MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND

U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#1
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 18-May-23 Good B.SELIMOGLU
Design length 18-May-23 5995mm B.SELIMOGLU
Form set-up length 18-May-23 5995mm B.SELIMOGLU
As cast length 18-May-23 5995mm B.SELIMOGLU
Design depth 18-May-23 300mm B.SELIMOGLU
Form set-up depth 18-May-23 300mm B.SELIMOGLU
As cast depth 18-May-23 300mm B.SELIMOGLU
Design width 18-May-23 4510mm B.SELIMOGLU
Form set-up width 18-May-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 18-May-23 4512mm B.SELIMOGLU


Squareness 18-May-23 B.SELIMOGLU
Openings - N/A -
Embedded items location 18-May-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 18-May-23 In place B.SELIMOGLU
No twisting or unevenness 18-May-23 5mm max. B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 18-May-23 Fairly good B.SELIMOGLU
Form release agent 18-May-23 Yes B.SELIMOGLU excessive form oil observed
Inserts 18-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 18-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 18-May-23 Installed as per design B.SELIMOGLU
Stirrup 18-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 18-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 18-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 18-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 18-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 18-May-23 Installed in-place B.SELIMOGLU
Concrete slump and cube sampling 19-May-23 A101036/38 B.SELIMOGLU
Compaction and curing condition 19-May-23 Performed B.SELIMOGLU
Surface condition 19-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 19-May-23 No B.SELIMOGLU
No crack 19-May-23 No B.SELIMOGLU
No chipping 19-May-23 No B.SELIMOGLU
Edge straight 19-May-23 Yes B.SELIMOGLU
No excessive pinholes 19-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 19-May-23 B.SELIMOGLU


Element markings 19-May-23 Yes B.SELIMOGLU
Dimensions check on elements 19-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 19-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 19-May-23 Good B.SELIMOGLU
Finishing and repair works 19-May-23 No B.SELIMOGLU
Concrete Strength before delivery 22-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 19-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 2mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 Not observed B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 9-Aug-23 12mm B.SELIMOGLU at bottom side
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 9-Aug-23 5mm B.SELIMOGLU
Measured Camber
Longitudinal Alignment
Inserts 9-Aug-23 Yes B.SELIMOGLU
Cracks 9-Aug-23 Not observed B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 1 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#1

REFERENCE: PCI-MNL-116-99 APPENDIX E 2 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#2
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 23-May-23 Good B.SELIMOGLU
Design length 23-May-23 5995mm B.SELIMOGLU
Form set-up length 23-May-23 5995mm B.SELIMOGLU
As cast length 23-May-23 5994mm B.SELIMOGLU
Design depth 23-May-23 300mm B.SELIMOGLU
Form set-up depth 23-May-23 300mm B.SELIMOGLU
As cast depth 23-May-23 300mm B.SELIMOGLU
Design width 23-May-23 4510mm B.SELIMOGLU
Form set-up width 23-May-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 23-May-23 4510mm B.SELIMOGLU


Squareness 23-May-23 2mm max B.SELIMOGLU
Openings - N/A -
Embedded items location 23-May-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 23-May-23 In place B.SELIMOGLU
No twisting or unevenness 23-May-23 5mm B.SELIMOGLU at U channel bottom side
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 23-May-23 Good B.SELIMOGLU
Form release agent 23-May-23 Yes B.SELIMOGLU
Inserts 23-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 23-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 23-May-23 Installed as per design B.SELIMOGLU
Stirrup 23-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 23-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 23-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 23-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 23-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 23-May-23 Installed in-place B.SELIMOGLU one of two sunk in concrete
Concrete slump and cube sampling 23-May-23 A101073 B.SELIMOGLU
Compaction and curing condition 23-May-23 Performed B.SELIMOGLU
Surface condition 23-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 23-May-23 No B.SELIMOGLU
No crack 23-May-23 No B.SELIMOGLU
No chipping 23-May-23 No B.SELIMOGLU
Edge straight 23-May-23 Yes B.SELIMOGLU
No excessive pinholes 23-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 23-May-23 B.SELIMOGLU


Element markings 23-May-23 Yes B.SELIMOGLU
Dimensions check on elements 23-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 23-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 23-May-23 Good B.SELIMOGLU
Finishing and repair works 23-May-23 No B.SELIMOGLU
Concrete Strength before delivery 25-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 23-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 2mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 9-Aug-23 5mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 9-Aug-23 5mm B.SELIMOGLU
Measured Camber
Longitudinal Alignment 9-Aug-23 Yes B.SELIMOGLU
Inserts 9-Aug-23 Not observed B.SELIMOGLU
Cracks 9-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 3 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#2

REFERENCE: PCI-MNL-116-99 APPENDIX E 4 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#3
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 23-May-23 Good B.SELIMOGLU
Design length 23-May-23 5995mm B.SELIMOGLU
Form set-up length 23-May-23 5995mm B.SELIMOGLU
As cast length 23-May-23 5993mm B.SELIMOGLU
Design depth 23-May-23 300mm B.SELIMOGLU
Form set-up depth 23-May-23 300mm B.SELIMOGLU
As cast depth 23-May-23 300mm B.SELIMOGLU
Design width 23-May-23 4510mm B.SELIMOGLU
Form set-up width 23-May-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 23-May-23 4511mm B.SELIMOGLU


Squareness 23-May-23 3mm max B.SELIMOGLU
Openings - N/A -
Embedded items location 23-May-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 23-May-23 In place B.SELIMOGLU
No twisting or unevenness 23-May-23 5mm B.SELIMOGLU at channel bottoms
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 23-May-23 Good B.SELIMOGLU
Form release agent 23-May-23 Yes B.SELIMOGLU
Inserts 23-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 23-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 23-May-23 Installed as per design B.SELIMOGLU
Stirrup 23-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 23-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 23-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 23-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 23-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 23-May-23 Installed in-place B.SELIMOGLU
Concrete slump and cube sampling 23-May-23 A101074 B.SELIMOGLU
Compaction and curing condition 23-May-23 Performed B.SELIMOGLU
Surface condition 23-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 23-May-23 No B.SELIMOGLU
No crack 23-May-23 No B.SELIMOGLU
No chipping 23-May-23 No B.SELIMOGLU
Edge straight 23-May-23 Yes B.SELIMOGLU
No excessive pinholes 23-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 23-May-23 B.SELIMOGLU


