FROM THE GENERAL MANAGER & CEO
When it comes to cooling large buildings many HVAC engineers simply default to standard
practices.
This issue of idronics addresses these contemporary methods and details several modern
hydronic concepts such as water source heat pumps, ice storage, heat recovery chillers,
radiant cooling, chilled beams, variable speed pumping, hydraulic separation and heat
metering. These concepts provide engineers with a wide palette of design opportunities,
and the ability to go far beyond “standard practice.”
We hope you enjoy this issue of idronics and encourage you to send us any feedback by
e-mailing us at idronics@caleffi.com.
For prior issues please visit us at www.caleffi.us, and click on the icon. There you
can download the PDF files. You can also register to receive hard copies of future issues.
Mark Olson
p.s. If a maintenance manager for a major Dallas hotel ever mentions the curious way a
customer was able to remove a tamper-proof HVAC panel, mums the word!
3
TABLE OFOF
TABLE CONTENTS
CONTENTS
5 Introduction
26
28
Reduced Electrical Energy Usage Chilled-Beam Cooling
7 Chilled
Pipe & Water
fittingOptions
nomenclature Possible Use Of Rejected Heat
Ease Of Zoning
Pipe vs. tube Thermal Storage
No Coil Frosting Lower Refrigerant Volume
Pipe size
11 A survey
Pipe fitting terminology
January2020
January 2020 of commercial cooling options
Biomass boilers
Window air conditioners “Classic” chiller/tower cooling for larger
Couplings
Packaged terminal air conditioners buildings
Elbows
(ptac units) Water-side economizers
Ductless mini-split heat pumps Chiller efficiency
14 Variable refrigerant flow (vrf) systems Continuing improvement
12 Rooftop
Metal units
pipe joining methods & materials
Steel pipe
22 Fundamental
Stainlesscooling concepts
steel pipe
Temperature & humidity indices Psychrometric chart
Wrought iron pipe
Dry-bulb temperature Sensible heat ratio
Blacktemperature
Wet-bulb iron pipe Cooling loads
Cast iron pipe
Dewpoint temperature Ventilation cooling load
A Technical Journal
Copper
Absolute water tube
humidity Energy recovery ventilation systems
from Relative
Brasshumidity
Bronze
CALEFFI NORTH AMERICA, INC
30 Metallurgical
Contemporary joining
sources formethods
chilled water
3883 W. Milwaukee Rd Soft air-to-water
Multiple soldering heat pumps as Air-cooled condensers with direct
chillers
Brazing expansion heat exchangers
Milwaukee, Wisconsin 53208 Multiple water-to-water heat pumps as Lake source cooling
Welding
USA chillers Lake water heat exchangers
Heat recovery chillers Buffer tanks for multiple chiller systems
E-mail: idronics@caleffi.com
47 Radiant
Cross-linked Polyethylene
panel & chilled
Oxygen diffusion
tubing (PEX)
beam systems
Radiant panels for cooling Dedicated outdoor air systems (doas)
Composite
Radiant PEX-AL-PEX tubing
floor cooling Latent cooling loads for chilled beams &
Website: www.caleffi.us
Polyethylene-raised
Radiant ceiling panels temperature tubing (PE-RT)
radiant panels
Chilled beams
PolyPropylene-random tubing (PP-R) Piping for decoupled sensible & latent loads
Fusion joining methods
To receive future idronics issues
58 Water loop heat pump systems
FREE, register online 41 Geothermal
Summary water loop heat pump
systems
www.caleffi.us
63 Ice-based thermal storage cooling systems
© Copyright 2019
Caleffi North America, Inc. 69 Appendix A: Generic piping symbol legend
Disclaimer: Caleffi makes no warranty that the information presented in idronics meets the mechanical, electrical or other code requirements
applicable within a given jurisdiction. The diagrams presented in idronics are conceptual, and do not represent complete schematics for any
specific installation. Local codes may require differences in design, or safety devices relative to those shown in idronics. It is the responsibility
4
4 N° 55 giugno 2019
INTRODUCTION
Figure 1-1
In 1758, Benjamin Franklin demonstrated that evaporation
of volatile compounds, such as ether, could cause the
object from which the evaporation was occurring to drop
below room temperature. During one of his experiments,
he managed to lower the temperature of a thermometer
from 64ºF down to 7ºF. Today, the evaporation of
refrigerant compounds is an essential process in millions
of cooling systems.
Figure 1-3
5
the body. However, fans alone cannot reduce interior Figure 1-5
humidity, and thus, were not a complete comfort solution.
Figure 1-4
Courtesy of Aermec
Some historians consider it one of the major technical
accomplishments of the 20th century.
6
ADVANTAGES OF HYDRONIC-BASED COOLING
Several methods for cooling commercial and institutional
buildings have been developed based on the use of Figure 2-1
56"
chilled water as the primary energy transport media.
These methods offer several distinct advantages that 2"
cannot be matched by “all-air” systems. They include:
air duct
24"
• Minimally invasive installation 2" tube
• Reduced electrical energy usage conveying
• Adaptability to many sources of chilled water water
• Easy zoning 2"
• No coil frosting
• Adaptability to radiant panel cooling air duct
40"
• Adaptability to chilled-beam cooling 2" tube
• Possibility of use of rejected heat conveying
water
• Adaptability to thermal storage
• Low refrigerant volume relative to VRF systems
Surface area of 2"copper tube = 0.556 sq ft/ linear ft
Each of these advantages is briefly described in this Surface area of 24"x56" duct = 13.33 sq ft/ linear ft
section. They will be more fully explained and applied in Surface area ratio = 24:1
later sections.
MINIMALLY INVASIVE INSTALLATION greater than that into the tube, assuming approximately
The heat capacity of water is 62.4 Btu/ft3/ºF. The heat equal internal temperatures and insulation R-values.
capacity of air is 0.018 Btu/ft3/ºF. The difference in this
thermal property allows liquid water to absorb almost REDUCED ELECTRICAL ENERGY USAGE
3,500 times more heat than the same volume of air. A cooling distribution system operating with chilled water
This has profound implications regarding the size of the can use significantly less electrical power compared to
piping required to convey chilled water through a building a forced-air distribution system of equivalent thermal
versus the size of ducting required to move a thermally capacity. The difference can be expressed through a
equivalent amount of air through that building. calculation of distribution efficiency, which is defined by
Formula 2-1:
For example, a 2-inch copper tube carrying chilled
water at a flow rate of 40 gallons per minute to a large Formula 2-1
air handler, and undergoing a temperature increase of
15ºF across the coil of that air handler, is absorbing rate of heating or cooling delivery(Btu/hr)
Distribution efficiency =
heat at a rate of 300,000 Btu/hr. To do this with a duct electrical power input to operate delivery system(watt)
operating at a face velocity of 1,000 feet per minute
and an air temperature change of 30ºF would require Here’s one comparison: Published data for the blower in a
a duct 24 inches deep and 56 inches wide, or a round geothermal water-to-air heat pump
53,000Btu/hr Btuusing
/ hr forced-air delivery
duct about 40 inches in diameter, as shown in Figure Distribution efficiency =
indicates that a 3/4-horsepower
690 watt
= 76.8
electronically
watt commuted
2-1. Accommodating such large ducts in commercial motor is required to deliver approximately 1500 CFM airflow
and institutional buildings usually requires a mechanical through a duct system. The estimated electrical input power
chase located above a suspended ceiling. This adds to to this motor 53,000
when operating atrate fullofcapacity
53,000 heating oris 690 watts.
cooling delivery(Btu/hr)
building height as well as cost. f = Distribution
The500 rated
=
× ∆Ttotal500cooling
10
= 10.6gpm
×efficiency =
capacity of this heat pump is about
electrical power input to operate delivery system(wat
53,000 Btu/hr (based on 60ºF entering fluid temperature
Piping carrying chilled water and ducting carrying chilled from the geothermal source). The heat pump’s distribution
air require insulation to prevent surface condensation. efficiency
0.4344 ×under
f × ∆ P these
0.4344conditions
× 10.6 × 5.6 is:
The 24-inch x 56-inch rectangular duct shown in Figure w=
e
= = 64.5watt
0.40 53,000Btu/hr Btu / hr
2-1 has 24 times more surface area compared to the Distribution efficiency = = 76.8
2-inch copper tube. Insulating the duct against surface 690 watt watt
condensation would require 24 times as much insulation An equivalent
efficiencyhydronic
53,000Btu /system
= 247 is assumed to have
hr Btu / hr
Distribution =
material as using the same insulation on the copper tube. 200 feet equivalent (64.5w + 150w)of 1-inch
length watt copper tubing. It
Undesirable heat gain into the duct will be substantially will operate 53,000with a 10ºF
53,000 chilled-water temperature rise
f = = = 10.6gpm
500
IPLV = 0.01A × ∆T+ 0.45C
+ 0.42B × 10
500+ 0.12D
q q 7
SHR = s
=0.4344
s
× f × ∆ P 0.4344 × 10.6 × 5.6
wqT= qs + qL = = 64.5watt
e 0.40
rate of heating or cooling delivery(Btu/hr)
Distribution efficiency =
electrical power input to operate delivery system(watt)
across a radiant ceiling panel. The hydronic system uses It’s important to remember that all electrical input to a
a circulator with an electronically commutated
rate of heatingmotor withdelivery(Btu/hr)
or cooling cooling distribution system ultimately becomes a heat
Distribution efficiency =
a wire-to-water efficiency of electrical
40%. 53,000Btu/hr
power input to operate hr gain
Btu / delivery to the building. When high energy efficiency is a
system(watt)
Distribution efficiency = = 76.8
690 watt watt primary design goal, it is imperative to minimize the
The water flow rate required for delivering 53,000 Btu/hr electrical input power required to create cooling effect
at a 10ºF temperature change is: AND move that effect through the building to where it’s
needed. Properly designed hydronic distribution systems
53,000Btu/hr
53,000 =53,000 Btu / hr
Distribution
f = efficiency
= =
= 10.6gpm76.8 require significantly less electrical energy compared to
500 × ∆T 500690 × 10watt watt
thermally equivalent “all-air” systems.
Assuming a 200-foot total equivalent length for the CHILLED WATER OPTIONS
circuit, the 53,000
pressure 53,000
drop in the circuit is 5.6 psi. The A wide variety of devices are now available to produce chilled
power fsupplied
= to =
the
0.4344 f × ∆=P10.6gpm
×circulator can
0.4344be estimated
× 10.6 × 5.6 using
500w×=∆T 500 × 10 = = 64.5watt water. They include the large dedicated (non-reversible)
Formula 2-2: e 0.40 chillers often used in large high-rise buildings, as well as
rate of heating or cooling delivery(Btu/hr)
Distribution efficiency = reversible heat pumps, and heat recovery chillers, such
Formula 2-2: electrical power input to operate delivery system(watt)
as shown in Figure 2-2. In some limited circumstances, it
0.4344 × f × ∆ P 0.4344 × 10.6 × 5.6 / hr is also possible to use water from a lake to directly cool a
53,000Btu Btu / hr
w = Distribution efficiency
= = = 64.5watt
= 247 building. These options are described in section 5.
e (64.5w + 150w)
0.40 watt
Where: 53,000Btu/hr Btu / hr Figure 2-2
w =Distribution
electrical efficiency
input power = to circulator = 76.8
(watts)
+ 0.45C + 0.12D watt
690 watt
f = flow rate IPLV = 0.01A + 0.42B
through circulator (gpm) / hr
53,000Btu Btu / hr
Distribution
∆P = pressure efficiency
increase =
across circulator = 247
(psi)
(64.5w + 150w)
e = wire-to-water efficiency of circulator (decimal %)
watt
53,000 53,000
f = = qs =qs10.6gpm
Assume 500that
IPLV 30%=500
SHR
×=∆T
0.01A +of0.42B
the
×=10 +53,000
0.45C + Btu/hr
0.12D total cooling load
qT qs + qL
is latent cooling. This is handled by a small air handler
with a blower operating at 150 watts.
Courtesy of MultiAqua
blower. It canq also be= 4840(CFM
calculated) using
AH Formula 2-1:
vent (latent ) ( − AH
out s )
qvent (sensible) = 1.08(CFM ) (Tout − Ts /) hr
53,000Btu Btu / hr
Distribution efficiency = = 247
(64.5w + 150w) watt
Btu
q (sensible) = 1.08(450) ( 90 − 60 ) = 14,580
This comparison
qvent (latent )vent shows that
= 4840(CFM ) ( AH the
out
− AH s)
chilled-water delivery
hr
IPLV is
system = 0.01A
using+ 0.42B only +about
0.45C +36%0.12Dof the electrical power
required by the equivalent forced-air system. The circulator
wattage (64.5 watts) was only about 9.4% of the power EASE OF ZONING
Btu Chilled-water cooling systems are very easy to zone. They
required
qventby the =blower
1.08(450) in (the 60 ) = 14,580
90 − heat pump. The 150-watt
blower in qthe
(sensible)
qs hr can be designed around electrically operated zone valves
SHR = s
= small air handler adds substantially to the
q
total powerT required q s
+ q L for the hydronic cooling method.
in combination with variable-speed pressure-regulated
circulators. This approach substantially reduces electrical
Hydronic cooling systems using radiant panels or chilled energy consumption relative to systems using multiple
zone circulators. Zoning also allows unoccupied areas to
beams will have
qvent (sensible) minimal
= 1.08(CFM ) (Tratios
− Ts )of total cooling capacity
out
divided by fan or blower input power. Commercial be minimally cooled, and thus reduces the energy used
and institutional buildings using these systems can by the chiller.
substantially reduce the electrical energy required to
qvent (latent ) = 4840(CFM ) ( AH out − AH s ) NO COIL FROSTING
convey cooling throughout a building. Radiant panel
cooling and chilled beams are discussed in more detail Many air handlers and fan coils used for cooling have
in section 7. direct expansion (“DX”) coils. Liquid refrigerant flows
Btu
qvent (sensible) = 1.08(450) ( 90 − 60 ) = 14,580
hr
8
Although relatively new to North
Figure 2-3
America, chilled beams have been
used in European buildings since the
1970s. Like radiant ceilings, they are
only intended to handle a portion
of the sensible cooling load. The
distribution energy saved through use
of chilled beams has proven to be as
much as 50% lower than that required
by VAV (Variable Air Volume) systems.
