TECHNICAL SELECTION DATA SRA153C / SRG151E

SPLIT DUCTED UNIT

3 THREE
PHASE

SCROLL

3 Phase 1 Stage
SINGLE

15.27 kW
STAGE

ECM FAN

LOUVRE

AXIAL FAN

UNIT FEATURES SPECIFICATION SUMMARY


• Compliant Scroll Compressor
OUTDOOR UNIT MODEL SRA153C
• ECM High Efficiency Indoor Fan Motor
• Multiple Speed Outdoor Fans INDOOR UNIT MODEL SRG151E
• Blue Epoxy Coat Coil Fin Protection - Indoor & Outdoor Coils (1)(2)
TOTAL COOLING CAPACITY (kW) 15.27
• Louvred Outdoor Coil Guard
• Pre-charged with R410A Refrigerant
(1)(2)
TOTAL COOLING SENSIBLE CAPACITY (kW) 12.61
• Integral Fan Coil Safety Tray with Drain Kit (1)(3)
TOTAL HEATING CAPACITY (kW) 14.45
• Adaptive Demand Defrost
• Overheat Safety Protection / Anti-Freeze Protection - Indoor Coil
(4)
COOLING INPUT POWER (kW) 4.43
• LM7 Wall Controller Supplied as Standard (4)
HEATING INPUT POWER (kW) 3.95
• 20m Data Cable Included (1)(2)
EER 3.45
(1)(3)
COP 3.66
CONTROL FEATURES (5)
INDOOR AIRFLOW (l/s) - MIN. / NOMINAL / MAX. 690 / 770 / 880
• 7-Day Programmable Controller with 2 Events per Day
• Auto, Heat & Cool Modes OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) - LOW / HIGH 50.0 / 52.0
• Auto/Continuous Indoor Fan Operation OUTDOOR SOUND POWER LEVEL dB(A) - LOW / HIGH 67.0 / 69.0
• 3 Speed EC Indoor Fan
• Hot Start Feature POWER SUPPLY - OUTDOOR 400V / 3Ph+N / 50Hz
• Fault Indication - Relay Output POWER SUPPLY - INDOOR 230V / 1Ph+N / 50 Hz
• 24-Hour ON/OFF Timer (6)
RATED LOAD AMPS - OUTDOOR / INDOOR / TOTAL 7.1 / 4.2 / 11.3
• Home/Building Automation ON/OFF Capability
(7)
FULL LOAD AMPS - OUTDOOR / INDOOR / TOTAL 11.7 / 4.3 / 16.0

UNIT / CONTROL OPTIONS


(8)
CIRCUIT BREAKER AND CABLE AMPS 20.0
• ActronConnect Module for Wireless Control APPROXIMATE STARTING AMPS 51.5
• LM24W (24-Hour Wall Controller) - Optional WEIGHT (kg) - INDOOR / OUTDOOR 59 / 135
Secondary Wall Controller with Mimic Logic
• Remote Temperature Sensors (1)
Total Capacities are based on unit rating excluding indoor fan kW.
• Compressor Soft Starter (2)
At 270C DB / 190C WB entering air temperatures and 350C ambient.
• Zone Kit for Control up to 8 Zones (See Control Section) (3)
At 200C DB entering air temperature and 70C DB / 60C WB ambient.
• Additional Full Coil Coat Protection
(4)
Input power includes indoor fan kW.
(5)
Max. - Min. airflow application range.
(6)
Measured and tested in accordance with AS/NZS 3823.1.2.
PLENUMS (Optional) (7)
Full Load Amps are based on compressor and fan motors’ maximum expected current.
(8)
See Specifications sheet for cable size and circuit breaker size details.
• Supply Air Plenums are Available in a 2 way or 3 way
Configuration (See Accessories Section for details of Note: Use input power to estimate running cost.
Spigots availability)
• Return Air Plenums are Available with 2 x 350 mm or
2 x 400 mm Spigots

