MODEL APD2500M-6
kVA 2500
Standby
Power kW 2000
Pf. 0.8 kVA 2275
Prime
kW 1820
Standby: Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046 .
Prime: Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528,ISO 3046.
Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
www.aksapowergen.com
ENGINE
MITSUBISHI
Model S16R-PTAA2
ALTERNATOR
Brushless, single bearing system, flexible disc, 4 poles Impregnation with tropicalised epoxy varnish
Insulation class H Solid state Automatic Voltage Regulator
Standard degree of protection IP21 (*IP22/IP23 is available.) Stator winding with 2/3 pitch for improved harmonics
Self-exciting and self-regulating
www.aksapowergen.com
CONTROL SYSTEM
Control supervision and protection panel is mounted on the genset base frame.
The control panel is equipped as follows:
OPTIONAL EQUIPMENTS
www.aksapowergen.com
CHASSIS
The complete gen-set is mounted as whole on a heavy-duty fabricated, steel base frame
Anti-vibration pads are fixed between the engine/ alternator feet and the base frame
Base frame design incorporates an integral fuel tank (Up to 750 kVA)
The generating set can be lifted or carefully pushed / pulled by the base frame
Dial type fuel gauge and drain plug on the fuel tank
Forklift pockets within base frame (up to 500kVA)
DIMENSIONS
OPEN TYPE
DIMENSIONS (LxWxH) mm 5814x2192x3390
DRY WEIGHT kg 13450
CANOPY
All canopy parts are designed with modular principles Exhaust silencer is protected against environment influences
Without welding assembly Thermally insulated engine exhaust system
Doors on each side Emergency stop push button is installed outside of the canopy
All metal canopy parts are painted by electrostatic Easy lifting and moving
polyester powder paint Easy maintenance and operation
ENGINE MOUNTING
Maximum Bending Moment at Rear Face of Flywheel Housing - kg・m(lbf・ft) 450 (3256)
AIR INLET SYSTEM
Maximum Intake Air Restriction (Includes piping
With Clean Filter Element - mm H2O (in.H2O) 400 (15.7)
With Dirty Filter Element - mm H2O (in.H2O) 635 (25.0)
EXHAUST SYSTEM
Maximum Allowable Back Pressure - mm H2O (in.H2O) 600 (23.6)
LUBRICATION SYSTEM
Oil Pressure at ldle - kgf/cm2(psi) 2~3 (29~43)
at Rate Speed - kgf/cm2(psi) 5~6.5 (71~93)
Maximum Oil Temperature - oC(oF) 110 (230)
Oil Capacity of Standard Pan High - liter (U.S.gal) 200 (52.8)
Low - liter (U.S.gal) 140 (37.0)
Total System Capacity (lncludes Oil Filter) - liter (U.S.gal 230 (60.8)
Maximum Angle of lnstallation (Std. Pan) Front Down 5o
(Engine Only) Front Up 5o
Side to Side 22.5o
COOLING SYSTEM
Coolant Capactiy - Engine - liter (U.S.gal) 170 (44.9)
- Radiator & Piping - liter (U.S.gal 243 (64.2)
Maximum External Friction Head at Engine Outlet - kgf/cm2(psi) 0.35 (5.0)
Maximum Static Head of Coolant above Crankshaft Center - m(ft) 10 (32.8)
Maximum Outlet Pressure of Engine Water Pump - kgf/cm2(psi) 2 (28.6)
Standard Thermostat (modulating)Range- oC(oF) 71~85 (160~185)
Maximum Coolant Temperature at Engine Outlet-oC(oF) 98 (208)
Minimum Coolant Expansion Space - % of System Capacity 10
Maximum Cooling Air Temperature at Air to Air Cooler Inlet, TAA type-oC(oF) 40 (104)
Maximum Air Restriction on Discharge Side of Radiator and Fan-mm H2O(in.H2O) 40 (1.6)
APPLICATION : GENERATOR
Pub. No. T13-0430-E
Jun. '03 Printed in Japan