Element markings 23-May-23 Yes B.SELIMOGLU
Dimensions check on elements 23-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 23-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 23-May-23 Good B.SELIMOGLU
Finishing and repair works 23-May-23 No B.SELIMOGLU
Concrete Strength before delivery 25-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 23-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 11mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 2mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 9-Aug-23 12mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 9-Aug-23 10mm B.SELIMOGLU
Measured Camber
Longitudinal Alignment 9-Aug-23 Yes B.SELIMOGLU
Inserts 9-Aug-23 Not observed B.SELIMOGLU
Cracks 9-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 5 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#3

REFERENCE: PCI-MNL-116-99 APPENDIX E 6 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#4
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 27-May-23 Good B.SELIMOGLU
Design length 27-May-23 5995mm B.SELIMOGLU
Form set-up length 27-May-23 5995mm B.SELIMOGLU
As cast length 27-May-23 5991mm B.SELIMOGLU
Design depth 27-May-23 300mm B.SELIMOGLU
Form set-up depth 27-May-23 300mm B.SELIMOGLU
As cast depth 27-May-23 300mm B.SELIMOGLU
Design width 27-May-23 4510mm B.SELIMOGLU
Form set-up width 27-May-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 27-May-23 4517mm B.SELIMOGLU


Squareness 27-May-23 3mm max B.SELIMOGLU
Openings - N/A -
Embedded items location 27-May-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 27-May-23 In place B.SELIMOGLU
No twisting or unevenness 27-May-23 5mm max B.SELIMOGLU at channel bottoms
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 27-May-23 Good B.SELIMOGLU
Form release agent 27-May-23 Yes B.SELIMOGLU
Inserts 27-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 27-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 27-May-23 Installed as per design B.SELIMOGLU
Stirrup 27-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 27-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 27-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 27-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 27-May-27 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 26-May-23 Installed in-place B.SELIMOGLU
Concrete slump and cube sampling 27-May-23 A101107 B.SELIMOGLU
Compaction and curing condition 27-May-23 Performed B.SELIMOGLU
Surface condition 27-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 27-May-23 No B.SELIMOGLU
No crack 27-May-23 No B.SELIMOGLU
No chipping 27-May-23 No B.SELIMOGLU
Edge straight 27-May-23 Yes B.SELIMOGLU
No excessive pinholes 27-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 27-May-23 11mm B.SELIMOGLU exterior face of wall surface


Element markings 27-May-23 Yes B.SELIMOGLU
Dimensions check on elements 27-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 27-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 27-May-23 Good B.SELIMOGLU
Finishing and repair works 27-May-23 No B.SELIMOGLU
Concrete Strength before delivery 29-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 27-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 7mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 4mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 9-Aug-23 4mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 9-Aug-23 5mm B.SELIMOGLU
Measured Camber
Longitudinal Alignment 9-Aug-23 Yes B.SELIMOGLU
Inserts 9-Aug-23 Not observed B.SELIMOGLU
Cracks 9-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 7 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#4

REFERENCE: PCI-MNL-116-99 APPENDIX E 8 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#5
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 18-Jun-23 Good B.SELIMOGLU
Design length 18-Jun-23 5995mm B.SELIMOGLU
Form set-up length 18-Jun-23 5995mm B.SELIMOGLU
As cast length 18-Jun-23 5994mm B.SELIMOGLU
Design depth 18-Jun-23 300mm B.SELIMOGLU
Form set-up depth 18-Jun-23 300mm B.SELIMOGLU
As cast depth 18-Jun-23 300mm B.SELIMOGLU
Design width 18-Jun-23 4510mm B.SELIMOGLU
Form set-up width 18-Jun-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 18-Jun-23 4510mm B.SELIMOGLU


Squareness 18-Jun-23 2mm max B.SELIMOGLU
Openings 18-Jun-23 In-place B.SELIMOGLU vent duct
Embedded items location 18-Jun-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 18-Jun-23 In place B.SELIMOGLU
No twisting or unevenness 18-Jun-23 5mm max B.SELIMOGLU at channel bottoms
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 18-Jun-23 Good B.SELIMOGLU
Form release agent 18-Jun-23 Yes B.SELIMOGLU
Inserts 18-Jun-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 18-Jun-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 18-Jun-23 Installed as per design B.SELIMOGLU
Stirrup 18-Jun-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 18-Jun-23 Installed in-place B.SELIMOGLU


Corrugated pipes 18-Jun-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 18-Jun-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves 19-Jun-23 In-place B.SELIMOGLU
MEP

Electrical Continuity 19-Jun-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 19-Jun-23 Installed in-place B.SELIMOGLU
Concrete slump and cube sampling 19-Jun-23 A101108 B.SELIMOGLU
Compaction and curing condition 19-Jun-23 Performed B.SELIMOGLU
Surface condition 19-Jun-23 Good (Class C) B.SELIMOGLU
No honeycomb 19-Jun-23 No B.SELIMOGLU
No crack 19-Jun-23 No B.SELIMOGLU
No chipping 19-Jun-23 No B.SELIMOGLU
Edge straight 19-Jun-23 Yes B.SELIMOGLU
No excessive pinholes 19-Jun-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 19-Jun-23 11mm B.SELIMOGLU exterior face of wall surface