UNIT COMPLIANCE
• MEPS 2012 ®
R

• Demand Response AS4755.3.1

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd. Page 1 of 9 SRA153C-0100 / SRG151E-0100 REVISION 10.0 - 150708
CAPACITY SELECTION DATA SRA153C / SRG151E
COOLING PERFORMANCE
AIR ENTERING TOTAL TOTAL SENSIBLE CAPACITY - kW
OUTDOOR INDOOR CAPACITY AT DB TEMPERATURE ONTO INDOOR COIL - 0C
DB - 0C WB - 0C kW 20 21 22 23 24 25 26 27 28 29 30
16 15.97 9.67 10.58 11.48 12.36 13.23 13.95
17 15.97 8.78 9.65 10.56 11.46 12.36 13.22 14.01
18 16.29 7.82 8.75 9.63 10.55 11.45 12.33 13.23 14.05 14.79
25
19 16.70 6.85 7.80 8.75 9.61 10.52 11.42 12.32 13.21 14.05 14.83 15.51
20 17.07 5.85 6.82 7.77 8.72 9.58 10.49 11.39 12.30 13.19 14.04 14.85
21 17.56 5.83 6.78 7.75 8.68 9.54 10.47 11.36 12.25 13.16 14.02
22 18.00 5.81 6.75 7.71 8.65 9.58 10.42 11.32 12.23 13.12
16 15.42 9.40 10.30 11.20 12.08 12.91 13.55
17 15.39 8.51 9.38 10.30 11.20 12.08 12.93 13.70
18 15.67 7.57 8.50 9.36 10.28 11.17 12.06 12.93 13.76 14.39
30 19 15.99 6.60 7.55 8.48 9.35 10.26 11.16 12.05 12.92 13.76 14.51
20 16.39 5.62 6.58 7.53 8.46 9.33 10.24 11.14 12.03 12.91 13.77 14.56
21 16.86 5.58 6.54 7.49 8.44 9.31 10.20 11.11 12.02 12.88 13.74
22 17.28 5.55 6.51 7.46 8.40 9.26 10.17 11.08 11.97 12.85
3 Phase 1 Stage

16 14.82 9.11 10.02 10.91 11.77 12.55


17 14.82 8.23 9.10 10.01 10.90 11.77 12.60 13.31
15.27 kW

18 15.01 7.29 8.21 9.08 9.99 10.88 11.76 12.62 13.42


35 19 15.27 6.32 7.27 8.21 9.06 9.98 10.88 11.76 12.61 13.44 12.14
20 15.67 5.35 6.30 7.25 8.19 9.04 9.95 10.85 11.73 12.60 13.45 14.22
21 16.06 5.33 6.28 7.23 8.15 9.03 9.91 10.82 11.70 12.58 13.44
22 16.45 5.30 6.25 7.19 8.13 8.99 9.88 10.78 11.68 12.56
16 14.09 8.77 9.68 10.55 11.39 12.09
17 14.11 7.86 8.77 9.67 10.55 11.42 12.19
18 14.20 6.97 7.90 8.75 9.67 10.55 11.40 12.23 12.92
40 19 14.43 6.01 6.96 7.95 8.73 9.64 10.54 11.40 12.25 13.02
20 14.77 5.04 6.00 6.94 7.86 8.72 9.62 10.51 11.39 12.24 13.05 13.73
21 15.13 5.02 5.97 6.92 7.84 8.70 9.59 10.49 11.37 12.22 13.07
22 15.51 5.00 5.95 6.88 7.81 8.67 9.55 10.46 11.34 12.22
16 13.31 8.40 9.32 10.18 10.98
17 13.33 7.51 8.41 9.30 10.18 11.01 11.69
18 13.33 6.63 7.50 8.39 9.29 10.18 11.01 11.80
45 19 13.53 5.68 6.61 7.48 8.39 9.28 10.16 11.02 11.84 12.47
20 13.82 4.71 5.66 6.60 7.52 8.37 9.25 10.14 11.01 11.85 12.60
21 14.16 4.70 5.64 6.58 7.50 8.35 9.24 10.12 11.01 11.85 12.64
22 14.55 4.67 5.61 6.56 7.47 8.33 9.22 10.10 10.97 11.82
16 12.45 8.01 8.93 9.75 10.43
17 12.46 7.12 8.01 8.92 9.76 10.54
18 12.46 6.26 7.12 8.00 8.90 9.77 10.58
50
19 12.56 5.32 6.24 7.11 8.00 8.88 9.77 10.59 11.33
20 12.80 4.36 5.30 6.23 7.10 7.99 8.86 9.74 10.60 11.39
21 13.11 4.34 5.29 6.22 7.12 7.97 8.84 9.73 10.60 11.40 12.12
22 13.45 4.31 5.26 6.19 7.10 7.95 8.83 9.71 10.57 11.40