Certified for US EPA/Tier 1/Constant Speed MITSUBISHI
S16R-Y1PTAA2-1 SPECIFICATION SHEET DIESEL ENGINES
FUEL SYSTEM
Fuel Injector Mitsubishi PS8 Type × 2
Maximum Suction Head of Feed Pump - mm Hg (in. Hg 75 (3.0)
Maximum Static Head of Return & Leak Pipe - mm Hg (in.Hg) 150 (5.9)
STARTING SYSTEM
Battery Charging Alternator - V-Ah 24-30
Starting Motor Capacity - V -kW 24-7.5×2
Maximum Allowable Resistance of Cranking Circuit - mΩ 1.5
Recommended Minimum Battery Capacity
At 5oC(41oF) and above - Ah 300
o o o o
Below 5 C(41 F) through - 5 C(23 F) 600
Bore mm 170
(in.) (6.69)
Stroke mm 180
(in.) (7.09)
Displacement liter 65.37
3
(in. ) (3989)
Brake Horse power without Fan HP 2882 2620 1823 1622
(kW) (2150) (1955) (1360) (1210)
2
Brake Mean Effective Pressure kgf/cm 22.4 20.3 14.1 12.6
without Fan (psi) (319) (289) (201) (179)
Mean Piston Speed m/s 10.8 10.8 10.8 10.8
(ft/min) (2126) (2126) (2126) (2126)
Maximum Regenerative Power HP 258 258 258 258
Absorption Capacity without Fan (kW) (192) (192) (192) (192)
Intake Air flow m3/min 181 164 114 102
(CFM) (6391) (5791) (4025) (3602)
Exhaust Gas Flow m3/min 478 433 302 271
(CFM) (16878) (15289) (10664) (9569)
Coolant Flow liter/min 1850 1850 1850 1850
(U.S. GPM) (489) (489) (489) (489)
Coolant Flow to Intercooler liter/min
- - - -
(TK only) (U.S. GPM)
3
Cooling Air Flow m /min 2500 2500 2500 2500
(Std. Fan) (CFM) (88275) (88275) (88275) (88275)
Fan Loss Horse Power HP 59 59 59 59
(Std. Fan) (kW) (44) (44) (44) (44)
Radiated Heat to Ambient kcal/hr 136076 123306 86077 77030
(BTU/min) (9000) (8155) (5693) (5095)
Heat Rejection to Coolant kcal/hr 589662 534327 373001 333797
(BTU/min) (38999) (35340) (24670) (22077)
Heat Rejection to Air to Air Cooler kcal/hr 544304 493225 344308 308120
(BTU/min) (36000) (32621) (22772) (20379)
Heat Rejection to Exhaust kcal/hr 1417210 1278769 896479 808324
(BTU/min) (93732) (84576) (59292) (53461)
Noise Level (1 m height & distance) dB(A) 112 109
(excludes, lntake,Exhaust & Fan)
APPLICATION : GENERATOR
Pub. No. T13-0430-E
Jun. '03 Printed in Japan
ITEM No. T0104-0003E Rev.5 (1/2)
MITSUBISHI DIESEL ENGINE
TECHNICAL INFORMATION DATE March, 2017
Sales literatures show the power output of the engines at the standard atmospheric conditions.
When the engine is operated under conditions different from the standard atmospheric conditions, the
output must be adjusted according to the chart shown below.
If the ambient temperature or the ambient pressure (altitude) conditions are different from the
standard atmospheric conditions, the output must be derated.
1500 0.0 0.0 2.0 5.0 8.0 11.0 14.0 17.0 PTAW2 models
2000 1.0 4.0 7.0 10.0 13.0 16.0 19.0 22.0
2500 6.0 9.0 12.0 15.0 18.0 21.0 24.0 27.0
3000 11.0 14.0 17.0 20.0 23.0 26.0 29.0 32.0
3500 16.0 19.0 22.0 25.0 28.0 31.0 34.0 37.0
4000 21.0 24.0 27.0 30.0 33.0 36.0 39.0 42.0
1500 0.0 0.0 2.0 5.0 10.8 16.5 are not included in S16R-(P)TAA2 and
2000 1.0 4.0 7.0 10.0 15.8 21.5 follow the above table.
2500 6.0 9.0 12.0 15.0 20.8 26.5
3000 11.0 14.0 17.0 20.0 25.8 31.5
3500 16.0 19.0 22.0 25.0 30.8 36.5
4000 21.0 24.0 27.0 30.0 35.8 41.5
䈜 When derating the output, confirm that the maximum lubricant temperature satisfies the limit stated
in the specification sheet (less than or equal to 110ºC/105ºC).
