You are on page 1of 84

LEONARDO EVOLUTION

INSTALLATION MANUAL

LEONARDO EVOLUTION

VERSION: 1.7
DATE: FEBRUARY 2010
LANGUAGE: ENGLISH
GB

VERSION: 1.7 DATE: FEBRUARY 2010

UNIFLAIR SPA POLICY IS ONE OF CONTINUOUS TECHNOLGICAL INNOVATION AND THE COMPANY
THEREFORE RESERVES THE RIGHT TO AMEND ANY DATA HEREIN WITHOUT PRIOR NOTICE.

2
Contents
GENERAL INSTRUCTIONS 4 Annual checks 36
Information contained in the manual 4 Checks to be performed every sixty months 36
Symbols 4 Cleaning and repalcing the filters 36
Storage 4 Troubleshooting 38
Storage after use 4 LEONARDO EVOLUTION - CHILLED WATER 42
Disposal 4 Technical characteristics 42
Disposal of the machine 4 Operating description 43
SAFETY 6 Name and description of the principle components 44
General Instructions 6 Checks to be made on delivery 46
Warning for lifting and transportation 6 Unloading the unit 46
Warnings for installation 6 Characteristics of the installation area 46
Intended use 6 Positioning of the unit 46
Warnings for use 6 Opening of the door and removal of the panels 47
Safety during maintenance work 6 Internal protection panels 48
INTRODUCTION 7 Electrical connections 49
Presentation of the system 7 Connection to the water drain 50
LEONARDO EVOLUTION - DIRECT EXPANSION 10 Hydraulic connections 51
Technical characteristics 10 Filling the hydraulic circuit 51
Operating description 13 Filling the primary circuit 51
Name and description of the principle components 14 Filling the hydraulic circuits of the conditioners 51
Checks to be made on delivery 17 MANUAL START UP AND SHUT DOWN OF THE UNIT 52
Unloading the unit 17 SETTING AND ADJUSTMENT 53
Characteristics of the installation area 17 Selecting the power supply of the fans 53
Positioning of the unit 17 Setting the regulation and safety devices 57
Door opening and removal of the panels 18 Setting the air flow sensor 58
Door opening 18 Setting the dirty filter sensors 58
Internal protection panels 19 MAINTENANCE 58
Electrical connections 20 Three-monthly checks 58
Connection to the drains 21 Six-monthly checks 58
Connection to the gas drain 21 Annual checks 58
Refrigerant connections on air cooled units 22 Cleaning and replacing the filters 59
Choosing the diameter of the discharge tube 22 Servomotor and chilled water valve 60
R407C 23 Servomotor and hot water valve 60
R410A 24 Troubleshooting 61
BACKFLOW LINE DIMENSIONING (LIQUID) 27 LEONARDO EVOLUTION ENERGY SAVING 63
Type of oil recommended with COPELAND Technical characteristics 63
compressors 29 Operating description 64
Type of oil recommended with MANEUROP Name and description of the principle parts 65
compressors 29 LEONARDO EVOLUTION TWIN-COOL 69
Type of oil recommended with SANYO compressors 29 Technical characteristics 69
Type of oil recommended with Scrolltech HCJ 072-HLJ Operating description 71
083 compressors 29 Name and description of the principle components 72
Connection for water cooled units 30 ACCESSORIES 77
MANUAL START UP AND SHUT DOWN OF THE UNIT 31 Humidifier 77
SETTING AND ADJUSTMENT 32 Operating principle 78
Selecting the power supply of the fans 32 Feed water 78
Connections 78
Setting the regulation and safety devices 35
Maintenance 79
Setting the pressostatic valve (optional on chilled water
Electric heaters 80
cooled models only) 35
Temperature and humidity sensor 81
Setting the air flow sensor 35
Connection to fresh air intake 82
Setting the dirty filter sensors 35 Maintenance 83
MAINTANENCE 36 Discharge temperature threshold sensor (only on
Three-monthly checks 36 CHILLED WATER models) 83
Six-monthly checks 36

3
GENERAL INSTRUCTIONS Disposal of the machine
Information contained in the manual The following instructions deal with the disposal of UNIFLAIR
machines.
The present manual describes the Leonardo Evolution
The procedures described below are guidelines only, provided
conditioning units. It supplies general information and safety
to make the machine disassembling easier. The purpose of
instructions, unit transportation and installation information,
these operations is to achieve homogeneous material
as well as necessary information about how to use the units.
quantities for disposal or recycling.
It is an integral part of the product.
These instructions are followed by a list of the possible typical
The descriptions and illustrations in this manual are unbinding;
CER 2002 codes to allow an easier disposal of the machine
"Uniflair S.p.A." reserves the right to make any alterations it
parts.
sees fit in order to improve the product without having to update
this document. WARNING! Observe the safety precautions at
The illustrations and images in this manual are examples work wearing the suitable individual protection
only and may differ from practical situations. devices (IPD) and using the appropriate
equipments.
Symbols
WARNING! Maintenance and service operations
The following graphic and linguistic symbols have been used
(disassembling included) must be performed by
in this manual:
qualified and expert personnel, aware of the
WARNING! This message may appear before essential precautions.
certain procedures. Failure to observe this
message may cause damage to equipment. PRELIMINARY OPERATIONS
Power supply and data processing system:
WARNING! This message may appear before
• Turn the machine off and unplug it from the power supply
certain procedures. Failure to observe this
and from the communication system.
message may cause injury to the operators and
damage the equipment. WARNING! The circuits can be pressurised; any
maintenance and service operation must only
Storage be carried out by expert and qualified personnel,
The following conditions must be respected should the unit aware of the essential safety precautions.
require storing for a given period of time: WARNING! The machine can contain hot water:
The packing must be kept intact. adopt all of the essential safety cautions.
The place of storage must be dry (<85% R.H.) and protected Hydraulic circuit:
against the sun (temperature <50°C). • Drain the hydraulic circuit and disconnect the hydraulic
Storage after use line.
Refrigerating circuit:
The unit must be packaged when stored for a long time.
• Purge the refrigeration system with suitable recovery
Disposal equipments to avoid gas leakage in the environment.
The unit is mainly made of recyclable materials which should DISASSEMBLING THE MACHINE
be separated from the rest of the unit before it is disposed. The following paragraphs describe the main macrocomponents
When disposing of the gas and oil inside the refrigerating to facilitate the disassembling, disposal and recycling of
circuit, consult a specialist company. materials with appropriate features.
To disassemble the machine properly, follow the guidelines
provided below.
• ELECTRICAL PANEL
Remove the electrical panel and dispose its parts
following the procedures provided by the relevant
standards. The models equipped with a "clock board" in
the electrical panel have a service battery which must
be disposed separately.
- Materials: electronic parts, electrical cables, metal and
plastic supports, batteries.

• COVER PANELS
Remove the metal cover and protection panels of the
machine.
The panels can be made of polypaired materials, that is
insulating material together with metal. In this case,
separate the different elements.
- Materials: galvanized sheet, aluminium, soundproof
panels: expanded polyurethane, thermoinsulating
panels: mineral wool.

4
• AIR FILTERS • COMPRESSORS AND LIQUID SEPARATORS
Remove the air filters. WARNING! Pay attention to oil contained in the
- Materials: metallic net, synthetic fibre. compressors. Avoid any loss of oil during
operations. If possible, dispose of oil and
• FINNED COIL compressors separately.
Remove the finned coils from the machine.
Finally remove the liquid separators and the compressors
- Materials: copper, aluminium, steel.
from the machine base.
- Materials: liquid separators and compressors
• HUMIDIFIER
If a humidifier is installed, remove it.
• METAL BASE
- Materials: polypropylene, iron materials.
Proceed with the recycling of the metal base.
- Materials: galvanised sheet.
• ELECTRO-MECHANICAL PARTS
Find and remove valves, electro-mechanical and
electronic parts (three-way valves, sensors, etc.) from WARNING! Waste deriving from machine
the machine. disassembly must be disposed of and classified
• RESISTANCES according to CER codes only consulting
Remove the resistances if they are installed. authorised and specialist companies.
- Materials: aluminium, inseparable copper + magnesium The following chart contains a partial list of the typical CER
oxide. codes applied to waste deriving from disassembling, so it
must be considered just as an indication.
• PIPES AND PARTS OF THE REFRIGERATING
CIRCUIT
ELEMENTS CER 2002 CODES
Find the connection pipes installed in the machine and
separate them from the other elements. Electrical cables 17 04 11
Pipes can be caulked: in this case, before recovery, se-
parate the insulating material from the metal pipe. Plastic materials 16 01 19
Even the elements of the refrigerating circuit are
Metal supports 16 01 17
considered as pipes: joints or valves.
- Materials: copper, brass, cast iron, steel and plastic. Galvanised sheet 17 04 07

• PUMP Aluminium 17 04 02
Remove the pump from the machine.
Metallic net 17 04 05
- Materials: pump.
Synthetic fibre 15 02 03
• CONDENSER
Remove the condenser, if installed. C opper 17 04 01
The condenser contains the elements of a machine,
Brass 17 04 01
equipped with a small electrical panel, fans and a thermal
exchange battery, usually characterized by aluminium Cast iron 17 04 05
structure and feet made of varnished steel.
- Materials: electrical elements, aluminium, steel Steel 17 04 07
(varnished).
Refrigerating gas 14 06 01
• BRAZED PLATE EXCHANGER Battery 16 06 04
If installed, remove the brazed plate exchanger.
- Materials: INOX AISI braze welding, with an alloy Pumps, electro-mechanical
17 09 04
containing a large amount of silver. elements, compressors

• FANS
Remove the fans. Disassemble the metal frame and
proceed with the recycling of the metal alloy.
- Materials: electro-mechanical elements, iron wrecks.
WARNING! The fans of some machine models
are integral part of the carrying structure.
Removing the fans can compromise the stability
of the frame. We recommend to pay attention
during disassembling operations.

5
SAFETY Warnings for use
General Instructions Only use the machinery for the purpose for which it was
designed and manufactured.
WARNING! Removal of, or tampering with,
safety devices is a violation of EUROPEAN Environmental limits for use
SAFETY STANDARDS. The environmental conditions for the use of Leonardo air
WARNING! During installation authorised conditioners are fall within the following values:
personnel must wear individual safety devices.
• Tmin=18°C • Tmax=30°C
Uniflair S.p.A will only consider itself responsible for the safety,
• %rHmin=30% • %rHmax=70%
reliability and performance of the machine if:
• repair work has only been carried out by authorised Safety during maintenance work
personnel; All repair work must be carried out by professionally qualified
• the electric installation conforms to the standards currently personnel authorised by Uniflair S.p.A.
in force; Unplug the machine form the power supply before starting
• the devices are used in conformity with the relative any maintenance work.
instructions. While drawing up this manual, we have considered all of the
Carefully read this instruction manual before carrying out any operations which are part of normal maintenance operations.
kind of use or maintenance work on the units.
Installation, maintenance and use must be carried out
N.B. Do not carry out any work which has not been specified
respecting all of the work safety standards.
in this manual.
The operator responsible for the above mentioned services
must be suitably specialised and possess expert knowledge
of the devices.
Uniflair S.p.A refuses all responsibility for damage to people
or objects due to the inobservance of the safety standards.

Warning for lifting and transportation


Lifting and transportation of the units must be carried out by
specialised personnel as described in the relative paragraphs.
The load must always be solidly anchored to the bearing
element of the lifting equipment and means of transport. No-
one must remain near the suspended load, nor in the working
area of the crane, forklift truck or any other lifting equipment
or means of transport. Adopt all of the cautions provided by
the relevant safety standards, in order to prevent any possible
damage to people or objects.

Warnings for installation


Any type of work on the electrical installation must only be
carried out by specialised technicians who are experts in
this field.
Specialised technical personnel must use appropriate
equipment when checking the grounding of devices.
Installation may only take place in locations where there is
NO public access.

Intended use
Leonardo Evolution air conditioning units have been designed
and produced to carry out air conditioning, within the limits
and methods described in the present manual. The air
conditioners must be used exclusively in internal
environments.
No modifications may be made to the units or their parts
without explicit written consent from Uniflair S.p.A.

6
INTRODUCTION

Presentation of the system


The Leonardo Evolution™ precision air conditioners are designed for environments which are characterised by the presence
of highly technologically advanced equipment: telecomms and internet centres, data processing rooms and any type of
environment which is characterized by high concentrations of power.

The Leonardo Evolution series consists of 4 types of conditioners:


• Direct expansion
• Chilled water
• Energy Saving
• Twin-Cool

AIR FLOW
In the LEONARDO EVOLUTION conditioners, the air can flow upwards or downwards (UPFLOW / DOWNFLOW).

UPFLOW
Upflow units (with upwards air discharge) are designed to distribute the air through a system of ducts or by means of a false
ceiling. Air intake is usually through the front of the unit, but versions are also available with air intake through the rear or the
base of the unit.

DOWNFLOW
Downflow units (with downwards air discharge) handle large volumes of air which are distributed uniformly into the environment
by means of a void under a raised access floor. The air enters the unit directly from the environment, or through a ventilated
or false ceiling.

7
MODELS
The code which distinguishes the models is composed of 4 characters:

Identifying prefix of the Leonardo family

Air discharge
U = Upflow (upwards discharge)
D = Downflow (downwards discharge)

Operating typology
C = Chilled water units
A = Air cooled direct expansion units
W = Water cooled direct expansion units
T = Air cooled twin cool units
D = Water cooled twin cool units
E = Energy saving units

Fan typology
V = Radial Electronically Commutated fans
R = Radial fans

Indicative cooling capacity

Number of compressors installed

Number of cooling circuits

Power supply voltage


A = 400 V / 3Ph (+N) / 50 Hz
B = 230 V / 1 Ph / 50 Hz
IDENTIFICATON PLATE
The units can be identified by the identification plate which is placed in the electrical panel of the machine. The model and
any eventual accessories which are installed are indicated by an "X" in the corresponding box
The plate carries the following data:
• Model and series number of the machine.
• Type of power supply.
• Power absorbed by the unit and the single components.
• Current absorbed by the unit and the single components.
• The set points of the cooling circuit pressostatic valve and safety valve.
• Type of refrigerant.
• Loading or pre-loading of each cooling circuit.

TDAV1422A(H) TDEV1422A(H) SERIAL No.


TUAV1422A(H) TUEV1422A(H)
TDWV1422A(H) TDDV1422A(H) TDTV1422A(H)
TUWV1422A(H) TUDV1422A(H) TUTV1422A(H)
TENS. 400V/3Ph+N/50Hz AUX. 24 VOLT
NO. TENS. (V) OA (A) [/1] FLA (A) [/1] LRA (A) [/1] P (kW) [TOT]
COMPRESSOR 2 400/3 10,7 14,0 98 11,2

ILE
FAN 2 400/3 4,7 5,6 0 5,42

IM ILE
HUMIDIFIER 1 400/3 9,1 0,0 0 6,29

AC-S IM
HEATERS STD 3 400/3 7,2 0,0 0 15

AC-S
ENHANCED HEATERS 3 400/3 8,7 0,0 0 18
UNIT (STD HEATERS) (*)
UNIT (ENHANCED HEATERS) (*)
UNIT (STD HEATERS+CAL max) (*)
41,7
46,0
41,7+10,5x1Ph
F 26,02
29,02
28,36 F
UNIT (ENH.
(ENH HEATERS+CAL max) (*) 46+10 5x1Ph
46+10,5x1Ph 31 36
31,36
Icu=15kA (CEI EN 60947-2) / (*) in operating conditions at 400V
TSR STOP: 310 °C MAN. RESET
TSRA STOP: 328 °C MAN. RESET
AP1-2 STOP: 26,5 bar MAN. RESET
SAFETY VALVE OPENS AT: 30 bar
CHARGE: R407C kg/circ. R22 kg/circ.
PRECHARGE: DRY NITROGEN N2

8
SYMBOLS APPLIED TO THE MACHINES

SYMBOL MEANING

High voltage

Sharp edges

Moving parts

SYMBOLS APPLIED TO THE PACKAGES


SYMBOL MEANING

FRAGILE: handle with care

DO NOT STORE IN DAMP CONDITIONS: the packaged unit must be stored in a dry
place

CENTRE OF GRAVITY: shows the centre of gravity of the packaged unit

KEEP AWAY FROM HEAT: the unit must be stored away from heat sources

THIS SIDE UP: indicates the correct position of the packaged unit

TEMPERATURE LIMITS: the packaged unit must be stored in a place within the
indicated temperature limits

DO NOT USE HOOKS: do not lift the packaged units using hooks

DO NOT STACK: the packaged units must not be stacked

9
LEONARDO EVOLUTION - DIRECT EXPANSION
Technical characteristics
AIR COOLED DIRECT EXPANSION UNITS WITH BACKWARD CURVED BLADE FANS
Model TDAR - TUAR 511A 611A 721A 722A 921A 922A 1021A 1022A
Height mm 1960 1960 1960 1960 1960 1960 1960 1960
Width mm 1010 1010 1310 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865 865
Weight kg 280 310 430 447 430 447 430 447
Number of refrigerant circuits 1 1 1 2 1 2 1 2
Number of compressors 1 1 2 2 2 2 2 2
Power supply voltage V 400V/3ph+N/50Hz

Model TDAR - TUAR 1121A 1122A 1321A 1322A 1422A 1622A 1822A
Height mm 1960 1960 1960 1960 1960 1960 1960
Width mm 1721 1721 1721 1721 2172 2172 2172
Depth mm 865 865 865 865 865 865 865
Weight kg 548 559 575 585 698 714 714
Number of refrigerant circuits 1 2 1 2 2 2 2
Number of compressors 2 2 2 2 2 2 2
Power supply voltage V 400V/3ph+N/50Hz

Model TDAR 2222 2242 2522 2542 2842 3342


Height mm 2175 2175 2175 2175 2175 2175
Width mm 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865
Weight kg 910 910 918 930 1040 1098
Number of refrigerant circuits 2 2 2 2 2 2
Number of compressors 2 4 2 4 4 4
Power supply voltage V 400V/3ph+N/50Hz