Element markings 19-Jun-23 Yes B.SELIMOGLU
Dimensions check on elements 19-Jun-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 19-Jun-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 19-Jun-23 Good B.SELIMOGLU
Finishing and repair works 19-Jun-23 No B.SELIMOGLU
Concrete Strength before delivery 21-Jun-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 19-Jun-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 1mm B.SELIMOGLU bottom side
Variation from Specif. Plan Squareness (Max.) 9-Aug-23 12mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 9-Aug-23 7mm B.SELIMOGLU
Measured Camber
Longitudinal Alignment 9-Aug-23 Yes B.SELIMOGLU
Inserts 9-Aug-23 Not observed B.SELIMOGLU
Cracks 9-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 9 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#5

REFERENCE: PCI-MNL-116-99 APPENDIX E 10 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#6
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 27-May-23 Good B.SELIMOGLU
Design length 27-May-23 5995mm B.SELIMOGLU
Form set-up length 27-May-23 5995mm B.SELIMOGLU
As cast length 27-May-23 5986mm B.SELIMOGLU
Design depth 27-May-23 300mm B.SELIMOGLU
Form set-up depth 27-May-23 300mm B.SELIMOGLU
As cast depth 27-May-23 300mm B.SELIMOGLU
Design width 27-May-23 4510mm B.SELIMOGLU
Form set-up width 27-May-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 27-May-23 4513mm B.SELIMOGLU


Squareness 27-May-23 3mm max B.SELIMOGLU
Openings - N/A -
Embedded items location 27-May-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 27-May-23 In place B.SELIMOGLU
No twisting or unevenness 27-May-23 4mm max B.SELIMOGLU at channel bottoms
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 27-May-23 Good B.SELIMOGLU
Form release agent 27-May-23 Yes B.SELIMOGLU
Inserts 27-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 27-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 27-May-23 Installed as per design B.SELIMOGLU
Stirrup 27-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 27-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 27-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 27-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 27-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 27-May-23 Installed in-place B.SELIMOGLU
Concrete slump and cube sampling 27-May-23 A101095 B.SELIMOGLU
Compaction and curing condition 27-May-23 Performed B.SELIMOGLU
Surface condition 27-May-23 Fairly good (Class C) B.SELIMOGLU
No honeycomb 27-May-23 No B.SELIMOGLU
No crack 27-May-23 Observed B.SELIMOGLU corner crack on top
No chipping 27-May-23 No B.SELIMOGLU
Edge straight 27-May-23 Yes B.SELIMOGLU
No excessive pinholes 27-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 27-May-23 8mm B.SELIMOGLU exterior face of wall surface


Element markings 27-May-23 Yes B.SELIMOGLU
Dimensions check on elements 27-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 27-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 27-May-23 Good B.SELIMOGLU
Finishing and repair works 27-May-23 No B.SELIMOGLU
Concrete Strength before delivery 29-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 27-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 3mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 9mm B.SELIMOGLU bottom side
Variation from Specif. Plan Squareness (Max.) 9-Aug-23 13mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 9-Aug-23 2mm B.SELIMOGLU
Measured Camber
Longitudinal Alignment 9-Aug-23 Yes B.SELIMOGLU
Inserts 9-Aug-23 Not observed B.SELIMOGLU
Cracks 9-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 11 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#6

REFERENCE: PCI-MNL-116-99 APPENDIX E 12 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#7
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 31-May-23 Good B.SELIMOGLU
Design length 31-May-23 5995mm B.SELIMOGLU
Form set-up length 31-May-23 5995mm B.SELIMOGLU
As cast length 31-May-23 5992mm B.SELIMOGLU
Design depth 31-May-23 300mm B.SELIMOGLU
Form set-up depth 31-May-23 300mm B.SELIMOGLU
As cast depth 31-May-23 300mm B.SELIMOGLU
Design width 31-May-23 4510mm B.SELIMOGLU
Form set-up width 31-May-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 31-May-23 4514mm B.SELIMOGLU


Squareness 31-May-23 3mm max B.SELIMOGLU
Openings - N/A -
Embedded items location 31-May-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 31-May-23 In place B.SELIMOGLU
No twisting or unevenness 31-May-23 3mm max B.SELIMOGLU at channel bottoms
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 31-May-23 Good B.SELIMOGLU
Form release agent 31-May-23 Yes B.SELIMOGLU
Inserts 31-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 31-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 31-May-23 Installed as per design B.SELIMOGLU
Stirrup 31-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 31-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 31-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 31-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 1-Jun-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 31-May-23 Installed in-place B.SELIMOGLU one of two sunk in concrete
Concrete slump and cube sampling 31-May-23 A101106 B.SELIMOGLU
Compaction and curing condition 31-May-23 Performed B.SELIMOGLU
Surface condition 31-May-23 Fairly good (Class C) B.SELIMOGLU
No honeycomb 31-May-23 No B.SELIMOGLU
No crack 31-May-23 No B.SELIMOGLU
No chipping 31-May-23 No B.SELIMOGLU
Edge straight 31-May-23 Yes B.SELIMOGLU
No excessive pinholes 31-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 31-May-23 6mm B.SELIMOGLU exterior face of wall surface


Element markings 31-May-23 Yes B.SELIMOGLU
Dimensions check on elements 31-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 31-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 31-May-23 Good B.SELIMOGLU
Finishing and repair works 31-May-23 No B.SELIMOGLU
Concrete Strength before delivery 31-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 31-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 4mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 3mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 9-Aug-23 9mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 9-Aug-23 3mm B.SELIMOGLU
Measured Camber
Longitudinal Alignment 9-Aug-23 Yes B.SELIMOGLU
Inserts 9-Aug-23 Not observed B.SELIMOGLU
Cracks 9-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 13 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#7

REFERENCE: PCI-MNL-116-99 APPENDIX E 14 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#8
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 31-May-23 Good B.SELIMOGLU
Design length 31-May-23 5995mm B.SELIMOGLU
Form set-up length 31-May-23 5990mm B.SELIMOGLU
As cast length 31-May-23 5989mm B.SELIMOGLU
Design depth 31-May-23 300mm B.SELIMOGLU
Form set-up depth 31-May-23 300mm B.SELIMOGLU
As cast depth 31-May-23 300mm B.SELIMOGLU
Design width 31-May-23 4510mm B.SELIMOGLU
Form set-up width 31-May-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 31-May-23 4514mm B.SELIMOGLU