Chilled-beam cooling is also known
to be very quiet and comfortable. It is
discussed in more detail in section 7.
9
make this approach feasible. Ice-
based thermal storage cooling Figure 2-6 variable refrigerant flow (VRF)
systems use large water-filled tanks, variable air volume (VAV)
(% of compressor power)
such as shown in Figure 2-4. hydronic
distribution system
30
10
A SURVEY OF COMMERCIAL COOLING OPTIONS
There are many options when it comes to cooling how the forced-air stream is directed into the occupied
commercial and institutional buildings. They range from space, and thus may create objectionable drafts. They
inexpensive (but intrusive) approaches, to sophisticated require much more effort to install and remove each year
systems that can independently cool and dehumidify compared to other, permanently installed options. In
hundreds of rooms with nearly imperceptible noise most cases, their use in commercial buildings is based
and drafts. on low installation cost, or the inability to accommodate
any other cooling hardware.
WINDOW AIR CONDITIONERS
The low-end approach to cooling large buildings, PACKAGED TERMINAL AIR CONDITIONERS (PTAC UNITS)
especially older buildings used for apartments or Other commercial cooling options included “through-the-
condominiums, is to use window air conditioners that wall” packaged terminal air conditioner (PTAC) units, as
are temporarily installed in late spring and removed in seen in Figures 3-2a and 3-2b.
fall. Window air conditioners are only useful in rooms
with exterior walls and suitably sized windows. Although Figure 3-2a
such rooms are common in residential buildings, this
requirement significantly impedes their use in many
non-residential commercial buildings, (i.e., those having
rooms without exterior walls). Window air conditioners
are also aesthetically unappealing. The sound that they
generate is present in the space being conditioned. Their
cooling efficiency is also lower than that of many other
central cooling options. They are very limited in terms of
Figure 3-1
Figure 3-2b
11
Still, most people who have spent time in hotel rooms Ductless systems require two refrigerant tubes between
conditioned by PTAC units can attest that the comfort each indoor cassette and the outdoor condenser. They
they provide is not ideal. A single point of high velocity air also require individual condensate drain tubes from
delivery into a room tends to create objectionable drafts. each cassette to a suitable drain and wiring between
Undesirable fan noise is also present. each cassette and the condenser. Like PTAC units,
ductless mini split systems allow individual temperature
DUCTLESS MINI-SPLIT HEAT PUMPS control within each space where a cassette is mounted.
Another commercial cooling option is a multiple-head
ductless mini-split air conditioner (or heat pump). In these Figure 3-4 shows the outdoor portion of a ductless
systems, a single outdoor condenser can supply chilled mini-split cooling system that serves four interior wall
refrigerant to several indoor wall or ceiling “cassettes,” cassettes.
which in turn supply cooled and dehumidified fan-forced
air to occupied spaces. A typical outdoor condenser Figure 3-4
for small system is shown in Figure 3-3a. One of its
associated wall cassettes is shown in Figure 3-3b.
Figure 3-3a
Figure 3-3b
12
Figure 3-5 VARIABLE REFRIGERANT FLOW (VRF) SYSTEMS
In larger commercial buildings the concept of ductless mini-
split systems can be expanded into a variable refrigerant flow
(VRF) system. One or more outdoor condenser units can supply
refrigerant to many (in some cases over 100) indoor cassettes.
Figure 3-6 shows the basic topology of a VRF system.
ROOFTOP UNITS
Air conditioning, ventilation, and in some cases heating, can also
be supplied from rooftop forced-air units. These systems are
commonly used on low-rise commercial or institutional buildings
with flat roofs.
Figure 3-6
refrigerant
VRF VRF
distribution
outdoor outdoor
manifold/controller
unit unit
refrigeration piping
refrigeration
tubing
13
Figure 3-7
A typical rooftop unit mounts to a curb that has been Because they are “all-air” systems, rooftop units are
secured and sealed to the flat roof of a building, as limited to applications where the supply and return
shown in Figure 3-8. Supply and return air ducts connect ducting can be accommodated within the building. In
to the rooftop unit through the opening in the curb. most cases, this requires a mechanical plenum space
Cooling is provided by a direct expansion refrigeration above the suspended ceiling at each floor of the building.
system. Outside air for ventilation enters the unit through The height of the plenum space depends on the size of
a modulating damper. Heating can be supplied by the the ducting that must be routed through it. The ducting
refrigeration system (operating as a heat pump), or by for all-air systems must be sized to accommodate
burners supplied by natural gas. The ducting system can the full (sensible + latent) cooling load, as well as the
be routed to several air diffusers within the building. ventilation airflow requirement. Rooftop units are also
Figure 3-8
14
Figure 3-9a Although they are a convenient
means of providing cooling in low rise
commercial or institutional buildings,
they do not offer the versatility of
hydronic-based systems.
“CLASSIC” CHILLER/TOWER
COOLING FOR LARGER BUILDINGS
Chilled water cooling has been used
for several decades in commercial
and institutional buildings such as
high-rise hotels and offices buildings.
One of its chief attractions, as
previously discussed, is the ability
to move “cooling effect” over large
distances using pipes that are much
smaller than ducting of equivalent
thermal capacity.
15
Figure 3-10 modulating
dampers return air
from building
exhaust
closed-loop
air
evaporative
cooling tower spray nozzles
air handler
fill media
outdoor air
cooled/
dehumidified
air
condensate
chilled water coil
drain
sump
make-up condenser
water expansion device
compressor
evaporator
chiller
pressures and temperatures in comparison to those mounted outside a cool storage warehouse. This unit
entering the compressor. includes several staged hermetic compressors, along
with multiple condenser coils and multiple fans.
The condenser releases heat to a stream of water that
flows through a cooling tower. As this warm water flows Water-cooled chillers are usually located inside buildings
through the cooling tower, it is cooled by the combined and are more commonly used in larger systems. They
action of upward airflow and a downward spray of water. also consist of fundamental refrigeration components
including an evaporator, condenser, compressor and
The two most common types of electrically powered expansion device. However, water-cooled chillers transfer
chillers are: heat gathered from the building into a stream of water
rather than directly to outside air. That water stream is
• air-cooled chillers circulated through a heat dissipation device, such as a
• water-cooled chillers cooling tower or geothermal earth loop, where the heat
is rejected. Figure 3-12 shows an example of a large
Air-cooled chillers are usually located outside buildings, water-cooled chiller with a centrifugal compressor. This
often on rooftops. They contain a complete refrigeration type of chiller is commonly used in large commercial and
system, which absorbs heat from a stream of water institutional chilled water-cooling systems.
supplied to the chiller from the building’s hydronic cooling
system. The temperature of this heat is increased by the In most applications, the typical leaving water temperature
refrigeration system and released to outside air through from modern chillers ranges from about 40 to 60ºF.
large refrigerant-to-air heat exchanger coils that serve as However, some chillers can create significantly lower
condensers for the refrigeration cycle. Large fans create a temperatures when operating with an antifreeze solution
strong airflow past these coils. Cold water produced by the rather than water.
chiller returns to the building’s hydronic cooling system.
Cold water from chillers is routed through piping within
Figure 3-11 shows a large, multi-stage, air-cooled chiller the building to one or more terminal units. In Figure 3-10,
16
Figure 3-11 Figure 3-13
Courtesy of cfm Distributors, Inc
17
Figure 3-14
water-side economizers in otherwise “classic” chiller/tower
cooling systems for installations in climate zone 4 or higher.
18
Figure 3-15
evaporative
DiscalDirtMag 100% chiller cooling to/from
cooling tower chilled-water
separator
spray nozzles
zones
fill
condenser variable-speed
check chiller on distribution
valves
evaporator circulator
on
on
on
glycol
feeder
plate & frame SEP4
pressure-
heat hydraulic
backflow reducing exchanger separator
preventer valve
make-up water (a) DiscalDirtMag diverter
separator valves
evaporative
DiscalDirtMag
100% economizer cooling to/from
cooling tower chilled-water
separator
spray nozzles
zones
fill
condenser variable-speed
check chiller off distribution
valves circulator
evaporator
on
off
on
glycol
feeder
plate & frame SEP4
pressure- hydraulic
heat
backflow reducing exchanger separator
preventer valve
make-up water (b) DiscalDirtMag diverter
separator valves
economizer pre-cooling
evaporative
DiscalDirtMag upstream of chiller to/from
cooling tower chilled-water
separator
spray nozzles
zones
fill
condenser
check chiller off
valves
evaporator
on
on
on
glycol
feeder
plate & frame SEP4
pressure- hydraulic
heat
backflow reducing separator
exchanger
preventer valve
make-up water (c) DiscalDirtMag diverter
separator valves
19
testable backflow preventer and a pressure-reducing Water-side economizers are especially well-suited to
valve upstream of the solenoid valve. chiller/tower systems serving with a high percentage of
sensible cooling load. Examples include data centers or
The closed cooling tower circuit operates with an industrial cooling in arid climates. These loads allow for
antifreeze solution. If the tower will be inactive in winter, higher chilled water temperatures, and thus increase the
its sump water would be drained. hours where the economizer can provide most, if not
all, of the cooling requirement. They are also well-suited
The heat exchanger in the cooling tower and the for applications where a high percentage of the sensible
economizer heat exchanger are protected against dirt cooling load is handled by radiant panel cooling or chilled
that could foul the heat transfer surfaces by DiscalDirtMag beams, and the latent load is handled by a separate
separators. These separators also collect air entrained chiller operating at a lower water temperature.
with the water and eject it from the system.
Figure 3-16
fans
water to
air coils
refrigerant modulating
to air coils valves
refrigeration system
outside
inside
to/from chilled-water
distribution system
20
Some air-cooled chillers are now available with optional A = EER of chiller operating at 100% capacity
water side economizers. One modular approach places B = EER of chiller operating at 75% capacity
a section of water-to-air coils that form the economizer C = EER of chiller operating at 50% capacity
next to the refrigeration-based hardware, as illustrated D = EER of chiller operating at 25% capacity
in Figure 3-16.
Formula 3-1 “weights” the EER of the chiller based on
The number of economizer modules, as well as the the assumption that it operates at full capacity for 1% of
number of refrigeration-based modules, can be varied the cooling season, 75% capacity for 42% of the season,
depending on the cooling capacity required, the ratio of 50% of capacity for 45% of the season, and 25% capacity
sensible versus latent cooling, and the climate where the for 12% of the season. When chillers operate at reduced
unit is installed. Applications with high sensible cooling capacity, their instantaneous EER increases based on
ratios, or those using radiant cooling and/or chilled lower rates of heat transfer through the same amount of
beams, allow for warmer chilled water temperatures, and heat exchange area. The IPLV is meant to capture this
thus extended the range of outdoor conditions over which improved performance under part load conditions in a
the economizer can be used. Applications in hot/humid standardized manner. It allows designers to compare the
climates would likely require more refrigeration-based performance of different variable-capacity chillers.
modules but still provide for limited use of the water-side
economizer during winter. The modular approach also CONTINUING IMPROVEMENT
allows cooling capacity to be controlled in stages, and Commercial chilled-water cooling systems have evolved
sometimes with variable-speed modulating ratewithin
of heating
stages. or cooling delivery(Btu/hr)
significantly since first being used in the late 1920s. The
Distribution efficiency =
two primary
electrical power input to operate delivery goalssystem(watt)
of this evolution have been to:
CHILLER EFFICIENCY
There are several indices that are used to express the • Reduce the electricity used, or in the case of
cooling efficiency of chillers. The one that is used usually absorption chillers, the fossil fuel used, to create
depends on the cooling capacity of the chiller and if it suitable chilled water.
operates as an on/off device or a variable-capacity device. • Improvements to hydronic delivery systems that
53,000Btu/hr Btu / hrreduce circulator power in chilled-water distribution
Distribution efficiency = efficiency index
For large water-to-water chillers, the690
= 76.8
used
watt watt systems.
to measure efficiency has been kilowatts of electrical • Other refinements including:
input power per ton (12,000 Btu/hr) of cooling capacity. • Improved load matching between the devices
Modern centrifugal chillers operating at full load, and producing chilled water and concurrent cooling loads.
using HFC-134a refrigerant, can attain efficiencies in the • Use of naturally cool outside air or water when
53,000
range of 0.55 Kw/ton. 53,000 available to reduce (or eliminate) the need for
f = = = 10.6gpm refrigeration-based cooling.
500 × ∆T 500 × 10
The efficiency of smaller chillers is often expressed as an • Use of alternative heat dissipation sub-systems,
Energy Efficiency Ratio. EER is the cooling output in Btu/ such as geothermal earth loops, that reduce reliance
hr divided by the electrical input power in watts, both of on cooling towers.
which are measured at industry standardized conditions • Designing systems to reduce peak loading on
for entering air and water. electrical utilities.