HEATING PERFORMANCE
HEATING CAPACITY - kW
WB TEMP
AT DB ENTERING INDOOR - 0C
ON OD
COIL- 0C 16 18 20 22 24
TH IH TH IH TH IH TH IH TH IH
-10 9.06 8.52 9.02 8.48 8.98 8.44 8.93 8.40 8.89 8.36
-8 9.68 9.00 9.63 8.95 9.57 8.90 9.52 8.85 9.47 8.81
-6 10.31 9.48 10.24 9.42 10.19 9.37 10.16 9.35 10.11 9.30
-4 10.97 9.82 10.89 9.75 10.87 9.73 10.80 9.67 10.74 9.61
-2 11.71 10.18 11.63 10.12 11.55 10.05 11.47 9.98 11.41 9.92
0 12.41 10.68 12.32 10.60 12.27 10.55 12.18 10.47 12.10 10.41
2 13.12 11.68 13.02 11.58 12.91 11.49 12.82 11.41 12.73 11.33
4 13.89 13.20 13.75 13.06 13.67 12.99 13.58 12.90 13.47 12.80
6 14.70 14.70 14.57 14.57 14.45 14.45 14.34 14.34 14.25 14.25
8 15.54 15.54 15.40 15.40 15.27 15.27 15.15 15.15 15.03 15.03
10 16.41 16.41 16.26 16.26 16.12 16.12 15.99 15.99 15.86 15.86
12 17.31 17.31 17.15 17.15 16.99 16.99 16.84 16.84 16.69 16.69
14 18.24 18.24 18.07 18.07 17.90 17.90 17.73 17.73 17.57 17.57 TH - Total Heating Capacity (kW).
16 19.21 19.21 19.01 19.01 18.83 18.83 18.64 18.64 18.46 18.46 IH - Integrated Heating Capacity (kW)
18 20.20 20.20 19.99 19.99 19.78 19.78 19.57 19.57 19.38 19.38 Includes defrost losses.

AIRFLOW CORRECTION MULTIPLIER


NOTES:
% VARIATION -10.39% -10% -5% NOMINAL 5% 10% 14.29% 1. No allowance has been made for the
INDOOR AIRFLOW (l/s) 690 693 732 770 809 847 880 effect of indoor fan motor.
TOTAL COOLING 0.983 0.985 0.994 1.000 1.008 1.014 1.020 2. Selection tables are based on nominal airflows.
SENSIBLE COOLING 0.939 0.941 0.971 1.000 1.030 1.057 1.081 Correction factors must be applied for selection
HEATING FACTOR 0.995 0.995 0.998 1.000 1.002 1.004 1.006 away from these conditions.

PIPE LENGTH CORRECTION MULTIPLIER


5m 10m 20m 30m 40m 50m 60m
COOLING 1.000 0.993 0.980 0.966 0.950 0.939 0.925
HEATING 1.000 1.000 1.000 1.000 1.000 1.000 1.000
Correction multipliers are based on horizontal pipe runs.
®
R

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd. Page 2 of 9 SRA153C-0100 / SRG151E-0100 REVISION 10.0 - 150708
DIMENSIONS AND FAN CURVE SRA153C / SRG151E
1320 O/A
OUTDOOR UNIT 255 565
SRA153C OVERALL NOMINAL DIMENSION (H x W x L)
= 990 x 1320 x 580
255 USE M12 BOLT FOR FEET MOUNTING
580
COMP O/A
PLEASE NOTE THAT UNDER ALL CIRCUMSTANCES, CONDENSER
AIR MUST NOT RECIRCULATE BACK ONTO CONDENSER COIL.
OUTDOOR COIL KEEP ALL CLEARANCES FREE OF ANY OBSTRUCTIONS
DRAIN
POINT
OUTDOOR OUTDOOR
AIR INLET AIR INLET OUTDOOR
AIR OUTLET
TOP VIEW
30

3 Phase 1 Stage

15.27 kW
65
990 925
O/A

550 OUTDOOR
AIR INLET

35
517 25
110 115 870 115 110 25
(MTG C-C DIST)
57.5 985
57.5
(MTG C-C DIST)
SIDE VIEW
FRONT VIEW
INDOOR UNIT
NOTES: THIRD ANGLE
SRG151E 1290 O/A
1. All dimensions are in mm unless specified.
PROJECTION
50 1100 70 2. Do not scale drawing.
3. Refer Pipe Connection Details on Specifications Sheet.
4. Additional Full Coil Coat Protection option available on all units.
INDOOR COIL