Squareness 31-May-23 3mm max B.SELIMOGLU
Openings - N/A -
Embedded items location 31-May-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 31-May-23 In place B.SELIMOGLU
No twisting or unevenness 31-May-23 7mm max B.SELIMOGLU at channel bottoms
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 31-May-23 Good B.SELIMOGLU
Form release agent 31-May-23 Yes B.SELIMOGLU
Inserts 31-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 31-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 31-May-23 Installed as per design B.SELIMOGLU
Stirrup 31-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 31-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 31-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 31-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 31-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 31-May-23 Installed in-place B.SELIMOGLU
Concrete slump and cube sampling 31-May-23 A101133 B.SELIMOGLU
Compaction and curing condition 31-May-23 Performed B.SELIMOGLU
Surface condition 31-May-23 Fairly good (Class C) B.SELIMOGLU
No honeycomb 31-May-23 No B.SELIMOGLU
No crack 31-May-23 No B.SELIMOGLU
No chipping 31-May-23 No B.SELIMOGLU
Edge straight 31-May-23 Yes B.SELIMOGLU
No excessive pinholes 31-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 31-May-23 6mm B.SELIMOGLU exterior face of wall surface


Element markings 31-May-23 Yes B.SELIMOGLU
Dimensions check on elements 31-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 31-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 31-May-23 Good B.SELIMOGLU
Finishing and repair works 31-May-23 No B.SELIMOGLU
Concrete Strength before delivery 2-Jun-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 31-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 4mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 6mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 9-Aug-23 15mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 9-Aug-23 9mm B.SELIMOGLU
Measured Camber
Longitudinal Alignment 9-Aug-23 Yes B.SELIMOGLU
Inserts 9-Aug-23 Not observed B.SELIMOGLU
Cracks 9-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 15 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#8

REFERENCE: PCI-MNL-116-99 APPENDIX E 16 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#9
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 13-Jun-23 Good B.SELIMOGLU
Design length 13-Jun-23 8220mm B.SELIMOGLU
Form set-up length 13-Jun-23 8217mm B.SELIMOGLU
As cast length 13-Jun-23 8220mm B.SELIMOGLU
Design depth 13-Jun-23 300mm B.SELIMOGLU
Form set-up depth 13-Jun-23 300mm B.SELIMOGLU
As cast depth 13-Jun-23 300mm B.SELIMOGLU
Design width 13-Jun-23 4510mm B.SELIMOGLU
Form set-up width 13-Jun-23 4510mm B.SELIMOGLU
MOULD INSPECTION

As cast width 13-Jun-23 4518mm B.SELIMOGLU


Squareness 13-Jun-23 7mm max B.SELIMOGLU
Openings 13-Jun-23 In-place B.SELIMOGLU vent duct
Embedded items location 13-Jun-23 In-place B.SELIMOGLU
Plate thickness - N/A -
Base Mould Support 13-Jun-23 In place B.SELIMOGLU
No twisting or unevenness 13-Jun-23 5mm max B.SELIMOGLU at channel bottoms
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 13-Jun-23 Good B.SELIMOGLU
Form release agent 13-Jun-23 Yes B.SELIMOGLU
Inserts 13-Jun-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 13-Jun-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 13-Jun-23 Installed as per design B.SELIMOGLU
Stirrup 13-Jun-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 13-Jun-23 Installed in-place B.SELIMOGLU


Corrugated pipes 13-Jun-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 13-Jun-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 7-Jun-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates 13-Jun-23 Installed in-place B.SELIMOGLU one of two sunk inside concrete
Concrete slump and cube sampling 13-Jun-23 A101257/58 B.SELIMOGLU
Compaction and curing condition 13-Jun-23 Performed B.SELIMOGLU
Surface condition 13-Jun-23 Fairly good (Class C) B.SELIMOGLU imperfections observed.
No honeycomb 13-Jun-23 No B.SELIMOGLU
No crack 13-Jun-23 No B.SELIMOGLU
No chipping 13-Jun-23 No B.SELIMOGLU
Edge straight 13-Jun-23 Yes B.SELIMOGLU
No excessive pinholes 13-Jun-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 13-Jun-23 5mm B.SELIMOGLU exterior face of wall surface


Element markings 13-Jun-23 Yes B.SELIMOGLU
Dimensions check on elements 13-Jun-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 13-Jun-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 13-Jun-23 Good B.SELIMOGLU
Finishing and repair works 13-Jun-23 No B.SELIMOGLU
Concrete Strength before delivery 15-Jun-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 13-Jun-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 9-Aug-23 4mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 9-Aug-23 8mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 6mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 5mm B.SELIMOGLU


Measured Camber
Longitudinal Alignment 9-Aug-23 Yes B.SELIMOGLU
Inserts 9-Aug-23 Not observed B.SELIMOGLU
Cracks 9-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 9-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES * Inspections made for wall panel exterior surfaces only. Interior surfaces of wall panels could not been inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 17 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-WP#9

REFERENCE: PCI-MNL-116-99 APPENDIX E 18 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#1
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 13-Jun-23 Good B.SELIMOGLU
Design length 13-Jun-23 8270mm B.SELIMOGLU
Form set-up length 13-Jun-23 8270mm B.SELIMOGLU
As cast length 13-Jun-23 8270mm B.SELIMOGLU
Design depth 13-Jun-23 400mm B.SELIMOGLU
Form set-up depth 13-Jun-23 400mm B.SELIMOGLU
As cast depth 13-Jun-23 400mm B.SELIMOGLU
Design width 13-Jun-23 3000mm B.SELIMOGLU
Form set-up width 13-Jun-23 3000mm B.SELIMOGLU
MOULD INSPECTION