0.4344 × f × ∆ P 0.4344 × 10.6 × 5.6
w= = = 64.5watt
Another efficiencye index used for 0.40 variable-capacity Later sections provide overviews of several contemporary
chillers is called Integrated Part Load Value (IPLV). This hydronic-based cooling systems for commercial and
rating, which is based on AHRI standard 550/290, is institutional buildings that leverage these refinements.
meant to approximate the seasonal efficiency that a
variable-capacity chiller could achieve when subject to a Optimal operation of any chilled-water cooling system
wide Distribution
range of operating 53,000Btu / hr
conditions Bturequires
/ hr good hydronic design and detailing. For example,
efficiency = over a representative
= 247
(
cooling season. IPLV is based on Formula
64.5w +3-1.
150w ) it’s imperative to keep all heat transfer surfaces in the
watt
chiller clear of dirt and scale. It’s also important to properly
Formula 3-1: balance water flow through each of several chilled-water
terminal units in the system. Chilled-water systems also
IPLV = 0.01A + 0.42B + 0.45C + 0.12D need to be free of air and have properly sized expansion
tanks. These details can be accomplished with modern
Where: hydronic system components. Several will be discussed
IPLV = Integrate Part Load Value as you read on.
qs qs
SHR = =
qT qs + qL 21
FUNDAMENTAL COOLING CONCEPTS
TEMPERATURE & HUMIDITY INDICES Figure 4-1
Air is a combination of gases
including oxygen (21%), nitrogen
(78%), and small amounts of carbon
dioxide, hydrogen and neon. Most
air — with the exception of what is
possible in a laboratory — contains
water vapor.
22
Figure 4-2 Figure 4-4a
23
Figure 4-4b The dewpoint temperature of air is generally considered
the same as the air’s current wet-bulb temperature and
can be read from a psychrometric chart. It can also
be read from Figure 4-5 based on the air’s dry-bulb
temperature and relative humidity.
ABSOLUTE HUMIDITY
There are several indices used to represent the amount of
water vapor contained in air. One that is particularly useful
for cooling system design is called absolute humidity. It is
commonly expressed as the pounds of water contained
in one pound of dry air. Perfectly dry air would have an
absolute humidity of 0. However, perfectly dry air is not
naturally occurring. Air at 70ºF and 50% relative humidity
has an absolute humidity of 0.0078 lb/lb indicating
that one pound of air at this condition contains 0.0078
pounds of water, and 0.9922 pounds of the gases that
make up air.
Courtesy of Foley Mechanical, Inc.
RELATIVE HUMIDITY
See idronics 27 for information on the minimum When people discussing weather talk about “humidity”
thicknesses of elastomeric insulation needed to they are usually referring to relative humidity. This is
prevent surface condensation on chilled-water piping. simply the ratio of the actual water mass in a given mass
of air divided by the maximum mass of water the air
could hold at its current temperature. Thus, air at 60%
relative humidity only contains 60% of the water vapor
Figure 4-5
that it is capable of holding at that temperature. A relative
humidity of 100% means that the air is saturated and
holding the maximum amount of water possible given the
air’s temperature. Air reaches 100% relative humidity at
the dewpoint temperature. Relative humidity is plotted as
a series of curves on a psychrometric chart.
PSYCHROMETRIC CHART
Willis Carrier is considered by most historians as “the
father of air conditioning.” In 1905, Carrier developed the
first psychrometric chart that quantified the properties
of air. That chart has been refined since its inception,
but modern versions still bear a close resemblance to
the original chart developed over a century ago. A full
psychrometric chart is provided in appendix B. Several
websites also have this chart available. Figure 4-6 shows
a limited approximation of the psychrometric chart.
24
0.4344 × f × ∆ P 0.4344 × 10.6
w= =
e 0.40
25
Figure 4-7
ret
relative humidity curves
urn
air
60% 0.4
on c
process
su
d
pp
itio
line
ly
ai
n
rc
40%
on
di
tio
line
n
s
71.2ºF ces
pro
lel to
ral
pa 0.95
ulb re
et b ratu
w pe
tem
80ºF db / 50% RH
reference point
dry bulb temperature 80ºF 85ºF 90ºF 95ºF
through a scale labeled sensible heat ratio (or sometimes • Building occupancy
labelled sensible heat factor). • Solar heat gain through windows and opaque
exterior surfaces of buildings
Knowing the sensible heat ratio helps determine the type • Operation of interior equipment (computers, office
of cooling equipment used. Cooling scenarios with high machines, production equipment, cooking, etc.)
SHR are well-suited to cooling using thinner cooling coils, • Lighting schedules
radiant panels or chilled beams. Cooling scenarios with • Ventilation requirements during occupied and
low SHR will require significantly more dehumidification unoccupied periods
and favor thicker, multi-row cooling coils. • Building thermal mass
• Combined temperature and humidity (e.g., enthalpy)
COOLING LOADS of outside air
The starting point for designing any chilled-water cooling
system is to establish the building’s cooling load. Those Some of these influencing factors do not add moisture
loads involve several influencing factors, each of which to spaces, and thus only effect the sensible cooling load.
can change with time. These include:
26
The sensible portion of the cooling load consists of: factors listed above interact over time to determine the
• Heat transfer through the exposed building surfaces building’s cooling load profile.
• Heat gain from sunlight through windows
• Heat gain from interior lighting There are also several commercially available software
• Heat gain from equipment operating within the programs that can be used to estimate sensible and
conditioned space latent cooling loads in commercial and institutional
• A portion of the metabolic heat output from occupants buildings. Some examples include:
rate of heating or c
Other sources of internal heating such as occupant Chvac: Distribution efficiency =
from Elite software
respiration/perspiration, cooking, showering, washing electrical power
Block Load (BLK): from Carrier Corporation input to
and infiltration of humid outside air increase the humidity Right-N: from Wrightsoft (based on ACCA Manual N)
of inside air. These sources contribute to the latent
cooling load as well as the sensible cooling load. In this VENTILATION COOLING LOAD
context, the word latent implies “hidden.” Latent heat Commercial and institutional buildings intended for
gains do not change the temperature of interior air but human occupancy require ventilation. The recommended
have a profound impact on human thermal comfort and 53,000Btu/hr
rates of outdoor air supplied to the building vary with the Btu
the total cooling load of the building. Distribution efficiency =
intended occupancy and activity.
= 76.8
690 watt wa
The latent portion of the cooling load consists of: For example, ASHRAE recommends the following
• Moisture that diffuses through exterior building ventilation rates in a school building:
surfaces due to vapor pressure difference
• Moisture carried in by air infiltration
• Moisture carried in by ventilation air
53,000 53,000
f = = = 10.6gpm
• Moisture given off by occupant respiration and 500 × ∆T 500 × 10
perspiration
• Moisture given off by cooking, bathing, showering,
laundry, interior plants and washing
Distribution
It’s worth noting efficiency =
that condensing
53,000Btu / hr
= 247into a
water vapor
Btu / hr both sensible ∑ heatAi and latent A1 +heat.
A2 + AThe
3
+ Alatter
4
areA6 also
+ A5 +
sometimes called “enthalpy” recovery systems.
liquid to remove it from an air 64.5w (+ 150w
stream watt
is an energy- ) all surfaces
intensive process. The average heat removal necessary Figure 4-8 illustrates the concept of an air handler
to condense one pound of water from typical summertime containing an “enthalpy wheel.”
IPLV =1076
air is about + 0.42B + 0.45C + 0.12D
0.01ABtu. T + TMR 75 + 78
To = air = = 76.5º F
The enthalpy2 wheel2 is composed of a cellular media
Consider a classroom of 29 students and 1 instructor (30 that allows air to flow through it. This media contains
people in total). Based on ASHRAE recommendations, a desiccant that absorbs moisture when cooled and
the ventilationq air supply qs should be 15 CFM per person, releases moisture when heated. The upper half of the
SHRthe
and thus = ventilation
q
s
=
q + q airflow rate would be 450 CFM.
If the outdoorT air s wasL at 90ºF dry-bulb temperature
qc = 1.23
wheel (
is inTothe )
− Texhaust
f (
= 1.23 duct, )
76.5 −while
69 = 9.2 Btu
the lower2 portion of
hr ⋅ ft
the wheel is in the supply air duct. The wheel is slowly
and 80% relative humidity, its absolute humidity (found rotated by an electric motor. The media in the lower half of
on a psychrometric chart) would be 0.0245 pounds of the wheel absorbs heat and moisture from the incoming
waterqper pound
vent (sensible)
= 1.08(CFM (
of dry air.) IfT the− T
out s )
ventilation air stream
was required to have a delivery temperature of 60ºF and
outside air causing the air temperature and moisture level
to drop.
⎛ ThisBtu “pre-conditioned”
⎞ air decreases the cooling
relative humidity of 50%, its absolute humidity would be and
Q =dehumidification
9.2 500 load
ft 2
=on the
4600 Btu
downstream cooling coil.
⎜ 2⎟
0.0056 pounds of water per pound of dry air. Based on The cells that absorbed the heathrand moisture eventually
⎝ hr ⋅ ft ⎠
these qconditions,
vent (latent )
= 4840(CFM (
the total) ventilation
AH out − AHair
s )
cooling load rotate into the upper duct, where they release heat and
(e.g., the sum of the sensible and latent loads) would be: moisture into the exhaust air stream. Enthalpy wheels
can significantly reduce the cooling load associated with
Sensible cooling load for ventilation air: building ventilation. They can also recover up to 70% of
Btu the thermal energy that would otherwise be exhausted
qvent (sensible) = 1.08(450) ( 90 − 60 ) = 14,580 with stale air during the heating season.
hr
28
Figure 4-8
bulkhead
slowly rotating
desiccant wheel
exhaust
air duct
supply
air duct
belt
motor air seal plate
perimeter air seal
heat &
return air from building
moisture flow
filter
outdoor air
delivered air
(hot / humid)
(70ºF db/62ºF wb)
(95ºF db/75ºF wb)
(48% RH)
(40% RH)
filter supply duct
heating coil to building
chilled water coil
pre-conditioned air
(81ºF db/68ºF wb)
(52% RH)
29
CONTEMPORARY SOURCES FOR CHILLED WATER
Section 2 discussed the types of chillers often found MULTIPLE AIR-TO-WATER HEAT PUMPS AS CHILLERS
in larger commercial and institutional cooling systems, An array of two or more single phase electric chillers (or
specifically: heat pumps) can be piped very similar to how multiple
boilers are piped. Figure 5-1 shows an example based
• air-cooled chillers on using three monobloc-style air-to-water heat pumps
• water-cooled chillers as chillers.
There are many electrically powered air-cooled and water- The system in Figure 5-1a uses individual circulators to
cooled chillers available in the 10- to 500-ton range (1 ton create flow through each heat pump. Each circulator
= 12,000 Btu/hr). These chillers are designed to operate operates only when its associated heat pump operates.
on 3-phase electrical power, which is usually available in Each heat pump has combination isolation/purging valves
urban areas, as well as areas designated for commercial and unions, allowing it to be isolated from the remainder
building development. However, 3-phase power may of the system and serviced, or even temporarily removed
not be available in rural areas. This doesn’t mean that if necessary. Each heat pump also has reinforced flexible
buildings requiring commercial-capacity cooling cannot hose connectors that reduce vibration transfer to rigid
be sited in such areas, which may only have single phase piping. A spring-loaded check valve is installed in the
utility power available. piping at each heat pump to prevent reverse flow when
some heat pumps are on and others are off. A QuickSetter
One solution could be an array of 2 or more single phase automatic balancing valve in the branch piping to each
chillers operated in stages. In this context, the word heat pump allows flow rates to be balanced.
“chiller” could represent a device that only provides
chilled water, or a heat pump that can provide chilled All the heat pumps connect to low head loss (generously
water for cooling and warm water for heating. Single sized) headers that lead to a hydraulic separator equipped
phase chillers are available with capacities up to about with a magnet for capturing dirt and iron oxide particles.
5 tons. Thus, a 20-ton cooling load could be handled by The entire system operates with a propylene glycol
four 5-ton chillers operated in stages. antifreeze solution sufficiently concentrated to prevent
freezing in any exterior piping. All piping is also insulated
The use of multiple smaller-capacity chillers has to prevent condensation and heat gain during cooling, as
advantages and limitations. One advantage is redundancy well as to reduce heat losses during heating mode.
— if one of the chillers is down for maintenance, the other
chillers can still provide partial load capacity. The system in Figure 5-1b uses a single variable-
speed, pressure-regulated circulator to provide flow to
Another advantage is load matching. An array of four all heat pumps. Each heat pump branch is equipped
fixed-speed 5-ton chillers could provide four incremental with a high Cv zone valve (or motorized ball valve) that
steps of cooling capacity. This allows instantaneous opens when its associated heat pump is operating.
cooling capacity to be better matched to variable cooling The variable-speed circulator operates in constant
loads. In some systems, it may also eliminate the need differential pressure mode and automatically adjusts
for a buffer tank. speed based on the number of operating heat pumps.
