You are on page 1of 7

GROUNDING AND BONDING

Using the Tables in Article 250 of the NEC®

Article 250 is a foundational pillar of NFPA 70®, National Grounding Conductor, Equipment (EGC) — The conductive
Electrical Code® (NEC®), and the tables within Article 250 path(s) that provides a ground-fault current path and connects
are critical resources for sizing the wiring for the grounding normally non-current-carrying metal parts of equipment
and bonding of an electrical system. Becoming more familiar together and to the system grounded conductor or to the
with the proper use of these tables can help installers ensure grounding electrode conductor, or both.
effective grounding and bonding on their projects and, in turn, � These are often called “ground” conductors in the trade.
help ensure the safety of those within the building. Section 250.119 requires these conductors to be bare,
covered, or insulated. Covered or insulated equipment
grounding conductors shall have a continuous outer finish
Essential NEC Terms for Understanding Article 250 that is either green or green with one or more yellow stripes.
Having a good understanding of the terms used within Article Grounding Electrode — A conducting object through which a
250 is critical to understanding the grounding and bonding direct connection to the earth is established.
requirements within the NEC®. The following definitions are � Section 250.52(A)(1–8) lists the permissible grounding
commonly used throughout Article 250, and knowing them electrode options. While all the available grounding
is essential to installing an effectively grounded and bonded electrodes are required to be bonded per 250.50, it’s fair to
electrical system. say the most common are typically rod and pipe electrodes
(i.e., ground rods), which are listed in 250.52(A)(5), and
Ground — The earth.
concrete-encased electrodes, which are listed in 250.52(A)(3).
Grounded (Grounding) — Connected (connecting) to ground Often, concrete-encased electrodes consist of rebar that is
or to a conductive body that extends the ground connection. embedded in the concrete footings of a building.
� An example of a conductive body that extends the ground Grounding Electrode Conductor — A conductor used
connection is the first 5 feet of a water pipe entering a to connect the system grounded conductor or the
building. It is permitted to connect at this point even equipment to a grounding electrode or to a point on the
though it is not a grounding electrode, as the first 5 feet of grounding electrode system.
the pipe is not physically in contact with the earth.
� This is the conductor that connects the grounding
Grounded Conductor — A system or circuit conductor that is electrodes to the electrical system.
intentionally grounded.
Ground-Fault Current Path — An electrically conductive path
� These are often regarded as “neutral” conductors in the from the point of a ground fault on a wiring system through
trade. Section 200.6 requires these conductors to be normally non-current-carrying conductors, equipment, or the
identified as continuous white, continuous gray, or having earth to the electrical supply source.
three continuous white or gray stripes along the conductor’s
entire length on other than green insulation. Be mindful Effective Ground-Fault Current Path — An intentionally
that grounded conductors can also be phase conductors in constructed, low-impedance electrically conductive path
certain applications. designed and intended to carry current under ground-fault

1
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued

conditions from the point of a ground fault on a wiring system Bonding Jumper, System — The connection between the
to the electrical supply source and that facilitates the operation grounded circuit conductor and the supply-side bonding
of the overcurrent protective device or ground-fault detectors. jumper, or the equipment grounding conductor, or both, at a
separately derived system.
� An effectively designed ground-fault current path will allow
for circuit breakers, fuses, and ground-fault detectors to
open properly when ground-fault conditions arise within the Sizing Grounding Electrode Conductors
electrical system. Using Table 250.66
Bonded (Bonding) — Connected to establish electrical
Table 250.66 of the NEC is used to size grounding electrode
continuity and conductivity.
conductors for alternating-current systems located at the
Bonding Conductor or Jumper — A reliable conductor to service, at each building or structure where supplied by a
ensure the required electrical conductivity between metal parts feeder(s) or branch circuit(s), or at a separately derived
required to be electrically connected. system, such as on the load side of transformers.
Bonding Jumper, Equipment — The connection between two or This table shows you how to use the size of your largest
more portions of the equipment grounding conductor. ungrounded (hot) conductor to determine the necessary size
Bonding Jumper, Main — The connection between the of your grounding electrode conductor. Where you have two or
grounded circuit conductor and the equipment grounding more sets of service-entrance conductors run in parallel, the
conductor at the service.
Table 250.66 Grounding Electrode Conductor for
Alternating-Current Systems

Size of Largest Ungrounded


Ungrounded service Conductor or Equivalent Area for Size of Grounding
conductors Parallel Conductors Electrode Conductor
(AWG/kcmil) (AWG/kcmil)
Grounded service conductor
Aluminum or Aluminum or
Copper-Clad Copper-Clad
Copper Aluminum Copper Aluminum