As cast width 13-Jun-23 3005mm B.SELIMOGLU


Squareness 13-Jun-23 3mm max B.SELIMOGLU
Openings - N/A B.SELIMOGLU
Embedded items location 13-Jun-23 All installed in-place B.SELIMOGLU
Plate thickness 13-Jun-23 12mm B.SELIMOGLU
Base Mould Support 13-Jun-23 N/A B.SELIMOGLU prefabricated steel mould
No twisting or unevenness 13-Jun-23 Not observed B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 13-Jun-23 Good B.SELIMOGLU
Form release agent 13-Jun-23 Yes B.SELIMOGLU
Inserts 13-Jun-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 13-Jun-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 13-Jun-23 Installed as per design B.SELIMOGLU
Stirrup 13-Jun-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 13-Jun-23 Installed in-place B.SELIMOGLU


Corrugated pipes 13-Jun-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 13-Jun-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 7-Jun-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates - N/A -
Concrete slump and cube sampling 13-Jun-23 A101258 B.SELIMOGLU
Compaction and curing condition 13-Jun-23 Performed B.SELIMOGLU
Surface condition 13-Jun-23 Good (Class C) B.SELIMOGLU
No honeycomb 13-Jun-23 No B.SELIMOGLU
No crack 13-Jun-23 No B.SELIMOGLU
No chipping 13-Jun-23 No B.SELIMOGLU
Edge straight 13-Jun-23 Yes B.SELIMOGLU
No excessive pinholes 13-Jun-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness B.SELIMOGLU


Element markings 13-Jun-23 Yes B.SELIMOGLU
Dimensions check on elements 13-Jun-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 13-Jun-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 13-Jun-23 Good B.SELIMOGLU
Finishing and repair works 13-Jun-23 No B.SELIMOGLU
Concrete Strength before delivery 15-Jun-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 13-Jun-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 11-Aug-23 4mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 11-Aug-23 - B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 11-Aug-23 1mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.)


Measured Camber
Longitudinal Alignment
Inserts 11-Aug-23 Installed in-place B.SELIMOGLU
Cracks 11-Aug-23 Not observed B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 11-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES *Bottom side of roof panels could not be inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 19 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#1

REFERENCE: PCI-MNL-116-99 APPENDIX E 20 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#2
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 28-Apr-23 Good B.SELIMOGLU
Design length 28-Apr-23 8270mm B.SELIMOGLU
Form set-up length 28-Apr-23 8270mm B.SELIMOGLU
As cast length 28-Apr-23 8270mm B.SELIMOGLU
Design depth 28-Apr-23 400mm B.SELIMOGLU
Form set-up depth 28-Apr-23 400mm B.SELIMOGLU
As cast depth 28-Apr-23 400mm B.SELIMOGLU
Design width 28-Apr-23 3000mm B.SELIMOGLU
Form set-up width 28-Apr-23 3000mm B.SELIMOGLU
MOULD INSPECTION

As cast width 28-Apr-23 3000mm B.SELIMOGLU


Squareness 28-Apr-23 1mm B.SELIMOGLU
Openings - N/A B.SELIMOGLU
Embedded items location 28-Apr-23 All installed in-place B.SELIMOGLU
Plate thickness 28-Apr-23 12mm B.SELIMOGLU
Base Mould Support 28-Apr-23 N/A B.SELIMOGLU prefabricated steel mould
No twisting or unevenness 28-Apr-23 Not observed B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 28-Apr-23 Good B.SELIMOGLU
Form release agent 28-Apr-23 Yes B.SELIMOGLU
Inserts 28-Apr-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 28-Apr-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 28-Apr-23 Installed as per design B.SELIMOGLU
Stirrup 28-Apr-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 28-Apr-23 Installed in-place B.SELIMOGLU


Corrugated pipes 28-Apr-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 28-Apr-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 23-Apr-28 Performed B.SELIMOGLU SIs witnessed


Grounding Plates - N/A -
Concrete slump and cube sampling 28-Apr-23 A100812 B.SELIMOGLU
Compaction and curing condition 28-Apr-23 Performed B.SELIMOGLU
Surface condition 28-Apr-23 Good (Class C) B.SELIMOGLU
No honeycomb 28-Apr-23 No B.SELIMOGLU
No crack 28-Apr-23 No B.SELIMOGLU
No chipping 28-Apr-23 No B.SELIMOGLU
Edge straight 28-Apr-23 Yes B.SELIMOGLU
No excessive pinholes 28-Apr-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 28-Apr-23 B.SELIMOGLU


Element markings 28-Apr-23 Yes B.SELIMOGLU
Dimensions check on elements 28-Apr-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 28-Apr-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 28-Apr-23 Good B.SELIMOGLU
Finishing and repair works 28-Apr-23 No B.SELIMOGLU
Concrete Strength before delivery 30-Apr-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 28-Apr-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 11-Aug-23 6mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 11-Aug-23 1mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 11-Aug-23 3mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.)