FloCal balancing valves automatically maintain a pre-set
When multiple chillers are used, they are typically flow rate through each heat pump when it operates. This
controlled by a system that uses a closed-loop PID piping configuration would have a lower electrical power
(proportional-integral-derivative) control algorithm that’s demand in comparison to use of individual circulators for
configured for a specific chilled water target temperature each heat pump.
to the load. The controller varies the number of operating
chillers to “steer” the delivered water temperature as The piping shown in Figure 5-1 assumes that heat pumps
close as possible to that target temperature. — rather than dedicated chillers — were selected so that
the system can provide heating and cooling. The piping
One potential drawback of multiple chillers is that they at the hydraulic separators is optimized for heating mode
typically require more piping and valving relative to a operation (e.g., heated fluid passed through the upper
single large chiller. Another is that the “footprint” required portion of the separator while cooler fluid passes through
for multiple chillers is usually more than a single chiller of the lower portion). If dedicated chillers were used for
equivalent capacity. a system that only provides cooling, the coldest fluid
leaving the chillers should pass through the lower portion
30
Figure 5-1
All piping and components
entire system filled with conveying chilled water must
antifreeze solution be insulated and vapor sealed
inside
high Cv zone valve FloCal
or motorized ball valve balancing
check
valve
valve
glycol
feeder
31
Figure 5-2
OFF
purging/
isolation ON
valves
OFF
QuickSetter
balancing
heat valves
pump
2 COOLING MODE
OFF
ON
OFF
heat
ON
pump
1
QuickSetter
balancing
valve
zone valve
Discal VS ∆P(p)
entire system filled with circulator
antifreeze solution
VS ∆P(p)
zone valve
chilled buffer tank circulator
QuickSetter balancing valve
32
of the separator. The slightly warmer fluid returning from Each buffer tank provides hydraulic separation between
the cooling load would pass through the upper portion the heat pump circulators and the load circulators.
of the separator. The warmer fluid would have a slightly
lower solubility for dissolved gases, and thus enhance The heating zones are supplied by low temperature
the air-separating function within the upper portion of the radiant panels. Flow to each manifold station is controlled
SEP4 separator. by a zone valve. Each manifold station piping assembly is
also equipped with a balancing valve and purging valve.
Figure 5-2 shows an array of six nominal 5-ton air-to- These valves are arranged so that each manifold station
water heat pumps that supply chilled water for cooling and its associated zone valve can be completely isolated
a small industrial facility equipped with chilled beam from the balance of the system if necessary for service.
terminal units (to be discussed in section 7). These heat
pumps also supply warm water for heating. The cooling zones are supplied by fan-coils. Each fan-
coil piping assembly is equipped with a balancing valve
It’s important to understand that the piping shown in Figures and purging valve. These valves are arranged so that
5-1a and 5-1b allows any of the heat pumps to operate, each fan-coil and its associated zone valve could be
in the same mode, as required by the load, but does not completely isolated from the balance of the system if
allow some of the heat pumps to operate in cooling mode necessary for service.
while others simultaneously operate in heating mode. Mixed
mode operation is useful in some buildings, especially Because this system can simultaneously supply heating
during swing season conditions. On a cool day in fall or and cooling, one mode of operation must take priority
spring, perimeter areas of a building may require heating, when staging the heat pumps. Several possibilities exist.
while core areas of the building require cooling. For example, during heating season the ability to maintain
adequate water temperature in the “hot” buffer would
Simultaneous heating and cooling from a multiple heat likely be the priority. Once that temperature is established,
pump array is possible, but requires more piping, valves at least one of the heat pumps would be allowed to
and controls. Figure 5-3 shows one example of piping operate in cooling mode if a cooling load is present.
that could be used with an array of three air-to-water heat During the cooling season, it’s likely that all heat pumps
pumps to allow simultaneous heating and cooling. would be prioritized to satisfy the cooling load.
This system has a “hot” buffer tank and a “cold” buffer MULTIPLE WATER-TO-WATER HEAT PUMPS AS CHILLERS
tank. The system controls monitor the temperature of The same piping concepts discussed for multiple air-
each tank and call for a heat pump to turn on when to-water heat pumps can also be applied to multiple
the temperature of either tank deviates slightly from its water-to-water heat pumps. In some applications, the
target temperature or outside of a set temperature range. heat pumps would be dissipating heat to earth loops or
The water temperature in the hot buffer tank would be “open” groundwater sources. In other applications, the
regulated based on outdoor reset control. The water for heat of rejection from the heat pumps may be used to
the cold buffer tank would be maintained between upper heat domestic water, or to preheat process water that
and lower temperature setpoints, such 45ºF and 60ºF would eventually be used for washing or sterilization in
whenever a cooling load is present. food processing facilities. Figure 5-4 shows an array of
two water-to-water heat pumps that could provide either
When a heat pump is called to operate, the zone valve staged heating capacity or staged cooling capacity, but
pairs associated with its mode of operation open. The not both at the same time.
status of the heat pump’s reversing valve is also set. A
variable-speed pressure-regulated circulator operates Flow to both sides of each heat pump is provided by a
to create flow through the appropriate buffer tank. variable-speed pressure-regulated circulator. A pair of
The speed of the circulator is based on proportional motorized ball valves, one on the condenser side of the
differential pressure control. The speed automatically heat pump and the other on the evaporator side, open
increases or decreases depending on how many heat when their associated heat pump operates. These valves
pumps are operating. have relatively high Cv ratings, and thus minimize head
loss in their associated branch piping paths. An end
The valving at each heat pump is also arranged so that switch within the actuator of each motorized ball valve
the zone valves or heat pump can be isolated from the closes when the valve reaches 80% of its fully open status.
balance of the system if necessary for service. This switch can be used as part of a “safety switching”
circuit to verify that both flow pathways (e.g., evaporator
33
Figure 5-4 supply
multi-stage load temperature
controller circulator sensor
to / from load
Quicksetter constant ∆P
circulator SEP4
balancing valves
Hydro Separator
low loss headers
motorized ball
reversing reversing valves
valve valve
compressor compressor
anti-vibration
hoses
condenser
condenser
evaporator
evaporator
thermal thermal
expansion expansion
valve valve
SEP4
Quicksetter Hydro Separator
balancing valves
Figure 5-5
and condenser) through the heat pump are open before allowing the heat pump’s
compressor to operate.
Figure 5-5 shows an array of two 5-ton rated water-to-water heat pumps that are used
in a maintenance facility. These heat pumps provide staged heat input to a radiant
floor slab. They also provide cooling through multiple chilled-water air handlers.
34
Each water-to-water heat pump is equipped with a Heat recovery chillers are ideal in situations where
desuperheater for domestic water heating (uninsulated simultaneous heating and cooling are required or possible.
piping connected to upper two ports on each heat Potential applications include:
pump). The two pipes that lead to the earth loop and the
two pipes the lead to the heating and cooling distribution • Cooling a building while simultaneously heating a
system are connected to the heat pump using reinforced swimming pool
flexible hose connectors to minimize vibration transfer. • Cooling the core area of a building while
The earth loop piping and distribution piping are insulated simultaneously heating perimeter areas
with an elastomeric foam to prevent surface condensation • Cooling a building while providing domestic water
and conserve energy. Each heat pump is mounted so heating
that front and side service panels can be accessed. • Cooling a building while providing hot water for an
industrial process such as laundry, food preparation
HEAT RECOVERY CHILLERS or greenhouse soil warming
One variation on standard air-cooled chillers is to add
an internal refrigerant-to-water heat exchanger that can Because both the chilled water stream and hot water
Btu
transfer some or all of the heat of rejection produced
during cooling mode operation to a stream of water
(
stream are being used, the effective COP of a heat
)
qvent (latent ) = 4840(450) 0.0245 − 0.0056 = 41,164
recovery chiller can be significantly higher than the COP hr
instead of dissipating all that heat to outside air. The of a stand-alone chiller or a stand-alone heat pump.
heated water can then be used for loads such as space In theory, the effective COP of a heat recovery chiller
heating, domestic water heating, pool heating or other would be:
process heating. Any heat not transferred to the warm
Qt
water stream is dissipated to outside air by a condenser COPe = = ( 2 × COPh − 1)
coil and fan. e input × 3413
Figure 5-6 shows an example of a 5-ton rated heat
recovery chiller. One set of pipes connects to the chilled- Where:
water distribution system, the other set connects to the COPe = Effective COP based on total useful energy
heated water distribution system. output, which
qc = 1.23 (
is the
To sum )
− T f of heating and cooling outputs
Qt = Total useful energy output of hot and cold water
Figure 5-6 streams (Btu/hr)
ei = electrical input to heat recovery chiller (kilowatts)
COPh = Measured heating COP of the unit based on heat
Tair electrical
+ TMR input
To =and
output only
3413 = Conversion 2 factor from kilowatt to Btu/hr
∑ A
i
Some heat recovery chillers
all surfaces can also switch between
outside air or a geothermal earth loop as the “source” for
low temperature heat, or the media to which excess heat
(e.g., heat not used by the hot stream load) is dissipated.
∑ Ti Ai T A + T A + T A + T A + T A + T A
all surfaces 1 1 2 2 3 3 4 4 5 5 6
MRT
Figure 5-7 =
shows = application
a possible using a heat
recovery chiller to ∑
A A
supply ieither 2-pipe
1
+ A + A + A
air2 handlers
3
+ A
4 or 5
+ A 6
all surfaces
4-pipe air handlers. Note that each air handler can
independently operate in heating or cooling mode. It
Courtesy of Multiaqua
( )
qc = 1.23 To − T f = 1.23( 76.5 − 69 ) = 9.2 Btu 2
hr ⋅ ft 35
Figure 5-7
variable-speed
pressure-regulated DISCALDIRT air/dirt separator
circulators 2-pipe air handler 2-pipe air handler 2-pipe air handler
in heating mode in cooling mode in cooling mode
6-port motorized dual
diverter valve, or two
3-way diverter valves
HWS
zone valves
FLOCAL
FloCal
balancing
balancing
valves valves
to / from
other cooling loads
CWS
CWR
HWS
to / from
other heating loads
(b)
heat recovery
chiller fluid feeder
Figure 5-8 shows how multiple heat recovery chillers can a pair of high Cv zone valves or a pair of motorized ball
be piped to provide staged input to either the heating or valves open and close to allow or prevent flow through the
cooling distribution system. chiller. Two variable-speed pressure-regulated circulators
automatically adjust speed to maintain a constant
The “hot side” and “cold side” of each chiller are connected differential pressure across the headers. The distribution
to low head loss header piping that leads to two hydraulic system is shown with variable-speed pressure-regulated
separators. Depending on the chiller’s flow requirements, circulators. The hydraulic separators prevent interaction
36
Figure 5-8
variable-speed
pressure-regulated
circulators SEP4
Hydro
Separator
low loss header piping CWR
QuickSetter to / from
balancing cooling
valves load
CWS
to / from
PRV heating
load
HWR
SEP4
Hydro
Separator
fluid
feeder
check valves
QuickSetter balancing valves
heat recovery chiller heat recovery chiller heat recovery chiller reinforced hoses
between the chiller circulators and the load circulators. In systems that require 10 or more tons of cooling, it’s
They also provide high-efficiency air, dirt and magnetic possible to use two more 5-ton single phase condensers
particle separation. Each chiller can be fully isolated for and operate them in stages based on the demand for
service if necessary. chilled water. Figure 5-9 shows how each condenser
unit is piped to a separate heat exchanger. A flow
Because the chillers are located outside, the entire switch should be installed on each branch, as shown
system operates with an antifreeze solution. A fluid feeder in Figure 5-9a.
is used to maintain system pressure as air is vented from
either side of the system. Each flow switch verifies that a suitable flow rate
exists through the water side of the refrigerant-to-
AIR-COOLED CONDENSERS WITH water evaporator before allowing the condenser unit
DIRECT EXPANSION HEAT EXCHANGERS to operate. Insufficient water flow through the heat
It’s also possible to produce chilled water by combining exchanger could result in freezing. Notice that all
one or more outdoor condensers with an external piping, as well as the lower body of the flow switch,
refrigerant-to-water heat exchanger. The heat exchanger are insulated to prevent condensation formation on
serves as the evaporator for the refrigeration system. components carrying chilled water.
This heat exchanger must be properly sized based on
the refrigerant used, the desired evaporator temperature,
the superheat setting of the thermal expansion valve
in the condenser unit, and the required chilled-water
temperature and flow rate.
37
Figure 5-9a
to / from cooling
distribution system
2-stage
temperature
DiscalDirtmag controller
separator
outside
inside
circulators
w/ checks
temperature
sensor flow
switches
variable-speed
pressure-regulated flat plate
circulator heat DX line
exchangers sets
(DX to water)
air-cooled condensers
flow switches
38
Lake source cooling has been done
Figure 5-10 on several large-scale projects. The
cool waters of Cayuga Lake in upstate
summer water New York provide approximately
temperature (ºF) 20,000 tons of cooling capacity for
Cornell University in Ithaca, NY. The
32 ºF 86 ºF
lake surface city of Toronto, Ontario, also uses the
cool water from about 600 feet below
the surface of Lake Ontario to provide
10 epilimnion
59,000 tons of cooling for downtown
high-rise office spaces. The lake water
20 absorbs heat from a large district
depth (feet)
39
Figure 5-12 This type of heat exchanger is designed to be used with
water source heat pumps. However, when properly sized
and used in a lake where the water temperatures at the
lakebed are stable and relatively low, it could provide
direct heat exchange to a chilled-water cooling system.
Figure 5-13 shows one concept for such a system.
Figure 5-13
air handlers
balancing
valve zone
valves
silt
40
from 6 to 10 gallons of water volume
Figure 5-14 per ton of cooling capacity.
VFD
45 ºF 25 gpm 25 gpm 75 gpm 125 gpm
45 ºF If the distribution system does
50 gpm 50 gpm 50 gpm not provide the required volume,
a “2-port” baffled buffer tank is
Figure 5-15
Courtesy of cfm Distributors, Inc
41
TRADITIONAL CHILLED-WATER TERMINAL UNITS
There are several devices that can absorb heat from
a room and transfer that heat to a stream of chilled Figure 6-2
water. Some have been used for several decades, while
others are relatively new. Some are delivered to a project
ready to be placed on a floor or suspended from a
ceiling and then piped to the chilled-water distribution
system. Others are integrated into the construction of
the building. This section provides a survey of traditional
Courtesy of SpacePak
chilled-water terminal units that are intended to handle
both sensible and latent cooling loads. Section 7 will
cover radiant cooling panels and chilled beams, which
are used in systems that separate the sensible and latent
cooling loads.