Supply side equipment 2 or smaller 1/0 or smaller 8 6


bonding jumper 1 or 1/0 2/0 or 3/0 6 4
2/0 or 3/0 4/0 or 250 4 2
Over 3/0 Over 250 2 1/0
through 350 through 500
Neutral bus
Over 350 Over 500 1/0 3/0
through 600 through 900

Grounded electrode Over 600 Over 900 2/0 4/0


conductor through 1100 through
1750

Main bonding jumper (may Over 1100 Over 1750 3/0 250
be wire, bus, or screw) Notes:
1. If multiple sets of service-entrance conductors connect directly to a
service drop, set of overhead service conductors, set of underground
Equipment grounding bus service conductors, or service lateral, the equivalent size of the largest
service-entrance conductor shall be determined by the largest sum of
Grounding electrode the areas of the corresponding conductors of each set.
2. Where there are no service-entrance conductors, the grounding
electrode conductor size shall be determined by the equivalent size of
the largest service-entrance conductor required for the load to be
A main bonding jumper installed at the service between the grounded served.
service conductor and the equipment grounding conductor. 3. See installation restrictions in 250.64.

2
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued

grounding electrode conductor must be sized according to the Sizing Grounding Electrode Conductors
largest sum of the corresponding conductors of each set. (See and Bonding Jumpers
the Application Example that follows the Table Tips.)
The exhibit below illustrates a grounding electrode conductor
Table Tips (GEC) installed from service equipment or a separately
derived system to a water pipe grounding electrode. The GEC
1. Ensure that you are using the proper column(s) based
is required by 250.66 to be sized based on the size of the
on the wire type you are installing—copper, aluminum, or
ungrounded supply conductors. The supply conductors could
copper-clad aluminum.
be service conductors or, in the case of separately derived
2. Section 250.66(A) references connections to rod, pipe, or systems, feeder conductors from a generator or other power
plate electrodes. If the connection does not extend on to other source or transformer secondary conductors.
types of electrodes that require a larger size conductor, the
The bonding jumpers that connect the other grounding
grounding electrode conductor is not required to be larger
electrodes together must be sized using 250.53(C), which
than 6 AWG copper or 4 AWG aluminum wire.
refers to 250.66. GECs and bonding jumpers are permitted
3. Section 250.66(B) references connections to concrete- to be sized based on the electrodes to which they connect,
encased electrodes, often referred to in the trade as “Ufer as specified in 250.66(A), (B), or (C). However, if the GEC or
ground.” If the connection does not extend on to other bonding jumper extends from this connection to an electrode
types of electrodes that require a larger size conductor, the that is not specified in 250.66(A), (B), or (C), it must be sized
grounding electrode conductor is not required to be larger per Table 250.66.
than 4 AWG copper wire.
In this exhibit, the sizes of the GEC and the bonding jumpers
4. Section 250.66(C) references connections to ground rings. are dependent on the electrode to which they are connected.
If the grounding electrode conductor or bonding jumper
connected to a ground ring does not extend on to other
types of electrodes that require a larger size conductor, the 3/0 AWG
ungrounded
grounding electrode conductor is not required to be larger than service-entrance Neutral
the conductor used for the ground ring. conductors

Service
Application Example: Parallel Conductors equipment

A 3-phase, 800-A service is supplied using two 500 kcmil


4 AWG Cu grounding
THWN copper conductors per phase. The parallel
electrode conductor
conductors are installed in two separate runs of rigid metal Not required
conduit. Using Table 250.66, determine the maximum size to be larger than
grounding electrode conductor required for this service. 6 AWG Cu Not required to be
larger than 4 AWG Cu
STEP 1. Determine the size of the largest ungrounded
conductor in each raceway.
4 AWG Cu
STEP 2. Determine the maximum size grounding
electrode conductor (GEC) required for this service.
SOLUTION. Two parallel 500 kcmil copper conductors: Ground rod Underground metal Concrete-encased
water pipe electrode
Total equivalent area = 2 x 500 kcmil = 1000 kcmil
Then refer to Table 250.66 for the ungrounded conductor
Required to be not Ground ring
and copper column values:
less than 2 AWG Cu
1000 kcmil falls into the “Over 600 through 1100”
row = size 2/0 copper GEC. GEC and bonding jumpers sized in accordance with 250.66 for a
service supplied by 3/0 AWG copper ungrounded conductors.