Model TUAR 2222 2242 2522 2542 2842 3342


Height mm 1960 1960 1960 1960 1960 1960
Width mm 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865
Weight kg 910 910 918 930 1040 1098
Number of refrigerant circuits 2 2 2 2 2 2
Number of compressors 2 4 2 4 4 4
Power supply voltage V 400V/3ph+N/50Hz

10
AIR COOLED DIRECT EXPANSION UNITS WITH EC BACKWARD CURVED BLADE FANS
Model TDAV - TUAV 511 611 721 722 921 922 1021 1022
Height mm 1960 1960 1960 1960 1960 1960 1960 1960
Width mm 1010 1010 1310 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865 865
Weight kg 280 280 430 447 430 447 430 447
Number of refrigerant circuits 1 1 1 2 1 2 1 2
Number of compressors 1 1 2 2 2 2 2 2
Power supply voltage V 400V/3ph+N/50Hz

Model TDAV - TUAV 1121 1122 1321 1322 1422 1622 1822
Height mm 1960 1960 1960 1960 1960 1960 1960
Width mm 1720 1720 1720 1720 2171 2171 2171
Depth mm 865 865 865 865 865 865 865
Weight kg 548 559 575 585 698 714 714
Number of refrigerant circuits 1 2 1 2 2 2 2
Number of compressors 2 2 2 2 2 2 2
Power supply voltage V 400V/3ph+N/50Hz

Model TDAV 2222 2242 2522 2542 2842 3342


Height mm 2175 2175 2175 2175 2175 2175
Width mm 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865
Weight kg 910 910 918 930 1040 1098
Number of refrigerant circuits 2 2 2 2 2 2
Number of compressors 2 4 2 4 4 4
Power supply voltage V 400V/3ph+N/50Hz

Model TUAV 2222 2242 2522 2542 2842 3342


Height mm 1960 1960 1960 1960 1960 1960
Width mm 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865
Weight kg 910 910 918 930 1040 1098
Number of refrigerant circuits 2 2 2 2 2 2
Number of compressors 2 4 2 4 4 4
Power supply voltage V 400V/3ph+N/50Hz

11
CHILLED WATER DIRECT EXPANSION UNITS WITH BACKWARD CURVED BLADE FANS

Model TDWR - TUWR 611 921 1321 1622 1822


Height mm 1960 1960 1960 1960 1960
Width mm 1010 1310 1720 2171 2171
Depth mm 750 865 865 865 865
Weight kg 310 430 575 714 714
Number of refrigerant circuits 1 1 1 2 2
Number of compressors 1 2 2 2 2
Power supply voltage V 400V/3ph+N/50Hz

Model TDWR 2242 2542 2842 3342


Height mm 2175 2175 2175 2175
Width mm 2580 2580 2580 2580
Depth mm 865 865 865 865
Weight kg 996 1020 1120 1140
Number of refrigerant circuits 2 2 2 2
Number of compressors 4 4 4 4
Power supply volatge V 400V/3ph+N/50Hz

Model TUWR 2242 2542 2842 3342


Height mm 1960 1960 1960 1960
Width mm 2580 2580 2580 2580
Depth mm 865 865 865 865
Weight kg 996 1020 1120 1140
Number of refrigerant circuits 2 2 2 2
Number of compressors 4 4 4 4
Power supply volatge V 400V/3ph+N/50Hz

12
CHILLED WATER DIRECT EXPANSION UNITS WITH EC BACKWARD CURVED BLADE FANS

Model TDWV - TUWV 611 921 1321 1622 1822


Height mm 1960 1960 1960 1960 1960
Width mm 1010 1310 1720 2171 2171
Depth mm 750 865 865 865 865
Weight kg 280 430 575 714 714
Number of refrigerant circuits 1 1 1 2 2
Number of compressors 1 2 2 2 2
Power supply voltage V 400V/3ph+N/50Hz

Model TDWV 2242 2542 2842 3342


Height mm 2175 2175 2175 2175
Width mm 2580 2580 2580 2580
Depth mm 865 865 865 865
Weight kg 996 1020 1120 1140
Number of refrigerant circuits 2 2 2 2
Number of compressors 4 4 4 4
Power supply volatge V 400V / 3 ph+N / 50 Hz

Model TUWV 2242 2542 2842 3342


Height mm 1960 1960 1960 1960
Width mm 2580 2580 2580 2580
Depth mm 865 865 865 865
Weight kg 996 1020 1120 1140
Number of refrigerant circuits 2 2 2 2
Number of compressors 4 4 4 4
Power supply volatge V 400V / 3 ph+N / 50 Hz

Operating description
AIR COOLED DIRECT EXPANSION UNITS (DXA)
The air cooled DX units extract heat from the room and transfer it to
the outside using air cooled refrigerant heat exchangers (condensers).
The room unit and external condenser form an autonomous sealed circuit
once installed. The UNIFLAIR remote condensers used with LEONARDO
units include a precise electronic system to regulate the fan speed to
ensure trouble-free operation throughout the year under a wide range of
external air temperatures. Special attention has been paid to the acoustic
design of the condensers to minimise noise levels. A wide range of
combinations is available to meet different site requirements.

WATER COOLED DIRECT EXPANSION UNITS (DXW)


In the DX water cooled units, the heat extracted from the room is
transferred to water via a stainless steel brazed plate exchanger within
the unit.
The cooling water may be fed from the mains supply, a cooling tower or
a well (open circuit), or recycled in a closed loop cooled by external
coolers.
In the latter case, an anti-freeze mixture of water and ethylene glycol is
normally used.
The water cooled units have the advantage that the refrigerant circuits
are charged and sealed in the factory. This makes installation extremely
simple, eliminating the need for any site-installed refrigerant pipework.

13
Name and description of the principle components

A User terminal
B Electrical panel door
C Cover panels
D Electrical panel
E Filters
C A F Fans
G Cooling circuit
H Brazed plate heat exchanger
(present in chilled water
B models)

MODELS TD./ TU. 511 ÷ 1822

E
D

H
G

MODELS TD./ TU. 2222 ÷ 3342

14
A1 Description of the components
A - User terminal
Allows the unit to be turned on or off and the configuration
A2 A5 and visualization of the condition of the machine.
• A1 LCD Display
A3 A6 • A2 ALARM key: visualization and reset of alarms;
when the alarm is activated, it flashes red.
A4 A7 • A3 PRG key: access to the configuration menu
• A4 ESC key : exit from the screens
• A5 UP key : scroll through the menu
• A6 ENTER key : confirm
MODELS TD./ TU. 511 ÷ 1822
• A7 DOWN key: scroll through the menu

B - Electrical panel door


Allows access to the electrical panel of the machine.
D2 C - Cover panels
Allow access to the internal components of the machine.
D - Electrical panel
• D1 Magnetothermic
D3 - auxiliary
D1 - heater (optional)
D4 - humidifier (optional)
- fans
- compressors
• D2 Interface board
• D3 Dirty filter sensor
• D4 Air flow sensor
D8 • D5 Main switch
D5 D6 • D6 Terminal board
• D7A Input/output electrical supply cables
D7C D7B
• D7B Input/output electrical auxiliary cables
• D7C Input/output condensing unit supply
D7A D7D
• (optional) - Only on units with air cooling
• D7D Entrance/exit signal cables (RS485 and/or LAN)
MODELS TD./ TU. 2222 ÷ 3342 • D8 Phase sequence relay
• D9 Maximum pressure manostat (only for mod. TD.
2222 ÷ 3342)
D2 D1 D4 D3 D9

D7D D8 D5 D7A D7C D7B D6

E F E - Filters
Filter the air released into the environment
F - Fans
F1 Allow the diffusion of air into the room
• F1 ATR Transformer: allows the setting of the fan rotation
speed

15
G4 G5 G - Cooling circuit
• G1 Compressor
G2 • G2 High pressure switch
• G3 Schrader Valve
G3 • G4 Safety Valve
G11 • G5 Shut -off valve
G1 • G6 Circuit Exit
• G7 Circuit entrance
G10 • G8 Liquid receiver
• G9 Dehydration filter
• G10 Flow sight glass
• G11 Electronic thermostatic valve

G8 G6 G7 G9

• G12 Evaporating coil

G12

H - Brazed plate heat exchanger (present on water cooled


units)
• H1 Input/output hydraulic circuit

H H1

I I - Room temperature and humidity sensor

16
Checks to be made on delivery Characteristics of the installation area
WARNING! Dispose of the packaging in WARNING! The unit must be installed internally
appropriate collection points. and protected from adverse conditions.
The Leonardo Evolution units are packaged in wooden crates The unit is predisposed for installation on raised access flooring
or anchored to a pallet and covered in cardboard. using mounting frames or appropriate floor stands supplied
Check that the delivery is complete and inform the carrier of on request from Uniflair. However, the upflow units (upwards
any damage to the unit which may be attributed too careless air flow) with air intake through the rear or front can also be
or inappropriate transportation. In particular, check any installed on floors which are not raised.
eventual damage to the panel in which the user terminal is The area of installation must have the following characteristics:
mounted. • to facilitate maintenance, leave a clearance (distance
Lifting and moving the unit must be carried out by a D) of at least 700mm free in front of the unit. Check that
mechanical lifter, supplied with a sling made up of textile the air intake and discharge connections are not blocked
belts, which, fixed under the machine, limits excessive stress in any way, not even partially;
on the upper edges.
The following must be contained within the packaging:
• The Leonardo Evolution unit;
• Leonardo Use and Installation Manual;
• Leonardo unit electrical diagrams;
• Leonardo unit cooling circuit diagrams;
• Leonardo unit installation diagrams;
• List of spare parts;
• CE declaration with a list of the European standards to
which the machine must conform;
• guarantee conditions

Unloading the unit


To unload the unit from the pallet, carry out the following pro- D
cedure:
• move the pallet as near as possible to where the unit is
to be installed; • a horizontal and even floor;
• not tilt or turn the unit upsidedown; • the electrical energy distribution system has been
• use a ramp to avoid any damage to the unit during produced in respect of CEI standards, suitable for the
unloading; characteristics of the unit;
• a cold water distribution implant (if a humidifier is to be
installed);
• implant for connection to the condensing unit;
• external air outlet (if a fresh air intake is to be installed);
• if or the refrigerating gas drain see paragraph "Connection
to gas drain";
• drainage system.
WARNING! The preparation of the installation
area must be carried out as indicated in the
installation drawing attached to the machine
documentation.

Positioning of the unit


WARNING! If the surface where the unit is placed
• remove the blocking screws which fix the unit to the is not even and horizontal, there is a risk of an
pallet; overflow from the condensation tray. A
• carefully push the unit along the ramp until it reaches maximumheight difference of 5mm between the
the floor. ends of the unit is allowed.
Installation on raised access flooring
Installation on raised access flooring occurs by means of a
mounting frame. The frame enables the installation of the
unit before the raised floor is installed, increased absorption
of noise and vibrations and the facilitation of connecting ipes
and cables.
The upflow models (upwards air flow) with rear or frontal air
intake may be installed without using the mounting frame.

17
Installation of the mounting frame Door opening and removal of the panels
To install the unit on raised flooring using the mounting fra-
me, carry out the following procedures: Door opening
• a flexible seal at least 5 mm thick should be fitted To open the door of the unit, carry out the following procedu-
between the raised floor panels and the mounting frame re:
which should also be isolated from the metallic floor • push the button and pull the handle lightly outwards;
structure; • turn the handle downwards until the door opens.
• position the unit of the mounting frame and fix it using
the M8 screw inserts found on the base of the unit.

Air conditioning unit

Raised Removal of the front and side panels


floor
To remove the front and side panels, carry out the following
procedure:
• firmly hold the panel;
• lift and incline the panel outwards until it is completely
Mounting
frame removed.

Flexible seal Flexible seal

Installation on flooring which is not raised Q.E.


Installation on flooring which is not raised can occur without
using bases, but only on upflow models
(upwards air flow) with rear or frontal air intake. Installation on
this type of floor does not require any additional operation
besides that of normal positioning.
Installation of the floor stand
To install the unit on the floor stand, carry out the following
procedures:
• position the unit on the floor stand;
• fix the unit to the floor stand using the M8 screw inserts NOTE: After having removed the side panels, the non-
found on the base of the unit. removable protective panel, blocks accessibility to the inside
of the machine.
Removal of the rear panels
To remove the rear panels, carry out the following procedure:
• unscrew, using a star screwdriver, the screws which fix
basamento the panel at the top of the machine;
Base of unit • firmly hold the panel;
condizionatore
• lift and incline the panel outwards until it is completely
removed.
Fixing screws

zoccolo
Floor stand
unità

18
MODELS TU. 2222 ÷ 3342
Internal protection panels
The technical compartment, the electric heaters and the
autotransformer fans are protected by internal protection
panels for safety reasons and to allow the opening of the
external panels without triggering the unit's safety alarms. In
the figures below, the different types of internal protection
panels are shown on various types of machines.
MODELS TD. 511 ÷ 1822

Before removing the internal protection panels,


disconnect the power supply by turning the main isolating
switch D5 to position "O", then wait until the fans stop and
the electrical heaters cool down.

MODELS TU. 511 ÷ 1822

MODELS TD. 2222 ÷ 3342

19
• refer to the wiring diagram and connect the cable to the
Electrical connections
main switch D5.
WARNING! Electrical connection of the machine
to the power supply must ONLY be carried out POWER SUPPLY CABLE
by a qualified electrician. (at customers at care)

WARNING! Electrical lines must be established


in full respect of CEI standards.
WARNING! Before establishing the electrical
connection, make sure that the power supply is
off. Also ensure that it is not possible to
reconnect the power during the operation.
WARNING! The power supply voltage must be ±
10%
To carry out the electrical connections of the machine to the
power supply, carry out the following procedures:
• use suitable equipment to check the efficiency of the
grounding system; 2222 - 2242 - 2522 - 2542 - 2842 - 3342
• check that the voltage and network frequency correspond
to those of the machine (see identification label);
• open the door of the electrical panel;
• remove the plastic screen of the electrical panel using a
star screwdriver;

POWER SUPPLY CABLE


(at customers at care)

• pass the cables inside using the power supply cable inlet
D7A which connects to the main switch D5;

D5
D7B

D7A

20
To connect the auxiliary connections to the terminal board, Connection to the humidifier (optional) and to the drains
carry out the following procedures: of the building
• pass the cables through the power supply cable inlet WARNING! The water discharged from the
D7B; humidifier is at a very high temperature. The
drainage tube has to withstand high
temperatures (at least 100°C) and must be kept
away from electrical cables.
D5 Connect the drainage tube of the unit to the collection tray
(U4) of the humidifier.
D7B
Connect the drainage tube of the humidifier (U7) to the drains
of the building using a rubber or plastic tube, which is resistant
D7A
to high temperatures (minimum 100 °C) with an internal
• refer to the wiring diagram and carry out the connection diameter of 22 mm.
to the terminal board.
U4
U7
20
20
20
20

50
51
52
The external drainage tube must be siphoned to avoid
unpleasant odours and an overflow of the water from the tray
of the humidifier. Maintain a minimum slope of 1% downstream
DIGITAL CONFIGURABLE INPUTS of the siphon.
Drain
Terminal board 51-20
- User
- ON - OFF Remote Minimum slope
- Flooding sensor (SAS) %
Terminal board 52-20 Siphon
- User
- ON-OFF Remote
- Fire-smoke (SFF)
Once the connections have been made, pour water into the
Terminal board 50-20
condensate collection tray of the Leonardo unit and in the
- User
condensate collection tray of the humidifier until both siphons
- ON-OFF Remote
are full.
- Tools (ATA-BTA-AUA-BUA)
Connection to the gas drain
The cooling circuit is equipped with a safety valve for the
Connection to the drains discharge of the refrigerant gas.
The condensed water drains from the tray through a siphoned The intervention of the valve pressurises the discharge of the
flexible tube fitted in the unit. refrigerant fluid, possibly also to high temperatures; in the
If the conditioner is fitted with a humidifier, the condensate case of installation in a closed environment, where there is
drain tray and the humidifier drain connection must be the risk of causing damage to people nearby, a conveying
connected to the drains of the building. tube must be used from the discharge to outside the room;
Direct connection to the drains of the building this must be done in such a way that the operation of the
Connect the drainage tube of the unit to the drains of the valve is not affected: it must not create a full flow, a counter-
building using a rubber or plastic tube with an internal diameter pressure higher than 10% of the pressure of the calibration.
of 25 mm. Where it is not possible to install a conveying tube it is good
The external drainage tube must be siphoned in order to avoid practice to create adequate aeration of the environment, and
unpleasant odours. Maintain a minimum slope of 1% indicate, through specific signs, the presence of the drain.
downstream of the siphon. Also check that the discharge of the valve does not take
place behind the electrical boards or electrical equipment.
Drain

Minimum slope
%
Siphon

SAFETY VALVE
OUTLET

Once the connections have been made, pour water into the
condensate drain until the siphon inside the unit is full.

21
Refrigerant connections on air cooled units
Installation guide
WARNING! The pipes must always be protected from the sun.

1/100
C

A
B

1/100
1/100 B
C

MAX.
5m MAX.
15 m

C
MAX.
A 5m

Choosing the diameter of the discharge tube


The discharge line must be sized in such a way that it guarantees the flow of oil, in particular when operating at partial load,
avoiding the return of the condensate refrigerant to the head of the compressor and prevent excessive vibration and noise
due to the pulsations of hot gas, vibrations of the compressor, or both.
Even if it would be preferable to have low losses of the load along the line, an oversized discharge line is necessary to
reduce the speed of the refrigerant so that it does not provoke a reduction in its speed and therefore reduce the flow of oil.
Moreover, when the machine uses more compressors for the cooling circuit, the discharge line must transport the oil at all
operating levels.
The minimum diameters needed to guarantee the flow of oil can be found in Graphics 1 -2 for the horizontal and vertical lines
respectively.
In the installation of machines which have more compressors per circuit, the vertical discharge line, sized in order to
guarantee the flow of oil at minimum load, may cause excessive loss of load when operating at its maximum level; in this
case it is possible to use pipes with a larger diameter together with an oil separator.
The loss of load along the discharge line causes an increase in the condensing temperature and therefore a decrease in the
cooling capacity of the conditioner. Please note that each percentage point of decrease in the cooling capacity corresponds
to a decrease of 1°C of the maximum operating temperature. Normally the systems are sized in such a way that the loss
of load from the discharge line does not cause a decrease in the efficiency of the machine of more than -3%.
The responsibility of establishing the refrigerant line between the condensing unit and the external unit lies
with the installer.