OVERALL NOMINAL DIMENSION (H x W x L)


575 = 412 x 1290 x 615
EC EC
INDOOR INDOOR SUPPLY DUCT (H x W) = 300 x 715
FAN FAN RETURN DUCT = 340 x 1100
DRAIN CONNECTION = 20mm OD

20 247.5 715 247.5 20 615 O/A

TOP VIEW 40 535 40


40 22

412 300 340


O/A SUPPLY
SUPPLY AIR RETURN
AIR AIR
80 72

50
1250 115

FRONT VIEW SIDE VIEW


INDOOR UNIT
FAN CURVE * 250
3.55 A
3.19 A
4.20 A
218
2.41 A 3.07 A
200

2.27 A 2.94 A 4.17 A


EXTERNAL STATIC
PRESSURE (Pa)

150

2.06 A 3.99 A
100 2.72 A
94

1.89 A 2.57 A 3.81 A * isPerformance Fan Curve shown


at Dry Coil Condition for
50
FD 9x7AM - 1/2Hp EC Fan.

0
500 550 600 650 700 750 800 850 900 950 1000
770

APPLICATION RANGE
®
R

AIRFLOW (l/s)

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd. Page 3 of 9 SRA153C-0100 / SRG151E-0100 REVISION 10.0 - 150708
SOUND DATA SRA153C / SRG151E

Outdoor Radiated

Sound Power
Level (SWL)

Fan Sound Power Level Octave Band Centre Frequency (Hz), dB


Speed dB(A)
125 250 500 1k 2k 4k 8k
Low 67.0 70.3 66.1 64.1 61.8 59.1 54.4 47.0
High 69.0 72.1 68.6 65.6 63.9 61.3 55.0 49.3
3 Phase 1 Stage

Indoor Outlet
15.27 kW

Sound Power
Level (SWL)

Sound Octave Band Centre Frequency (Hz), dB


Airflow Airflow
Power Level
Setting Li/s
dB(A) 125 250 500 1k 2k 4k 8k

Nominal 770 74.0 71.8 72.6 71.5 69.1 66.0 61.7 57.4

OUTDOOR RADIATED INDOOR OUTLET

SRA153C Sound Power Level SRG151E Sound Power Level

80.0 80.0
Octave Band Sound Power Level (dB)

Octave Band Sound Power Level (dB)

70.0 70.0

60.0 60.0

50.0 50.0

Low
Nominal
High
40.0 40.0
125 250 500 1k 2k 4k 8k 125 250 500 1k 2k 4k 8k

Octave Band Centre Frequency (Hz) Octave Band Centre Frequency (Hz)

NOTES:
1. Radiated sound power levels are based on ISO 3743-2.
2. Outlet sound power levels are based on ISO 13347-2.

®
R

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd. Page 4 of 9 SRA153C-0100 / SRG151E-0100 REVISION 10.0 - 150708
SPECIFICATIONS SRA153C / SRG151E
CONSTRUCTION COMPRESSOR
CABINET (Indoor Unit) 0.5 - 0.9 mm Galvanized Steel NUMBER PER UNIT x TYPE 1 x Scroll (Hermetic)
CABINET (Outdoor Unit) 0.9 - 1.2 mm Zinc & Galv. Steel FULL LOAD AMPS 10.0
SURFACE FINISH (Outdoor Unit) 65 μ Baked Polyester Powder Coat LOCKED ROTOR AMPS 51.5
STARTING METHOD D.O.L. (optional soft starter)
INSULATION (Indoor Unit)
10 mm Foil Faced Polyethylene REFRIGERATION SYSTEM
TYPE
12 mm Expanded Polystyrene REFRIGERANT TYPE R-410A
EXPANSION CONTROL Direct Expansion Orifice
ELECTRICAL
FACTORY CHARGE (grams) 4650
OUTDOOR UNIT
PRE-CHARGE LENGTH (metres) 15
Power Supply - 50 Hz 400 Volts x 3 Phase + N
ADDITIONAL REF. CHARGE (gm/m) 50
Voltage Range (min - max) 380 V - 440 V
Full Load Amps* 11.7 FILTER DRIER
Rated Load Amps** 7.1 CONNECTION SIZE & TYPE 9.5 mm (3/8”) ODF Soldered Bi-Flow
Approximate Starting Amps 51.5 FACTORY SUPPLIED / FITTED No

