 440 V 460 V 480 V
60
50
Voltage Dip [%]
40
30
20
10
0
0 1000 2000 3000 4000 5000 6000 7000
(*): A coefficient of 0,85 must be applied to the voltage dip if the load has a power factor equal or greater than 0,8.
SIN.DT.037.4 Data and Technical Specification are subject to change in order to update or improve the products, without prior notice