22
R407C
Graphic 1
Grafic Tubazioni
Discharge tube - horizontal di mandata
line (External - linea orizzontale
diameter)

18,0

12 mm
16,0

14,0
14

12,0

16 mm
DP/L [Kpa/m]

10,0 18 mm

8,0
20 mm

6,0

22 mm

4,0
24 mm

2,0 28

35 mm
0,0
0 10 20 30 40 50
Resa frigorifera/circuito [KW]
Cooling capacity / circuit [KW]
Graphic 2 Grafic Tubazioni
Discharge tube - vertical di mandata
line (External - linea verticale
diameter)

18,0

12 mm

16,0

14,0
14 mm

12,0
16 mm
DP/L [Kpa/m]

10,0
18 mm

8,0

20 mm
6,0

22 mm
4,0

24

2,0

0,0
0 10 20 3 0 40 5 0
Resa frigorifera/circuito [KW]
Cooling capacity / circuit [KW]
DP/LDP/L
:Load
:Perditaloss per
di carico meter
per metro calculated
calcolata by R407C
per R407C (Temperatura (Condensing
di condensazione temperature 50°C dew point)
50°C dew point)

23
Graphic 3

Not allowed
3 -Non consentito DP/L=14,5 DP/L=12 DP/L=10
DP/L=8
DP/L=7

DP/L=6

DP/L=5

Allowed
2 -Consentito

DP/L=4

DP/L=3

DP/L=2
Ideal
1 -Ideale

DP/L=1

0,0 5,0 10,0 15,0 20,0 25,0 30,0 35,0 40,0


Lunghezza Equivalente [m]
Equivalent lenght

R410A
Graphic 1
Discharge tube - horizontal line

18,0

12 mm 14 mm
16,0
16 mm

14,0

12,0
DP/L [kPa/m]

10,0

18 mm
8,0

6,0
20 mm

4,0
22 mm

2,0 24 mm
28 mm

0,0
0 10 20 30 40 50

Cooling capacity/circuit [kW]

24
Graphic 2
Discharge tube - vertical line

18,0

12 mm 14 mm
16,0
16 mm

14,0

12,0
DP/L [kPa/m]

10,0

18 mm
8,0

6,0

20 mm
4,0
22 mm

2,0 24 mm

0,0
0 10 20 30 40 50

Cooling capacity/circuit [kW]

DP/L : Pressure drop per metre based on R410A

Graphic 3

3 - Non consentito - Unacceptable


DP/L = 14 DP/L = 12 DP/L = 10 DP/L = 8

DP/L = 7

DP/L = 6

2 - Consentito - Acceptable DP/L = 5

DP/L = 4

DP/L = 3

DP/L = 2
1 - Ideale - Recommended

DP/L = 1

-5 0 5 10 15 20 25 30 35 40

Equivalent line [m]

25
Conforming to the Standards EN 14276-1 and EN 14276-2 the minimum recommended thickness for the gas supply pipe
where bends are made for the air cooled units with R410A refrigerant, must be equal to the values present in the attached
table below. The value `R' refers to the minimum allowed radius of the bend.

External diameter Radius of the bend Thickness


De (mm) r [mm] t [mm]
28 100 1,2
22 66 1 De r
18 27 1
16 26 1
12 20 1 t

Line
Line s izing
sizing R407C

V ertical line Horizontal line


T ype of line

C ooling capacity/circuit at C hart 2 C hart1 C ooling capacity/circuit at


full load operation (100)% full load operation (100)%

DP /L (100%)
Allowed diameters
C ooling capacity/circuit at
partial load operation (50)%

Y es
T andem unit
only R407C

No
Allowed diameters

E quivalent length

Acceptable C hart 3 Unacceptable

Ideal

Allowed diameter but no recomended Ideal diameter Not allowed diameter

EXAMPLE - Choosing the diameter of the discharge tube


with R407C refrigerant
Conditioner selected: TDAR0721A 14mm DP/L= 11,5 Kpa/m
Cooling capacity per circuit: 24 Kw Operating at 50% (1 compressor - cooling capacity per
Discharge line: vertical circuit = 12 KW): possible diameters:
Equivalent length of the line: 20 m 16mm DP/L= 1,7 Kpa/m
1) Graphic 2: 14mm DP/L= 3,4 Kpa/m
Operating at 100% (2 compressors - cooling capacity per 2) Graphic 3:
circuit = 24KW): Operating at 100% (2 compressors)
possible diameters: Diameter 16mm 6,0 Kpa/m Allowed Diameter 14mm
20mm DP/L= 1,8 Kpa/m 11,5 Kpa/m Not allowed
18mm DP/L= 3,0 Kpa/m The advised diameter is 16 mm
16mm DP/L= 6,0 Kpa/m

26
BACKFLOW LINE DIMENSIONING (LIQUID)
To avoid gas development inside the line and to ensure an
adequate pressure is reached inside the laminating unit, the
liquid line must be correctly dimensioned. Generally, the
systems are dimensioned so that pressure loss along the
line causes a variation of the saturation temperature between
0,5 K and 1 K

During the installation of the cooling unit, a solenoid


valve should be fitted on the liquid line between the
inner unit and the external condenser, to avoid
malfunctioning and to protect the compressor from
unwanted liquid migration during start- up.

Liquid line external diameters

TDA* - TDT* - TUA* - TUT*


0511 0611 0721 - 0921 0722 - 0922 1322 - 1422 2222 2522 - -
MODEL
1021 - 1321 1022 - 1122 1622 - 1822 2242 2542 2842 3342
1x 1x 1x 2x 2x 2x 2x 2x 2x
R 407C + R 410A
16 mm 16 mm 16 mm 16 mm 16 mm 18 mm 18 mm 22 mm 22 mm
Refrigerant R407C and R410A

Remote air cooled condenser R410A


TDA* - TUA*
MODEL 0511 0611 0721 0722 0921 0922 1021
Number/ 1x 1x 1x 2x 1x 2x 1x
Suggested model (1) (2) CAP0661 CAP0661 CAP0801 CAP0331 CAP1011 C A P 0361 C A P 1301

TDA* - TUA*
MODEL 1022 1121 1122 1322 1311 1422 1622 1822
1x 1x 1x 1x
Number/ 2x 1x 2x 1x C A P 1802 C A P 1802 C A P 2002 C A P 3002
Suggested model (1) (2) CAP0511 CAP1301 CAP0511 CAP1301 2x 2x 2x 2x
CAP0661 CAP0801 CAP0801 CAP1011

TDA* - TUA*
MODEL 2222 2242 2522 2542 2842 3342
Number/ 1x 1x 1x 2x 1x 2x
Suggested model (1) (2) C A P 2002 C A P 2002 C A P 3002 C A P 3002 C A P 4002 C A P 5002

(1) With fan speed control


(2) External temperature = 35°C

Remote air cooled condenser R407C

TDA* - TUA*
MODEL 0511 0611 0721 0722 0921 0922 1021
Number/ 1x 1x 1x 2x 1x 2x 1x
Suggested model (1) (2) C A L0661 C A L0661 C A L0801 C A L0331 CAL1011 C A L0361 C A L1301

TDA* - TDT* - TUA* - TUT*


MODEL 1022 1121 1122 1322 1311 1422 1622 1822
1x 1x 1x 1x
Number/ 2x 1x 2x 1x C A L1802 C A L1802 C A L2002 C A L3002
Suggested model (1) (2) CAL0511 CAL1301 CAL0511 CAL1301 2x 2x 2x 2x
CAL0661 CAL0801 CAL0801 CAL1011

27
TDA* - TUA* TD T* - TU T*
MODEL 2222 2242 2522 2542 2842 3342 2242 2542 2842
Number/ 1x 1x 1x 1x 1x 1x 1x 1x 1x
Suggested model (1) (2) CAL2002 CAL2002 CAL3002 CAL3002 CAL4002 CAL5002 CAL2002 CAL3002 CAL4002
(1) With fan speed control
(2) External temperature = 35°C

Dry coolers
TDW*- TDD*- TDE*- TUW*- TUD*- TUE*
MODEL 0511 0611 0721 0722 0921 0922 1021
Number/ 1x 1x 1x 1x 1x 1x 1x
Suggested model RAL1500 RAL1500 RAL1500 RAL1500 RAL1500 RAL1500 RAL1500
Max outdoor
41,5°C 40,0°C 40,5°C 40,5°C 40,0°C 42,5°C 41,5°C
temperature

TDW*- TDD*- TDE*- TUW*- TUD*- TUE*


MODEL 1022 1121 1122 1311 1322 1422 1622 1822
Number/ 1x 1x 1x 1x 1x 1x 1x 1x
Suggested model RAL1500 RAL1500 RAL1500 RAL2300 RAL2300 RAL2300 RAL3600 RAL3600
Max outdoor
41,5°C 41,8°C 42,2°C 43,5°C 44,6°C 43,5°C 44,2°C 43,4°C
temperature

TDW*- TDD*- TDE*- TUW*- TUD*- TUE*


MODEL 2242 2542 2842 3342
Number/ 1x 1x 1x 1x
Suggested model RAL2300 RAL3600 RAL3600 RAL3600
Max outdoor
40°C 42°C 41°C 39°C
temperature
Installation
WARNING! The laying of the lines and the • weld the rotalock valve to the inlet and outlet pipes of the
refrigerant connections must be carried out by condensing unit;
a qualified refrigerant circuit technician. • using the teflon gaskets screw the rotalock valves to the
The refrigeration circuit must be connected to the condensing inlet and outlet pipes of the refrigeration circuit of the
unit with copper pipes. conditioner.
The diameter of the pipes must be chosen according to the
length of the refrigerant line itself (preferably less than 30 m)
therefore it is possible that the internal diameter of the rotalock
valves supplied by Uniflair will not coincide with the diameter
of the pipes, see note at page bottom. To connect the
refrigeration circuit to the condensing unit, carry out the
following procedure:
• check that the diameter of the rotalock valves coincides
with the diameter of the connecting pipe;

ATTACCHI ROTALOCK

INLET

OUTLET
Note: the units with R410A refrigerant all have welded connections
28
Evacuation of the refrigeration circuit and charging of refrigerant
WARNING! The charging and maintenance of the refrigeration circuit must only be carried out by a
qualified hydraulic technician.
The refrigeration circuit is pre-charged with nitrogen.
To load the refrigerant, carry out the following procedure:

R22 R407C - R410A


• open any shut-off valves present in the machine to ensure • open any shut-off valves present in the machine to ensure
that all of the components will be evacuated; that all of the components will be evacuated;
• connect a pump to empty the schrader connections • connect a pump to empty the schrader connections
efficiently, or to the 1/4" SAE connections present on efficiently, or to the 1/4" SAE connections present on
the intake and delivery sides of the compressors; the intake and delivery sides of the compressors;
• connect the refrigerant cylinder to the loading • connect the refrigerant cylinder to the loading
connections; connections;
• create a vacuum within the lines while maintaining the • create a vacuum within the lines whilst maintaining the
pressure below 100 Pa absolute (0,7 mm Hg) for a long pressure below 10 Pa absolute (0,07 mm Hg) for a long
time in order to evacuate the air as well as any traces of time in order to evacuate the air as well as any trace of
humidity. It is preferable that the vacuum is reached humidity. It is preferable that the vacuum is reached
slowly and maintained for a long period of time; slowly and maintained for a long period of time;
• wait for a build up period of 100 seconds and check that • wait for a build up period of 100 seconds and check that
the pressure has not exceeded 200 Pa absolute. the pressure has not exceeded 200 Pa absolute.
Generally, in the case of suspicion of strong hydration of Generally, in the case of suspicion of strong hydration of
the circuit or an extremely extensive system, it will be the circuit or an extremely extensive system, it will be
necessary to break the vacuum with anhydrous nitrogen necessary to break the vacuum with anhydrous nitrogen
and then repeat the evacuation procedure as described; and then repeat the evacuation procedure as described;
• break the vacuum by performing a preload from the R22 • break the vacuum by performing a preload in liquid phase
coolant cylinder; from the R407C and R410A coolant cylinder;
• after having started the compressor, slowly complete the • after having started the compressor, slowly complete the
loading phase until the pressure within the lines has been loading phase until the pressure within the lines has been
stabilised and the gaseous bubbles have disappeared stabilised and the gaseous bubbles have disappeared
from the flow sight glass; from the flow sight glass;
• the loading process must be controlled in environmental • the loading process must be controlled in environmental
conditions with a delivery pressure of approximately 18 conditions with a delivery pressure of approximately 18
bar (equivalent to a saturated temperature of 48 °C); in bar (equivalent to a dew temperature of 48 °C and a bubble
the case of units with ON/OFF condensation controls, temperature of 43 °C); in the case of units with ON/OFF
avoid switching the condenser fan on and off, which may condensation controls, avoid switching the condenser
partially obstruct the intake surface. It is wise to check fan on and off, which may partially obstruct the intake
that the sub-cooling of the liquid at the entry of the surface. It is wise to check that the sub-cooling of the
thermostatic valve is between 3 and 5 °C below the liquid at the entry of the thermostatic valve is between 3
condensation temperature read on the scale of the and 5 °C below the condensation temperature read on
pressure gauge and that the overheating of the vapour at the scale of the pressure gauge and that the overheating
the exit of the evaporator is equal to 5-8 °C. of the vapour at the exit of the evaporator is equal to
approximately 5-8 °C.

Type of oil recommended with COPELAND compressors


R22 (Mineral oil) Suniso 3 GS Texaco WF 32 Fuchs KM
R407C (POE) Mobil EAL Arctic 22 cc ICI EMKARATE RL 32S

Type of oil recommended with MANEUROP compressors


R22 (Mineral oil) Maneurop 160 P - Mineral / ISO 32
R407C (POE) Maneurop 160 SZ
R410A (POE) Maneurop 160 SZ

Type of oil recommended with SANYO compressors


R22 (Mineral oil) SAY - 56T
R407C (PVE) F V 68S
R410A (PVE) F V 68S

Type of oil recommended with Scrolltech HCJ 072-HLJ 083 compressors


R410A (PVE) Daphne PVE FVC8D

29
If the water temperature falls to below the dew point of the air
Connection for water cooled units
conditioner, isolate the piping with closed cell material (e.g.:
WARNING! The laying of the lines and hydraulic Armaflex or equivalent) to avoid condensation; the isolation
connections must only be carried out by a must allow the accessibility of the valves and the three piece
qualified plumber. joints. Seal the piping holes through the base of the conditioner
WARNING! The chilled water must contain a to avoid a bypass of air.
percentage of ethylene glycol (of the passive WARNING! The water cooled pressure must not
type, which is therefore not corrosive) according be above 6 bar.
to the minimal external temperature predicted
(see the table below).
Table of condenser fitting dimensions
Percentage of ethylene glycol 10% 20% 30% 40% 50%
Freez ing temperature -4°C -10°C -17°C -25°C -37°C
0722
If the temperature of the chilled water is not checked it may 0721 0922
fall to under 25°C, therefore it is necessary to use a 0921 1022 2222
pressostatic valve (available as an optional) for each 1021 1122 2242
condenser; in this case the pressure of the supply must not 1121 1322 2522
be less then 200 kPa (2 bar). 1321 1422 2542
0511 1411 1622 2842
WARNING! Do not use chilled water with an 0611 1421 1822 3342
evaporating tower because the condensers will
quickly become encrusted with limescale.
Water condenser inlet 1" 1.1/4" 2x1.1/4" 2x1.1/4"
The condenser must be connected to the chilled water
distribution network, paying attention to the direction of the
water inlet and outlet. Water condenser
1" 1.1/4" 2x1.1/4" 2x1.1/4"
The condensers are supplied by water pumped in a closed outlet
circuit and chilled by external refrigerators; check that the
section of piping and the characteristics of the circulation
pump are suitable: an insufficient flow of water can have a
negative effect on the capacity of the conditioner.
The chilled water temperature must be checked to ensure
that it does not fall to below 25°C, preferably according to
the plan indicated in the figure.
The microprocessor control system is predisposed for
measuring the temperature of the water using probes (A)
and modulating the servomotor of the valve (B) or by driving
the fans (C) of the external refrigerators.

Once the connections have been made to the hydraulic circuit,


≥ 25 °C the system can be filled.