3
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued

The illustration is not intended to show a mandatory physical Table 250.102(C)(1) Grounded Conductor, Main Bonding
routing and connection order of the bonding jumpers and Jumper, System Bonding Jumper, and Supply-Side Bonding
the GEC, as the NEC does not specify an order or hierarchy Jumper for Alternating-Current Systems
for these connections. The sizes of the bonding jumpers to
Size of Largest Ungrounded
the ground rod and the concrete-encased electrode shown Conductor or Equivalent Area for Size of Grounded Conductor
here are the maximum sizes required by the NEC based on Parallel Conductors or Bonding Jumper*
250.66(A) and (B). If the GEC from the service equipment is (AWG/kcmil) (AWG/kcmil)
run to the ground rod first and then to the water pipe, the GEC Aluminum or Aluminum or
to the ground rod is required to be sized based on Table 250.66 Copper-Clad Copper-Clad
as if it were run to the water pipe electrode. The use of bonding Copper Aluminum Copper Aluminum
jumpers or GECs larger than those required by 250.66 is not 2 or smaller 1/0 or smaller 8 6
prohibited. 1 or 1/0 2/0 or 3/0 6 4
2/0 or 3/0 4/0 or 250 4 2
Sizing Grounded (Neutral) Conductors and Bonding
Over 3/0 Over 250 2 1/0
Jumpers Using Table 250.102(C)(1) through 350 through 500
Table 250.102(C)(1) is used to size the grounded conductor, Over 350 Over 500 1/0 3/0
main bonding jumper, system bonding jumper, and supply- through 600 through 900
side bonding jumper for alternating-current systems. Keep Over 600 Over 900 2/0 4/0
in mind that this table is for sizing grounded conductors through through
1100 1750
and the bonding jumpers listed, NOT for sizing grounding
electrode conductors, which must be done using Table Over 1100 Over 1750 See Notes 1 and 2.
250.66. Notes:
1. If the ungrounded supply conductors are larger than 1100 kcmil
Table 250.102(C)(1) uses the size of the largest ungrounded copper or 1750 kcmil aluminum, the grounded conductor or bonding
(hot) conductor to determine the sizes of your grounded jumper shall have an area not less than 121∕2 percent of the area of the
(neutral) conductor and bonding jumpers. When sizing the largest ungrounded supply conductor or equivalent area for parallel
supply conductors. The grounded conductor or bonding jumper shall
grounded conductor or jumper where two or more ungrounded not be required to be larger than the largest ungrounded conductor or
conductors are connected in parallel and the total equivalent set of ungrounded conductors.
area is larger than 1100 kcmil copper or 1750 kcmil aluminum, 2. If the ungrounded supply conductors are larger than 1100 kcmil
Table Note 1 requires the size to be not less than 12½ percent copper or 1750 kcmil aluminum and if the ungrounded supply
conductors and the bonding jumper are of different materials (copper,
of the area of the largest ungrounded supply conductor or the
aluminum, or copper-clad aluminum), the minimum size of the
equivalent area for parallel supply conductors. grounded conductor or bonding jumper shall be based on the assumed
use of ungrounded supply conductors of the same material as the
Table Tips grounded conductor or bonding jumper and will have an ampacity
equivalent to that of the installed ungrounded supply conductors.
1. Make sure that you are using the proper 3. If multiple sets of service-entrance conductors are used as permitted
column(s) based on the wire type that you are installing— in 230.40, Exception No. 2, or if multiple sets of ungrounded supply
copper, aluminum, or copper-clad aluminum. conductors are installed for a separately derived system, the equivalent
size of the largest ungrounded supply conductor(s) shall be
2. If your ungrounded conductor or equivalent parallel determined by the largest sum of the areas of the corresponding
conductors’ area is larger than 1100 kcmil copper or 1750 conductors of each set.
kcmil aluminum, follow Table Note 1. 4. If there are no service-entrance conductors, the supply conductor
size shall be determined by the equivalent size of the largest service-
3. See the Sizing Supply-Side Bonding Jumpers section and entrance conductor required for the load to be served.
the application example that follows on the next page. *For the purposes of applying this table and its notes, the term bonding
jumper refers to main bonding jumpers, system bonding jumpers, and
4. See also the Sizing Main and System Bonding Jumpers supply-side bonding jumpers.
section on the next page.

