Moore Fans LLC

Phone: (660) 376-3575 www.moorefans.com Fax: (660) 376-2909


Cameron Compression Reference No. Project #10184 - DItem No. 20214
System
Class 10000 Performance
Performance Curve Curve
(Maximum recommended angle is 30 degrees)

600000 45
45 90.0%
21.7 25.7
Power
17.8 40
40 Efficiency % 14.2 80.0%
500000
Air Volume
10.8 25.7
Power 35
35 70.0%

400000 30
30 60.0%

14.2 21.7

Efficiency
25
Air Volume
(BHP)

25 50.0%

Power
Power

300000
20
20 40.0%
17.8
200000 14.2 15
15 30.0%
14.2
10
10 20.0%
100000
10.8
5
5 10.0%

0 0
0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 0.0%
0.0 5.0 10.0
Blade Angle (Degrees) 15.0 20.0 25.0 30.0
600000 1.20
Air Volume
Static Pressure
25.7
500000 25.7 1.00

21.7

17.8 21.7
400000 0.80

Static Pressure
14.2
Air Volume

(in H2O)
17.8
(lb/hr)

10.8
300000 0.60
7.6
14.2
4.6
200000 0.40
10.8
1.9

7.6
100000 0.20
4.6

1.9
0 0.00
0.0 5.0 10.0 15.0 20.0 25.0 30.0

Blade Angle (Degrees)

Design Angle= 21.8


Est. API Angle= 25.5
Maximum Angle= 25.7
Design Conditions
Class: 10000 Blade Type: SC Temperature: 142 Deg. F Static Pr.: 0.875 in H2O
Series: 36 Blade Tip: BR Elevation: 774 feet Power Req'd: 28.75 bhp
Diameter: 8.00 feet Adjustment: MAN Density Ratio: 0.856 Design Angle: 21.8 deg
RPM: 427 Blades: 6 Air Volume: 438075.00 lb/hr Weight: 123 lbs
Moore Fans LLC Rating
Phone: (660) 376-3575 http://www.moorefans.com Fax:(660) 376-2909
Version 2.26
8/15/2014 13:07
Cameron Compression Ref No.: Project #10184 - DItem No: 20214
Class: 10000 10K Hub Type: HD Blade Type: SC
Blade Tip: BR Adjustment: MAN MAN Rotation: RH
Series: 36 Diameter: 8 feet Blades: 6
Temperature: 142 Deg. F Elevation: 774 feet Density Ratio: 0.856
Volume: 438075 lb/hr Air Vel.: 2528.13 fpm Speed: 427 RPM
Static Pressure: 0.875 in H2O Pv: 0.340 in H2O Pt: 1.317 in H2O
Power Reqd.: 28.75 bhp Motor: 40 bhp Total Eff: 82.2%
Power @ 20 deg. 36.05 bhp Bld Natural Freq.: 15.0 Hz Static Eff: 54.6%
Blades Required: 5.50 API Blades Req.: 6 Blade Load: 0.917
Tip Speed: 10731.7 fpm Deflection Angle: 47.0 deg. Pitch Number: 1.97
Entry Correction: 1.3 Tip Clearance: 0.5 inches Design Angle: 21.8 deg
Exit Correction: 1.00 Draft: Induced Orientation: Vertical
Torque Factor: 2 Motor Torque: 984 ft. lbs Torq/Bld: 164 ft. lbs
Appr fan weight: 123 lbs 56 kg Bore Size: 2.4375 inches
WR2 361 lb-ft2 15.2 kg m2 Bushing Type: U
Thrust Load: 344 lbs 156 kg Qty required: 1
Noise Levels Per Fan ( Induced Draft) (Vertical Orientation) See Note 2
Sound Power Level
dBA HZ 63 125 250 500 1000 2000 4000 8000
100.7 106.7 105.7 102.7 97.7 95.7 89.7 83.7 77.7

Sound Pressure Level 1 meter from face of unit


86.0 92.0 91.0 88.0 83.0 81.0 75.0 69.0 63.0

Sound Pressure Level 1 meter radially from blade tip


83.4 89.4 88.4 85.4 80.4 78.4 72.4 66.4 60.4

Estimated Sound Pressure Level Multiple Fans (1 fans at 50 ft from periphery)


69.0 75.0 74.0 71.0 66.0 64.0 58.0 52.0 46.0
0
0.0 6.0 5.0 2.0 (3.0) (5.0) (11.0) (17.0) (23.0)
Class 10000, Series 36, 8 feet Diameter, 6 Blades
Manual Adjustment, Heavy Duty, Standard Chord, Right Hand Rotation

Fan Model No. 1036/073-U0-A/36R-BR-3-8.00-6


Fan Drawing: http://www.moorefans.com/pdfs/TMC_816_C.pdf
Note 1: Maximum blade angle to prevent fan stall is 25.7 degrees.
Available motor power may limit maximum angle to a lower value.
Note 2: Noise levels are the best estimate of the fan noise with 0 dBA additional noise
included due to drive components, flow obstructions or structure reflection and reverberation.