30
MANUAL START UP AND SHUT DOWN OF WARNING! During prolonged breaks a
THE UNIT spontaneous migration of the refrigerant may
occur in the casing of the compressor, which may
WARNING! Check that the refrigerant circuit has
cause foaming of the oil and consequent damage
been filled.
by the lack of lubrification. It is recommended
To start up the unit, carry out the following procedure: that the main switch is not turned off during
• open the door of the electrical panel and the front weekly breaks.
panels;
• wait at least 12 hours before start up so that the oil in
• position the automatic switch of the auxiliary circuit to
the compressors warms up sufficiently;
"I" (on);
• open the shut off valves (I5) of the refrigerating circuits;
• position all of the automatic switches on the electrical
board to "I" (on);

I5

• fuel the unit by positioning the main switch


to "I" (on); • check that the remote condensers are powered (on air
cooled models);
• check that the external dry coolers are powered and
check the presence of the water flow for condensation
(on water cooled models);
• check that the tracts of siphoned corrugated pipe, both
internal and external to the conditioner, have been filled
with water in the installation phase;
D5
• close the door and the front panels;
• wait for the oil in the compressors to heat (12 hours for
compressors equipped with heaters);
• press the ENTER key (A6) of the user terminal; a sliding
bar and a ventilator icon will appear on the display;
• check that both of the led RSF sequence phases (D8)
are lit up; the green led indicates that the power is on,
the yellow led indicates that the phase sequence is
correct. In the event of incorrect phase sequence, invert
2 of the 3 phases of power supply following the
instructions indicated in the paragraph "electrical
connections" and return to the start up procedure;
A1

L1 L2 L3 A2 A5

A3 A6
D8 LED
A4 A7

LED
• if an alarm is indicated, consult the user interface manual
UG40;
12 14 11

31
To shut down the unit carry out the following procedure: HOW TO ADJUST FAN SPEED
WARNING! During prolonged breaks a In the TD*R and TU*R units, the speed of the fan rotation can
spontaneous migration of the refrigerant may be varied by using the ATR transformer (F1).
occur in the casing of the compressor, which may
cause foaming of the oil and consequent damage
F1
because of the lack of lubrification. It is
recommended that the main switch is not turned
off during weekly breaks.
• on the first screen of the user terminal, press keys A5
or A7 until the SWITCH OFF UNIT screen appears;
• press the ENTER key to confirm;
• the following icons will appear
OFF

Press the ENTER to confirm

To obtain the required prevalence of the implant, it is possible


SETTING AND ADJUSTMENT
Selecting the power supply of the fans to vary the voltage by selecting one of the following levels:
Models 0511-0611
WARNING! Before establishing the electrical 140V -160V -180V -190 - 200V -210V -220V -230V
connection, make sure that the power supply is Models 0721-1822
off. Also ensure that it is not possible to 230V - 250V - 260V - 270V - 280V - 290V - 300V - 310V -
reconnect the power during the operation. 320V - 340V - 360V - 380V - 400V.
WARNING! In the case of a unit with ducts, the Models 2222 - 2242 - 2522 - 2542 - 2842 - 3342 : 150V -
load loss from the exhaust duct must be less than 180V - 200V - 230V - 240V - 260V - 280V - 300V - 320V -
100 Pa. 340V - 360V - 380V - 400V.
In the following table the voltage levels for each model working In the following table the maximum pressure available
in the standard version are given. (expressed in Pa) for each voltage level of the transformer is
indicated. The values are given for the maximum air flow
T*AR - T*WR: Air and w ater condensing direct expansion unit (expressed in m3/h).
Refrigerant: R407C
P o st T*AR - T*WR T*AR - T*WR
P o st Model
20 P a EU 4 EU 5 heating 0511 - 0611 0511 - 0611
heating Air flow [m3/h] 5740 5740
+ EU 5
Pow er supply voltage Refrigerant R 407C R 410A
[V] [V] [V] [V] Pow er supply
0511A - 0611A 180 180 180 190 voltage
0721A - 0722A - [V] [Pa] [Pa]
0921A 0922A - 1021A 260 260 260 270
- 1022A
140 - -
1121A - 1122A - 160 20 20
260 260 260 270
1321A - 1322A 180 44 44
1422A - 1622A - 190 71 71
270 270 270 280
1822A
200 101 101
2222A - 2242A 230 230 240 240
2522A - 2542A 240 240 260 260 210 137 137
2842A - 3342A 260 260 260 280 220 176 176
230 196 196

T*AR - T*WR: Air and w ater condensing direct expansion unit SERIES T*AR - T*WR T*AR - T*WR
0721 - 0722 1422 0721 - 0722 1422
Refrigerant: R410A Model 0921 - 0922
1121 - 1122
1622 0921 - 0922
1121 - 1122
1622
1321 - 1322 1321 - 1322
P o st 1021 - 1022 1822 1021 - 1022 1822
P o st Refrigerant R 407C R 410A
20 P a EU 4 EU 5 heating
heating Air flow [m3/h] 8180 11710 15600 8180 11650 5740
+ EU 5
Pow er supply
0511A - 0611A 180 180 180 190 voltage
0721A - 0722A - [V] [Pa] [Pa] [Pa] [Pa] [Pa] [Pa]
0921A 0922A - 1021A 260 260 260 270 230 - - - - - -
- 1022A 250 - - - - 20 -
1121A - 1122A - 260 18 20 - 20 25 -
250 260 260 270
1321A - 1322A 270 24 38 20 37 55 20
1422A - 1622A - 280 49 65 36 62 83 36
270 270 270 280
1822A 290 76 97 65 89 113 65
2222A - 2242A - 300 101 125 124 114 142 124
230 240 240 240 310 127 154 125 143 173 125
2522A - 2542A
320 152 184 153 166 200 153
2842A 240 240 240 260
340 178 228 196 204 245 196
3342A 240 260 260 260 360 229 287 256 255 305 256
380 332 346 315 307 363 315
400 369 433 403 389 457 403

32
SERIES T*AR - T*WR T*AR - T*WR
Model 2222 - 2242 2522 - 2542 2842 3342 2222 - 2242 2522 - 2542 2842 3342
Refrigerant R 407C R 410A
Air flow [m3/h] 22000 23000 23500 23500 22000 23000 23500 23500
Pow er supply
voltage
[V] [Pa] [Pa] [Pa] [Pa] [Pa] [Pa] [Pa] [Pa]
150 - - - - - - - -
180 - - - - - - - -
200 - - - - - - - -
230 - - - - 20 - - -
240 20 - - - 54 20 - -
260 123 20 20 - 145 111 20 -
280 171 130 65 20 193 155 88 20
300 213 170 102 66 236 197 129 98
320 251 208 135 101 275 235 163 134
340 285 240 166 133 309 265 195 165
360 314 268 195 162 338 295 222 195
380 327 294 245 187 362 320 295 218
400 345 300 277 254 369 327 305 289

After having selected the voltage level, carry out the MODELS MODELS MODELS
connection in the following way: 0511-0611 da 721 a 1822 da 2222 a 3342
• with the unit turned off, open the front panels and the
door of the electrical panel and the internal protection ATR1 ATR2

  
panels; &?

@
>
?
• select the supply voltage by positioning the main switch ATR1 ATR2
to "0" (D5); !  !
&!?
• Follow the diagrams displayed below and refer to the

@
>
?
wiring diagram enclosed to connect the two electric wires ATR1 ATR2

  
found on the fan, or on the connector block, to the &?

@
>
?
corresponding terminals on the autotransformer
ATR1 ATR2

  
&?

@
>
?
ATR1 ATR2

  
&?

@
>
?
ATR1 ATR2

  
&?

@
>
?
ATR1 ATR2

!  !
&!?
@
>
?

ATR1 ATR2

  
&?
@
>
?

ATR1 ATR2

  
&?
@
>
?

ATR1 ATR2

  
&?
@
>
?

ATR1 ATR2

  
&?
@
>
?

ATR1 ATR2

!  !
&!?
@
>
?

ATR1 ATR2

  
&?
@
>
?

33
MODELS WITH A PHASE CONTROL VOLTAGE REGULATOR
To reach the head required by the system for conditioners with fans carrying a CE marking, the input voltage percentage can
be adjusted from the user terminal (A).
To select the voltage percentage to be applied, carry out
the following procedures:
• on the user terminal press the PRG button;
• using the UP or DOWN key select SERVICE MENU and confirm using the ENTER key;
• enter the password (see the envelope attached to the manual);
• using the UP or DOWN key select HARDWARE SETTING and confirm using the ENTER key;
• using the UP or DOWN key select EVAPORATING FAN and confirm using the ENTER key;
• set the amount and confirm using the ENTER key.
In the following table the maximum pressure available (expressed in Pa) for each voltage level of the transformer is
indicated. The values are given for the maximum air flow (expressed in m3/h).

T*AV - T*WV: Air and w ater condensing direct expansion unit T*AV - T*WV: Air and w ater condensing direct expansion unit
20 Pa Refrigerant: R407C 20 Pa Refrigerant: R410A
P o st P o st
P o st P o st
20 P a EU 4 EU 5 heating 20 P a EU 4 EU 5 heating
heating heating
+ EU 5 + EU 5
Pow er supply voltage Pow er supply voltage
[% ] [% ] [% ] [% ] [% ] [% ] [% ] [% ]
0511A - 0611A 59 60 60 61 0511A - 0611A 58 59 59 60
0721A - 0722A - 0921A 0721A - 0722A - 0921A
69 70 70 71 68 69 69 70
0922A - 1021A - 1022A 0922A - 1021A - 1022A
1121A - 1122A - 1321A - 1121A - 1122A - 1321A -
63 65 65 67 61 63 62 64
1322A 1322A
1422A - 1622A - 1822A 71 72 73 74 1422A - 1622A - 1822A 70 71 71 72
2222A - 2242A 64 65 65 66 2222A - 2242A 62 63 63 64
2522A - 2542A 66 68 68 69 2522A - 2542A 65 66 66 67
2842A 68 69 69 70 2842A 66 67 67 69
3342A 69 70 71 72 3342A 67 69 69 69

T*AV - T*WV T*AV - T*WV


Model
0511 - 0611 0511 - 0611
Air flow [m3/h] 5740 5740
Refrigerant R 407C R 410A
Pow er supply voltage
[% ] [Pa] [Pa]
50 - -
55 - -
59 20 -
60 55 20
65 153 125
70 235 218
75 333 298
80 395 385
85 483 455
90 545 525
95 628 593
100 682 660

SERIES T*AR - T*WR T*AR - T*WR SERIES T*AR - T*WR T*AR - T*WR
0721 - 0722 1422 0721 - 0722 1422 Model 2222 - 2242 2522 - 2542 2842 3342 2222 - 2242 2522 - 2542 2842 3342
1121 - 1122 1121 - 1122
Model 0921 - 0922 1622 0921 - 0922 1622 Refrigerant R 407C R 410A
1321 - 1322 1321 - 1322
1021 - 1022 1822 1021 - 1022 1822
Air flow [m3/h] 22000 23000 23500 23500 22000 23000 23500 23500
Refrigerant R 407C R 410A Pow er supply
3
Air flow [m /h] 8220 11710 15600 8220 12320 5740 voltage
Pow er supply [% ] [Pa] [Pa] [Pa] [Pa] [Pa] [Pa] [Pa] [Pa]
voltage 55 - - - - - - - -
[% ] [Pa] [Pa] [Pa] [Pa] [Pa] [Pa] 60 - - - - - - - -
50 - - - - - - 65 10 - - - 20 - - -
55 - - - - - - 70 80 30 - - 90 50 25 -
60 - - - - - - 75 160 115 97 65 170 140 120 98
65 - 45 - - 70 - 80 248 190 181 160 260 230 207 185
70 40 120 10 63 145 10 85 335 290 270 248 351 320 305 284
75 130 200 87 140 215 87 90 430 380 370 350 440 410 400 378
80 220 282 182 237 300 182 95 540 490 465 440 555 520 492 470
85 325 364 270 338 385 270 100 704 670 651 628 728 697 680 662

90 412 450 370 420 475 370


95 512 555 475 533 577 475
100 647 687 604 667 707 604

34
Setting the regulation and safety devices Setting the air flow sensor
After starting up the unit, set the following set points (see The FS differential pressure switch intervenes if the fan (or
the microprocessor control manual): one of the fans) stops working.
• Room temperature (cooling and heating set point); The factory set point of the FS differential pressure switch is
• Relative room humidity (humidification and at 0.5 mbar (= 50Pa).
dehumidification set point); As the difference in pressure between the suction and
• Dirty filter differential pressure switch: see paragraph discharge of the fans depends on the air flow, it may be
"Setting the dirty filter sensor". necessary to calibrate the instruments after installation,
The settings of the safety devices must not be modified. checking that the contact closes when the fans are in
operation.
R22 - R407C To set the FS pressure switch, carry out the following proce-
C ode Description Opening Model Re-set dure:
High pressure 26.5 bar 0511 - 1822 Manual • simulate a fan fault by stopping a fan; check that the
AP1-AP2
switch 27.5 bar 2222 - 3342 Reset pressure switch intervenes;
First emergency 310 °C Manual • if the pressure switch does not intervene, gradually
TSR All
safety thermostat (opening) Reset
increase the setting until the pressure switch switches
Second emergency 328 °C Manual
TSRA
safety thermostat (opening)
All
Reset off:
VS Safety valve 30 bar All - - using an adjustment screw, set the differential pressure
switch on a scale (from 0.5 to 4.0 mbar - from 50 to 400
R410A Pa).
C ode Description Opening Model Re-set
High pressure 40,5 bar Manual
AP1-AP2 All
switch (opening) Reset
First emergency 310 °C Manual
TSR All
safety thermostat (opening) Reset
Second emergency 328 °C Manual
TSRA All
safety thermostat (opening) Reset
VS Safety valve 45 bar All -

Maximum and minimum water temperatures


The maximum and minimum water temperatures for chilled
water circuits and for hot water re-heat circuits are: 5°C ÷
90°C.
The accepted maximum amount of ethylene glycol is 50%.

Setting the pressostatic valve (optional on


chilled water cooled models only) Setting the dirty filter sensors
The pressostatic valve, by controlling the water flow, prevents The PFS differential pressure switch is set according to the
the condensing pressure falling too low and at the same time loss of load dependent on the dirt inside the filters and the air
minimises water consumption. When necessary, set the flow.
pressostatic valve by turning the regulation knob (the pressure The PFS differential pressure switch must be set at 3 mbar
increases when turning it clockwise) until the condensation (=300 Pa).
pressure stabilizes to recommended* checking the pressure To set the PFS pressure switch, carry out the following pro-
with a gauge fitted to the pressure tapping of the compressor cedure:
discharge valve. • gradually cover the surface of the air filter and check
that the pressure switch intervenes when the filter is about
50-60 % covered;
• if the pressure switch does not intervene, gradually lower
the setting, if it cuts in too soon, increase the setting:
- using a star screw driver turn the regulation screws of
the pressure switch to the desired value.

* R22-R407c : pressure 17 bar = temperature 45°C


R410A : pressure 26 bar = temperature 45°C
35
MAINTANENCE Cleaning and repalcing the filters
Three-monthly checks Models TD. 2222 ÷ 3342
To clean and replace the filters carry out the following
Carry out the following checks every three months:
procedures:
• check the power supply;
• remove the front cover of the filters by turning
• check the alarm status;
anticlockwise the panels screws;
• check the working pressures and temperatures;
• check the correct operation of the local/remote controls;
• check the air filters, cleaning and replacing them if
necessary;
• check the efficiency of the condensing drain;
• check the steam cylinder is clean, replacing it if
necessary;
• check and clean if necessary the condensing coil.

Six-monthly checks
Carry out the following checks every six months:
• repeat these checks on a three-monthly basis;
• check and clean if necessary the cooling coil;
• check the operation of the humidifier (if present). • remember the direction of the air flow indicated on the
Annual checks label of each filter and draw the filters;
Carry out the following checks every year:
• repeat these checks on a six-monthly basis;
• check the varnish and the nuts and bolts;
• check the hinges, rabbets and gaskets;
• check the cables and wiring;
• tighten the terminal blocks;
• check and reset if necessary the safety device settings
(pressure switches, thermostats, protection devices);
• check the operation of the post heating electrical heaters
• check the fittings, operation and absorption of the
evaporating fan/s; • clean them using a blast of compressed air or replace
• check the fittings, operation and absorption of the them;
compressor/s; • clean them using a blast of compressed air or replace
• check and if necessary replace the seal of the refrigerant them;
circuit/s and tighten the joints and connections of the • mount the front cover of the filters.
unit;
• check and top up if necessary the refrigerant gas and/or
oil;
• check and if necessary reset the regulation devices
setting;
• check and if necessary replace the seal of the hydraulic
circuits/s and tighten the unit couplings;
• check the fittings and operation of the condensing fan/s;
• check and reset if necessary the condensing speed
setting.

Checks to be performed every sixty months


• Check and if necessary replace the gas filters;
• check and if necessary replace the compressor oil.

36
OTHER MODELS
To clean and replace the filters carry out the following
procedures:
• open the front panels of the machine;
• remove the filter blocking supports;

• remove the filters checking the direction of the air flow


indicated on the label of each filter;

• clean them using a blast of compressed air or replace


them;
• reposition the filters in the unit checking the direction of
the air flow which was previously noted;
• reposition the filter blocking supports.

37
Troubleshooting
Troubleshooting is made easier by the indications on the control panel display: when an alarm signal is displayed, consult
the control panel instruction manual. If necessary, call the nearest Service Centre describing the nature of the fault and its
possible cause displayed on the control.

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION


Check that the power is on and the unit main switch on the
A) No power supply to the unit's electrical panel.
electrical panel is closed.
1) Check that the IM automatic circuit breaker on the AUX
THE UNIT DOES NOT
B) No power to the auxiliary circuits. circuit is set.
START
2) Check the fuse on the main board.
Check that the control panel connectors are correctly located
C) The control panel does not start the unit.
in their sockets.

TEMPERATURE CONTROL

PR OB LEM POSSIB LE C AU SE C H EC K /C OR R EC TIVE AC TION

A) The parameter setti ngs on the control panel


See control panel i nstructi on manual
are not correct.
B) The ai r flow i s low or absent. See "LAC K OF / ABSENT AIR FLOW".
C heck the electri cal connecti ons and the control
C ) The temperature sensor i s not worki ng.
confi gurati on.
D ) The thermal load i s hi gher than expected. C heck the room's thermal load.
THE ROOM C heck the electri cal connecti ons of the servomotor
TEMPERATURE IS TOO valve.
E) The three-way valve i s not worki ng.
HIGH Open the valve by means of the manual control
knob.
C heck the chi lled water supply; check that the
E) Valvola a tre vi e non funzi onante.
shut-off valves are open.
F) There i s an i nsuffi ci ent chi lled water flow. C heck the chi lled water funti on.
See "THE C OMPRESSOR(S) D OESN'T / D ON'T
G) The chi lled water temperature i s too hi gh.
WORK".
H) The compressor(s) not worki ng despi te control See "THE C OMPRESSOR(S) D OESN'T / D ON'T
call WORK".
A) The parameter setti ngs on the control are not
See the mi croprocessor control manual.
correct
1) C heck that the IM of the heati ng element i s
armed.
B) There i s i nsuffi ci ent power supply to the elcttri c 2) C heck the electri c feedi ng ci rcui t of the
heaters or the heaters are not worki ng heaters.
3) If there i s a heater alarm, remove the cause and
re-set the safety thermostat.
ROOM TEMPERATURE
1) C heck the hot water capaci ty and temperature.
TOO LOW
C ) The hot water coi l i s not worki ng. 2) C heck the functi on of the regulati on valve (see
valve and servomotor).
1) C heck the hot gas 3 way valve functi on.
D ) The hot gas coi l i s not worki ng duri ng 2) C heck the functi on of the compressor servi ng
dehumi di fi cati on wi th re-heat. the re-heat. See "THE C OMPRESSOR(S)
D OESN'T / D ON'T WORK".
E) The three way valve of the chi lled water ci rcui t C lose the valve usi ng the manual control knob and
i s blocked open. replace the servomotor.