4
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued

Sizing Supply-Side Bonding Jumpers (via connection to a grounding electrode), the main and system
bonding jumpers will be placed directly in the supply-side
Similar to how you size the main bonding jumper per
ground-fault current return path.
250.28(D), supply-side bonding jumpers must be sized based
on the size of the ungrounded conductors with which they Where the largest ungrounded supply conductor exceeds
are associated. If the ungrounded conductors are 1100 kcmil the parameters of Table 250.102(C)(1), Note 1 in the table
copper or 1750 kcmil aluminum or smaller, the supply-side requires you to establish a proportional relationship between
bonding jumper must be selected from Table 250.102(C)(1) the ungrounded conductor and the main or system bonding
based on the size of the largest ungrounded supply conductor. jumper. Where the service-entrance conductors are larger
If the ungrounded conductors are larger than 1100 kcmil than 1100 kcmil copper or 1750 kcmil aluminum, the
copper or 1750 kcmil aluminum, the size of the supply-side bonding jumper must have a cross-sectional area of not less
bonding jumper(s) must be calculated based on 12½ percent than 12½ percent of the cross-sectional area of the largest
of the area of the largest ungrounded supply conductor or phase conductor or phase conductor set. In equipment such
the equivalent area of the parallel supply conductors. Where as panelboards or switchboards that are listed for use as
an installation consists of multiple raceways for parallel service equipment, the manufacturer provides a bonding
conductors, an individual supply-side bonding jumper can be jumper that can be installed as the main or system bonding
installed for each raceway; the jumper must be sized based on jumper. It is not necessary to provide an additional bonding
the size of the ungrounded conductors in that raceway. jumper.

Sizing Main and System Bonding Jumpers Main Bonding Jumper for Service with
In a grounded system, the primary function of the main
More Than One Enclosure
bonding jumper and the system bonding jumper is to create Where a service consists of more than one disconnecting
the ground-fault current link between the EGCs and the means in separate enclosures, each enclosure must
grounded conductor. Table 250.102(C)(1) can be used to be treated separately, as depicted in the following exhibit.
determine the minimum size of the main and system bonding Based on the 3/0 AWG ungrounded service conductors and
jumpers. Unlike the GEC, which carries current to the ground Table 250.102(C)(1), the minimum size of the main bonding

Application Example

A 3-phase, 1600-A service is supplied using five 400 kcmil THWN conductors per phase. The parallel conductors are
installed in five separate runs of rigid metal conduit. In accordance with 300.12, Exception No. 2, a supply-side bonding
jumper is needed for each raceway at the point at which it enters the open-bottom switchboard. Using 250.102(C)(2),
determine the necessary size of the supply-side bonding jumper.

Multiple Supply-Side Bonding Jumpers Single Supply-Side Bonding Jumper


STEP 1. Determine the size of the largest ungrounded STEP 1. Determine the equivalent area of parallel supply
conductor in each raceway. conductors.

STEP 2. Determine the size of the supply-side bonding STEP 2. Determine the size of the supply-side bonding
jumper for each raceway using Table 250.102(C)(1). jumper using Table 250.102 (C)(1), Note 1.

SOLUTION. For 400 kcmil supply conductors, use the SOLUTION. Five parallel 400 kcmil conductors:
“Over 350 through 600” row of Table 250.102(C)(1). This Total equivalent area = 5 × 400 = 2000 kcmil
leads you to a 1/0 AWG copper or 3/0 AWG aluminum
This total exceeds 1100 kcmil; therefore, the total must be
supply-side bonding jumper.
multiplied by 0.125 (12.5 percent).
2000 kcmil × 0.125 = 250 kcmil copper

5
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued

jumper for the enclosure on the left is 4 AWG copper. The 1/0
Sizing Equipment Grounding Conductors
AWG main bonding jumper for the enclosure on the right must
Using Table 250.122
be derived from Table 250.102(C)(1) based on the 500 kcmil
ungrounded service conductors. The bonding jumper provided Table 250.122 is used to size the equipment grounding
by the manufacturer for listed service equipment provides the conductor (EGC) for grounding raceways and equipment.
equivalent current capacity to that of a field-fabricated bonding Unlike Table 250.66 and Table 250.102(C)(1), which both utilize
jumper sized per Table 250.102(C)(1). the size of the ungrounded conductor as the determining
factor for sizing, Table 250.122 uses the rating of the
Separately Derived System with overcurrent protective device (OCPD) ahead of the equipment
More Than One Enclosure or load that is being supplied to properly size the EGC.
To prevent parallel neutral current paths in raceways and
Table Tips
enclosures, the system bonding jumper can be either be
internal to the panelboards or installed at the separately 1. 
In the first column, select the rating that matches the
derived system enclosure so that it connects any supply-side OCPD protecting the circuit. If the rating of the OCPD that
bonding jumpers to the system grounded conductor terminal. is protecting the circuit is not shown, the next higher rating
The system bonding jumper cannot be installed at both should be chosen. For example, if the OCPD protecting the
locations. circuit is rated at 30 A, which is not included in the table, the