䈜 If the atmospheric conditions fall outside the range of output derating chart, judgement is made
according to individual case.
䈜 Output adjustment chart is used only for reducing the rated output, it must never be used for
increasing the rated output.
M
Specification Sheet. Hoja de Especificaciones
The different solutions of controls that have Las diferentes soluciones de controles que
for our range of gensets, allows a simple se tienen para nuestra gama de grupos
operation in manual and automatic mode. generadores, permite una operación
simple en modo manual y automático.
This control provides an automatic start
due to network failure. Allows to monitor Este módulo de control proporciona un
the power supply. arranque automático por fallo de red.
Permite monitorear la red eléctrica.
InteliLiteNT AMF25 is a comprehensive AMF-controller for single InteliLiteNT AMF25 es un controlador AMF integral para grupos
generating sets operating in stand-by mode. IL-NT AMF25 features generadores individuales que operan en modo de espera. IL-NT
extended support of electronic engines and extension modules. AMF25 ofrece soporte extendido de motores electrónicos y módulos
de extensión.
InteliLiteNT controllers are equipped with a powerful graphic display
showing icons, symbols and bar-graphs for intuitive operation, Los controladores InteliLiteNT están equipados con una potente
which sets, together with high functionality, new standards in Gen- pantalla gráfica que muestra iconos, símbolos y gráficos de barras
set controls. para un funcionamiento intuitivo, que establece, junto con una gran
funcionalidad, nuevos estándares en los controles Gen-set.
InteliLiteNT automatically starts the Gen-set, closes the Gen-set
C.B. when all conditions are met, then stops the engine on external InteliLiteNT inicia automáticamente el conjunto Gen, cierra el
signal or by pressing push buttons. conjunto Gen C.B. cuando se cumplen todas las condiciones, luego
detiene el motor en una señal externa o presionando los botones.
InteliLiteNT provides gas engine support without ventilation.
InteliLiteNT proporciona soporte para motor de gas sin ventilación.
The key feature of InteliLiteNT is its easy-to-use operation and
installation. Predefined configurations for typical applications are La característica clave de InteliLiteNT es su operación e instalación
available as well as user-defined configurations for special fáciles de usar. Se encuentran disponibles configuraciones
applications. predefinidas para aplicaciones típicas, así como configuraciones
definidas por el usuario para aplicaciones especiales.
• Generator current per phase (amps) • Corriente de generador por fase (amperes)
• Generator frequency (Hz) • Frecuencia de generador (Hz)
• Voltage C.A. Between L-L and L-N • Voltaje C.A. entre L-L y L-N
• Engine coolant temperature (° C) • Temperatura del refrigerante de motor (°C)
• Engine oil pressure (PSI) • Presión de aceite de motor (PSI)
• Battery Voltage V.C.D. • Voltaje de Batería V.C.D.
• kW per phase and total • kW por fase y total
• kVAr per phase and total • kVAr por fase y total
• kVA per phase and total • kVA por fase y total
• Power factor per phase and total • Factor de potencia por fase y total
• kWh and kVARh • kWh y kVARh
• Operation hours counter • Contador de horas de operación
• Start counter • Contador de arranques
• Maintenance hours counter • Contador de horas de mantenimiento
• Fuel level in percent (%) • Nivel de combustible en por ciento (%)
4 03_2020
5 03_2021
Engine warning functions Funciones de advertencias del motor
• Low oil pressure • Baja presión de aceite
• Analogue pressure sensor failure • Avería de sensor analógico de presión
• High coolant temperature • Alta temperatura del refrigerante
• Analog refrigerant sensor failure • Avería de sensor analógico de refrigerante
• High battery voltage • Voltaje alto de batería
• Low battery voltage • Voltaje bajo de batería
• Ineffective Battery • Batería Ineficaz
• Low fuel level • Bajo nivel de combustible
• Necessary maintenance • Mantenimiento necesario
Optionally, remote communication can be provided according to De manera opcional se puede suministrar comunicación remota de
the type of need of the user, being this: acuerdo al tipo de necesidad del usuario, siendo ésta:
• Through dry contacts, failures and configurable • A través de contactos secos, de fallas y alarmas
alarms, for example: configurables, por ejemplo:
1. Low oil pressure. 1. Baja presión de Aceite.
2. Start attempts. 2. Intentos de arranque.
3. Overload. 3. Sobrecarga.
4. Generator voltage failure. 4. Falla de voltaje del generador.
5. High temperature 5. Alta temperatura.
6. Low battery voltage. 6. Bajo voltaje de batería.
7. Low fuel level. 7. Bajo nivel de combustible.
8. Group in operation 8. Grupo en operación
• Through communication via RS232, RS485, GPRS,
ETHERNET / INTERNET, etc., with information • A través de comunicación via RS232, RS485,GPRS,
through MODBUS RTU (Standard) or some other ETHERNET/INTERNET, etc., con información a través de
protocol (BACNET, PROFIBUS, SNMP) for MODBUS RTU (Estándar) o algún otro protocolo
integration to any type of platform. (BACNET, PROFIBUS, SNMP) para integración a
cualquier tipo de plataforma.
6 03_2021
Control Module Option 2
Módulo de Control Opción 2
The different solutions of controls that have Las diferentes soluciones de controles que
for our range of gensets, allows a simple se tienen para nuestra gama de grupos
operation in manual and automatic mode. generadores, permite una operación
simple en modo manual y automático.
This control provides an automatic start
due to network failure. Allows to monitor Este módulo de control proporciona un
the power supply. arranque automático por fallo de red.
Permite monitorear la red eléctrica.
DS7320. It has a digital LCD screen, wich provides easy reading of DS 7320. Dispone de una pantalla digital de LCD, que permite una
the information regarding the engine, alternator, mains and load. fácil lectura de la información referente del motor, generador, red y
carga.
Readings that can be made:
Lecturas que pueden realizarse:
Engine:
Motor:
• Coolant temperature • Temperatura del refrigerante
• Oil pressure • Presión de aceite
• Speed (rpm) • Velocidad (r.p.m.)
• Fuel level • Nivel de Combustible
• Battery voltage • Voltaje de batería
• Battery alternator voltage • Voltaje del alternador de batería
• Operating hours • Horas de operación
• Number of start-ups • Número de arranques
7 03_2021
Alternator. Generador.
• The real-time clock provides an exact record of eventes • El reloj en tiempo real permite un registro de eventos
• Extensive number of configurables inputs and outputs exacto
• Configurable alarms and timers • Amplio número de entradas y salidas configurables
• USB connectivity • Alarmas y temporizadores configurables
• Fully configurable via software and PC • Conectividad USB
• Modbus RTU • Modbus RTU
• Possibility of SMS text messages • Posibilidad de mensajes SMS
• Communications Ethernet, RS 232 and RS 485 • Comunicaciones Ethernet, RS 232, RS 485
• Programmer Clock with multiple maintenance events • Reloj Programador con multiples eventos de
which can be configured for the optimal operation of the mantenimiento que pueden configurarse para un óptimo
engine. Weekly and/ or monthy programming of up to 16 funcionamiento del motor. Programación semal y/o
starts and stops per week. mensual hasta 16 arranques y paradas por semana.
8 03_2021
PI734E - Technical Data Sheet
PI734E
SPECIFICATIONS & OPTIONS
STANDARDS WINDINGS & ELECTRICAL PERFORMANCE
Newage Stamford industrial generators meet the All generator stators are wound to 2/3 pitch. This
requirements of BS EN 60034 and the relevant sections of eliminates triplen (3rd, 9th, 15th …) harmonics on the
other national and international standards such as voltage waveform and is found to be the optimum design
BS5000, VDE 0530, NEMA MG1-32, IEC60034, CSA for trouble-free supply of non-linear loads. The 2/3 pitch
C22.2-100, AS1359. design avoids excessive neutral currents sometimes seen
Other standards and certifications can be considered on with higher winding pitches. A fully connected damper
request. winding reduces oscillations during paralleling. This
winding, with the 2/3 pitch and carefully selected pole and
DESCRIPTION tooth designs, ensures very low levels of voltage waveform
distortion.
The STAMFORD PI range of synchronous ac generators
are brushless with a rotating field. They are separately TERMINALS & TERMINAL BOX
excited by the STAMFORD Permanent Magnet Generator
(PMG). This is a shaft mounted, high frequency, pilot Standard generators feature a main stator with 6 ends
exciter which provides a constant supply of clean power brought out to the terminals, which are mounted on the
via the Automatic Voltage Regulator (AVR) to the main frame at the non-drive end of the generator. A sheet steel
exciter. The main exciter output is fed to the main rotor, terminal box contains the AVR and provides ample space
through a full wave bridge rectifier, protected by surge for the customers' wiring and gland arrangements. It has
suppression. removable panels for easy access.