38
HUMIDITY CONTROL

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) The parameter settings on the control panel


See control panel instruction manual.
are not correct.
Check the latent load, fresh air conditions and
B) The latent load is higher then expected.
volume; external air infiltration.
ROOM HUMIDITY TOO
C) The compressor does not function during See "THE COMPRESSOR(S) DOESN'T / DON'T
HIGH
dehumidification. WORK".
D) The chilled water is not sufficiently cold for the
Lower the chilled water temperature until
dehumidification function (in energy saving and
condensate is present on the surface of the coil.
twin cool units).
A) The parameter settings on the control panel Check the room humidity settings (see control
are not correct. panel instruction manual).
B) The latent load is lower than expected. Check the quantity of latent heat.
1) Check the water supply pressure.
ROOM HUMIDITY TOO 2) Check the function of the manual control system
C) The humidifier doesn't work.
LOW and of the steam production group (see panel
instruction manual).
See the control panel instruction manual; check
D) The control system does not work. that the control panel and/or sensors work
properly.

FANS

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) There is no power to the fans. Check the power supply to the fans
1) Shake the dust out of the cartridge and clean
with a vacuum cleaner. Replace the filter if it is
completely blocked.
B) The air filters are clogged (dirty filter alarm
enabled).
2) Check the correct setting of the dirty filter
pressure switch PFS.

Check that the air flow is not obstructed, not even


ABSENT OR LOW AIR
C) The air flow is obstructed. partially.
FLOW
Check the resistance of the fan motor windings.
D) The fans' thermal protection intervenes. Re-set then measure the voltage and absorption.

E) (In TD*R, TU*R units with backward curved


Change the power supply voltage to the fans.
blade fans). The power supply to the fans is
(See paragraph. 'Setting and adjustment).
insufficient.
Check the air pressure distribution (ducts, ceiling
F) The air distribution output pressure is too high.
or floor plenum, grilles).

ELECTRIC HEATER
PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) There is insufficient air flow. See "LACK OF / ABSENT AIR FLOW".


ELECTRIC HEATER SAFETY Check the connection between the safety
B) The thermostat connection wire is interrupted
THERMOSTAT INTERVENES thermostat and the control system.
C) The thermostat is faulty. Replace the thermostat.

39
REFRIGERANT CIRCUIT
PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) There is non-condensable air or gas in the


refrigerant circuit, with bubbles in the flow sight glass; Evacuate the refrigerant circuit and recharge.
excessive sub-cooling.
1) Check the fan operation and rotation direction in the
remote heat exchanger.
2) Check to see if the exchanger is dirty and if necessary
remove any obstructing material (leaves, paper, seeds, dust,
B) The air flow to the remote heat exchanger is
etc.) with a blast of compressed air or a brush;
insufficient or too warm.
3) In the external unit check for obstructions in the air flow
HIGH COMPRESSOR and in the recirculation of the cooling air.
DISCHARGE PRESSURE 4) Check that the temperature of the cooling air is within
the planned limits.
1) Check the condenser water flow, pressure and
C) The water flow to the condenser is insufficient or temperature in the closed circuit water system.
too warm. 2) Check the setting and function of the pressostatic
regulation valve.
D) There is too much refrigerant in the circuit; the
condenser is partially flooded. The refrigerant Remove some refrigerant from the circuit.
subcooling is too high at the condenser outlet
E) The discharge valves are partially closed Check the opening of the valves.
1) Check the fan function of the condenser and of the
AP HIGH PRESSURE
A) The condensing pressure control system is not relative protection; re-set or replace the faulty fans.
SWITCH INTERVENES
functioning efficiently. 2) Check the setting and function of the fan speed
(high compressor discharge
regulator of the remote condenser.
pressure)
B) The system discharge pressure is too high See "HIGH COMPRESSOR DISCHARGE PRESSURE".
A) The condensing pressure control system is not Check the setting and function of the condenser fan
functioning efficiently (see control panel manual). pressure switch or speed regulator.
1) Check the condenser water flow and temperature;
2) Check the setting and function of the pressure regulating
LOW COMPRESSOR B) The water flow to the condenser is too high or too
valve (if fitted).
DISCHARGE PRESSURE cold.
3)Fit a pressure regulating valve to control the water
pressure according to the condensing pressure.
See "LOW COMPRESSOR SUCTION PRESSURE".
C) The suction pressure is too low.
Check the room's thermal load; check in case of over
A) The thermal load is too high.
dehumidification, check the air flow and conditions of
external air, check the external air infiltration.
B) The discharge pressure is too high.
HIGH COMPRESSOR See "HIGH COMPRESSOR DISCHARGE PRESSURE".
SUCTION PRESSURE
C) There is an overcharge of refrigerant in the circuit.
Remove some refrigerant from the circuit.
D) There is a return of liquid refrigerant to the Check that the super heat setting of the thermostatic valve is
compressor intake correct.

40
COMPRESSORS

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) The room temperature is too low. See "ROOM TEMPERATURE TOO LOW".
B) The air flow is too low or is absent. See "LOW AIR FLOW".
C) The liquid line solenoid valve is not completely
Check the valve opening.
open.
LOW COMPRESSOR SUCTION D) The refrigerant filter is obstructed. Check the refrigerant filter.
PRESSURE (and possible freezing Check the super heat setting of the thermostatic
E) The thermostatic valve is incorrectly calibrated or
of the coil) valve; check that the sensor bulb has not lost its
defective.
charge and is well positioned, fixed and insulated.
Check the sub-cooling of the refrigerant liquid at
F) There is an insufficient refrigerant charge. the condenser outlet;check to see if there are any
leaks and re-charge the unit.

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

Re-set the automatic switch and check the cause of the


short circuit.Before re-starting the compressor, check the
THE COMPRESSOR(S) A ) The s ho rt c i rc ui t p ro te c ti o n ha s i nte rve ne d .
resistance and continuity of the compressor motor
DOESN'T/DON'T WORK
windings.
B) The contactor is not working. Check the contacts and the contactor coil.
Check the resistance of the compressor motor windings.
A) A phase is missing. After re-setting, measure the voltage and current
absorption of the three phases.
THE COMPRESSOR'S
Check that the unit pressure operates within the planned
INTERNAL PROTECTION B) The motor is overloaded.
limits.
INTERVENES
Check that the voltage is within -10% and
C) The power supply voltage is too high or too low.
+10% of the nominal value.
D) The rotor is blocked. Replace the compressor.
Call the nearest Service Centre in order to replace the
A) The compressor is damaged.
THE COMPRESSOR IS NOISY compressor.
B) There is liquid return to the compressor. Check the setting and function of the thermostatic valve.

41
LEONARDO EVOLUTION - CHILLED WATER
Technical characteristics
CHILLED WATER UNITS WITH BACKWARD CURVED BLADE FANS

Model TDCR - TUCR 600B 700B 600A 700A 1000A


Height mm 1960 1960 1960 1960 1960
Width mm 1010 1010 1010 1010 1310
Depth mm 750 750 750 750 865
Weight kg 210 220 210 220 306
Chilled water flow (*) l/h 4080 4646 4080 4646 5850
Chilled water flow (**) l/h 2830 3240 2830 3240 4480
Electric supply voltage V 400V/3ph+N/50Hz 400V/3ph+N/50Hz

Model TDCR - TUCR 1200A 1700A 2000A 2500A


Height mm 1960 1960 1960 1960
Width mm 1310 1721 2172 2172
Depth mm 865 865 865 865
Weight kg 314 395 443 458
Chilled water flow (*) l/h 7510 9660 11950 15090
Chilled water flow (**) l/h 5370 6340 8240 10650
Electric supply voltage V 400V/3ph+N/50Hz

Model TDCR - TUCR 2700 3400 4000 4300 (only TDCR)


Height mm 1960 1960 1960 2170
Width mm 2170 2580 2580 2580
Depth mm 865 865 865 865
Weight (Complete version) (1) kg 502 720 740 820
Chilled water flow (*) l/h 16854 19279 21658 28146
Chilled water flow (**) l/h 12817 14617 16059 20813
Electric supply voltage V 400V/3ph+N/50Hz
(*) Based on 24°C@50% air temperature, ESP=20Pa, chilled water 7/12°C, ethylene glycol 0%
(**) Based on 24°C@50% air temperature, ESP=20Pa, chilled water 10/15°C, ethylene glycol 0%

42
CHILLED WATER UNITS WITH EC BACKWARD CURVED BLADE FANS

Model TDCV - TUCV 600 700 1000A 1200A 1700A 2000A


Height mm 1960 1960 1960 1960 1960 1960
Width mm 1010 1010 1310 1310 1721 2172
Depth mm 750 750 865 865 865 865
Weight kg 280 280 306 314 395 443
Chilled water flow (*) l/h 4180 4690 5750 7270 9210 11950
Chilled water flow (**) l/h 3060 3380 4420 4990 6060 8240
Electric supply voltage V 400V/3ph+N/50Hz

Model TDCV - TUCV 2500A 2700 3400 4000 4300 (only TDCV)
Height mm 1960 1960 1960 1960 2170
Width mm 2172 2170 2580 2580 2580
Depth mm 865 865 865 865 865
Weight (Complete version) (1) kg 458 502 720 740 820
Chilled water flow (*) l/h 15230 16887 19000 21680 29060
Chilled water flow (**) l/h 10740 13063 14675 16059 21220
Electric supply voltage V 400V/3ph+N/50Hz
(*) Based on 24°C@50% air temperature, ESP=20Pa, chilled water 7/12°C, ethylene glycol 0%
(**) Based on 24°C@50% air temperature, ESP=20Pa, chilled water 10/15°C, ethylene glycol 0%

Operating description

CW CHILLED WATER UNITS


The CW uses the availability of chilled water to control the room conditions.
This version of LEONARDO has a relatively simple construction and
gives outstanding reliability.
The microprocessor controls the modulating action of the 3 way (or op-
tional 2 way) chilled water valve to give accurate control.
Careful sizing of the heat exchanger coils allows a high sensible to total
cooling ratio under most operating conditions.

43
Name and description of the principle components

A User terminal
B Electrical panel door
C Cover panels
D Electrical panel
E Filters
C A F Fans
G Chilled water valve

E
D

Description of the components


A - User terminal
A1
Allows the unit to be turned on or off and the configuration
and visualization of the condition of the machine.
• A1 LCD Display A2 A5
• A2 ALARM key: visualisation and re-set of alarms; when
the alarm is activated, it flashes red. A3 A6
• A3 PRG key : access to the configuration menu
• A4 ESC key : exit from the screens A4 A7
• A5 UP key : scroll through the menu
• A6 ENTER key : confirm
• A7 DOWN key: scroll through the menu
B - Electrical panel door
Allows access to the electrical panel of the machine
44
C - Cover panels
Allow access to the internal components of the machine.

D - Electric panel
D2 • D1 Magnetothermic
- auxiliary
- heater (optional)
- humidifier (optional)
D3 - fans
• D2 Interface board
D1
D4 • D3 Dirty filter sensor
• D4 Air flow sensor
• D5 Main switch
• D6 Terminal board
• D7A Input/output electrical supply cables
• D7B Input/output electrical auxiliary cables
• D7C Input/output signal cables (RS485 and/or LAN)
D5 D6
D7B

D7A D7C

E E - Filters
F
F1 Filter the air released into the environment

F - Fans
Allow the diffusion of air into the room
• F1 ATR Transformer: allows the setting of the fan rotation
speed of the TD*R and TU*R units.

G - Chilled water valve


G • G1 Servomotor
• G2 Manual control knob
• G3 Valve stem
G1

G3
G2

H - Cooling coil

H1

45
Checks to be made on delivery Characteristics of the installation area
WARNING! Dispose of the packaging in WARNING! The unit must be installed internally
appropriate collection points. and protected from adverse conditions.
The Leonardo Evolution units are packaged in wooden crates The unit is predisposed to be installed on raised access flooring
or anchored to a pallet and covered in cardboard. using mounting frames or appropriate floor stands supplied
Check that the delivery is complete and inform the carrier of on request from Uniflair. However, the upflow units (upwards
any damage to the unit which may be attributed too careless air flow) with air intake through the rear or front can be installed
or inappropriate transportation. Check, in particular, any also on floors which are not raised.
eventual damage to the panel in which the user terminal is The area of installation must have the following characteristics:
mounted. • make sure to leave a 700mm clearence (distance D) in
Lifting and moving the unit must be carried out by a front of the unit once it has been fitted. Check that air
mechanical lifter. intake and discharge connections are not blocked in any
The following must be container within the packaging: way, not even partially;
• The Leonardo Evolution unit;
• Leonardo Use and Installation Manual;
• Leonardo unit electrical diagrams;
• Leonardo unit cooling circuit diagrams;
• Leonardo unit installation diagrams;
• List of spare parts;
• CE declaration with a list of the European standards to
which the machine must conform;
• guarantee conditions

Unloading the unit


To unload the unit from the pallet, carry out the following pro-
cedure:
• move the pallet as near as possible to where the unit is
to be installed; D
• use a ramp to avoid any damage to the unit during
unloading; • a horizontal and even floor;
• the electrical energy distribution system has been
produced in respect of CEI standards, suitable for the
characteristics of the unit;
• a cold water distribution implant (if a humidifier is to be
installed);
• implant for connection to the condensing unit;
• external air outlet (if a fresh air intake is to be installed);
• for the refrigerating gas drain see paragraph "Connection
to gas drain";
• drainage system.
WARNING! The preparation of the installation
area must be carried out as indicated in the
installation drawing attached to the machine
documentation.
• remove the blocking screws which fix the unit to the
pallet; Positioning of the unit
• carefully push the unit along the ramp until it reaches WARNING! If the surface where the unit is placed
the floor. is not even and horizontal there, is a risk of an
overflow from the condensation tray.
Installation on raised access flooring
Installation on raised access flooring occurs by means of a
mounting frame. The frame enables the installation of the
unit before the raised floor is installed, increased absorption
of noise and vibrations and the facilitation of connecting pipes
and cables.
The up flow models (upwards air flow) with rear or frontal air
intake may be installed without using the mounting frame.

46
Installation of the mounting frame Opening of the door and removal of the panels
To install the unit on raised flooring using the mounting fra-
Opening the door
me, carry out the following procedures:
To open the door of the unit carry out the following procedures:
• a flexible seal at least 5 mm thick should be fitted
• push the button and pull the handle lightly outwards;
between the raised floor panels and the mounting frame
• turn the handle downwards until the door opens.
which should also be isolated from the metallic floor
structure;
• position the unit of the mounting frame and fix it using
the M8 screw inserts found on the base of the unit.

Air conditioning unit


Removal of the front and side panels
To remove the front and side panels carry out the following
procedure:
Raised
floor • firmly hold the panel;
• lift and incline the panel outwards until it is completely
removed.
Mounting
frame

Flexible seal Flexible seal

Q.E.

Installation on flooring which is not raised


Installation on flooring which is not raised can occur without
using bases, but only on upflow models (upwards air flow)
with rear or frontal air intake. Installation on this type of floor
does not require any additional operation besides that of
normal positioning.
Installation of the floor stand
To install the unit on the floor stand carry out the following
procedures:
• position the unit on the floor stand; NOTE: After having removed the side panels, the non-
• fix the unit to the floor stand using the M8 screw inserts removable protective panel, blocks accessibility to the inside
found on the base of the unit. of the machine.
Removal of the rear panels
To remove the rear panels, carry out the following procedure:
• unscrew, using a star screwdriver, the screws which fix
basamento the panel at the top of the machine;
Base of unit
condizionatore • firmly hold the panel;
• lift and incline the panel outwards until it is completely
removed.

fixing screws
zoccolo
Floor stand
unità

Installation of discharge temperature limit probe (STM)


- optional -
To install the discharge temperature limit probe, refer to the
chapter entitled "Accessories".

47
MODELS TDCR 3400A - TDCR 4000A - TDCV 3400A - TDCV
Internal protection panels
4000A - TDCV 4300A
The technical compartment, the electric heaters and the
autotransformer fans are protected by internal protection
panels for safety reasons and to allow the opening of the
external panels without triggering the unit's safety alarms. In
the figures below the different types of internal protection
panels are shown on various types of machines.

MODELS TUCR -TUCV: 600B, 600A, 700A, 700B, 1000A,


1200A, 1700A, 2000A, 2500A, 2700A

Before removing the internal protection panels,


disconnect the power supply by turning the main isolating
switch D5 to position "O", then wait until the fans stop and
the electrical heaters cool down.

MODELS TDCR - TDCV: 600A, 600B, 700A, 700B, 1000A,


1200A, 1700A, 2000A, 2500A, 2700A

MODELS TUCR - TUCV: 3400A, 4000A

48
• refer to the wiring diagram and connect the cable to the
Electrical connections
main switch D5.
WARNING! Electrical connection to the machine
to the power supply must ONLY be carried out POWER SUPPLY CABLE
by a qualified electrician. (at customers at care)
WARNING! Electrical lines must be established
in full respect of CEI standards.
WARNING!mBefore establishing the electrical
connection, make sure that the power supply is
off. Also ensure that it is not possible to reconnect Version C
the power during the operation.
To carry out the electrical connections of the machine to the
power supply, carry out the following procedures:
• use suitable equipment to check the efficiency of the
grounding system;
• check that the voltage and network frequency POWER SUPPLY CABLE
correspond to those of the machine (see identification (at customers at care)
label);
• open the door of the electrical panel;
• remove the plastic screen of the electrical panel using a
star screwdriver; Version D-T-H

600A - 700A - 1000A - 1200A - 1700A - 2000A


• pass the cables inside using the power supply cable 2500A - 2700A - 3400A - 4000A - 4300A
inlet D7A which connects to the main switch D5;

D5 N: Neutralpole
Only with option:
D7B - condensate drain pump
POWER SUPPLY CABLE - Fresh air fan motor
D7A (at customers at care)

49
To connect the auxiliary connections to the terminal board
Connection to the water drain
carry out the following procedures:
Condensation water drains from the tray by
• pass the cables through the power supply cable inlet
means of a flexible siphoned tube, which is fitted in the unit.
D7B;
If the unit is fitted with a humidifier, the condensate drain tray
and the humidifier drain connection must be connected to
the drains of the building.
Direct connection to the drains of the building
D5 Connect the drainage tube of the unit to the drains of the
building using a rubber or plastic tube with an internal diameter
D7B of 25 mm.
The external drainage tube must be siphoned in order to avoid
D7A unpleasant odours. Maintain a minimum slope of 1%
• refer to the wiring diagram and carry out the connection
downstream of the siphon.
to the terminal board.