Table 250.122 Minimum Size Equipment Grounding


Conductors for Grounding Raceway and Equipment
750 kcmil ungrounded conductor
Supply conductors (only one phase shown) Rating or Setting of Size (AWG or kcmil)
Minimum 2/0 AWG grounded conductor Automatic Overcurrent
2/0 AWG supply-side bonding jumper
Device in Circuit Ahead
of Equipment, Conduit, Aluminum or
etc., Not Exceeding Copper-Clad
(Amperes) Copper Aluminum*
Neutral terminal bus
15 14 12
20 12 10
3/0 AWG 4 AWG 500 kcmil 1/0 AWG 60 10 8
ungrounded grounded ungrounded grounded 100 8 6
conductor conductor conductor conductor
200 6 4
200-A 400-A 300 4 2
circuit circuit 400 3 1
breaker breaker
500 2 1/0
4 AWG 600 1 2/0
main 800 1/0 3/0
bonding
GarmaJon 101509 GarmaJon 101509
L2 Series L2 Series

1000 2/0 4/0


jumper
Manufactured LR Manufactured LR
A A

1200 3/0 250


1600 4/0 350
2000 250 400
2/0 AWG 4 AWG 1/0 AWG 1/0 AWG 2500 350 600
grounding supply-side main supply-side 3000 400 600
electrode bonding bonding bonding
conductor jumper jumper jumper 4000 500 750
5000 700 1250
6000 800 1250
An example of the bonding requirements for service equipment.
Note: Where necessary to comply with 250.4(A)(5) or (B)(4), the
equipment grounding conductor shall be sized larger than given in this
table.
*See installation restrictions in 250.120.

6
GROUNDING AND BONDING
Using the Tables in Article 250 of the NEC® Continued

next higher size, which is 60 A, should be selected, resulting


Application Example
in a 10 AWG copper EGC for this circuit.
2. If the ungrounded circuit conductors are increased in size A 240-V, single-phase, 250-A load is supplied by a
for any reason other than temperature correction or due to 300-A breaker located in a panelboard 500 ft away.
The conductors are 250 kcmil copper installed in
the number of current-carrying conductors in a raceway,
rigid nonmetallic conduit with a 4 AWG copper EGC.
the EGC must be increased proportionally. For more details,
If the conductors are increased to 350 kcmil, what is
see the following section and its associated Application the minimum required size of the EGC based on the
Example. proportional increase requirement?

Generally, the minimum-sized EGC is selected from Table STEP 1. Calculate the size ratio of the new conductors to
250.122 based on the rating or setting of the feeder or branch- the existing conductors:
circuit OCPD(s). Where the ungrounded circuit conductors 350,000 circular mils
Size ratio = = 1.4
are increased in size to compensate for voltage drop, the EGCs 250,000 circular mils
must be increased proportionately. This will lower the overall
impedance of the ground-fault current return path, which will STEP 2. Calculate the cross-sectional area of the new
facilitate the operation of the OCPD in the event of a line-to- EGC:
ground fault. 41,740 circular mils × 1.4 = 58,436 circular mils
According to Table 8 of Chapter 9, the size of the existing
grounding conductor, 4 AWG, has a cross-sectional area of
Grounded 41,740 circular mils.
service STEP 3. Determine the size of the new EGC. Again,
conductor
referring to Chapter 9, Table 8, we find that 58,436 circular
Service mils is too large for a 3 AWG EGC. The next larger size is
equipment N
66,360 circular mils, which converts to a 2 AWG copper
Equipment EGC.
Load
Grounding grounding
electrode terminal bar Equipment
Main bonding bonded to
conductor grounding
jumper enclosure conductor

Grounding and bonding arrangement for grounded systems, per Learn More
250.130(A), illustrating connection of the EGC (bus) to the enclosures
and to the grounded service conductor � Visit nfpa.org/ElectricalSolutions for more of the
latest electrical resources from NFPA, including
research, featured products, training options, and
certification opportunities.

This material contains some basic information about NFPA 70®, National Electrical Code® (NEC®). It identifies some of the
requirements in NFPA 70 as of the date of publication. This material is not the official position of any NFPA Technical Committee
on any referenced topic which is represented solely by the NFPA documents on such topic in their entirety. For free access to
the complete and most current version of all NFPA documents, please go to nfpa.org/docinfo. The NFPA makes no warranty or
guaranty of the completeness of the information in this material and disclaims liability for personal injury, property, and other
damages of any nature whatsoever, from the use of or reliance on this information. In using this information, you should rely on
your independent judgment and, when appropriate, consult a competent professional.

© 2020 National Fire Protection Association / June 2020

You might also like