3 Phase 1 Stage
IP Rating IP44 See Installation Section for complete Filter Drier specifications.

15.27 kW
INDOOR UNIT
INTERCONNECTING PIPE RUN
Power Supply - 50 Hz 230 Volts x 1 Phase + N
MAX PIPE LENGTH (metres) 60
Voltage Range (min - max) 216 V - 253 V
MAX. VERTICAL LENGTH (metres) 20 (Included in Max. Pipe Length)
Full Load Amps* 4.3
FIELD PIPE SIZES
IP Rating IP20
Liquid Pipe 9.52 mm (3/8”)
OUTDOOR & INDOOR UNIT (TOTAL)
Gas Pipe 19.05 mm (3/4”)
Full Load Amps* - Phase 1 16.0
PIPE CONNECTIONS
Full Load Amps* - Phase 2 & 3 10.6
Indoor Liquid Pipe 9.52 mm (3/8”) Swaged to fit
Rated Load Amps** 11.3 9.52 mm (3/8”) field pipe
IMPORTANT - The local electricity authority may require limits on starting current and Gas Pipe 19.05 mm (3/4”) Swaged to fit
voltage drop, please check prior to purchase. 19.05 mm (3/4”) field pipe
* Full Load Amps are based on Compressor and Fan Motor’s maximum expected current. Outdoor Liquid Pipe 9.52 mm (3/8”) Swaged to fit
** Rated Load Amps are measured and tested in accordance with AS/NZS3823.1.2. 9.52 mm (3/8”) field pipe
Gas Pipe 19.05 mm (3/4”) Swaged to fit
CABLE SIZE & CIRCUIT BREAKER SIZE
Suggested minimum cable size should be used as a guide only, refer to AS/NZS 3000 19.05 mm (3/4”) field pipe
“Australian/New Zealand Wiring Rules” for more details. CONNECTION TYPE Solder
Cable Size (main line) 2.5 mm2 (SUGGESTED MINIMUM) Insulate both gas and liquid pipes separately.

Cable Size (indoor to outdoor wire) 1.0 mm2 (SUGGESTED MINIMUM)


PROTECTION DEVICES
Circuit Breaker Size 20.0 Amps HIGH PRESSURE CUTOUT SWITCH Nonadjustable (Automatic Reset)
OUTDOOR COIL LOW PRESSURE CUTOUT SWITCH Nonadjustable (Automatic Reset)
TUBE TYPE Copper - Rifle Bore COMPRESSOR MOTOR TEMP. Internal Thermal Cut-Out
FIN TYPE Aluminium - Wave INDOOR FAN OVERLOAD Internal Thermal Cut-Out

FACE AREA (m sqr) 1.10 OUTDOOR FAN OVERLOAD Internal Thermal Cut-Out
SUMP HEATER WATTS ‫٭‬ 30 W during Compressor Off Cycle
FIN SPACING (per m) 709
‫ ٭‬Crankcase Heater is to be disconnected for pipe lengths 8m or less.
COIL COATING Blue Epoxy Coat Coil Fin Protection
ROWS --- ELECTRIC CONTROLS
DEFROST METHOD Reverse Cycle
OUTDOOR FAN
DEFROST TYPE Adaptive Demand Defrost
NUMBER OF FANS x TYPE 2 x Axial
CONTROL CIRCUIT BREAKER 10.0 Amps
NUMBER OF BLADES PER FAN 5
CONTROL FIELD WIRING 2 Core 14 / 0.20 Screened Cable
DIAMETER (mm) 450
OUTPUT kW 0.145 OPERATING RANGE
It is essential that the unit is correctly sized for the application and operates within its
MOTOR TYPE / DRIVE TYPE 6 Pole External Rotor / Direct recommended range of operating conditions as shown below.
FAN SPEED CONTROL 2 Speed via Capacitor
INDOOR OUTDOOR
The standard type outdoor fans fitted to this unit will accept up to 5Pa MODE RANGE AIR INTAKE AIR INTAKE
of external static resistance.
TEMPERATURE TEMPERATURE
INDOOR COIL Max. 29oC DB / 19oC WB 50oC DB
Cooling
TUBE TYPE Copper - Rifle Bore Min. 20 C DB / 15 C WB
o o
15oC DB
FIN TYPE Aluminium - Louvre Max. 24oC DB 21oC DB / 16oC WB
Heating
FACE ARE (m sqr) 0.41 Min. 16oC DB -10oC DB