AIR HANDLERS
One of the most common chilled-water terminal units is Horizontal air handlers are usually suspended within
an air handler. A basic air handler consists of a chilled- a mechanical chase above a suspended ceiling. The
water coil, condensate drip pan, blower, air filter and weight of the air handler and its associated ducting and
enclosure, as illustrated in Figure 6-1. piping is supported by an overhead structure such as a
concrete slab, wood framing or steel trusses. Figure 6-3
shows an example where a small chilled-water air handler
Figure 6-1 is suspended on steel channel strut that is supported
return duct by threaded rods attached to a structure ceiling. Each
enclosure steel rod includes a vibration dampener that minimizes
vibration transfer to the structure.
air filter
coil (4-tube pass)
blower The small air handler in Figure 6-3 is contained within
the thermal envelope of the building. This protects the
water within the coil from freezing. The air handler is also
Figure 6-3
supply duct
drip pan
condensate drain
(with trap)
chilled water in
42
Figure 6-4
control building pressurization, heat recovery wheels,
multiple levels of filtration, UV light sterilization hardware,
acoustical suppression and humidifiers. The air handler
shown in Figure 6-4 has doors allowing service technicians
to work inside the unit. The overall functionality of such
complex devices is usually coordinated by a building
automation system.
43
Figure 6-7
chilled water coil
hot water coil
SEP4 variable-
Hydro speed
Separator circulator
to / from
chiller other cooling loads
heated
to / from
water
other heating loads
source
variable
speed
circulator
mains. A 4-pipe system allows each air handler to operate capacity can be obtained by subtracting sensible cooling
in either heating or cooling, independent of the other air capacity from total cooling capacity.
handlers in the system. Figure 6-7 shows an example of
a distribution system using 4-pipe air handlers. Other performance measures for air handlers include:
Notice that the heated water and chilled water circuits are • Fluid head loss or pressure drop across the coil as a
completely separated. As such, each should be equipped function of the flow rate through the coil.
with make-up water systems, expansion tanks, air/dirt/
hydraulic separators and safety devices.
Figure 6-8
Most air handlers are rated at specific operating conditions
for both the incoming chilled water temperature and the low fan speed
incoming air. Those conditions are typically as follows: high fan speed
0.5
• Entering chilled water temperature: 45ºF
0.45
Static pressure (inch water column)
44
• Airflow rate produced by the blower as a function of Like air handlers, fan coils have an internal blower or
the external static pressure of the ducting system. This fan, a chilled-water coil and a condensate drip pan.
is typically stated in cubic feet per minute (CFM), versus Some fan coils also have intake air filters. They are
the static pressure of the duct system, which is stated in designed to deliver cooling (and in some cases heating)
inches of water column (e.g., inch w.g.). If the air handler to a single room or space, and are not connected to
has a multiple-speed motor, this information is often given ducting. Fan coils come in a range of capacities, as well
for each speed setting. as configured for either a 2-pipe or 4-pipe distribution
system, as discussed for air handlers. They often have
Figure 6-8 shows an example of airflow rate produced by electrical controls that allow for multiple-speed operation
a nominal 3-ton air handler with a 3-speed motor versus of the blower or fan during heating or cooling, or in some
the static pressure developed by its blower. The static cases just the fan for air circulation. Some also have
pressure at which the air handler operates is determined programmable controls.
by the design of the ducting system it supplies.
Most fan coils have very low internal water volume.
A typical airflow rate for a chilled-water air handler is 400 This allows them to respond to demands for cooling (or
CFM per ton of delivered cooling capacity. heating) very quickly.
FAN COILS: Fan coils equipped with condensate drain pans, and thus
Another commonly used chilled-water terminal unit is suitable for chilled-water cooling, are also available in
called a fan coil. These units can be mounted into a other mounting configurations. One example is the “high
recessed wall cavity or fastened to a wall surface. An wall” cassette shown in Figure 6-10.
example of two surface-mounted “console” fan coils that
can be used for chilled-water cooling, as well as hydronic Figure 6-10
heating, are shown in Figure 6-9.
Figure 6-9a
Courtesy of Myson
45
Cooling capacity increases as chilled water
Figure 6-11 temperature decreases, especially when the
total cooling capacity supplied chilled water temperature is well below
the dewpoint of air entering the terminal unit.
100
90 Cooling capacity is also influenced by flow
rate. Figure 6-11 shows a typical relationship.
80
% total cooling capacity
% latent capacity
50 change in flow rate at high flow rates. This
30 40 100 characteristic is similar to that of hydronic heat
20 30 80 emitters operating at a constant supply water
60 temperature.
20
10 40
10 20
0 0 0
If a modulating valve will be used to control the
0 10 20 30 40 50 60 70 80 90 100 total cooling capacity of an air handler or fan
% flow through coil coil by controlling flow rate through it, that valve
should use an internal flow control element with
an equal percentage characteristic.
capacity is usually listed in a way that allows sensible and
Figure 6-11 also shows that the sensible cooling capacity
latent cooling capacity to be determined based on the
of the coil begins to rise at lower flow rates, while the
chilled water temperature and flow rate supplied, along
coil’s latent cooling capacity begins at approximately
with typical indoor air and humidity conditions assumed
25% of total flow rate, and rises in a quasi-linear manner
for the rated outputs.
with increasing flow.
46
RADIANT PANEL & CHILLED BEAM SYSTEMS
The classic approach to absorbing ceilings, to be lowered by circulating building. For example, on a humid
heat and humidity from occupied cool water through tubing embedded day the dewpoint temperature within
spaces is to pass air from those in or fastened to those surfaces. This a frequently used entry vestibule
spaces through a chilled-water coil allows those surfaces to absorb long- is likely to be higher than that
in an air handler. That coil provides wave thermal radiation given off by within an interior building space.
both sensible and latent cooling. The occupants or other warmer objects in This is also true for spaces used
extent of total cooling capacity and the the room. It also allows the surfaces for food preparation, commercial
proportions of sensible versus latent to absorb some of the incident solar laundry, washing or exercising. Such
cooling are constrained by the coil radiation entering through windows areas should be zoned and use
selection, as well as the temperature or skylights. independent controls for regulating
and flow rates of the chilled water chilled water supply temperature.
stream and airflow through the coil. To avoid condensation, it is critically
This approach “couples” the sensible important that cooled ceilings or RADIANT FLOOR COOLING
and latent cooling loads and handles floors operate at temperatures One common radiant panel
both through a common device above the dewpoint temperature of configuration uses PEX, PERT or
(e.g., the coil in the air handler). This the spaces they serve. . This also PEX-AL-PEX tubing embedded in a
approach also delivers both sensible applies to components that serve concrete floor slab. This approach
and latent cooling using a forced-air those surfaces, such as piping in a has been applied in a wide range
stream, typically delivered through mechanical chase above a cooled of commercial and institutional
ducting. ceiling. The chilled water supplied buildings. Due to the thermal mass of
to radiant cooling panels and their the concrete, this approach is often
Another option that has enjoyed associated piping should be a referred to as a “high-mass” radiant
increasing interest over the last two minimum of 3ºF above the current panel. This type of panel can be used
decades, is based on “decoupling” dewpoint temperature of the room. for heating and sensible cooling.
the sensible and latent cooling loads. Designers should also consider
The majority of the sensible cooling how the dewpoint temperature Many multi-story commercial and
load is handled by absorbing heat varies in different spaces within a institutional buildings have structural
into radiant panels built into floors or
ceilings, or into devices commonly
known as “chilled beams.” This Figure 7-1 topping slab (concrete of gypsum underlayment)
heat absorption occurs above the
dewpoint of the interior air, and (min. 1.5" coverage over tubing)
thus does not create any surface PEX tubing secured to WWF
condensation. The remainder of the
welded wire fabric WWF
cooling load (e.g., small portion of
the sensible load and all of the latent polystyrene insulation
load) is handled by a chilled-water floor covering
coil operating at temperatures well 6" - 9"
below the dewpoint of the interior
air. That coil is typically integrated
into an air handler that also provides
ventilation to interior spaces.
47
∑ Ti Ai Qt
COPe = MRT = = ( 2 × COPh − 1)
all surfaces
Here’s
qc = 1.23an example: ( )
(surfaces
The− 69 mean ) = 9.2radiant
Btu temperature
( )
all surfaces i
TMRT − TMRT = = 1.23 76.5
=allallsurfaces
qc = 1.23 To − T f
o f
of a room with floor cooling ∑ ∑ A i Ais determined
i
hr ⋅ ft 2 to be 78ºF.
all surfaces
The room’s dry-bulballair temperature is 75ºF. The floor
surfaces
Qt
Where: COPe =
e × 3413
(
= 2 × COPh − 1absorption into a floor,)
area of the room is 500 ft2. Estimate the rate of heat
∑ Tassuming A
i i
T A + the
T A + average
T A + T floor A +T A +T A
surface temperature∑is ∑
all surfaces
qc = cooling absorption fluxinput 2
(Btu/hr/ft ) MRT = T A
69ºF. = 1 1 2 2 3 3 4 4 5 5 6 6
1.23 = combined convective+radiative surface coefficient
⎛
Q = ⎜ 9.2 MRT Btu ⎞=500 all surfaces∑ i iT Ai iATi 1 A1 + T2 A12 + TA32A+3 +A3T+4 AA44++TA
= 4600= Btu
ftall2surfaces T1 A1 + T2 A2 + T3 A3 + T4 A45 +A
+ AT66 A6
5 5T+A + T6 A6
T T
surfaces
+
5 5
MRT ⎟ = =
Btu 2
Solution: The room’s ∑ ∑
all
A hr A + A + A + A + A + A
( )
2
for cooling (Btu/hr/ft /ºF) ⎝ hr ⋅ ft ⎠ operative
i A temperature
1 A 2+ A 3+ A is3 4+found
A4 5+ A5 6+ A6
Tqovent=(latentair) = 4840(450)
To = operative temperature
MR 0.0245 − 0.0056 = 41,164
of the room (ºF) using Formula
all surfaces
7-2:
i 1 2
2 hr all surfaces
q c
=
The operative temperature 1.23 T (− T )
oof a froom is the average
between the room’s dry-bulb air temperature and the
To = air
T + TMR 75 + 78
Tair T + T2MR +
To =T = air =MR = 75 +=78 T
=
75 + 782
= 76.5º F
76.5º F
Q o 2 2 2 2 = 76.5º F
room’s mean radiant temperature.
COPe =
eall ×
t
∑Ti A
3413
(
=i 2 × COPh − 1 )
The cooling flux into the floor is calculated using
Formula 7-1:
Formula 7-2: MRT = inputsurfaces ( )
qc = 1.23 To − T f = 1.23( 76.5 − 69 ) = 9.2 Btu 2
Tair + TMR Ai ∑ qc =q1.23 = To −TT f− T= 1.23
1.23 ( ( ) ) = ( ( − 69−) 69
76.576.5
1.23 )
= 9.2= 9.2
hr ⋅ ft
Btu Btu
To = all surfaces c o f hr ⋅ hr ft 2⋅ ft 2
2
Where: qc = 1.23 To − T f (
To = operative temperature of the room (ºF)
) The rate of heat absorption would be the cooling flux
multiplied by the⎛ floor Btu
area:⎞
Tair = dry-bulb temperature of air in the room (ºF) Q = ⎜ 9.2 500 ft 2 = 4600 Btu
∑
TMR = mean radiant temperature of Tisurfaces
Ai in the room Q =Q
⎛ ⎝
⎜ 9.2
hr ⋅ ⎞
ft
⎛ Btu Btu500
2⎟
⎠ ⎞ ft 2 = 4600 Btuhr
Btu
MRTT =+ T ∑
(ºF) all surfaces Ti Ai T A
1 1
+ T A
2 2
+ T A
3 3
+ T A + T= A
9.2+
4 4 ⎝ 5⎜⎝ hr5 ⋅ hr
2T⎟ A 500 ft = 4600
ft ⋅⎠6ft 2 ⎟⎠6
2
hr hr
=
TMRT ∑ air
= = all surfaces Ai MR
A1 + A2 + A3 + A4 + A5 + A6
∑is givenAiin Formula 7-3.
o
A simplified approach for
2 determining the mean radiant There is also a relationship between the water temperature
all surfaces
temperature (T ) of a space
MR in the embedded tubing, the tube spacing and the
all surfaces
thermal resistance of any floor covering over the slab.
Formula 7-3 In qualitative terms, the closer the tube spacing, the
∑ Ti Ai lower the water temperature, and the lower the thermal
MRT T
= +T all surfaces resistance of any floor covering, the greater the heat
To = air ∑∑ = i Ai + 78 = 76.5º F
MRAi T75 absorption capacity of the cooled slab.