Drain

Minimum slope
20
20
20
20

50
51
52
60
%
Siphon

DIGITAL CONFIGURABLE INPUTS


Once the connections have been made, pour water into the
Terminal board 51-20 condensate collection tray until the siphons have been filled.
- User
- ON - OFF Remote
- Flooding sensor (SAS)
Terminal board 52-20 Connection of the humidifier (additional fitting) and to
- User the storm sewer system
- ON-OFF Remote WARNING! The water discharged from the humidifier
- Fire-smoke (SFF) is at a very high temperature. The drainage tube has
Terminal board 50-20 to withstand high temperatures (at least 100°C) and
- User must be kept away from electrical cables.
- ON-OFF Remote
Connect the drainage tube of the unit to the collection tray
- Tools (ATA-BTA-AUA-BUA)
(U4) of the humidifier.
Terminal board 60-20
Connect the drainage tube of the humidifier (U7) to the drains
- Summer-Winter remote
of the building using a rubber or plastic tube, which is resistant
- Water flow meter
to high temperatures (minimum 100 °C) with an internal
diameter of 22 mm.

U4
U7

The external drainage tube must be siphoned to avoid


unpleasant odours and an overflow of the water from the tray
of the humidifier.

50
Maintain a minimum slope of 1% downstream of the siphon.
Filling the hydraulic circuit
Drain WARNING! The water used to fill the hydraulic
circuit must be filtered.
WARNING! Filling the hydraulic circuit must only
Minimum slope be carried out exclusively by a qualified
hydraulic technician.
%
Siphon WARNING! Before carrying out any type of
intervention, disconnect the power supply.

Filling the primary circuit


WARNING! The primary circuits must be
Once the connections have been made, pour water into the equipped with mechanical filters.
condensate collection tray of the Leonardo unit and in the
condensate collection tray of the humidifier until both siphons WARNING! Check that all of the shut off valves
are full. are closed.
Open the drain valve of the primary circuit and regulate the
pressure switch to 5 bar;
bleed the air from the circuits;
Hydraulic connections turn on the primary circulation pumps;
For all hydraulic connections (except for the condensate drain) clean the circuits leaving the pumps on; check for any loss
it is recommended to use the following: from the primary circuits.
- flexible hoses to avoid the transmission of vibrations and
to allow the unit to be moved; Filling the hydraulic circuits of the conditioners
- three piece joints near the connections; WARNING! Clean the primary circuits before
- shut off valves to isolate the unit from the water circuit: if filling the conditioners.
possible, use full sphere valves to minimise the pressure
WARNING! Check that all of the bleeding valves
drop.
on the conditioners are closed.
Check that the chilled water pipe sizes and the circulating
pump characteristics are adequate: an insufficient water Open the shut off valves of the conditioner;
flow affects the performance of the unit. Open the bleeding valve (on the upper part of the cooling
Check that the water flow directions are respected. coil) and wait for the water to come out.
Insulate all of the chilled water pipes with closed cell insulating
material (e.g.: Armaflex or equivalent) to avoid condensation;
the insulation must allow accessibility to the valves and three
piece joints.
Check that the hydraulic circuits (both chilled and hot water)
are fed with a maximum water pressure of 6 bar: to this
purpose the installer must install a safety valve in the hydraulic
with a set point of not more than 6 bar.
The minimum and maximum water temperatures inside the
unit (for the chilled water circuit and the post- heating with
hot water) are: 5°C ÷ 90°C.
The maximum amount of ethylene glycol is 50%.

INLET

OUTLET

51
MANUAL START UP AND SHUT DOWN OF • check that the tracts of corrugated pipe with siphon,
THE UNIT both internal and external to the conditioner, have been
filled with water in the installation phase;
WARNING! Check that the refrigerant circuit has
• close the door and the front panels;
been filled
• press the ENTER key (A6) of the user terminal; a sliding
To start up the unit carry out the following procedure: bar and a ventilator icon will appear on the display;
• open the door of the electrical panel and the front
panels;
• position the automatic switch of the auxiliary circuit to
"I" (on);
• position all of the automatic switches on the electrical
board to "I" (on); A1

A2 A5

A3 A6

A4 A7

• if an alarm is indicated, consult the user interface


manual UG40;
• check the rotation direction of the fans; the correct
direction is indicated with an arrow which is on the fan
itself. If the rotation is in the wrong direction, invert two
• fuel the unit by positioning the main switch of the three power supply phases following the
to "I" (on); instructions indicated in the paragraph entitled "Electrical
connections" and then restart the start-up procedure

D5

To turn the unit off, carry out the following procedure:


• on the first screen of the user terminal, press the A5 or
A7 buttons until the SWITCH OFF UNIT screen appears;
• press the ENTER button to confirm;
• the following icons will appear
OFF

Press the ENTER button to confirm

52
SETTING AND ADJUSTMENT
TDCR/TUCR 0600
Selecting the power supply of the fans FA[m3/h=] 4310 4500 5000 5500 5990 6600
WARNING! Before establishing the electrical % V Pa
connection, make sure that the power supply is
40 142 68 56 20 - - -
off. Also ensure that it is not possible to
reconnect the power during the operation. 50 168 139 124 77 23 - -
55 180 179 162 111 52 - -
WARNING! In the case of a unit with ducts, the
load loss from the exhaust duct must be less than 60 195 237 217 160 94 25 -
100 Pa. 70 215 333 309 240 164 84 -
In the following table the voltage levels for each model working 80 222 373 347 274 193 108 -
in the standard version are given. 90 227 401 374 298 214 126 5
100 230 424 396 317 231 140 20
Models V
0600 190
0700 195
1000 - 2000 310
1200 340 TDCR/TUCR 0700
1700 260 FA[m3/h=] 4280 4500 5000 5500 6060 6500
TD C R - TU C R
2500 320 % V Pa
2700 340
40 142 68 54 15 - - -
3400 280
50 168 140 122 75 21 - -
4000 300
55 180 180 160 109 50 - -
4300 380
60 195 238 216 158 92 20 -
70 215 335 307 238 162 67 -
HOW TO ADJUST FAN SPEED 80 222 375 346 272 191 91 20
In the TD*R three phase models the rotation speed of the 90 227 403 373 296 212 108 24
fans be varied by using the ATR transformer (F1). 100 230 427 395 315 228 122 35

F1

TDCR/TUCR 1000
FA[m3/h=] 5700 7000 8000 9000 10200 11440
V Pa
230 129 73 14 - - -
250 181 124 65 - - -
260 206 150 91 8 - -
270 232 175 117 34 - -
280 257 201 142 59 - -
To obtain the required prevalence of the implant, it is possible
to vary the voltage by selecting one of the following levels, 290 283 226 168 85 - -
suitable for models from 0600 to 0700: 300 309 252 194 111 - -
140V -160V -180V -190V -200V -210V -220V -230V 310 334 278 219 136 - -
models from 1000 to 2700: 320 360 303 245 162 20 -
230V - 250V - 260V - 270V - 280V - 290V - 300V - 310V -
340 411 355 296 213 69 -
320V - 340V - 360V - 380V - 400V.
models 3400 - 4000 - 4300: 360 462 406 347 264 121 -
150V - 180V - 200V - 230V - 240V - 260V - 280V - 300V - 380 514 457 399 316 172 -
320V - 340V - 360V - 380V - 400V. 400 565 508 450 367 223 20
In the following table the maximum pressure available
(expressed in Pa) for each voltage level of the transformer is
indicated. The values are given for the maximum air flow
(expressed in m3/h).

53
TDCR/TUCR 1200 TDCR/TUCR 2500
FA[m3/h=] 5700 7000 8000 9000 10200 11440 FA[m3/h=] 10000 12000 16000 18680 19500 20570
V Pa V Pa
230 123 64 3 - - - 230 58 20 - - - -
250 174 115 54 - - - 250 117 59 - - - -
260 200 141 80 - - - 260 147 89 - - - -
270 225 166 105 20 - - 270 176 118 - - - -
280 251 192 131 46 - - 280 205 147 20 - - -
290 277 218 157 71 - - 290 235 177 60 - - -
300 302 243 182 97 - - 300 264 206 94 - - -
310 328 269 208 123 - - 310 294 236 124 - - -
320 354 294 234 148 - - 320 323 265 153 - - -
340 405 346 285 199 20 - 340 382 324 212 20 - -
360 456 397 336 251 71 - 360 441 383 271 88 20 -
380 507 448 387 302 122 20 380 500 442 330 157 80 -
400 559 499 439 353 189 56 400 579 523 379 205 137 20

TDCR/TUCR 1700 TDCR/TUCR 2700


FA[m3/h=] 7800 9000 11000 14920 17000 19380 FA[m3/h=] 13530 16030 17000 18725 19000 19500 20650
V Pa
V Pa
230 - - - - - - -
230 125 70 - - - -
250 22 - - - - - -
250 184 129 68 - - -
260 54 - - - - - -
260 213 159 90 - - - 270 87 - - - - - -
270 243 188 119 - - - 280 119 6 - - - - -
280 272 217 149 - - - 290 150 35 - - - - -
290 301 247 178 20 - - 300 181 63 14 - - - -
300 321 276 208 60 - - 310 210 91 41 - - - -
320 238 118 67 - - - -
310 360 306 237 93 - -
340 290 168 117 20 4 - -
320 390 335 267 152 - -
360 338 214 162 64 48 17 -
340 449 394 326 211 50 -
380 380 256 204 105 88 57 -
360 507 453 384 270 109 - 400 418 294 242 142 125 94 20
380 566 512 443 300 168 -
400 611 569 503 352 230 20

TDCR/TUCR 2000 TDCR/TUCR 3400


3
FA[m /h=] 10000 12000 15000 18680 19500 20810 FA[m3/h=] 15300 19000 23000 24777 26000 28000 28520
V Pa
V Pa
150 - - - - - - -
230 80 40 - - - -
180 55 - - - - - -
250 140 91 - - - -
200 131 3 - - - - -
260 170 120 30 - - - 230 235 103 - - - - -
270 200 150 55 - - - 240 267 134 - - - - -
280 277 180 91 - - - 260 327 191 45 - - - -
290 259 217 116 - - - 280 381 244 90 20 - - -

300 289 250 145 - - - 300 430 291 131 57 5 - -


320 473 333 168 91 36 - -
310 317 275 176 - - -
340 511 370 202 122 66 - -
320 349 335 203 - - -
360 544 402 232 151 94 - -
340 390 394 266 20 - - 380 571 429 259 178 120 21 -
360 449 453 324 115 46 - 400 592 451 282 201 144 46 20
380 508 512 381 173 106 -
400 580 533 440 232 162 20

54
TDCR/TUCR 4000 After having selected the voltage level, carry out the connection
FA[m3/h=] 15940 19000 23000 25200 26500 27500 28100 in the following way:
V Pa • with the unit turned off, open the front panels and the
150 - - - - - - - door of the electrical panel and the internal protection
180 20 - - - - - -
panels;
• select the supply voltage by positioning the main switch
200 96 - - - - - -
to "0" (D5);
230 200 89 - - - - -
• Follow the diagrams displayed below and refer to the
240 232 120 - - - - -
wiring diagram enclosed to connect the two electric wires
260 292 177 28 - - - -
found on the fan, or on the connector block, to the
280 346 230 73 - - - - corresponding terminals on the autotransformer
300 395 277 114 20 - - -
320 439 319 151 53 - - - MODELS MODELS MODELS
340 477 356 185 84 22 - - from 0600 to 0700 from1000to 2700 from 3400 to 4300
360 509 388 215 112 49 - -
380 536 415 242 139 75 25 - ATR1 ATR2

400 227 437 265 162 99 50 20   


&?

@
>
?
ATR1 ATR2

!  !
TDCR/TUCR 4300 &!?

@
>
?
3
FA[m /h=] 15940 19000 23000 25200 26500 27500 28100
ATR1 ATR2
V Pa   
&?

@
>
?
150 - - - - - - -
ATR1 ATR2
180 20 - - - - - -
  
200 96 - - - - - - &?

@
>
?
230 200 79 - - - - - ATR1 ATR2

  
240 232 109 - - - - - &?

@
>
?
260 291 165 24 - - - -
ATR1 ATR2
280 346 216 66 - - - -   
&?
300 394 262 105 2 - - -

@
>
?
320 438 303 140 32 - - - ATR1 ATR2

!  !
340 476 340 173 61 14 - - &!?

@
>
?
360 508 372 202 88 40 - - ATR1 ATR2

380 535 399 229 114 66 20 -   


&?

@
>
?
400 556 421 252 138 91 45 20
ATR1 ATR2

  
&?

@
>
?
ATR1 ATR2

  
&?

@
>
?

ATR1 ATR2

  
&?
@
>
?

ATR1 ATR2

!  !
&!?
@
>
?

ATR1 ATR2

  
&?
@
>
?

55
MODELS WITH FANS CARRYING A CE MARKING
To reach the head required by the system for conditioners with fans carrying a CE marking, the imput voltage percentage
can be adjusted from the user terminal (A).
To select the voltage, carry out the following procedure:
• on the user terminal press the PRG button;
• using the UP or DOWN key select SERVICE MENU and confirm using the ENTER key;
• enter the password (see the envelope attached to the manual);
• using the UP or DOWN key select HARDWARE SETTING and confirm using the ENTER key;
• using the UP or DOWN key select EVAPORATING FAN and confirm using the ENTER key;
• set the amount and confirm using the ENTER key.
In the following table the maximum pressure available (expressed in Pa) for each voltage level of the transformer is indicated.
The values are given for the maximum air flow (expressed in m3/h).

TDCV/TUCV 600 TDCV/TUCV 1200


3
3
FA[m /h=] 4350 5000 5990 6500 7000 8000 FA[m /h=] 5900 7000 8000 10000 11000 11740
% V Pa % V Pa
50 400 90 - - - - - 50 400 21 - - - - -
55 400 170 80 - - - - 55 400 81 - - - - -
60 400 250 170 20 - - - 60 400 145 38 - - - -
65 400 330 260 127 30 - - 65 400 212 113 - - - -
70 400 410 340 217 137 50 - 70 400 284 192 79 - - -
78 400 530 480 359 290 152 20 75 400 361 274 167 - - -
80 400 560 503 389 331 205 72 80 400 441 359 258 - - -
85 400 634 573 465 398 327 151 85 400 526 448 351 58 - -
90 400 704 653 549 480 411 240 90 400 614 540 446 163 - -
95 400 790 728 612 551 473 314 95 400 707 634 543 268 74 -
100 400 857 793 679 614 543 382 100 400 804 732 643 374 184 20

TDCV/TUCV 700 TDCV/TUCV 1700


FA[m3/h=] 4350 5000 6060 6500 7000 8000 FA[m3/h=] 9790 11000 12000 14000 16000 20180
% V Pa % V Pa
50 400 80 - - - - - 50 400 20 - - - - -
55 400 160 70 - - - - 55 400 69 - - - - -
60 400 240 160 10 - - - 60 400 125 55 - - - -
65 400 320 250 117 20 - - 65 400 186 120 63 - - -
70 400 400 330 207 127 40 - 70 400 252 189 135 4 - -
78 400 520 470 349 280 142 10 75 400 323 264 212 86 - -
80 400 550 493 379 321 195 62 80 400 400 343 293 171 20 -
85 400 624 563 455 388 317 141 85 400 481 426 378 260 110 -
90 400 694 643 539 470 401 230 90 400 568 514 467 352 205 -
95 400 780 718 602 541 463 304 95 400 660 606 560 446 302 -
100 400 847 783 669 604 533 372 100 400 757 703 657 555 402 21

TDCV/TUCV 1000 TDCV/TUCV 2000


3 3
FA[m /h=] 5700 7000 8000 10000 11000 11830 FA[m /h=] 11090 12000 14000 16000 18680 21600
% V Pa % V Pa
50 400 47 - - - - - 50 400 0 - - - - -
55 400 105 - - - - - 55 400 60 - - - - -
60 400 167 47 - - - - 60 400 118 80 - - - -
65 400 233 122 4 - - - 65 400 181 117 - - - -
70 400 304 201 90 - - - 70 400 250 190 75 - - -
75 400 380 283 178 - - - 75 400 335 267 157 59 - -
80 400 459 368 269 - - - 80 400 420 348 242 153 - -
85 400 543 457 362 75 - - 85 400 508 432 331 250 22 -
90 400 631 549 457 180 - - 90 400 595 521 422 345 130 -
95 400 724 643 555 285 94 - 95 400 687 614 517 445 240 -
100 400 821 741 654 391 204 20 100 400 784 724 615 525 325 20
56
TDCV/TUCV 2500 TDCV/TUCV 4000
FA[m /h=] 3
10540 12000 14000 16000 18680 21350 FA[m3/h=] 16570 19000 23000 25217 2700 28500 31920
% V Pa
% V Pa
55 400 20 - - - - - -
50 400 20 - - - - -
60 400 80 - - - - - -
55 400 80 0 - - - -
65 400 146 64 - - - - -
60 400 140 70 - - - - 70 400 216 139 - - - - -
65 400 202 137 14 - - - 75 400 290 217 58 - - - -
70 400 269 205 95 - - - 79 400 353 282 129 20 - -
75 400 341 280 175 41 - - 80 400 369 299 147 39 - - -
80 400 419 337 258 136 - - 82 400 418 350 201 95 - - -
85 400 452 385 238 133 36 - -
85 400 501 422 347 234 - -
90 400 540 475 332 230 135 45 -
90 400 587 511 448 324 90 -
95 400 632 568 428 329 236 148 -
95 400 679 604 543 4 24 200 -
100 400 729 665 527 429 338 252 20
100 400 763 712 621 504 280 20