FIN SPACING (per m) 590 AIR FILTERS


COIL COATING Blue Epoxy Coat Coil Fin Protection All return air including fresh air must have adequate filters supplied and fitted by the
ROWS --- installing contractor. Filters must be located in accessible location between the
return air grille and the unit.-
ActronAir ® does not supply or make any provisions for return air filter.
INDOOR FAN
NUMBER OF FANS x TYPE 1 x Twin Deck Centrifugal EC Fan
DIAMETER / WIDTH (mm) 240 x 180
OUTPUT kW 0.373
MOTOR TYPE / DRIVE TYPE Variable Speed EC Motor / Direct

®
R

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd. Page 5 of 9 SRA153C-0100 / SRG151E-0100 REVISION 10.0 - 150708
15.27 kW
3 Phase 1 Stage

),(/':,5,1*)2506(5,(6 /(*(1'
&21752/621/<

®
5-62&.(76)25$&7521$,5
$0=
&$7(=21(&$%/(6 3&%-803(53,1 $0,%
&21'(16(5:,5,1* )86( 326,7,217$%/(6
&0 7; =21( =21( =21( =21(
 9$
$ 02'(/+$6 &%
(&),/7(5),77(' &&+
2)5& 3&%0RGHO$0,%3(&
%52:1 %/8( &0
&21'(16(5)$16 -XPSHU3LQ
2) 63(('&$3$&,7256 $&0RGHO
 ,1'225)$1 ,) 3RVLWLRQ &0&
1(87 $&7 5/<
%/$&. 02'(/ 2)5& /6& ,17(51$/$8725(6(7 $ 65*(
65$& 29(5/2$'3527(&7,21 (0&
2)5& 65$& % 65*(
%52:1 %/8(
65$& (&0 )
2) &21752/ ,) & 65*(

&0&
65$& +3
 02'8/( (&
%/$&. ' 65*(
,)
( 65*(
,)5&
,1'225
&2,/,1 /3

&&+
6(1625
)(55,7(
WIRING DIAGRAM

&% 6((-803(53,1 /6&


326,7,217$%/(6
$ )25&255(&7 2&%
6(77,1*

(&&21752/
2)

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd.
2)5&
59

/6&
7;

&0&
1
$
:&

59
$&7
1(87
($57+
'$7$
&20
.(<
3:5
&20
6&51

($57+
1(87
(0&

+3

/3
( 6(1625
1
$ .(<

%/(('
5(6,6725
&20
32:(5

+3
+3
$&7

5(9
2&%

+,*+

1(87
1(87

1(87

1(87
1(87

&203
($57+
127(
'2127
$&7 &211(&7
&21'(16(5&38%2$5' ,) 6&5((1$7
9,1'225)$1 :$//
212))
&21752/
&22/21/<21 )$8/7
67$*(21 ),(/':,5,1*%<

Page 6 of 9
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
%2267+($721
1(87 6(1625
,167$//(5
:$//&21752/
&217)$1 67$1'$5' .(<
6,1*/(63((' $//06(5,(6 6(772 127,&( &20
,1'225)$1 &21752/66(7

6:
67$1'$5'
21 7267$1'$5' 32:(5

3
'$<
2))
'8$/63(('
,1'225)$1
86(')25
$872)$1
5(027(212)) 237,21$/
0$18$/,13876
23(5$7,21 5(027(212))
:$//&21752/ 6:,7&+
67$1'$5'
86(21/<
',36:,7&+ 9
6(77,1*6

&38&+,3
'$7$

'&38
&20 6(1625:,5,1*

'$7$
,13876
6&5((1 237,21$/ 237,21$/

67(3
'(,&(
&$1&(/
7,0(56

&20

'()
),(/':,5,1*%<,167$//(5 6(1625 6(1625
&$%/(0867%(&25(6&5((1('&$%/(
:,7+75$&(:,5(&211(&7('727+(6&5((1&200217(50,1$/
287'225&2,/6(1625