Measured Camber
Longitudinal Alignment 11-Aug-23 Yes B.SELIMOGLU
Inserts 11-Aug-23 Not observed B.SELIMOGLU
Cracks 11-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 11-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES *Bottom side of roof panels could not be inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 21 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#2

REFERENCE: PCI-MNL-116-99 APPENDIX E 22 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#3
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 12-May-23 Good B.SELIMOGLU
Design length 12-May-23 8270mm B.SELIMOGLU
Form set-up length 12-May-23 8270mm B.SELIMOGLU
As cast length 12-May-23 8270mm B.SELIMOGLU
Design depth 12-May-23 400mm B.SELIMOGLU
Form set-up depth 12-May-23 400mm B.SELIMOGLU
As cast depth 12-May-23 400mm B.SELIMOGLU
Design width 12-May-23 3000mm B.SELIMOGLU
Form set-up width 12-May-23 3000mm B.SELIMOGLU
MOULD INSPECTION

As cast width 12-May-23 3000mm B.SELIMOGLU


Squareness 12-May-23 B.SELIMOGLU
Openings - N/A B.SELIMOGLU
Embedded items location 12-May-23 All installed in-place B.SELIMOGLU
Plate thickness 12-May-23 12mm B.SELIMOGLU
Base Mould Support 12-May-23 N/A B.SELIMOGLU prefabricated steel mould
No twisting or unevenness 12-May-23 Not observed B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 12-May-23 Good B.SELIMOGLU
Form release agent 12-May-23 Yes B.SELIMOGLU
Inserts 12-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 12-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 12-May-23 Installed as per design B.SELIMOGLU
Stirrup 12-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 12-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 12-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 12-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 23-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates - N/A -
Concrete slump and cube sampling 12-May-23 A100957 B.SELIMOGLU
Compaction and curing condition 12-May-23 Performed B.SELIMOGLU
Surface condition 12-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 12-May-23 No B.SELIMOGLU
No crack 12-May-23 No B.SELIMOGLU
No chipping 12-May-23 No B.SELIMOGLU
Edge straight 12-May-23 Yes B.SELIMOGLU
No excessive pinholes 12-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 12-May-23 B.SELIMOGLU


Element markings 12-May-23 Yes B.SELIMOGLU
Dimensions check on elements 12-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 12-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 12-May-23 Good B.SELIMOGLU
Finishing and repair works 12-May-23 No B.SELIMOGLU
Concrete Strength before delivery 14-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 12-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 11-Aug-23 3mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 11-Aug-23 6mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 11-Aug-23 2mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.)


Measured Camber
Longitudinal Alignment 11-Aug-23 Yes B.SELIMOGLU
Inserts 11-Aug-23 Not observed B.SELIMOGLU
Cracks 11-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 11-Aug-23 Class C and D finish B.SELIMOGLU No patching
NOTES *Bottom side of roof panels could not be inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 23 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#3

REFERENCE: PCI-MNL-116-99 APPENDIX E 24 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#4
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 16-May-23 Good B.SELIMOGLU
Design length 16-May-23 8270mm B.SELIMOGLU
Form set-up length 16-May-23 8270mm B.SELIMOGLU
As cast length 16-May-23 8270mm B.SELIMOGLU
Design depth 16-May-23 400mm B.SELIMOGLU
Form set-up depth 16-May-23 400mm B.SELIMOGLU
As cast depth 16-May-23 400mm B.SELIMOGLU
Design width 16-May-23 3000mm B.SELIMOGLU
Form set-up width 16-May-23 3000mm B.SELIMOGLU
MOULD INSPECTION

As cast width 16-May-23 3000mm B.SELIMOGLU


Squareness 16-May-23 B.SELIMOGLU
Openings - N/A B.SELIMOGLU
Embedded items location 16-May-23 All installed in-place B.SELIMOGLU
Plate thickness - 12mm -
Base Mould Support 16-May-23 N/A B.SELIMOGLU prefabricated steel mould
No twisting or unevenness 16-May-23 Not observed B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 16-May-23 Good B.SELIMOGLU
Form release agent 16-May-23 Yes B.SELIMOGLU
Inserts 16-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 16-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 16-May-23 Installed as per design B.SELIMOGLU
Stirrup 16-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 16-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 16-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 16-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 12-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates - N/A -
Concrete slump and cube sampling 16-May-23 A1010998 B.SELIMOGLU
Compaction and curing condition 16-May-23 Performed B.SELIMOGLU
Surface condition 16-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 16-May-23 No B.SELIMOGLU
No crack 16-May-23 No B.SELIMOGLU
No chipping 16-May-23 No B.SELIMOGLU
Edge straight 16-May-23 Yes B.SELIMOGLU
No excessive pinholes 16-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 16-May-23 B.SELIMOGLU


Element markings 16-May-23 Yes B.SELIMOGLU
Dimensions check on elements 16-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 16-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 16-May-23 Good B.SELIMOGLU
Finishing and repair works 16-May-23 No B.SELIMOGLU
Concrete Strength before delivery 18-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 16-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 11-Aug-23 2mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 11-Aug-23 3mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 11-Aug-23 7mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.)


Measured Camber
Longitudinal Alignment 11-Aug-23 Yes B.SELIMOGLU
Inserts 11-Aug-23 Not observed B.SELIMOGLU
Cracks 11-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 11-Aug-23 Class C and D finish B.SELIMOGLU
NOTES *Bottom side of roof panels could not be inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 25 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#4

REFERENCE: PCI-MNL-116-99 APPENDIX E 26 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#5
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 22-May-23 Good B.SELIMOGLU
Design length 22-May-23 8270mm B.SELIMOGLU
Form set-up length 22-May-23 8270mm B.SELIMOGLU
As cast length 22-May-23 8270mm B.SELIMOGLU
Design depth 22-May-23 400mm B.SELIMOGLU
Form set-up depth 22-May-23 400mm B.SELIMOGLU
As cast depth 22-May-23 400mm B.SELIMOGLU
Design width 22-May-23 3000mm B.SELIMOGLU
Form set-up width 22-May-23 3000mm B.SELIMOGLU
MOULD INSPECTION

As cast width 22-May-23 3002mm B.SELIMOGLU


Squareness 22-May-23 3mm B.SELIMOGLU
Openings - N/A B.SELIMOGLU
Embedded items location 22-May-23 All installed in-place B.SELIMOGLU
Plate thickness 22-May-23 12mm B.SELIMOGLU
Base Mould Support 22-May-23 N/A B.SELIMOGLU prefabricated steel mould
No twisting or unevenness 22-May-23 Not observed B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 22-May-23 Good B.SELIMOGLU
Form release agent 22-May-23 Yes B.SELIMOGLU
Inserts 22-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 22-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 22-May-23 Installed as per design B.SELIMOGLU
Stirrup 22-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 22-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 22-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 22-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 22-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates - N/A -
Concrete slump and cube sampling 22-May-23 A101068 B.SELIMOGLU
Compaction and curing condition 22-May-23 Performed B.SELIMOGLU
Surface condition 22-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 22-May-23 No B.SELIMOGLU
No crack 22-May-23 Yes B.SELIMOGLU corner edge crack on top surface
No chipping 22-May-23 No B.SELIMOGLU
Edge straight 22-May-23 Yes B.SELIMOGLU
No excessive pinholes 22-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 22-May-23 B.SELIMOGLU