TDCV/TUCV 2700 T D C V 4300


3
FA[m /h=] 12350 15000 17500 18761 19500 21000 22420 FA[m3/h=] 17100 19000 23000 25217 29600 30000 32620

% V Pa % V Pa

55 400 20 - - - - - - 55 400 20 - - - - - -

60 400 86 - - - - - - 60 400 82 16 - - - - -

65 400 155 4 - - - - - 65 400 149 87 - - - - -

70 400 229 86 - - - - - 70 400 220 162 3 - - - -

75 400 306 171 - - - - - 75 400 295 240 89 - -- - -

78 400 355 224 50 - - - 79 400 358 305 160 56 - -

80 400 388 259 88 - - - - 80 400 374 322 178 75 - - -

82 400 421 295 126 20 - - - 82 400 424 373 232 131 - - -

85 400 473 349 184 80 12 - - 85 400 458 408 269 169 - - -

90 400 562 443 282 181 115 - - 90 400 546 498 363 266 20 - -

95 400 655 539 38 2 284 219 71 - 95 400 639 591 459 365 124 98 -

100 400 752 637 484 387 324 179 20 100 400 735 688 558 465 229 204 20

Setting the regulation and safety devices


TDCV/TUCV 3400 After starting up the conditioner, set the following set points
FA[m3/h=] 16900 18500 21500 24875 26500 28000 32250 (see Microprocessor Control Manual):
% V Pa • Room temperature (cooling and heating set point);
55 400 20 - - - - - - • Relative room humidity (humidification and
60 400 82 26 - - - - - dehumidification set point);
65 400 148 96 - - - - - • Dirty filter differential pressure switch: see paragraph
70 400 218 169 57 - - - - "Setting the dirty filter sensor".
75 400 295 247 140 - - - - The settings of the safety devices must not be modified.
77 400 324 279 174 20 - - C ode Description Opening Differential Re-set
80 400 372 328 226 76 - - - Safety thermostat 310 °C Manual
TSR -
83 400 422 379 279 132 46 - - (T and H versions) (opening) reset
85 400 456 413 315 170 85 - - Safety thermostat 328 °C Manual
TSRA -
90 400 544 503 407 266 183 98 -
(T and H versions) (opening) reset

95 400 636 596 202 364 284 200 -


100 400 733 693 600 464 385 303 20

57
Setting the air flow sensor MAINTENANCE
The FS differential pressure switch intervenes if the fan (or Three-monthly checks
one of the fans) stops working.
Carry out the following checks every three months:
The factory set point of the FS differential pressure switch is
• check the power supply;
at 0.5 mbar (= 50Pa).
• check the alarm status;
As the difference in pressure between the suction and
• check the working temperatures;
discharge of the fans depends on the air flow, it may be
• check the correct operation of the local/remote controls;
necessary to set the instruments after installation, checking
• check the air filters, cleaning and replacing them if
that the contact closes when the fans are in operation.
necessary;
To set the FS pressure switch, carry out the following proce-
• check the efficiency of the condensing drain;
dure:
• check the steam cylinder is clean, replacing it if
• simulate a fan fault by stopping a fan; check that the
necessary (see pag.78).
pressure switch intervenes;
• if the pressure switch does not intervene, gradually Six-monthly checks
increase the setting until the pressure switch switches Carry out the following checks every six months:
off: • repeat these checks on a three-monthly basis;
- using an adjustment screw, set the differential pressure • check and clean if necessary the cooling coil;
switch on a scale from 0.5 to 4.0 mbar (from 50 to 400 • check the operation of the humidifier (if present: see
Pa). pag.78).

Annual checks
Carry out the following checks annually:
• repeat these checks on a six-monthly basis;
• check the varnish and the nuts and bolts
• check the hinges, rabbets and gaskets
• check the cables and wiring
• tighten the terminal blocks
• check and reset if necessary the safety device settings
(pressure switches, thermostats, protection devices);
• check the operation of the post heating electrical heaters;
• check the fittings, operation and absorption of the fan/s
motor;
• check and if necessary reset the regulation devices
Setting the dirty filter sensors setting;
• check and if necessary replace the seal of the hydraulic
The PFS differential pressure switch is set according to the
circuits/s and tighten the unit couplings;
loss of load dependent on the dirt inside the filters and the air
• check and reset if necessary the water regulation valve/
flow.
valves setting.
The PFS differential pressure switch must be set at 3 mbar
(=300 Pa).
To set the PFS pressure switch, carry out the following pro-
cedure:
• gradually cover the surface of the air filter and check
that the pressure switch intervenes when the filter is about
50-60 % covered;
• if the pressure switch does not intervene, gradually lower
the setting, if it cuts in too soon, increase the setting:
- using a star screw driver, turn the regulation screws of
the pressure switch to the desired value.

58
MODELS WITH HIGH INTAKE (MOD. TDCR - TDCV:
Cleaning and replacing the filters
3400, 4000, 4300)
To clean and replace the filters carry out the following proce-
• remove the filter blocking supports;
dure:
• remove the filters checking the direction of the air flow
• open the front panels of the machine;
indicated with a sticker on each filter;
MODELS WITH REAR AIR INTAKE
• clean them using a blast of compressed air or replace
• follow the instructions below and check the direction of
them;
the air flow indicated with a sticker on each filter;
• reposition the filters in the unit checking the direction of
theair flow which was previously noted;

• clean them using a blast of compressed air or replace


them;
• reposition the filters in the unit checking the direction of
the air flow which was previously noted.

OTHER MODELS
• remove the filter blocking supports;

• remove the filters checking the direction of the air flow


indicated with a sticker on each filter;

• clean them using a blast of compressed air or replace


them;
• reposition the filters in the unit checking the direction of
theair flow which was previously noted;
• reposition the filter blocking supports.

59
Servomotor and chilled water valve
If necessary (in the event of a fault in the servomotor or the
control system) manually move the valve as described below:
• pull the manual control knob (G2);
• turn the knob clockwise to lower the valve stem (G3)
(OPEN) and anti-clockwise to raise the valve stem (G3)
(CLOSE).

G4

G1

G3
G2

In the 600 and 700 models the following servomotor is installed:

To manually move the valve, use the hexagonal key and screw
to open and unscrew to close.

Alternatively, it is possible to remove the servomotor from the


body of the valve and move the valve stem itself.

Servomotor and hot water valve


To manually move the valve by turning the control knob
clockwise to open and anti-clockwise to close.

Alternatively, it is possible to remove the servomotor from the


body of the valve and move the valve stem itself.

60
Troubleshooting
Troubleshooting is made easier by the indications on the control panel display: when an alarm signal is displayed, consult
the control panel instruction manual. If necessary, call the nearest Service Centre describing the nature of the fault and its
possible cause displayed on the control.

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION


Check that the power is on and the unit main switch on the
A) No power supply to the unit's electrical panel.
electrical panel is closed.
1) Check that the IM automatic circuit breaker on the AUX
THE UNIT DOES NOT
B) No power to the auxiliary circuits. circuit is set.
START
2) Check the fuse on the main board.
Check that the control panel connectors are correctly located
C) The control panel does not start the unit.
in their sockets.

TEMPERATURE CONTROL

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) The parameter settings on the control panel


See control panel instruction manual
are not correct.
B) The air flow is low or absent. See "LACK OF / ABSENT AIR FLOW".
Check the electrical connections and the control
C) The temperature sensor is not working.
configuration.
D) The thermal load is higher than expected. Check the room's thermal load.
THE ROOM Check the electrical connections of the servomotor
TEMPERATURE IS TOO valve.
E) The three-way valve is not working.
HIGH Open the valve by means of the manual control
knob.
Check the chilled water supply; check that the
E) Valvola a tre vie non funzionante.
shut-off valves are open.
F) There is an insufficient chilled water flow. Check the chilled water funtion.
See "THE COMPRESSOR(S) DOESN'T / DON'T
G) The chilled water temperature is too high.
WORK".
A) The parameter settings on the control are not
See the microprocessor control manual.
correct
1) Check that the IM of the heating element is
armed.
B) There is insufficient power supply to the elcttric 2) Check the electric feeding circuit of the
heaters or the heaters are not working heaters.
3) If there is a heater alarm, remove the cause and
re-set the safety thermostat.
ROOM TEMPERATURE
1) Check the hot water capacity and temperature.
TOO LOW
C) The hot water coil is not working. 2) Check the function of the regulation valve (see
valve and servomotor).
1) Check the hot gas 3 way valve function.
D) The hot gas coil is not working during 2) Check the function of the compressor serving
dehumidification with re-heat. the re-heat. See "THE COMPRESSOR(S)
DOESN'T / DON'T WORK".
E) The three way valve of the chilled water circuit Close the valve using the manual control knob and
is blocked open. replace the servomotor.

61
HUMIDITY CONTROL

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) The parameter settings on the control panel


See control panel instruction manual.
are not correct.
Check the latent load, fresh air conditions and
B) The latent load is higher then expected.
volume; external air infiltration.
Check the feeding solenoid valve of the
C) Dehumidification valve not shutting.
ROOM HUMIDITY TOO dehumidification circuit is working properly.
HIGH See: Control system user instruction manual;
D) Control system not working. check the panel and/or the probe are working
properly.
E) The chilled water is not sufficiently cold for the
Lower the chilled water temperature until
dehumidification function (in energy saving and
condensate is present on the surface of the coil.
twin cool units).
A) The parameter settings on the control panel Check the room humidity settings (see control
are not correct. panel instruction manual).
Check the latent load, fresh air conditions and
B) The latent load is lower than expected.
volume; external air infiltration.
1) Check the water supply pressure.
ROOM HUMIDITY TOO
2) Check the function of the manual control system
LOW C) The humidifier doesn't work.
and of the steam production group (see panel
instruction manual).
See the control panel instruction manual; check
D) The control system does not work. that the control panel and/or sensors work
properly.

FANS

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) There is no power to the fans. Check the power supply to the fans
1) Shake the dust out of the cartridge and clean
with a vacuum cleaner. Replace the filter if it is
completely blocked.
B) The air filters are clogged (dirty filter alarm
enabled).
2) Check the correct setting of the dirty filter
pressure switch PFS.

Reverse input phases and check if fans are


C) Fans rotating in the wrong direction.
rotating in the correct direction
ABSENT OR LOW AIR D) The air flow is obstructed. Check paragraph "AIR DISTRIBUTION"
FLOW Check the resistance of the fan motor windings.
E) The fans' thermal protection intervenes.
Re-set then measure the voltage and absorption.
See paragraph FAN SPEED ADJUSTMENT AND
F) Fan speed regulator not set correctly.
SPEED REGULATOR SETTING.
1) Check the dimensioning of the air distribution
system, as well as all its parts (ducts, suspended
ceilings, floor plenum, air grilles)
G) Excessive head loss in the air distribution sistem. 2) (For TDCR and TUCR models - having fans
with backward curved blades) change the power
supply voltage of the fans, in order to increase the
fan rotation speed.

ELECTRIC HEATERS

PROBLEM POSSIBLE CAUSE CHECK/CORRECTIVE ACTION

A) There is insufficient air flow. See "LACK OF / ABSENT AIR FLOW".


ELECTRIC HEATER SAFETY Check the connection between the safety
B) The thermostat connection wire is interrupted
THERMOSTAT INTERVENES thermostat and the control system.
C) The thermostat is faulty. Replace the thermostat.

62
LEONARDO EVOLUTION ENERGY SAVING
Technical characteristics
ENERGY SAVING UNIT WITH BACKWARD CURVED BLADE FANS
Model TDER - TUER 511A 611A 721A 722A 921A 922A 1021A 1022A
Height mm 1960 1960 1960 1960 1960 1960 1960 1960
Width mm 1010 1010 1310 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865 865
Weight kg 280 310 430 447 430 447 430 447
Number of refrigerating circuits 1 1 1 2 1 2 1 2
Number of compressors 1 1 2 2 2 2 2 2
Electric supply voltage V 400V/3ph+N/50Hz

Model TDER - TUER 1121A 1122A 1321A 1322A 1422A 1622A 1822A
Height mm 1960 1960 1960 1960 1960 1960 1960
Width mm 1720 1720 1720 1720 2171 2171 2171
Depth mm 865 865 865 865 865 865 865
Weight kg 548 559 575 585 698 714 714
Number of refrigerating circuits 1 2 1 2 2 2 2
Number of compressors 2 2 2 2 2 2 2
Electric supply voltage V 400V/3ph+N/50Hz

Model TDER 2242 2542 2842


Height mm 2175 2175 2175
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 996 1020 1120
Number of refrigerant circuits 2 2 2
Number of compressors 4 4 4
Power supply voltage V 400V/3ph+N/50Hz

Model TUER 2242 2542 2842


Height mm 1960 1960 1960
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 996 1020 1120
Number of refrigerant circuits 2 2 2
Number of compressors 4 4 4
Power supply voltage V 400V/3ph+N/50Hz

ENERGY SAVING UNIT WITH EC BACKWARD CURVED BLADE FANS

Model TDEV - TUEV 511 611 721 722 921 922 1021 1022
Height mm 1960 1960 1960 1960 1960 1960 1960 1960
Width mm 1010 1010 1310 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865 865
Weight kg 280 280 430 447 430 447 430 447
Number of refrigerating circuits 1 1 1 2 1 2 1 2
Number of compressors 1 1 2 2 2 2 2 2
Electric supply voltage V 400V/3ph+N/50Hz

Model TDEV - TUEV 1121 1122 1321 1322 1422 1622 1822
Height mm 1960 1960 1960 1960 1960 1960 1960
Width mm 1720 1720 1720 1720 2171 2171 2171
Depth mm 865 865 865 865 865 865 865
Weight kg 548 559 575 585 698 714 714
Number of refrigerating circuits 1 2 1 2 2 2 2
Number of compressors 2 2 2 2 2 2 2
Electric supply voltage V 400V/3ph+N/50Hz

63
Model TDEV 2242 2542 2842
Height mm 2175 2175 2175
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 996 1020 1120
Number of refrigerant circuits 2 2 2
Number of compressors 4 4 4
Power supply voltage V 400V/3ph+N/50Hz

Model TUEV 2242 2542 2842


Height mm 1960 1960 1960
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 996 1020 1120
Number of refrigerant circuits 2 2 2
Number of compressors 4 4 4
Power supply voltage V 400V/3ph+N/50Hz

Operating description

ENERGY SAVING
LEONARDO Energy -Saving units represent the ultimate energy saving
efficient solution.
The operating principle exploits the "free cooling" effect available when
the outside air temperature is lower than that in the conditioned space.
The lower the outside temperature, the greater the energy saving is.
The sophisticated microprocessor control manages the operation of the
unit automatically in three different situations.
In summer, the unit operates as a normal closed circuit glycol cooled
system (see the "Direct Expansion Operation" diagram). As the external
temperature falls, the chilled water can be used directly for the free- Direct expansion operation
cooling of the air. In this case the cold water is circulated in the coil
inside the unit (see the "Mixed cooling operation" diagram); both the
glycol circuit and the chilled water circuit contribute to the cooling,
therefore reducing the energy used by the compressor. If the outside
temperature falls further to a level where the coolant can dissipate the
entire heat load from the room then the refrigerant circuit is shut down
completely and the unit functions as a traditional chilled water unit with
a regulating valve (see the "Free-cooling operation" diagram).
With this technology, LEONARDO Energy-Saving units provide significant
reductions in operating costs and notably reduce the depreciation time
of the units.

Mixed cooling operation

Free cooling operation


64
Name and description of the principle parts

A User terminal
B Electric panel door
C Cover panels
D Electrical panel
E Filters
C A F Fans
G Cooling circuit

MODELS TD./ TU. 511 ÷ 1822

E
D

H
G

MODELS TD./ TU. 2222 ÷ 2842

65
A1 Description of the components
A - User terminal
Allows the unit to be turned on or off and the configuration
A2 A5 and visualization of the condition of the machine.
• A1 Display LCD
A3 A6 • A2 ALARM key: visualization and re-set of alarms;
when the alarm is activated it flashes red.
A4 A7 • A3 PRG key: access to the configuration menu
• A4 ESC key: exit from the screens
• A5 UP key: scroll through the menu
• A6 ENTER key: confirm
MODELS TD./ TU. 511 ÷ 1822 • A7 DOWN key: scroll through the menu

B - Electrical panel door


Allows access to the electrical panel of the machine.
C - Cover panels
Allow access to the internal components of the machine
D - Electrical panel
D2 • D1 Magnetothermic
- auxiliary
- heater (optional)
- humidifier (optional)
D1 D3 - fans
- compressors
D4 • D2 Interface board
• D3 Dirty filter sensor
• D4 Air flow sensor
• D5 Main switch
• D6 Terminal board
• D7A Input/output electrical supply cables
D8
• D7B Input/output electrical auxiliary cables
D5 D6 • D7C Input/output signal cables (RS485 and/or LAN)
D7B • D8 Phase sequence relay
• D9 Maximum pressure manostat (only for mod. TD.
D7A D7C 2222 ÷ 2842)

MODELS TD./ TU. 2222 ÷ 2842


D2 D1 D4 D3 D9

D7D D8 D5 D7A D7C D7B D6

E - Filters
E F Filter the air released into the room,

F - Fans
F1 Allow the diffusion of air into the room.
• F1 ATR transformer: allows the setting of the fan rotation
speed

66
G3 G2 G1 G - Cooling circuit
• G1 Compressor
• G2 High pressure switch
• G3 Schrader valve

• G4 Safety valve
• G5 Liquid receiver
• G6 Dehydrating filter
• G7 Flow sight glass
G8 • G8 Electronic thermostatic valve
G9 • G9 Brazed plate exchanger

G7

G4 G5 G6

• G10 Evaporating coil

G10

H - Chilled water valve


H • H1 Servomotor
• H2 Manual control knob
• H3 Valve stem
H1

H3
H2

67
I I - Room temperature and humidity sensor

Installation and maintenance of the Energy Saving units should be carried out as described in the DIRECT
EXPANSION section. For the water circuit, follow the instructions in the CHILLED WATER section.