%DVH0RGHO1R 9DULDWLRQ&RGH 9DULDWLRQ


5

& :$//&21752/632:(5 &206:$33('  5/  'HVFULSWLRQ


'',*,7$/&21752/6<67(0:,5,1*',$*5$0:,7+
SRA153C / SRG151E

% :,5()5202&%+,*+722) :$6*5(<  5/  06(5,(6,1'225%2$5' :$//&21752/

3&5 %\ 'DWH 7KLVGUDZLQJUHPDLQVWKHLQWHOOHFWXDOSURSHUW\RI$FWURQ(QJLQHHULQJ 'UDZQ 'DWH 'UDZLQJ1R 5HYLVLRQ 6L]H


5HY 'HVFULSWLRQ 5/ 
3W\/WG5HSURGXFWLRQPRGLILFDWLRQDQGRUGLVWULEXWLRQDUHSURKLELWHG
$SSURYHG 'DWH :' & $
$ 25,*,1$/ ZLWKRXWZULWWHQFRQVHQW 0-+ 

SRA153C-0100 / SRG151E-0100 REVISION 9.0 - 150218


OUTDOOR UNIT VARIATION SRA153C-H

H OUTDOOR UNIT - HORIZONTAL DISCHARGE FANS 5 Pa

OVERALL NOMINAL DIMENSION (H x W x L) 1320 O/A


= 960 x 1320 x 610 OUTDOOR OUTDOOR
USE M12 BOLT FOR FEET MOUNTING AIR INLET AIR INLET
OUTDOOR COIL
DRAIN
NOTES:
THIRD ANGLE POINT
1. All dimensions are in mm unless specified. COMP
PROJECTION
2. Do not scale drawing.
3. Additional Full Coil Coat Protection option available on all units.
4. Suggested Service Clearance and Airflow Allowances are based on
conditions that the spaces are free from obstructions and
walkway passage of 1000mm is available.
5. Minimum service access areas are responsibilities of the installer. OUTDOOR OUTDOOR
AIR OUTLET AIR OUTLET

3 Phase 1 Stage

15.27 kW
TOP VIEW
610 O/A

580 30 85 625 395 300

285

65
960 925 355
O/A ACCESS
PANEL
550

35
517 25
25 110 115 870 115 110
(MTG C-C DIST)
57.5 985 57.5
(MTG C-C DIST)

SIDE VIEW FRONT VIEW

MINIMUM SERVICE ACCESS CLEARANCES & AIRFLOW SPACE ALLOWANCES

300 mm PLEASE NOTE THAT UNDER ALL CIRCUMSTANCES, CONDENSER


AIRFLOW ALLOWANCE AIR MUST NOT RECIRCULATE BACK ONTO CONDENSER COIL.
KEEP ALL CLEARANCES FREE OF ANY OBSTRUCTIONS
LF LR
OUTDOOR COIL
STACKING OF UNITS
600 mm
SERVICE ONE IN FRONT OF THE OTHER SIDE BY SIDE
SERVICE
ACCESS
300 mm

CLEARANCE (DISTANCE BET. LF & LR) (DISTANCE BET. LF & RF)


(COMPRESSOR
& 600 mm 1500 mm
ELECTRICALS)
COMP

RF RR

1500 mm
AIRFLOW ALLOWANCE

HEIGHT CLEARANCE = 600

®
R

TOP VIEW

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd. Page 7 of 9 SRA153C-0100 / SRG151E-0100 REVISION 10.0 - 150708
INDOOR UNIT VARIATION SRG151E-V

V INDOOR UNIT - UPRIGHT FAN COIL WITH VERTICAL DISCHARGE

OVERALL NOMINAL DIMENSION (H x W x L)


= 875 x 1275 x 405
1275 O/A SUPPLY DUCT (H x W) = 300 x 715
25 RETURN DUCT (H xW) = 365 x 1095
DRAIN CONNECTION = 20mm OD

300 405
SUPPLY O/A
AIR
INDOOR COIL 80

TOP VIEW
3 Phase 1 Stage
15.27 kW

45 SUPPLY
75 1095
AIR
250 715 250 40

EC EC
INDOOR INDOOR FAN
ELECTRICAL 415
FAN FAN
BOX
875
RETURN 835 O/A
AIR
40 365

110

55
55 115 875 115 55 25 350 25

112.5 990 112.5


(MTG C-C DIST)
SIDE VIEW
FRONT VIEW

MINIMUM SERVICE ACCESS CLEARANCES & AIRFLOW SPACE ALLOWANCES

NO CLEARANCE
LF LR
THIRD ANGLE
NOTES:
(ELECTRICALS)

CLEARANCE

1. All dimensions are in mm unless specified.


EC
600 mm

PROJECTION
2. Do not scale drawing.
INDOOR
NO

3. Refer Fan Curve to corresponding standard SRG151E model.


FAN
4. Additional Full Coil Coat Protection option available on all units.
5. Suggested Service Clearance and Airflow Allowances are based on
INDOOR COIL conditions that the spaces are free from obstructions and
RF RR walkway passage of 1000mm is available.
6. Minimum service access areas are responsibilities of the installer.