The PI range generators, complete with a PMG, are All generator rotors are dynamically balanced to better than
available with one of two AVRs. Each AVR has soft start BS6861:Part 1 Grade 2.5 for minimum vibration in
voltage build up and built in protection against sustained operation. Two bearing generators are balanced with a half
over-excitation, which will de-excite the generator after a key.
minimum of 8 seconds.
Underspeed protection (UFRO) is also provided on both INSULATION/IMPREGNATION
AVRs. The UFRO will reduce the generator output voltage
proportional to the speed of the generator below a pre-
The insulation system is class 'H', and meets the
settable level.
requirements of UL1446.
All wound components are impregnated with materials and
The MX341 AVR is two phase sensed with a voltage
processes designed specifically to provide the high build
regulation of ± 1 %. (see the note on regulation).
required for static windings and the high mechanical
strength required for rotating components.
The MX321 AVR is 3 phase rms sensed with a voltage
regulation of 0.5% rms (see the note on regulation). The QUALITY ASSURANCE
UFRO circuit has adjustable slope and dwell for controlled
recovery from step loads. An over voltage protection circuit
Generators are manufactured using production procedures
will shutdown the output device of the AVR, it can also trip
having a quality assurance level to
an optional excitation circuit breaker if required. As an
BS EN ISO 9001.
option, short circuit current limiting is available with the
addition of current transformers.
NOTE ON REGULATION
The stated voltage regulation may not be maintained in the
Both the MX341 and the MX321 need a generator
presence of certain radio transmitted signals. Any change
mounted current transformer to provide quadrature droop
in performance will fall within the limits of Criteria 'B' of EN
characteristics for load sharing during parallel operation.
61000-6-2:2001. At no time will the steady-state voltage
Provision is also made for the connection of the
regulation exceed 2%.
STAMFORD power factor controller, for embedded
applications, and a remote voltage trimmer.
Note: Continuous development of our products entitles us to
change specification details without notice, therefore they must not
be regarded as binding.
2
PI734E
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX341 MX321
VOLTAGE REGULATION ±1% ± 0.5 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)
PROTECTION IP23
WINDING LEADS 6
MAIN STATOR RESISTANCE 0.00093 Ohms PER PHASE AT 22°C STAR CONNECTED
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6228 C3
BEARING NON-DRIVE END BALL. 6319 C3
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR 3556 kg 3506 kg
3
PI734E
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES
4
PI734E
Winding 312
60
THREE PHASE EFFICIENCY CURVES
Hz
5
PI734E
Winding 312
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
LOCKED ROTOR kVA
60
30
Hz 380V 416V 440V 460V 480V
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
LOCKED ROTOR kVA
6
PI734E
SYMMETRICAL
ASYMMETRICAL
CURRE NT (Am p s)
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
60 100000
Hz
SYMMETRICAL
ASYMMETRICAL
CURRE NT (Am p s)
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
7
PI734E
Winding 312 / 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
kVA 1715 1770 1770 1735 1845 1900 1900 1865 1920 1980 1980 1940 1975 2035 2035 1995
kW 1372 1416 1416 1388 1476 1520 1520 1492 1536 1584 1584 1552 1580 1628 1628 1596
Efficiency (%) 95.9 96.0 96.1 96.3 95.7 95.8 96.0 96.1 95.6 95.7 95.8 96.1 95.5 95.6 95.8 96.0
kW Input 1431 1475 1473 1441 1542 1587 1583 1553 1607 1655 1653 1615 1654 1703 1699 1663
60Hz Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
kVA 1935 2055 2100 2140 2070 2210 2255 2300 2155 2300 2345 2395 2215 2365 2415 2465
kW 1548 1644 1680 1712 1656 1768 1804 1840 1724 1840 1876 1916 1772 1892 1932 1972
Efficiency (%) 95.8 95.9 96.0 96.1 95.7 95.8 95.9 95.9 95.6 95.7 95.8 95.9 95.5 95.6 95.7 95.8
kW Input 1616 1714 1750 1781 1730 1846 1881 1919 1803 1923 1958 1998 1855 1979 2019 2058
DIMENSIONS
204
25 1"
BARRENOS 12X
6.4
762
204
1 1
662 26 16 " 362 14 4 "
6.4
100
24
406
VISTA FRONTAL VISTA LATERAL
1050 1050
254 PUNTO
GUIA
331
254
406
770
2100
Ottomotores se reserva el derecho de hacer modificaciones sin aviso con el fin de mejorar nuestros equipos.