68
LEONARDO EVOLUTION TWIN-COOL
Technical characteristics
TWIN COOL UNIT WITH BACKWARD CURVED BALDE FANS
Model TDTR - TUTR - TDDR - TUDR 611 921 1321 1622 1822
Height mm 1960 1960 1960 1960 1960
Width mm 1010 1310 1720 2171 2171
Depth mm 750 865 865 865 865
Weight kg 310 430 575 714 714
Number of refrigerating circuits 1 1 1 2 2
Number of compressors 1 2 2 2 2
Electric supply voltage V 400V/3ph+N/50Hz

Model TDTR 2242 2542 2842


Height mm 2175 2175 2175
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 910 930 1040
Number of refrigerating circuits 2 2 2
Number of compressors 4 4 4
Electric supply voltage V 400V / 3Ph + N / 50Hz

Model TDDR 2242 2542 2842


Height mm 2175 2175 2175
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 996 1020 1120
Number of refrigerating circuits 2 2 2
Number of compressors 4 4 4
Electric supply voltage V 400V / 3Ph + N / 50Hz

Model TUTR 2242 2542 2842


Height mm 1960 1960 1960
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 910 930 1040
Number of refrigerating circuits 2 2 2
Number of compressors 4 4 4
Electric supply voltage V 400V / 3Ph + N / 50Hz

Model TUDR 2242 2542 2842


Height mm 1960 1960 1960
Width mm 2580 2580 2580
D eph mm 865 865 865
Weight kg 996 1020 1120
Number of refrigerating circuits 2 2 2
Number of compressors 4 4 4
Electric supply voltage V 400V / 3Ph + N / 50Hz

69
TWIN COOL UNIT WITH EC BACKWARD CURVED BLADE FANS

Model TDTV - TUTV - TDDV - TUDV 611 921 1321 1622 1822
Height mm 1960 1960 1960 1960 1960
Width mm 1010 1310 1720 2171 2171
Depth mm 750 865 865 865 865
Weight kg 280 430 575 714 714
Number of refrigerating circuits 1 1 1 2 2
Number of compressors 1 2 2 2 2
Electric supply voltage V 400V/3ph+N/50Hz

Model TDTV 2242 2542 2842


Height mm 2175 2175 2175
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 910 930 1040
Number of refrigerating circuits 2 2 2
Number of compressors 4 4 4
Electric supply voltage V 400V / 3Ph + N / 50Hz

Model TDDV 2242 2542 2842


Height mm 2175 2175 2175
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 996 1020 1120
Number of refrigerating circuits 2 2 2
Number of compressors 4 4 4
Electric supply voltage V 400V / 3Ph + N / 50Hz

Model TUTV 2242 2542 2842


Height mm 1960 1960 1960
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 910 930 1040
Number of refrigerating circuits 2 2 2
Number of compressors 4 4 4
Electric supply voltage V 400V / 3Ph + N / 50Hz

Model TUDV 2242 2542 2842


Height mm 1960 1960 1960
Width mm 2580 2580 2580
Depth mm 865 865 865
Weight kg 996 1020 1120
Number of refrigerating circuits 2 2 2
Number of compressors 4 4 4
Electric supply voltage V 400V / 3Ph + N / 50Hz

70
Operating description

TWIN-COOL
The LEONARDO Twin-Cool units are characterised by two completely
different independent cooling circuits:
• A chilled water circuit.
• An air cooled or water cooled direct expansion circuit.
The unit is normally used where an installation has a chilled water source
but the direct expansion circuit can be used according to demand.
The control system automatically starts the direct expansion circuit if
the chilled water supply fails of if the water is not cold enough to dissipa-
te the entire heat load. Alternatively, the unit control can be set to direct
expansion, activating chilled water operation only in the event of a
compressor malfunction, if the water temperature in relation to the room
temperature allows it.
Twin-Cool units therefore provide a very high level of security, ensuring
continuous system operation at all times and with the flexibility to manage
the cooling resources in the best way for the particular installation.

71
Name and description of the principle components

A User terminal
B Electrical panel door
C Cover panels
D Electrical panel
E Filters
C A F Fans
G Cooling circuit

MODELS TD./ TU. 511 ÷ 1822

E
D

H
G

MODELS TD./ TU. 2222 ÷ 2842

72
A1 Description of the components
A - User terminal
Allows the unit to be turned on or off and the configuration
A2 A5 and visualization of the condition of the machine.
• A1 LCD display
A3 A6 • A2 ALARM key: visualization and re-set of alarms;
when the alarm is activated, it flashes red.
A4 A7 • A3 PRG key: access to the configuration menu
• A4 ESC key: exit from the screens
• A5 UP key: scroll through the menu
MODELS TD./ TU. 511 ÷ 1822 • A6 ENTER key: confirm
• A7 DOWN key: scroll through the menu

B - Electrical panel door


Allows access to the electrical panel of the machine.

D2 C - Cover panels
Allow access to the internal components of the machine.

D - Electrical panel
D1 D3 • D1Magnetothermic
- auxiliary
D4 - heater (optional)
- humidifier (optional)
- fans
- compressors
• D2Interface board
• D3Dirty filter sensor
D8
• D4Air flow sensor
D5 D6
• D5Main switch
D7B • D6Terminal board
D7C
• D7AInput/output electrical supply cables
D7A D7D • D7BInput/output electrical auxiliary cables
• D7CInput/output condensing unit supply (optional) - (only
on air cooled units)
• D7DInput/output signal cables (RS485 and/or LAN)
MODELS TD./ TU. 2222 ÷ 2842 • D8Phase sequence relay
• D9 Maximum pressure manostat (only for mod. TD.
D2 D1 D4 D3 D9
2222 ÷ 2842)

D7D D8 D5 D7A D7C D7B D6

E - Filters
E
F Filter the air released into the room.

F1 F - Fans
Allow the diffusion of air into the environment.
• F1 ATR transformer allows the setting of the fan rotation
speed.

73
G3 G2 G1 G - Cooling circuit
• G1 Compressor
• G2 High pressure switch
• G3 Schrader valve

• G4 Safety valve
• G5 Liquid receiver
• G6 Dehydration filter
• G7 Flow sight glass
G8 • G8 Electronic thermostatic valve
G9 • G9 Brazed plate exchanger

G7

G4 G5 G6

• G10 Evaporating coil

G10

H - Chilled water valve


H H1 Servomotor
H2 Manual control knob
H3 Valve stem
H1

H3
H2

74
I I - Room temperature and humidity sensor

Installation and maintenance of the Twin-cool units should be carried out as described in the DIRECT EXPANSION
section. For the water circuit, follow the instructions in the CHILLED WATER section.

For the paragraph "Selecting the supply voltage of the fans", refer to the table below

STANDARD VOLTAGE LEVELS


Models V
0511 200
0611 200
0721 - 0722 - 0921 - 0922 -1021
280
- 1022
1121 - 1122 - 1321 -1322 270
1422 - 1622 - 1822 280
2242 230
2542 240
2842 260
MODELS WITH AUTOTRANSFORMERS
In the following table the maximum available pressures are indicated (expressed in Pa) for each voltage level of the
transformer. The values are given for the maximum air flow (expressed in m3/h).
0721
0722
0921 1121
T*ER 0922 1122 1422
T*TR 0511 1021 1321 1622
T*DR 0611 1022 1322 1822 2242 2542 2842
FA[m3/h=] 5550 7970 11390 15320 21000 22000 22700
V Pa Pa Pa Pa Pa Pa Pa
142 0 - - - - - -
150 - - - - 0 0 0
168 0 - - - - - -
180 0 - - - 0 0 0
195 0 - - - - - -
200 - - - - 0 0 0
215 58 - - - - - -
222 86 - - - - - -
227 106 - - - - - -
230 123 0 0 0 0 0 0
240 - - - - 37 0 0
250 - 0 0 0 - - -
260 - 0 0 0 92 50 21
270 - 0 24 0 - - -
280 - 3 53 5 140 98 68
290 - 29 82 34 - - -
300 - 55 112 63 186 140 110
310 - 80 141 93 - - -
320 - 106 171 122 226 180 148
340 - 157 230 181 262 215 181
360 - 208 288 240 293 246 212
380 - 260 347 299 320 273 239
400 311 406 358 343 295 261
Per variare le tensioni fare riferimento alle tabelle di pagina 33
75
MODELS WITH FANS CARRYING A CE MARKING
In the following tables the maximum available pressures are indicated (expressed in Pa) for each supply voltage selected.
The values are given for the maximum air flow (expressed in m3/h).

Models %
0511 - 0611 63
0721 - 1022 72
1121 - 1322 64
1422 - 1622 73
2242 63 TD
2542 72 TD
2842 74 TD
2242 70 TU
2542 73 TU
2842 75 TU

0721
0722
0921 1121
T*EV 0922 1122 1422
T*TV 0511 1021 1321 1622
T*DV 0611 1022 1322 1822 2242 2542 2842
3
FA[m /h=] 5550 7940 11650 15420 21000 22000 22700
% Pa Pa Pa Pa Pa Pa Pa
50 0 0 0 0 0 0 0
55 0 0 0 0 0 0 0
60 0 0 0 0 0 0 0
63 20 - - - - - -
65 45 0 30 0 0 0 0
70 132 0 80 0 45 35* 0
75 0 45 156 27 135 85 45
80 302 136 236 117 230 175 135
85 0 229 320 208 317 265 230
90 450 324 409 302 395 353 310
95 0 421 501 399 510 455 415
100 589 520 598 498 555 515 485

* Per modelli “TU” considerare -20 Pa

76
ACCESSORIES
Humidifier

U2 U2

U3

U1
U4
U5

U9
U8

U6

U11
U2
U3
U12

U7

U13
U U1
10
U1 Boiler cylinder
U8 U9 U2 Water supply tray
U14 U3 High water level detector electrodes in the boiler cylinder
U4 Condenser drain
U5 Collector charge/discharge
U6 Water input
U7 Drain
U8 Feed water solenoid valve
U9 Boiler cylinder electric drainage valve
U10 Overflow pipe (behind the cylinder)
U11 Amperometric transformer for measuring the current
(within the electrical panel)
U12 Humidifier interface board (inside the electrical panel)
U13 Microprocessor control board
U14 Temperature and humidity probe

77
Operating principle
In the electrode boiler humidifier, the current flowing between the electrodes in the water in the cylinder generates the heat
necessary to boil the water.
By controlling the water level and the concentration of salt measured in the steam cylinder (U1) using the feed water
solenoid valve (U8) and the boiler cylinder electric drainage valve (U9), the electric current is regulated by means of an
amperometric transformer (U11).
When steam is needed, the humidifier contact is closed (see the electrical diagram) which provides power to the immersed
electrodes. When the current falls below the value required as a result of the fall in the water level, the feed water solenoid
valve is opened (U8).
The boiler cylinder electric drainage valve (U9) is opened at intervals depending on the characteristics of the feed water
supply in order to maintain the optimum concentration of dissolved salts in the water in the cylinder (U1).
Feed water
Values for the feed water for medium-high level of conductibility of a humidifier with immersed electrodes.
LIMITS
Min. Max.
Hydrogen ion activity pH - 7 8.5
Specific conductibility at 20 °C σR , 20 °C - μS/cm 300 1250
Total dissolved solids TDS - mg/l (1) (1)
Residual fixed at 180 °C R180 - mg/l (1) (1)
Total hardness TH - mg/l CaCO3 100(2) 400
Temporary hardness - mg/l CaCO3 60(3) 300
Iron + Manganese - mg/l Fe + Mn 0 0.2
Chlorides - ppm C l 0 30
Silica - mg/l SiO2 0 20
Residual chloride - mg/l Cl- 0 0.2
Calcium sulphate - mg/l CaSO4 0 100
Metallic impurities - mg/l 0 0
Solvents, dilutents, soaps, lubricants - mg/l 0 0
(1) Values dependent on the specific conductibility; in general: TDS @ 0,93 * s20; R180 @ 0,65 * s20
(2) not lower than 200% of the Chloride content in mg/l di Cl-
(3) not lower than 300% of the Chloride content in mg/l di Cl-
Connections
The installation of the humidifier requires connection to the feed tubes of the water drain.

Feed tubes
valve
Drain
Filter

Siphon

78
Maintenance
The only maintenance required is periodic inspection and cleaning of the steam boiler components. This should be carried
out at least once a year, preferably before the summer holiday shutdown.

BOILER CYLINDER
Limescale deposits must be cleaned periodically from the electrodes and particles of limescale must be removed from the
filter at the base of the cylinder.
To dismantle the cylinder:
• - completely drain the water from the cylinder:
- using the user terminal, press the UP or DOWN key until the INPUT/OUTPUT screen appears;
- confirm by using the ENTER key;
- press the UP or DOWN key until DO6 HUMIDIFIER DRAIN is selected;
- confirm by using the ENTER key;
• disconnect the power supply by opening the main isolator on the electrical panel;
• disconnect the steam distributor hose from the top of the cylinder;
• disconnect the power connections to the electrodes by unscrewing the terminal connectors and pull off the connectors
of the electrodes;
• unclip the cylinder fixing strap;
• pull the cylinder upwards.
The boiler cylinder can be used many times after the electrodes are cleaned: however, it will eventually require replacement
when the electrode meshes are too worn out to make further cleaning worthwhile.
The spare part consists of only the cylinder itself (with the filter inside).

FEED AND DRAIN CONNECTIONS


Periodic inspections of the feed and drain connections are advisable in order to guarantee trouble-free operation of the
humidifier.
Proceed as follows:
• - completely drain the water from the cylinder:
- using the user terminal, press the UP or DOWN key until the INPUT/OUTPUT screen appears;
- confirm by using the ENTER key;
- press the UP or DOWN key until DO6 HUMIDIFIER DRAIN is selected;
- confirm by using the ENTER key;
• disconnect the power supply by opening the main isolator on the electrical panel;
• disconnect the feed line at the ¾ GAS connection to the inlet solenoid valve connection (U8);
• extract, clean and replace the filter located inside the solenoid valve connection;
• remove the drain solenoid valve, clean out the water pathways and remove any particles of limescale from the drain
siphon.

79
Electric heaters
Leonardo Evolution units can be equipped with electric heaters. For each model there are two levels available: standard
and improved.
The finned elements are characterised by maintaining low power density of the surfaces in a highly efficient way, therefore
limiting overheating of the elements and consequently increasing their lifespan.
Thanks to the low surface temperature of the heating elements, the ionisation effect on the air is limited. This heating
system has two functions:
• heating the air to arrive at the set point conditions;
• post-heating during the phase of dehumidification, in such a way as to retain the air temperature at set point.
Therefore, the heating power installed is able to maintain the dry bulb temperature in the room during the dehumidification
process.

STANDARD CAPACITY V No kW OA
0511 - 0611 400/3/50 2 6 8,7
0721 - 0722 - 0921
400/3/50 3 9 13,0
0922 - 1021 - 1022
1121 - 1122 - 1321 - 1322
400/3/50 5 15 21,7
1422 - 1622 - 1822
2222 - 2522 400/3/50 6 18 26
2242 - 2542 400/3/50 6 18 26
2842 - 3342 400/3/50 8 24 34,7

IMPROVED CAPACITY V No kW OA
0511 - 0611 400/3/50 3 9 13,0
0721 - 0722 - 0921
400/3/50 5 15 21,7
0922 - 1021 - 1022
1121 - 1122 - 1321 - 1322 THERMOSTAT
400/3/50 6 18 26,0 TSR and TSRA
1422 - 1622 - 1822
2222 - 2522 400/3/50 8 24 34,7
2242 - 2542 400/3/50 8 24 34,7
2842 - 3342 400/3/50 9 27 39

TSR and TSRA heaters safety thermostata are fixed on the


external edges of the electrical panel.
In position A for UPFLOW models
In position B for DOWNFLOW models
B

80
Replacing the electrical heaters
WARNING! Before replacing the electrical heaters, disconnect the power supply from the unit. Make
sure that it is not possible for the power to be turned on again while they are being replaced.
WARNING! The heaters must only be replaced by a qualified electrician.

The total power of the electrical heaters is divided into different


elements, each of 3 kW.
The colour of the wires on each element has the following
meaning:
- BLACK wire = low power absorption (1 kW);
- WHITE wire = high power absorption (2 kW);
- RED wire = standard.
The wires of each element are connected to the CR1 and
CR2 connectors on the electrical panel in such a way as to
balance the load across the phases and create three stages
of heating (refer to the electric diagram on the side of the
machine).

Temperature and humidity sensor


The diagram shows an optional temperature and humidity sensor. When replacing the sensor, release the white plastic lid
by pressing on point (A) with a screwdriver or a pointed tool; lifting the lid (B) to gain access to the fixing screws (C) and the
terminals (D).
A screened cable is used for the electrical connections to the sensor; the connections to the terminals are shown on the
electrical diagram.

A
80

126 mm

C C
D

81
Connection to fresh air intake
The unit can be fitted with an optional fresh air filter.
During installation, connect the intake of the fresh air filter to the nearest external air inlet with a flexible hose which has a
diameter of 100mm and secure the hose to the fresh air intake with a fastening collar.
The connection from the unit to the external air inlet must have the shortest and straightest path possible.

Unit TD*C 0600 - 0700 Unit TU*C 0600 - 0700

Unit TD*C 1000 ÷ 2500 Unit TU*C 1000 ÷ 2500

82
Unit TDA-E-W 0511 - 0611 Unit TUA-E-W 0511 - 0611

Maintenance
Clean, using a blast of compressed air, or replace the fresh air intake filters periodically.

Discharge temperature threshold sensor (only on CHILLED WATER models)


An NTC temperature sensor is an optional accessory which maintains the supply air temperature of the unit above a
threshold value. The sensor is connected to the microprocessor control system as described in the electrical diagram of
the unit.
The sensor has a temperature range of -50°C and +50°C and a protection level of IP67; it can be installed outside the unit
by means of a cable which is 3 metres long. A minimum distance of 2 metres is advisable from the unit discharge, as shown
in the diagram for upflow units.

STM

2m

STM

83
UNIFLAIR S.p.A.
Legal and administrative headquarters: Viale della Tecnica, 2 35026
Conselve (PD) - ITALY
Tel. +39 049 5388211 Fax +39 0495388212
uniflair.com - info@uniflair.com
P. IVA 02160760282 C.C.I.A.A. di PD R.E.A. 212586 del 21/04/1988
- R.I.N. 02160760282 M. PD004505

Fully paid-up share capital o 19.550.000 06MM115@00B0170

You might also like