Current Transformers Test Report Akim Transformatörü Test Raporu
Current Transformers Test Report Akim Transformatörü Test Raporu
Composite Error OK
(Birleşik Hata)
VALUES OF SATURATION
DOYMA DEĞERLERİ
EXPLANATION / Açıklama :
TERMINALS Rct
CORE1&2 :5P20-15VA;Ek>=530V,Rct<=18 ohm.Icth :1.2xIn TERMİNALLER (@ 75°C) Ikn (A) Vkp (V)
(Ohm)
1S1-1S2 15.60 21.14mA 702.5V
RATIO / ÇEV. ORANI : 2500/1-1A
2S1-2S2 15.62 22.04mA 699.6V
INSULATION TEST IEC 61869-2 (CLAUSE 7.3.1 and 7.3.3/7.3.4)
YALITIM TESTLERİ
PWR.FRQ.ON PRI.WNDG BETWEEN PRIM.WNDG PWR.FRQ.ON SEC.WNDG. BETWEEN SEC. WNDG.
PRİMER YALITIM TESTİ SEK. YALITIM TESTİ SEK. YALITIM TESTİ SEK. SARGILAR ARASI
28 kV --- 3 kV 3 kV
OK OK OK
C1= PF
VALUES CAPACITIVE
C2= PF
1 00 -0,01 1
1 20 -0,01 1
1 00 -0,02 1
1 20 -0,02 1
PARTIAL DISCHARGE TEST IEC 61869-1 (CLAUSE 7.3.2) INSULATION RESISTANCE TEST
KISMİ DEŞARJ TESTİ
VOLTAGE/GERİLİM 1.2Um 1.2Um/V3 Prim - Sec + GndSec - Prim + Gnd Prim1 - Prim2 + Gnd Sec1 - Sec2 + Gnd
(kv)
LEVEL/SEVİYE 12 (pC) 2 (pC)
DATE 04/08/2023 TEST OPERATOR EKO SASMITO APPROVED
Tarih Test Operatörü Onay
This document is electronically signed by authorized personnel, the signatories may vary in case of printing out and wet signing.
Form No: IMS-F-QSHE-08 REV 02 23-10-2015