Rev. Descripción Fecha Modificado Cantidad
Título: SILENCIADOR ACUSTICO Ø 10" EN L de pzas: 01
-- -- -- --
Medida
para corte
A LIBERADO PARA PRODUCCION 13/03/2017 JEMM Dibujó: VANYA R.E. Revisó: ELOY M
Clave SW: 41060614002-A en (mm): x
Aprobó: ABRAHAM R.T. Fecha de Emisión: 13/03/2017 Material:
Cliente: OTP: Clave ERP: 41060614002-A VARIOS
Depto.: Ingeniería Plano: TOLERANCIAS: Calibre:
Acot: mm.(pulg.) 1 CNC: +/- 0.5mm VARIOS
OTTOMOTORES N/A Scale: 1:20
De:
CORTE: +/- 2mm
DOBLEZ: +/- 2mm
ROLADO: +/- 2mm
Peso
en (kg): 173
4 ENSAMBLES: +/-3 mm
ESTE DIBUJO Y LOS ANEXOS ENTREGADOS AL DESTINATARIO SON PROPIEDAD DE OTTOMOTORES, QUEDA PROHIBIDA SU REPRODUCCIÓN,
LA COMUNICACIÓN A TERCEROS, O EL EMPLEO DE SU CONTENIDO SON DERECHOS RESERVADOS
GEMM: N/A COLOR: ALUMINIO AREA (m2): N/A
BELGE SAHİBİ KURULUŞUN ADRESİ NO:19 TONGJIANG NORTH ROAD, CHANGZHOU NEW DISTRICT,
ADRESS OF THE LICENCE HOLDER CHANGZHOU,CHİNA -/ÇİN
ÜRETİM YERİ ADI AKSA POWER GENERATION (CHINA) CO., LTD.
NAME OF THE MANUFACTURING PLACE
ÜRETİM YERİ ADRESİ NO:19 TONGJIANG NORTH ROAD, CHANGZHOU NEW DISTRICT,
ADRESS OF THE MANUFACTURING PLACE CHANGZHOU, CHINA - / ÇİN
İPTAL EDİLEN BELGE NUMARASI (Varsa) 109513-TSE-02/03
INDICATION OF SUPERSEDED LICENCE (if any)
TESCİLLİ TİCARİ MARKASI AKSA JENERATÖR
REGISTERED TRADE MARK
İLGİLİ TÜRK STANDARDI TS ISO 8528-5 / 15.10.2015 -- TS EN ISO 8528-13 / 13.04.2018
RELATED TURKISH STANDARD
BELGE KAPSAMI
SCOPE OF LICENCE
-APDXXXA Model, AKSA Engine, Prime 10,6 KVA / 8,5 kW (included), from Standby 11,5 KVA / 9,2 kW (Prime 10,6
KVA - Standby 11,5 KVA included), Prime 410 KVA, to 328 kW Standby 450 KVA / 360 kW (including Prime 410 kVA
- Standby 450 kVA)
230 / 400V, 50Hz, G3 Performance class IP 21 M UNCABINET-IP 23M CABINET, 3-phase Automatic or Manual
operation control unit Generator groups, Diesel fueled
-APDXXXA Model, CROWN KRAFT Engine, Prime 11 KVA / 8,8 kW (included), from Standby 12 KVA / 9,6 kW
(including Prime 11 KVA - Standby 12 KVA), prime 410 KVA, to 328 kW standby 451 KVA / to 360,8 kW (including
e-imzalı/e-signed
02.12.2020
On Behalf Of The Head Of Certification Center
Gürsel ERATAK
MANAGER of ELECTROTECNICAL SECTOR
*This certificate also shows that the production place of the certified product meets the requirements of Institute.
*This certificate under any circumstances cannot be changed, duplicated partially or in a way that makes it difficult to read and erasure cannot be done.