2
all surfaces
2 T A +T A +T A +T A +T A +T A
Where: MRT = all surfaces = 1 1 2 2 3Figure 3 4 4 5 5 6 6
7-2 shows the relationship between heat absorption
MRT = estimated mean radiant temperature
(ºF)
Ai ∑ A1 + A2 +flux
of a space A3 (in A4 + A52)+and
+ Btu/hr/ft A6the temperature difference between
all surfaces the operative temperature of the space and the average
Ti = surface temperature of surface ∑
Ti Ai (i) in the room (ºF)
T A + T A + T A + T A water
+ T5 A5temperature
+ T6 A6 in the embedded tubing circuits. Tube
Ai = area of surface
MRT (i) in surfaces
= all the room (ft
(
qc = 1.23 To − ATi f = 1.23A1 +76.5
∑ )A2 +−A69
3 (
= 2)1 1 2 2 3 3 4 4spacings
+ A4=+9.2
Btu
A5 + A6 2
floor
of
covering
hr ⋅ ft
)
6 inches and 9 inches are shown, along with
resistances of 0 (bare or painted slab), 0.5
For a typical rectangular room with 6 surfaces (4 walls,
all surfaces
and 1.0 ºF•hr•ft2/Btu.
T 7-3
ceiling, floor), Formula + TMR is just shorthand for the
following: To = air = 75 + 78 = 76.5º F Here’s an example: A room has a floor area of 500
2 2 square feet. The entire bare floor slab has embedded
Tair + TMR 75 + 78
To = = = 76.5º F
2 2
⎛ ⎞
Q = ⎜ 9.2 Btu 2 ⎟ 500 ft 2 = 4600 Btu
( )
48
The total
∆T = 77º sensible
F − 62º F = 15º F cooling
Figure 7-2 provided is this cooling flux
18 multiplied by the room area.
⎛ ⎞
16 6" spacing / R=0 Q = ⎜ 6.0 Btu 2 ⎟ 500 ft 2 = 3000 Btu
⎝ hr ⋅ ft ⎠ hr
Cooling flux (Btu/hr/ft^2)
Tair + TMR 75 + 79
To = = = 77º F
2 Tair + TMR
2
To = = 75 + 79 = 77º F
2 2
The difference between the room’s operative temperature Each panel consists of a painted steel frame pan into
and the average water temperature in the embedded which is fitted a copper tube circuit, graphite heat
tubing is: diffusion layers and top-side insulation. The graphite
∆T = 77º F − 62º F = 15º F layers provide lateral heat conduction between the tubing
∆T = 77º F − 62º F = 15º F and panel areas between the tubing. Although these
panels are relatively light, they still require support from
Using the graph in Figure 7-2, the cooling flux is found to light gauge chain or steel cable connected to structural
⎛ ⎞ elements such as bar joints or concrete slabs.
6.0 Btu 500 ft 2 = 3000 Btu
be 6.0 2.
Q =Btu/hr/ft ⎜ ⎛ 2⎟ ⎞
⎝ Qhr=⋅⎜ft6.0⎠ Btu 2 ⎟ 500 ft 2 hr
= 3000 Btu
⎝ hr ⋅ ft ⎠ hr
49
qL
∆w=
4842(CFM ) qL
Figure 7-4
Figure 7-7
CHILLED BEAMS
Although relatively new in North America, chilled beams
have been used for cooling in European buildings for
more than four decades. They operate at chilled water
temperatures above the room’s dewpoint, and thus
can only absorb sensible heat. They must therefore be
Figure 7-6 Figure 7-8a Courtesy of Dadanco div. of Mestek
Courtesy of Zehnder Rittling.
50
air nozzles
Passive chilled beams do not have
Figure 7-8b chilled beam ventilation airflow. They are used to
dry, supplement heating or cooling capacity
ventilation in spaces where sufficient ventilation
air intake
air is introduced through active chilled
chilled water coil
beams or other means.
Chilled beams are categorized as “active” or “passive.” Figure 7-9a shows an active chilled beam in an exposed
Active chilled beams have ventilation air ducted to them. ceiling application. A small duct supplies ventilation
This air has been preconditioned in both temperature air to each chilled beam. The chilled beam and its
and moisture content before it is sent to the chilled Figure 7-9a
beam. This preconditioning allows the air to absorb
moisture from the space, and thus manage the latent
portion of the cooling load. The preconditioned “dry”
air enters the chilled beam and passes through nozzles
that increase airflow velocity and decrease local air
pressure. The reduced pressure induces airflow through
the chilled-water coil, where the temperature of the air
is reduced. This reduced temperature air then mixes
with the dry ventilation air, and it is reintroduced to the
room through the slot diffusers near the outer edges of
the chilled beam.
Figure 7-9a
Courtesy of Dadanco div. of Mestek
51
connected piping and ducting are result in operating costs that are up Figure 7-10 shows a typical DOAS
suspended from the steel bar joists to 50% lower than those of variable air handler.
in the ceiling. Figure 7-9b shows air volume (VAV) systems.
chilled beams installed flush within a DOAS air handlers use a multi-
suspended ceiling. DEDICATED OUTDOOR AIR SYSTEMS row chilled-water coil to extract a
(DOAS) high amount of moisture from the
Chilled-beam systems operate in Chilled beams, as well as radiant ventilation air. The highly dried air
combination with an air-handling cooling panels, are frequently is then introduced to the occupied
system that provides both ventilation combined with an air handling/ space in a manner that mixes it
air and controls the humidity of the air dehumidification system called a with the more humid air in the
supplied to the active chilled beams. DOAS, which stands for Dedicated space, such as through an active
These air-handling systems vary in Outdoor Air System. chilled beam. This mixing allows
how they condition air supplied to the moisture being released into the
the chilled beams. The goal is to DOAS systems use 100% outside space by occupants, activities or
reduce the humidity level to a point air, rather than recirculating a infiltration of humid outside air to be
where the air volume supplied to the portion of the air in the occupied absorbed at a rate that doesn’t allow
chilled beams is no more than 15% space. During cooling operation, the the relative humidity of that space to
higher than the airflow rate required objective of a DOAS air handler rise above an established threshold,
for ventilation. is to provide sufficient airflow to such as a typical 50% RH.
meet ventilation requirements AND
Active chilled beams significantly to reduce the absolute humidity of Return air from the space is routed
reduce the size of ducting required that air to a condition that allows it through an enthalpy wheel within
in the building. In dry climates, the to absorb the entire latent cooling the DOAS unit to recover some
ducting is primarily sized for the peak load of the space. Because the sensible and latent cooling effect
ventilation airflow. In climates with very low-humidity air handles the before being exhausted outside.
higher humidity, the airflow rate is full latent cooling load, devices
based on handling the latent load and such as chilled beams and radiant During winter, a heating coil in
is usually higher that the airflow required cooling panels can be operated at the DOAS air handler can warm
for ventilation. Reduced airflow means temperatures above the dewpoint incoming ventilation air prior to
that smaller ducting can be used, as of the room air and not experience introducing it into occupied spaced.
can lower power blowers. This can surface condensation.
Figure 7-10
rotating desiccant wheel
(exchanges enthalpy
DOAS air handler
b/w air streams)
flow building
outdoor air
delivered air
(very low humidity)
52
Figure 7-11 Tair + TMR 75 + 79
The combination of chilled beams or To = = = 77º F
radiant panels operating just above 2 2
Activity Male TOTAL Adjusted total Sensible Latent heat
room dewpoint temperature, along heat output heat output heat output output
with a DOAS system for ventilation (Btu/hr) (Btu/hr) (Btu/hr) (Btu/hr)
and latent cooling, is highly efficient
from the standpoint of distribution Seated at rest 393 341 205 136
∆T = 77º F − 62º F = 15º F
energy. This is largely based on Seat light work 478 410 222 188
shifting the majority of the sensible
cooling load from “air-side” delivery Light bench work 870 785 341 444
using ducting to “water-side” ⎛ ⎞
delivery using a hydronic distribution
Heavy work 1604 1604 = ⎜ 6.0 Btu 2 1041
Q563 2 Btu
⎟ 500 ft = 3000 hr
⎝ hr ⋅ ft ⎠
system. With good design, the Athletics 1997 1792 631 1161
electrical power required for the
hydronic portion of the system can can be found in Chapter 14 of Formula 7-2:
be approximately 10% of the power the 2017 ASHRAE Handbook of
required for an equivalent forced-air qL
Fundamentals, or similar references. ∆w=
distribution system. 4842(CFM )
Step 2: Using these design where: T +T
DOAS systems also allow the conditions, perform calculations to = air in MR
∆w =Toincrease = 75 +humidity
absolute
79 = 77º F
distribution ducting to be significantly determine the sensible and latent 2 2
caused by occupants (lb water/lb
smaller, and thus less expensive, cooling load of the space. dry air)
compared to ducting that must handle
qL= latentwmaxload
= wdidue ( )
+ ∆tow occupancy
occupants
the full sensible, latent and ventilation Step 3: Use a psychrometric (Btu/hr)*
load. Smaller ducting can also reduce chart (provided in Appendix B) to CFM = required airflow rate of
the height requirements for mechanical determine the absolute humidity for ∆T = 77º F − 62º F = 15º F
outside air (ft3/minute)
chases above suspended ceilings. the indoor air (wi), as well as the
outdoor air at design conditions. *A typicalqsah = 1.08(CFM
adult engaged )(T − Tdbi )
in very
dbo light
LATENT COOLING LOADS FOR Absolute humidity is expressed as activity creates a latent load of about
CHILLED BEAMS & RADIANT PANELS either pounds of water per pound of 188 Btu/hr. ⎛ The latent ⎞load for 2other
Since chilled beams and radiant dry air or grains of water per pound activity = ⎜ 6.0canBtu
Q levels be 2found = 3000 Btu
⎟ 500inftFigure
panels are limited to sensible cooling, of dry air. 7000 grains of water = 1 q⎝srad =hr ⋅ ft− ⎠q
qstotal hr
7-11. sah
it is necessary to provide latent pound of water.
cooling (e.g., moisture removal from Step 6: Determine the increased
the air) by other means. Step 4: Determine the outside airflow absolute humidity when the room
rate required for ventilation based is occupied by adding
qL the absolute
The following procedure can be on occupancy. Recommended ∆ wq=at
humidity L
= 4842(CFM
the ∆ w air
design ) indoor ( )
used to determine the operating ventilation airflow rates for different 4842(CFM
conditions (i.e., ) 50% RH)
75ºF and
conditions of the radiant panel or building types and activities can be to the increase in humidity caused
chilled beam, and the DOAS air found in the 2019 ASHRAE HVAC by occupants:
handler. It assumes a situation in Applications Handbook. These Qheating = Qcooling + Pelectrical
which outside air at design cooling rates can vary from 5 to 20 CFM Formula 7-3:
load conditions is drawn into the per person. In general, the higher
building to provide the required the metabolic activity level, and the wmax = wdi + ∆ w ( )occupants
ventilation airflow. higher the potential for undesirable
pollutants to be generated within a where:
Step 1: Establish the design values space, the higher the recommended wmax = absolute humidity of space
for dry-bulb and wet-bulb air ventilation airflow rate per occupant. based on design load conditions
temperature both inside and outside. plus q
moisture added by
Typical indoor design conditions Step 5: Determine the increase in
= 1.08(CFM )(Toccupants
−T )
and activities
sah (lb water/lb dry
dbo air) dbi
are 75ºF and 50% relative humidity absolute humidity (∆w) created by (∆w)occupants = increase in absolute
(which yields a wet-bulb temperature occupants or other processes within humidity caused by occupants or
(e.g., dewpoint temperature) of 55ºF). the room giving off moisture using other moisture-generating processes
Typical outdoor design conditions Formula 7-2: (lb water/lb
q =dry
q air) − q
srad stotal sah
53
qL = 4842(CFM ) ∆ w ( )
∆T = 77º F − 62º F = 15º F
⎛ ⎞ qsah = 1.08(CFM )(Tdbo − Tdbi )
Q = ⎜ 6.0 Btu 2 ⎟ 500 ft 2 = 3000 Btu
⎝ hr ⋅ ft ⎠ hr
wdi = absolute humidity of indoor air at design conditions safely operate above the maximum (occupied) dewpoint
(lb water/lb dry air) temperature of the room.
⎛ ⎞
Q = 6.0 Btu(provided
Step 7: Use a psychrometric chart
B) to determine the⎜ elevated dewpoint
2⎟
in Appendix
ft 2 = 3000
500temperature Btu
Step 14: The latent load
qsrad =
coil in the air handler
that−must
qstotal qsah be carried by the
is based on the change in air
corresponding ⎝qL hr ⋅ absolute
ft ⎠ humidity. The hr
∆ w =to this maximum conditions across the coil and can be calculated using
minimum chilled4842(CFM )
water temperature supplied to the Formula 7-6.
chilled beams or radiant panels should be 3ºF above this
elevated dewpoint temperature. Formula 7-6:
where:
wmax
= w + ∆w
di ( ) occupants
a flow rate that satisfies the ventilation requirement of the
space. When introduced into the space for ventilation,
qsah = sensible load carried by the air handler (Btu/hr) this dry air will absorb moisture at a rate that satisfies the
CFM = airflow rate through air handler latent cooling load and maintains a reasonable relative
Tdbi = dry-bulb
qsrad temperature
= qstotal − qofsahair delivered to space (ºF) humidity within the space.
Tdbo = dry-bulb temperature of outdoor air at design
conditions (ºF) PIPING FOR DECOUPLED SENSIBLE & LATENT LOADS
q = 1.08(CFM )(T
sah cooling load that remains
dbo
−T )
dbithe
Systems using chilled beams or radiant panels require
Step 10: The sensible for piping and controls that can maintain the chilled water
radiant panels is the total sensible cooling load minus the temperature to the chilled beams or radiant panels a
sensible load
q =
L
carried
4842(CFM ( )
by the air) handler.
∆w minimum of 3ºF above the dewpoint temperature of
the room. The 3ºF margin allows the chilled beams or
Formula 7-5: radiant panels to absorb as much of the sensible cooling
qsrad = qstotal − qsah load as possible, while still providing a slight “safety
factor” against formation of surface condensation due
Q =Q +P to sensor and controller accuracy tolerances.