600 mm STACKING OF UNITS


SERVICE CLEARANCE
ONE IN FRONT OF THE OTHER SIDE BY SIDE
(FAN COIL & INDOOR FAN)
(DISTANCE BET. LF & LR) (DISTANCE BET. LF & RF)

600 mm 1000 mm

HEIGHT CLEARANCE = DUCT WORK

TOP VIEW

®
R

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd. Page 8 of 9 SRA153C-0100 / SRG151E-0100 REVISION 10.0 - 150708
INDOOR FAN DATA / FAN CURVE SRG151E-B

B INDOOR UNIT - WITH 3RD PARTY CONTROL

EXTERNAL STATIC PRESSURE (Pa)

AIRFLOW 50 75 100 125 150 175 200


(l/s) % PWM W % PWM W % PWM W % PWM W % PWM W % PWM W % PWM W
690 64 298 69 341 71 360 77 421 81 467 86 515 90 559

700 65 301 70 344 74 384 78 425 82 472 87 519 91 562

725 69 325 73 365 77 409 81 453 86 499 90 547 96 591

750 72 345 76 389 81 437 85 481 90 530 95 579

770 74 370 79 411 84 468 88 516 93 560 98 609

775 75 374 80 417 85 471 89 518 94 564

3 Phase 1 Stage

15.27 kW
800 79 398 84 443 89 495 94 546 98 596

825 83 426 88 475 93 525 98 582

850 87 455 92 510 97 566 MOTOR / BLOWER LIMIT

875 92 500 97 556

880 93 507 98 564

NOTES:
W = Indoor Fan Power, Watts (CPI3-2) RESIDENTIAL PWM INTERFACE BOARD
PWM = Pulse Width Modulation Setting, % PWM
JUMPER PIN JUMPER
(Adjustable through CPI3-2 Board located in electrical panel).
PWM1 OUT

P3 MODEL

DISP2 DISP1 R10


A
SET AS PER PIN INDOOR FAN
Factory PWM Setting = 84 % PWM for 100 Pa.
R4 C7 R11 B

TABLE ON RIGHT
R12

LED FAN
R3 C

POSITION
R2
R13 D
D3

- Data in the box indicates Factory Default Setting.


R14
R1 E

PWM
R15
C5 F
C8
U4 U3 INPUT
ADJUST

A SRG091E
GND 0 - 10V

DISPLAY PWM
V2.1

V2 RV1 +

C2
C3
P6
ADJUSTMENT
(POTENTIOMETER) B SRG131E
C1
D1
TRA-0100-R

DAMAGE DUE TO
+ INCORRECT WIRING
D2 VOIDS WARRANTY

CPI3-2

C SRG151E
S/N: XXXXXXXX

P5

CPI 3
P1 23787-3

ActronAir
IF IF
PWR ON/OFF 240VAC IN
D SRG171E

NOTES: E SRG201E
• LED will show PWM without %.
Example: 84% PWM = 84 in LED. F NOT USED
• LED adjustments are in 1 digit increment.

200

175

MOTOR / BLOWER LIMIT


150
EXTERNAL STATIC
PRESSURE (Pa)

125
99
%
95 PW
84% PWM % M
PW
100 90 M
%
PW
M
85
75 %
PW
75% 80 M
%
PW PW
M M
50 70%
PW
65% M
PW
M
25 60
%
PW
55% M
PW
M
0
650 675 700 725 750 775 800 825 850 875 900
770

APPLICATION RANGE

Nominal Airflow = 770 l/s ®


R

AIRFLOW (l/s)

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
®

Please check prior to purchase. Copyright © 2015 Actron Engineering Pty. Ltd. Page 9 of 9 SRA153C-0100 / SRG151E-0100 REVISION 10.0 - 150708

You might also like