Element markings 22-May-23 Yes B.SELIMOGLU
Dimensions check on elements 22-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 22-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 22-May-23 Good B.SELIMOGLU
Finishing and repair works 22-May-23 No B.SELIMOGLU
Concrete Strength before delivery 24-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 22-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 11-Aug-23 5mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 11-Aug-23 B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 11-Aug-23 2mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.)


Measured Camber
Longitudinal Alignment 11-Aug-23 Yes B.SELIMOGLU
Inserts 11-Aug-23 Not observed B.SELIMOGLU
Cracks 11-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 11-Aug-23 Class C and D finish B.SELIMOGLU no patching observed
NOTES *Bottom side of roof panels could not be inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 27 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#5

REFERENCE: PCI-MNL-116-99 APPENDIX E 28 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#6
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 26-May-23 Good B.SELIMOGLU
Design length 26-May-23 8270mm B.SELIMOGLU
Form set-up length 26-May-23 8270mm B.SELIMOGLU
As cast length 26-May-23 8270mm B.SELIMOGLU
Design depth 26-May-23 400mm B.SELIMOGLU
Form set-up depth 26-May-23 400mm B.SELIMOGLU
As cast depth 26-May-23 400mm B.SELIMOGLU
Design width 26-May-23 3000mm B.SELIMOGLU
Form set-up width 26-May-23 3000mm B.SELIMOGLU
MOULD INSPECTION

As cast width 26-May-23 3002mm B.SELIMOGLU


Squareness 26-May-23 3mm B.SELIMOGLU
Openings - N/A B.SELIMOGLU
Embedded items location 26-May-23 All installed in-place B.SELIMOGLU
Plate thickness 26-May-23 12mm B.SELIMOGLU
Base Mould Support 26-May-23 N/A B.SELIMOGLU prefabricated steel mould
No twisting or unevenness 26-May-23 Not observed B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 26-May-23 Good B.SELIMOGLU
Form release agent 26-May-23 Yes B.SELIMOGLU
Inserts 26-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 26-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 26-May-23 Installed as per design B.SELIMOGLU
Stirrup 26-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 26-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 26-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 26-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 22-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates - N/A -
Concrete slump and cube sampling 26-May-23 A101095 B.SELIMOGLU
Compaction and curing condition 26-May-23 Performed B.SELIMOGLU
Surface condition 26-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 26-May-23 No B.SELIMOGLU
No crack 26-May-23 Yes B.SELIMOGLU corner edge crack at the bottom
No chipping 26-May-23 No B.SELIMOGLU
Edge straight 26-May-23 Yes B.SELIMOGLU
No excessive pinholes 26-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 26-May-23 B.SELIMOGLU


Element markings 26-May-23 Yes B.SELIMOGLU
Dimensions check on elements 26-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 26-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 26-May-23 Good B.SELIMOGLU
Finishing and repair works 26-May-23 No B.SELIMOGLU
Concrete Strength before delivery 28-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 26-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 11-Aug-23 3mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 11-Aug-23 1mm B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 11-Aug-23 3mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.)


Measured Camber
Longitudinal Alignment 11-Aug-23 Yes B.SELIMOGLU
Inserts 11-Aug-23 Not observed B.SELIMOGLU
Cracks 11-Aug-23 No B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 11-Aug-23 Class C and D finish B.SELIMOGLU No patching observed
NOTES *Bottom side of roof panels could not be inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 29 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#6

REFERENCE: PCI-MNL-116-99 APPENDIX E 30 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#7
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 31-May-23 Good B.SELIMOGLU
Design length 31-May-23 8270mm B.SELIMOGLU
Form set-up length 31-May-23 8270mm B.SELIMOGLU
As cast length 31-May-23 8270mm B.SELIMOGLU
Design depth 31-May-23 400mm B.SELIMOGLU
Form set-up depth 31-May-23 400mm B.SELIMOGLU
As cast depth 31-May-23 400mm B.SELIMOGLU
Design width 31-May-23 3000mm B.SELIMOGLU
Form set-up width 31-May-23 3000mm B.SELIMOGLU
MOULD INSPECTION

As cast width 31-May-23 3000mm B.SELIMOGLU


Squareness 31-May-23 B.SELIMOGLU
Openings - N/A B.SELIMOGLU
Embedded items location 31-May-23 All installed in-place B.SELIMOGLU
Plate thickness 31-May-23 12mm B.SELIMOGLU
Base Mould Support 31-May-23 N/A B.SELIMOGLU prefabricated steel mould
No twisting or unevenness 31-May-23 Not observed B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 31-May-23 Good B.SELIMOGLU
Form release agent 31-May-23 Yes B.SELIMOGLU
Inserts 31-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 31-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 31-May-23 Installed as per design B.SELIMOGLU
Stirrup 31-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 31-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 31-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 31-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 22-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates - N/A -
Concrete slump and cube sampling 31-May-23 A101106 B.SELIMOGLU
Compaction and curing condition 31-May-23 Performed B.SELIMOGLU
Surface condition 31-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 31-May-23 No B.SELIMOGLU
No crack 31-May-23 No B.SELIMOGLU
No chipping 31-May-23 No B.SELIMOGLU
Edge straight 31-May-23 Yes B.SELIMOGLU
No excessive pinholes 31-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 31-May-23 B.SELIMOGLU