Step 11: When radiant panel
heating coolingcooling is used, the sensible
electrical
heat flux required of the panel is the total sensible load These systems also require control of chilled water
carried by the radiant panel divided by the area of the through the coil of a DOAS air handler so that ventilation
panel. air can be conditioned to a low dewpoint temperature,
54
local controller or
connection to BAS
Figure 7-12a chilled heated
water water
mains mains
variable
speed
injection
pump
SEP4
chilled beams hydraulic
separator
local controller or
connection to BAS
hydro
separator
radiant floor panel
FloCal
radiant ceiling panel balancing
valve
motorized
mixing
valve
zoned
zone
air
static purge valve valve
dampers
pressure
hydraulic separation
sensor
VFD
dry/cool air
exhaust air
outside air
SEP4
hydraulic
separator
hydro
check separator
variable speed controller
valves chiller chiller
(cooling & heating
modes)
of simultaneous heating and cooling. It also shows a mix controlled by a zone valve. FloCal balancing valves are
of radiant panels and chilled beams, either of which can used to automatically regulate the flow rate through each
operate in heating or cooling mode. chilled beam when it is operating. Flow to the chilled
beams is provided by a variable-speed pressure-regulated
An array of three chilled beams operating in cooling mode circulator operating in proportional differential pressure
is shown at the top of the schematic and in more detail in mode. The speed of this circulator automatically changes
Figure 7-12b. These are active chilled beams that provide as the zone valves at each chilled beam open and close.
sensible cooling and also introduce ventilation air into their The water temperature supplied to the chilled beams is
associated spaces. Water flow to each chilled beam is regulated by another variable-speed “injection” pump.
55
Figure 7-12b
local controller or
closely-spaced tee
connection to BAS
(hyraulic separation)
closely-spaced tee
(hyraulic separation)
air damper purge
zone
(manual or valves
valves
motorized)
off
FloCal
on
balancing
valves
on
off
The speed of this injection pump is regulated to maintain maintaining a set pressure differential between inside
a set chilled water supply temperature to the chilled and outside air. Although not shown in Figure 7-12a,
beams that is slightly above the current dewpoint an enthalpy wheel could be added to the DOAS air
temperature of the space. Flow from the chilled-water handler to enable energy recovery from the building
mains is allowed to pass through a pair of closely spaced exhaust air stream.
tees when any of the chilled beams are active. This flow
rate is regulated by FloCal balancing valves. The closely- The other cooling loads on the system are supplied by
spaced tees provide hydraulic separation between radiant panels. The upper radiant panel manifold can
the pressure across the chilled-water mains and the supply heating or cooling. The smaller radiant panel
differential pressure of the injection circulator. Another manifold only supplies cooling. The upper radiant panel
set of closely-spaced tees separate the injection pump manifold is separated from the heating and cooling mains
from the differential pressure of the variable-speed by a hydraulic separator. A 3-way motorized mixing valve
circulator supplying the chilled beams. The injection is used to keep the chilled water temperature to the
pump can also be controlled to regulate the supply radiant panel circuits slightly above dewpoint. This same
water temperature to the chilled beams during heating mixing valve can be operated in heating mode based on
mode. That temperature could be a setpoint or based outdoor reset control.
on outdoor reset control.
The DOAS air handler has a “deep” chilled-water coil
Ventilation air that has been conditioned to a low dewpoint capable of lowering the dewpoint of the ventilation air to
temperature is supplied from a DOAS air handler to each a very dry condition. Flow through this coil is regulated
chilled beam and regulated by a motorized damper. by a variable-speed circulator operated by a controller
The speed of the intake blower is regulated based on that monitors the dewpoint of the air leaving the air
maintaining a set static pressure in the ducting system. handler. Flow through the heating coils is also regulated
The speed of the exhaust blower is regulated based on by a variable-speed circulator. Hydraulic separation of
56
these injection circulators from the mains is provided by • Using a DOAS air handler with variable-speed blowers
a hydraulic separator. to supply chilled ventilation air at a low dewpoint
temperature to absorb the latent cooling load. The same
The chilled-water plant consists of two chillers, each with air handler can also heat incoming ventilation air during
its own circulator. The chiller output is linked to the mains winter.
using a hydraulic separator. A duplex pair of variable-
speed circulators creates flow in the chilled-water mains. • Use of variable-speed pressure-regulated circulators
The speed of the active circulator automatically varies as with on/off flow control through branch circuits to reduce
the zone valves that lead to the loads open and close. electrical energy consumption.
Heated water is provided by a pair of modulating/ • Use of automatic flow-balancing valves to control flow
condensing boilers. These boilers are also linked to the rates in key areas of the system.
heated water mains through a hydraulic separator. . A
duplex pair of variable-speed circulators creates flow • Using a staged approach to chilled water production
in the heated water mains. The speed of the active and heated water production.
circulator automatically varies as the zone valves that lead
to the heating loads open and close. • Using central hydraulic separators to isolate the
pressure dynamics of the chiller and boiler plants from
There are many possible variations of this concept those of the distribution system.
drawing. The key underlying concepts are:
• Using sets of closely-spaced tees or hydraulic separators
• Separation of the sensible and latent cooling loads. to isolate the pressure dynamics established by the main
distribution circulators from those established by the
• Use of water-based heating and cooling conveyance branch circulators.
to reduce air-side delivery to the ventilation requirements
and a small portion of the sensible cooling load. • The option to use either 3-way motorized valves or
variable-speed injection pumps to regulate heat transfer
• Using chilled beams and/or radiant panels to absorb rates at coils.
the majority of the sensible cooling load.
57
WATER LOOP HEAT PUMP SYSTEMS
Many commercial and industrial buildings have heating Buildings with simultaneous heating and cooling loads
and cooling load characteristics that are very different are well-suited to a water loop heat pump system, which
from smaller buildings. One of those characteristics is a can move heat from core areas to perimeter areas.
frequent need for simultaneous heating and cooling in
different parts of the building. On many days during fall Water loop heat pump systems consist of several water-
and spring, the perimeter areas of commercial buildings to-air heat pumps. Each heat pump has a refrigerant-
may require heating, while the building’s core areas (e.g., reversing valve, allowing it to operate in either heating
those without exposed surfaces) require cooling, as or cooling mode. All the heat pumps are connected to
depicted in Figure 8-1. a common hydronic distribution system. Heat pumps
operating in heating mode extract heat from the water
Although it’s possible to operate two separate systems circulating in the hydronic distribution system. Heat
— one for heating and the other for cooling — and pumps operating in cooling mode dissipate heat into this
use devices such as zoning dampers or zone valves hydronic distribution system. This allows excess heat
to direct the heating or cooling where needed, this is in the building’s core areas to be moved to where it’s
not the most efficient approach. The heating system needed in the perimeter areas. Heat that is moved is heat
would be burning fuel or consuming electricity to create that doesn’t have to be created.
heat for the perimeter areas. The cooling system would
be consuming electricity to absorb heat (e.g., create Figure 8-2 shows an example of a typical water-to-air heat
cooling effect). Neither system is attempting to move pump that would be used in this type of system. Heat
heat from where it’s present in access to where it’s pumps with horizontal orientation are typically installed
needed in the building. above suspended ceilings in commercial buildings. Those
with vertical orientation are usually installed in mechanical
Figure 8-1
LARGER BUILDINGS
WINTER / SPRING / FALL
perimeter areas require heating
ENVELOPE-DOMINATED BUILDINGS core areas require cooling
WINTER
(all spaces require heating)
SUMMER
(all spaces require cooling)
core areas
perimeter areas
58
qL = 4842(CFM ) ∆ w ( )
rooms or mechanical closets. These heat pumps are Formula 8-1:
available in nominal cooling capacities ranging from 0.5
to 5.0 tons (6,000 to 60,000 Btu/hr). Qheating = Qcooling + Pelectrical
Where:
Figure 8-2a Qheating = total heating requirement of the building (Btu/hr)
Qcooling = total concurrent cooling load of building (Btu/hr)
Courtesy of McQuay div. of DaikinApplied
59
Figure 8-3
anti-condensation
boiler(s)
mix C mixing valve
(ThermoProtec)
H
cooling mode heating mode cooling mode
check DiscalDirtMag
separator
valve
conventional
boiler
variable-speed
Alternative piping when a
pressure-regulated check valves
conventional boiler is used "2-pipe" reverse return water loop
circulator
(1 on / 1 off)
cooling mode cooling mode heating mode
closed-loop
evaporative
cooling tower spray nozzles diverter
valve
fill
cooling mode
ball valve
isolation/purge valve
set flow rate through the heat pump when it operates. as a backup. A controller automatically determines
Most heat pump manufacturers specify flow rates of 2 which circulator is operating and attempts to creates
to 3 gallons per minute per ton of heat pump heating approximately equal elapsed run time for each circulator.
capacity. Reinforced hoses are used to reduce vibration
transfer between the heat pump and rigid piping. Each A DiscalDirtMag separator provides high-efficiency air,
heat pump branch is also equipped with isolation and dirt and magnetic particle separation for the system.
purging valves. These allow any heat pump to be
isolated from the distribution loop and removed for Some water loop heat pump systems use closed-loop
servicing if necessary, without affecting operation of the cooling towers. The same fluid that passes through the
other heat pumps. water loop also passes through closed piping paths
within the cooling tower. There is no contact between this
Flow through the building loop is typically maintained water and the sump water used to enhance the tower’s
24/7. It’s provided by a duplex set of variable-speed evaporative heat dissipation. This is the type of cooling
pressure-regulated circulators that automatically adjust tower shown in Figure 8-3.
flow rate based on proportional differential pressure
control. As more heat pumps turn on, flow in the loop If the building loop system operates with all water,
is automatically increased, and vice versa. Only one of the cooling tower must be protected from freezing in
the two circulators operates at a time. The other serves winter. In some systems, the tower is isolated from the
60
Figure 8-4
variable-speed check
pressure-regulated valves
circulator (1 on / 1 off)
"2-pipe" reverse return water loop
balance of the system and drained during winter. In treatment chemicals in the sump water, from being
other systems, a small flow of water from the loop is discharged where they could cause adverse effects.
maintained through the tower to keep it from freezing.
The modulating 3-way motorized valve shown in Figure GEOTHERMAL WATER LOOP HEAT PUMP SYSTEMS
8-3 can provide this flow. The latter approach allows Water loop heat pump systems can also be adapted to
the tower to come online quickly during an abnormally geothermal earth loops. In some systems, the earth loop
warm day in winter. is sized to eliminate the need for a cooling tower and
auxiliary boiler. In other systems, the earth loop may be
Other systems use open cooling towers. In these sized to minimize the size of the cooling tower and boiler.
systems, the tower is typically separated from the closed/ Figure 8-4 shows an example of a system where the
pressurized building water loop by a plate & frame heat boiler and cooling tower have been eliminated.
exchanger. That heat exchanger should be sized for a
small approach temperature difference in the range of 2 The earth loop portion of this system is interfaced to
to 4ºF. This helps keep the loop temperature down during the building loop using a SEP4 hydraulic separator. This
cooling mode operation on hot summer days, and thus component provides high-efficiency air, dirt and magnetic
minimizes the drop in heat pump cooling performance. particle separation. It also provides hydraulic separation
between the earth loop circulator and the building loop
In most systems, the cooling tower is located outside the circulator. The hydraulic separation also allows the
building. However, it is possible to use a cooling tower potential for the speed of the earth loop circulator to be
mounted inside the building. Outside air enters the tower regulated independently of the building loop circulator.
through a large louvered panel in an exterior wall. After For example, the speed of the earth loop circulator could
passing through the tower, this air is discharged back be ramped up and down depending on the thermal load
outside through another larger louvered panel. When of the building. If there is a near balance between the
this type of tower is used, the discharge air should be heating and cooling loads in the building, the earth loop
directed away from nearby windows, doors, parked circulator could be operated at a very low speed since
vehicles or areas of outdoor gatherings. This prevents there is very little need for additional heat input to, or heat
water droplets in the discharge air, or residual water dissipation from the building loop.
61
cooling mode
Figure 8-5
variable-speed check
pressure-regulated valves
circulator (1 on / 1 off)
CONTECA
Earth loop circuits heat meter
fluid
feeder
BAS
system
variable-speed
pressure-regulated
circulator, or duplex pair
The earth loop circulator speed could be regulated based Modern water-to-air heat pumps intended for geothermal
on the rate of heat transfer supplied from the earth loop applications can operate across these wide temperature
compared to the measured load in the building loop. These ranges. Still, if the minimum loop temperature is expected
two rates of heat transfer can be monitored by CONTECA to approach freezing, the system should be operated with
heat meters and transferred to a building automation an antifreeze solution. All piping and piping components
system that in turn regulates the speed of the earth loop must also be insulated to prevent surface condensation
circulator. The piping for this concept is shown in Figure 8-5. when operating at fluid temperatures below the dewpoint
of interior air.
Aside from the source of supplemental heat supply and
dissipation, there are important differences between Another possibility is to connect one or more water-
a water loop heat pump system supplied by an earth to-water heat pumps to the building loop. These heat
loop versus one configured around a cooling tower and pumps could be used to heat domestic hot water, supply
supplemental boiler. radiant panels in some areas of a building, or supply
heated or chilled water for a process load.