*TSE ELECTROTECHNIC SECTOR DIRECTORATE * Address: Necatibey Cad.No:112 06100 Bakanlıklar/ANKARA * Telephone: 0312 416 63 96* Fax: 0312-416 66 17
*TSE HEAD OF CERTIFICATION CENTER; Address: Necatibey Cad. No:112 06100 Bakanlıklar/ANKARA – Telephone: 0 312 416 64 81 / 416 64 27, Fax:0 312 416 66 17 E-mail
:bmb@tse.org.tr , web : www.tse.org.tr
Please check the accuracy and validity of the certificate from https://evrakkontrol.tse.org.tr/BelgeDogrulama.aspx?p=yclboqvh 1/2
TÜRK STANDARDLARI ENSTİTÜSÜ
TÜRK STANDARDLARINA UYGUNLUK BELGESİ
BELGE KAPSAMI ( 109513-TSE-02/04nolu belge devamı) : AKSA POWER GENERATION (CHINA) CO., LTD.
İLGİLİ TÜRK STANDARDI(RELATED TURKISH STANDARD) TS ISO 8528-5 / 15.10.2015 -- TS EN ISO 8528-13 /
13.04.2018
-APDXXXXC Model, CUMMINS Engine, Prime 27 KVA / 21,6kW - from Standby 30 KVA / 24 kW (including Prime 27
KVA - Standby 30 KVA included), Prime 2750 KVA / 2200kW - to Standby 3000 KVA / 2400 kW, (Prime 2700 kVA -
Including 3000 kVA in standby) ,
230 / 400V, 50Hz, G3 Performance Class, IP21M UNCABINET-IP 23M CABINET, 3 phase Automatic or Manual
operation control unit, Generator groups, Diesel Fueled
-APDXXXXM Model, MITSUBISHI Engine, Prime 600 KVA / 480kW - from Standby 660 KVA / 528kW (Including
Prime 600 KVA - Standby 660 KVA) Prime 2500 KVA / 2000kW – to Standby 2750 KVA / 2200kW (Prime 2500 KVA -
Including Standby 2750 kVA)
230 / 400V, 50Hz, G3 Performance Class, IP21M UNCABINET - IP23M CABINET, Three Phase Automatic or
Manual Operation Control Unit Generator Groups, Diesel Fueled
- ADXXX Model, Doosan Engine, Prime 84KVA / 67,2kW - From Standby 93 KVA / 74,4kW (Including Prime 84 KVA-
Standby 93KVA) Prime 750KVA / 600kW- to Standby 825 KVA / 660 kW (Prime 750KVA - Standby 825 KVA
included)
230 / 400V, 50Hz, G3 Performance Class, IP21M UNCABINET - IP23M CABINET, Three Phase Automatic or
Manual Operation Control Unit, Diesel Generator Groups
Stamford brand Alternator maximum power Prime 2790 KVA / 2232 kW, Standby up to 3069 KVA / 2455 kW
Meccalte brand Alternator maximum power Prime 750KVA / 600 kW, Standby, up to 825 KVA / 660 kW
Aksa brand Alternator maximum power Prime 450 KVA / 360 kW Standby up to 495 KVA / 396 Kw
Leroy Somer brand Alternator maximum power Prime 2700 KVA / 2160 kW, Standby up to 2970 KVA / 2276 kW
(S.D-K.D 11.09.2019)
e-imzalı/e-signed
02.12.2020
On Behalf Of The Head Of Certification Center
Gürsel ERATAK
MANAGER of ELECTROTECNICAL SECTOR
*This certificate also shows that the production place of the certified product meets the requirements of Institute.
*This certificate under any circumstances cannot be changed, duplicated partially or in a way that makes it difficult to read and erasure cannot be done.
*TSE ELECTROTECHNIC SECTOR DIRECTORATE * Address: Necatibey Cad.No:112 06100 Bakanlıklar/ANKARA * Telephone: 0312 416 63 96* Fax: 0312-416 66 17
*TSE HEAD OF CERTIFICATION CENTER; Address: Necatibey Cad. No:112 06100 Bakanlıklar/ANKARA – Telephone: 0 312 416 64 81 / 416 64 27, Fax:0 312 416 66 17 E-mail
:bmb@tse.org.tr , web : www.tse.org.tr
Please check the accuracy and validity of the certificate from https://evrakkontrol.tse.org.tr/BelgeDogrulama.aspx?p=yclboqvh 2/2