Element markings 31-May-23 Yes B.SELIMOGLU
Dimensions check on elements 31-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 31-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 31-May-23 Good B.SELIMOGLU
Finishing and repair works 31-May-23 No B.SELIMOGLU
Concrete Strength before delivery 31-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 31-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 15-Aug-23 B.SELIMOGLU
Horizontal Out of Spec (Max.) 15-Aug-23 B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 15-Aug-23 3mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 15-Aug-23 B.SELIMOGLU


Measured Camber
Longitudinal Alignment
Inserts 15-Aug-23 installed in-place B.SELIMOGLU
Cracks 15-Aug-23 Not observed B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 15-Aug-23 Class C and D finish B.SELIMOGLU no patching observed
NOTES *Bottom side of roof panels could not be inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 31 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#7

REFERENCE: PCI-MNL-116-99 APPENDIX E 32 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#8
Checklist Date Result Inspected by Remarks
Form condition / Cleanliness 31-May-23 Good B.SELIMOGLU
Design length 31-May-23 8270mm B.SELIMOGLU
Form set-up length 31-May-23 8270mm B.SELIMOGLU
As cast length 31-May-23 8270mm B.SELIMOGLU
Design depth 31-May-23 400mm B.SELIMOGLU
Form set-up depth 31-May-23 400mm B.SELIMOGLU
As cast depth 31-May-23 400mm B.SELIMOGLU
Design width 31-May-23 3000mm B.SELIMOGLU
Form set-up width 31-May-23 3000mm B.SELIMOGLU
MOULD INSPECTION

As cast width 31-May-23 3000mm B.SELIMOGLU


Squareness 31-May-23 B.SELIMOGLU
Openings - N/A B.SELIMOGLU
Embedded items location 31-May-23 All installed in-place B.SELIMOGLU
Plate thickness 31-May-23 12mm B.SELIMOGLU
Base Mould Support 31-May-23 N/A B.SELIMOGLU prefabricated steel mould
No twisting or unevenness 31-May-23 Not observed B.SELIMOGLU
Fitting - N/A -
Provision for bar protrusion or openings - N/A -
Level and anchorage - N/A -
Mould cleanliness 31-May-23 Good B.SELIMOGLU
Form release agent 31-May-23 Yes B.SELIMOGLU
Inserts 31-May-23 Installed in-place B.SELIMOGLU
Lifting loops (Type, Quantity) 31-May-23 4 each D25 bent rebar B.SELIMOGLU
No size and position 31-May-23 Installed as per design B.SELIMOGLU
Stirrup 31-May-23 Installed as per design B.SELIMOGLU
REINFORCEMENT

Lifting hooks and inserts 31-May-23 Installed in-place B.SELIMOGLU


Corrugated pipes 31-May-23 Installed in-place B.SELIMOGLU
Starter bars - N/A -
Anchorage and lapping - N/A -
Cover 31-May-23 Yes B.SELIMOGLU
Recessed or block outs and openings - N/A -
Electrical Services – conduit sleeves - N/A -
MEP

Electrical Continuity 22-May-23 Performed B.SELIMOGLU SIs witnessed


Grounding Plates - N/A -
Concrete slump and cube sampling 31-May-23 A101133 B.SELIMOGLU
Compaction and curing condition 31-May-23 Performed B.SELIMOGLU
Surface condition 31-May-23 Good (Class C) B.SELIMOGLU
No honeycomb 31-May-23 No B.SELIMOGLU
No crack 31-May-23 No B.SELIMOGLU
No chipping 31-May-23 No B.SELIMOGLU
Edge straight 31-May-23 Yes B.SELIMOGLU
No excessive pinholes 31-May-23 Not observed B.SELIMOGLU
CONCRETING

Flatness or evenness 31-May-23 B.SELIMOGLU


Element markings 31-May-23 Yes B.SELIMOGLU
Dimensions check on elements 31-May-23 Checked B.SELIMOGLU
Recess, groove line, water drip line 31-May-23 Not observed B.SELIMOGLU
Reinforcement, links, bar protrusion, fitting, and - N/A -
prestressing strands (if any)
Storage condition and stacking method 31-May-23 Good B.SELIMOGLU
Finishing and repair works 31-May-23 No B.SELIMOGLU
Concrete Strength before delivery 31-May-23 More than 20Mpa B.SELIMOGLU
Protection works for delivery 31-May-23 Yes B.SELIMOGLU
Vertical Out of Square (Max) 15-Aug-23 2mm B.SELIMOGLU
Horizontal Out of Spec (Max.) 15-Aug-23 B.SELIMOGLU
Variation from Specif. Plan Squareness (Max.) 15-Aug-23 4mm B.SELIMOGLU
FINISHED PRODUCT

Variation from Specif. Elev. End Squarness (Max.) 15-Aug-23 B.SELIMOGLU


Measured Camber
Longitudinal Alignment
Inserts 15-Aug-23 Installed in-place B.SELIMOGLU lift inserts
Cracks 15-Aug-23 Not observed B.SELIMOGLU
Chamfers N/A N/A -
Surface Textures N/A N/A -
Finishing and Patching 15-Aug-25 Class C and D finish B.SELIMOGLU no patching observed
NOTES *Bottom side of roof panels could not be inspected.

REFERENCE: PCI-MNL-116-99 APPENDIX E 33 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.


MUNITIONS STORAGE AREA POWIDZ AIR BASE, POLAND
U.S. AIR FORCE - NATO SECURITY INVESTMENT PROGRAM - POLISH MINISTRY OF NATIONAL DEFENSE POWIDZ AIR BASE - POLAND
CONTRACT NO: W912GB21C0031

PRODUCT INSPECTION SHEET


Location ECM C-01

ID
Element Tag No C01-RP#8

REFERENCE: PCI-MNL-116-99 APPENDIX E 34 / 34 HATCON INSAAT TAAH. IHRA. LTD. STI.