One is the water temperature in the building loop. Whereas
a “boiler/tower” heat pump system typically maintains the When water-source heat pumps are used for heating
loop temperature between 70 and 90ºF, a building loop and cooling, the ventilation air is typically provided by
supplied from a geothermal system will operate over a a dedicated outdoor air system (DOAS). . During warm
much wider temperature range. Depending on the earth months, the DOAS cools and dehumidifies entering
loop design, the site location and the cooling load, the outside air. This air can be introduced directly into spaces
summer loop temperatures can be comparable to those by a separate duct system, or it can be mixed into the
achieved using a properly sized cooling tower. However, supply air stream leaving each heat pump. During winter,
during winter, the earth loop temperatures could drop the DOAS would pre-heat the incoming ventilation air.
much lower than 70ºF, perhaps as low as 30ºF.
62
ICE-BASED THERMAL STORAGE COOLING SYSTEMS
As the use of electrical-powered building cooling continues
to expand, electric utilities face a challenge: how to supply Figure 9-2
the necessary electrical energy in ways that do not create average power demand
increasingly sharp peaks in their power demand profile. For over 24 hours actual power
many utilities, especially those in warmer locations, peak demand
power demand occurs in late afternoon on hot and humid due to cooling
days, as represented in Figure 9-1.
100
90
Figure 9-1 peak
demand 80
70 40
30
60
20
50
10
40
0
30 0 4 8 12 16 20 24
hour of the day
20
10
One way to conceptually achieve this “ideal” scenario
0
would be to “clip off” the high-demand area shown in red
0 4 8 12 16 20 24 in Figure 9-3 and use this area to “fill in” the low-demand
hour of the day areas shown in green in Figure 9-3.
to the load over the 24 hour period. Figure 9-2 shows 70 demand
the average power that — if maintained for 24 hours — 60 area
would result in the same total electrical energy supply.
50
40 low
For this specific load profile, the average power is only
low demand
about 46% of the peak power. 30 demand area
20 area
An “ideal” scenario for an electric utility would be to
provide the same total amount of electrical energy over 10
the 24-hour period, but for the load profile shown in 0
Figure 9-2, supply it at a constant power of 46% of the 0 4 8 12 16 20 24
peak. This scenario is represented by the yellow area in hour of the day
Figure 9-2.
63
One method that has been used Figure 9-5
to reduce peaks and shift more
electrical power demand to periods
of low demand is called “demand-
side management.” In essence,
electric utilities encourage customers
to install equipment that can operate
during low-demand periods and
store energy until it’s needed.
Courtesy of CALMAC®
Financial incentives, such as time-
of-use electrical rates and demand
charges, is one of the key methods
used for demand-side management.
Time-of-use electrical rates offer
electrical energy at significantly loads is through ice storage systems. Notice the significant increase
lower cost per kilowatt•hour when it Each pound of liquid water at 32ºF in energy as a pound of water
is used during pre-defined periods of must give up 144 Btus to form one changes from ice to water. This
low demand. Those periods include pound of ice at 32ºF. This allows ice transition can also be viewed in
nighttime hours, and in some cases to store much more cooling effect per reverse, as a large increase in
weekends and holidays. Each utility pound of water compared to simply “cold storage” as a pound of liquid
offering these rates will have specific lowering the water’s temperature. water changes to a pound of ice.
rate structures and times at which A pound of liquid water would
they apply. Figure 9-4 shows the total thermal have to change its temperature
energy in water versus its absolute by 144ºF to store an equivalent
One way to apply demand-side temperature. amount of thermal energy.
management to commercial cooling
Also notice that the change
between ice and liquid water
Figure 9-4 occurs at a constant temperature
superheated steam
of 32ºF. This temperature is very
saturated steam close to the typical supply water
1600 temperature of 45ºF in chilled-
r) water cooling systems.
total thermal energy in water (vapo
thermal energy in water (Btu/lb)
1400 stea m
at atmospheric pressure The fundamental concept of an
ice storage cooling system is to
1200 operate a chiller during periods
liquid to vapor (970 Btu/lb) of low utility rates (typically at
1000 night) to transform a volume of
liquid water, held in one or more
800 45 ºF
large, unpressurized, insulated
typical chilled water
containers, into ice. This ice is then
supply temperature
600 melted to supply cooling during the
subsequent peak loading period.
400 id
liqu
ice to water (144 Btu/lb) One possibility is a configuration
200 called a “full storage” system. In
e this approach, the amount of ice
)all ic
(solid 32 ºF 212 ºF created during a given “off-peak”
0
period will be sufficient to meet the
0 100 200 300 400 500 600 700 800 building’s entire cooling load during
absolute temperature (ºRankine) the subsequent “on-peak” period.
In theory, this eliminates the need
to operate the chiller during the
64
“on-peak” period, and significantly
lowers both the cost of operation Figure 9-6
and the peak power demand of the small diameter PE tubing
system. Most commercial buildings ice annulus forming around tubing
are billed for both the amount of enlarging ice annulus
electrical energy used over a billing
period (e.g., kilowatt•hours), as well water
liquid
as the peak power demand (e.g., (32.5ºF)
water
kilowatts) over any 15-minute period
during that billing period.
65
Figure 9-7
4-pipe air handlers
in cooling mode
antifreeze
feeder SEP4
Hydro
Separator
SEP4
Hydro
Separator
31ºF
ice-building cycle
(loads assumed to be off)
25ºF
31ºF
chiller chiller
25ºF
If a condition is reached where the ice storage tanks The load consists of multiple 4-pipe air handlers. Flow to
can no longer supply the cooling load, one of the each chilled-water coil is controlled by a zone valve. A
chillers would be operated, perhaps at partial capacity, pressure-independent balancing valve maintains a stable
to supplement the output of the ice storage tanks. predetermined flow rate through each coil when the
The modulating 3-way valve would determine the associated zone valve is open, regardless of the on/off
proportions of flow through the ice bank versus straight status of the other air handlers. A variable-speed pressure-
through the valve. regulated circulator automatically adjusts its speed based
on proportional differential pressure control. The 3-way
Figure 9-9 shows a scenario where the cooling effect available mixing valve downstream of the load circulator would have
from the ice storage tank has been depleted (e.g., all ice its bypass fully closed. System fluid would be supplied to
melted and the water in the tanks elevated to a temperature each air handler at 44ºF. The fluid leaving each active air
that can no longer provide adequate cooling at the loads). handler at approximately 58ºF would pass through the
hydraulic separator and back to the chiller. If modern ECM
At this point, the chillers supply the entire cooling load. circulators are used, a building automation system can be
The two hydraulic separators allow the chiller flow rates used to match flow rate of the main loop circulator to the
to be independent of the main loop flow. They also allow flow rate of the load circulator. This prevents mixing within
the load flow rate to be independent of the main loop the hydraulic separator and assures that the warmest fluid
flow rate. is returned to the chiller.
66
Figure 9-8
4-pipe air handlers
in cooling mode
antifreeze
feeder SEP4
Hydro
Separator
58ºF
58ºF
44ºF
load supplied from ice bank
(chillers are off)
58ºF
31ºF
58ºF
chiller chiller mixing point
Ice-based thermal storage can be retrofitted to existing • Ability to provide some cooling capacity during a
chilled-water distribution systems. In these situations, it is power outage, assuming a sufficient backup
possible to install a generously sized (e.g., low approach generator is available to power the circulators.
temperature difference) plate & frame heat exchanger to • Some utilities offer incentives to reduce the
separate the antifreeze solution in the thermal storage installation cost of this type of system.
portion of the system from the water in the existing
portion of the system.
SUMMARY
Ice-based thermal storage cooling systems provide Today, there are very few new or remodeled commercial
several benefits, including: buildings or institutional buildings that do not have a
means of cooling. Its appeal, and availability in many
• Lower operating cost based on off-peak electrical rates. different forms, make it an expectation rather than a
• Reduced capacity chiller sizing relative to peak load luxury. As population patterns within the U.S. have
(66% of peak load is a starting point estimate). progressively shifted to warmer climates, the market
• Reduced utility demand charges due to reduced for cooling in nearly all commercial and institutional
chiller capacity. buildings has created continuously expanding market
• Ability to provide several hours of cooling if the chiller opportunities. This issue of idronics has discussed the
is temporarily offline for maintenance following a full unique and unmatched role that modern hydronics
ice-making cycle. technology can play in supplying that market.
67
heat coil
Figure 9-8 (inactive)
antifreeze
feeder SEP4
Hydro
Separator pressure-
zone
independent
balancing valve
58ºF valve
variable-speed
pressure-regulated
circulator
44ºF 44ºF 44ºF
SEP4
44ºF
Hydro
Separator
58ºF
44ºF 44ºF
chiller chiller
The following points summarize the design considerations • Multiple staged chillers or heat pumps can provide
for these systems: commercial cooling capacity in locations that only
have single phase power.
• The starting point for all cooling system design is an
accurate estimate of sensible and latent cooling loads. • Heat recovery chillers can serve simultaneous heating
and cooling loads. So can water loop heat pump systems.
• Piping for conveyance of chilled water is much
smaller than ducting of equivalent cooling capacity. • Circulator power should be minimized, since it all adds
to the cooling load. Use of variable-speed circulators in
• Hydronic-based cooling systems have much higher combination with valve-based zoning will significantly
distribution efficiency compared to air-based cooling lower operating costs in multi-zone systems.
distribution systems.
• Radiant cooling panels and chilled beams must
• All terminal units that provide latent cooling must remain above the current dewpoint temperature of
have drip pans. the room to avoid condensation.
• All chilled-water piping must be insulated and vapor- • Ice storage cooling systems can significantly lower
sealed to prevent condensation. operating cost and reduce the size of required chiller
plants.
68
APPENDIX A: GENERIC PIPING SYMBOL LEGEND
GENERIC COMPONENTS
3-way motorized
circulator mixing valve
blower compressor
filter
circulator w/ 4-way motorized
mixing valve
coil reversing!
valve
union
evaporator
circulator w/
internal check valve
evaporator
condenser
swing check valve comp. RV
TXV
spring-loaded
water-to-air
gate valve check valve
heat pump TXV
(in heating mode)
water-to-water
globe valves purging valve heat pump
blower (in heating mode)
ball valve
filter
pressure gauge
compressor
primary/secondary coil
fitting
pressure
relief
condenser
valve
reversing!
hose bib valve
drain valve pressure & comp. RV
TXV
temperature
relief valve
condenser
evaporator
diverter tee water-to-air
heat pump
cap metered (in cooling mode)
balancing
valve
TXV
water-to-water
heating mode
heat pump
diaphragm-type (in cooling mode)
brazed-
expansion tank
plate
heat reversing
exchanger valve
evaporator
condenser
Comp.
solar collector
Modulating / condensing boiler
indirect water heater (with trim) solar water tank (with electric element)
69
APPENDIX A: CALEFFI COMPONENT SYMBOL LEGEND
CALEFFI COMPONENTS
Float - type
air vent inline check valve
3-way
thermostatic mixing valve
DIRTCAL®
dirt
separators
pressure
reducing
valve distribution
(3/4") station
HYDROFILLTM
backflow
NA10045
preventer
pressure-
NA10045
reducing
valve
CO N TECA CONTECATM
EASY
heat calculator
RS485
differential
pressure
bypass valve
sensor fittings
flow meter
zone valve
(3 way)
ThermoCon buffer tank
LEGIOMIX® thermoelectric
zone valve
(2 way)
Hydro
Separator
Hydro
Separator
TANKMIXERTM motorized
ball valve
(2 way)
Hydro
Separator
motorized
THERMOSETTERTM
ball valve
adjustable
balancing (3 way)
valve
variable orifice
balancing
valve
solar
thermostatic
circulation
FLOWCALTM radiator valve
station
balancing
valve
thermostatic
FLOWCALTM
radiator valve
balancing
valve
dual isolation
SEP4TM valve for
SEP4TM fixed orifice panel radiators
SEP4 TM
balancing
valve
high-temperature
solar 3-way thermostatic
QuickSetterTM high-temperature mixing valve
balancing solar DISCAL
valve w/ air separators
HydroBlock flowmeter isolar
mixing units
differential
high-temperature temperature
solar pressure controller
70
PSYCHROMETRIC Grains of moisture Pounds of moisture
CHART per pound of dry air per pound of dry air
Normal Temperature
`
`
I-P Units
SEA LEVEL 180
BAROMETRIC PRESSURE: 29.921 in. HG .025
45
170
.024
0.40
160 .023
80
.022
40
150
0.45
.021
140 .020
14.5
0.50
35 75 .019
Btu
130
90%
-0.1
.018
0.55
120 .017
tu
0.60
80%
70 .016
-0.2 B
30
110
0.65
.015
%
0.70
70
100
.014
APPENDIX B: PSYCHROMETRIC CHART
0.75
65
R
AI
25
Y
90 .013 0.80
DR
14.0
OF
0.85
60
ND
.012
U
VOL
0.90
PO
R
80 0.95
UME
60
PE
U
.011 1.00
T
tu
- CU
-B
`
2B
.FT
PY
-.0
20 %
Btu
Sensible
AL
50 70 .010
. PE
TH
Heat
-.04
EN
Factor
Btu
55
R LB
-.06
.009
. DR
Btu
60
-.08
%
Y AIR
40 .008
50
13.5
15
50 .007
45
30% .006
40
40
-0.3 Btu - Enthalpy deviation Btu per pound of dry air
.005
10 35
30
20%
13.0
.004
30
B tu
0.1 .003
25 20
Btu Y
0.2 TIVE HUMIDIT
Wet-Bulb Btu 10 % RELA .002
12.5
Dewpoint or 0.3
`
Saturation 10
Btu
Temperature F 0.4 .001
0 .000
Dry-Bulb 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
`
Temperature F
Below 32 F, properties and enthalpy deviation lines are for ice. Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com
71
www.caleffi.com
RELIABLE